To configure or manage a network device in a telecommunications network, a user typically connects directly to the network device through a network management system. Most network management software is based on the Simple Network Management Protocol (SNMP), and a user connects to a network device by issuing an SNMP command, for example, read/write or read only, followed by a password in the form of a community string. Often, only one community string is used to access the network device, and thus, all users allowed to access the network device must “share” the community string. Sharing the community string and directly connecting a user to the network device reduces the security of the network device.
More advanced systems allow multiple SNMP community strings to be used to gain access to a network device. Generally, these community strings are stored in a table within the network device. Where a large number of users may be connected to the device, however, community strings may still need to be shared or the table in the network device must be very large.
Although one or more community strings may be shared by multiple users and used to access the same network device, community strings are normally different for each network device. Thus, to connect to multiple network devices, a user must separately connect (i.e., issue an SNMP command and community string) to each network device. This may take considerable time and requires the user to remember multiple community strings.
In addition, if the one or more community strings needed to access a network device must be changed—for example, in response to a security problem—every user allowed to access the device must be notified of the community string change. If the community string is changed quickly, then some users may be denied access until they receive the notification including the new password. If the community string is not changed until after an amount of time necessary to notify all users, then until the change is implemented, the security problem will continue.
The present invention provides a method and apparatus for accessing network device data through user profiles. User profiles may be created by network administrators, and the corresponding user profile data may be stored in a central network management system (NMS) database. When a user requests data from a particular network device, the NMS utilizes the user profile data in the central database to access the network device and retrieve the required network device data. Since the user profile data is stored in a central database, the user may log into the NMS from any location and connect to any network device in the network. Further, the user profile data may be used to limit which network devices and which network device configured resources the user may access as well as the user's access level.
In one aspect, the present invention provides a method of managing a telecommunications network including storing user profile data corresponding to a user profile in a first data repository, storing network device data corresponding to a network device in the telecommunications network in a second data repository, detecting a request from a user for network device data corresponding to the network device, where the user request is associated with the user profile, generating a data access request to the second data repository utilizing the user profile data from the first data repository and retrieving network device data from the second data repository in accordance with the user request. The first data repository may be a central data repository, the second data repository may be embedded within the network device and both the first and second data repositories may be databases. The method may also include displaying the retrieved network device data in a user interface. The user profile data may include an IP address or DNS name assigned to the network device, and may also include a port identification for a port on the network device. The user profile data may include a group access level and may also include a password corresponding to the group access level for gaining access to the network device, and the user profile data may include a simple network management protocol (SNMP) community string.
The user profile data may include one or more group names corresponding to the network device and generating a data access request to the second data repository using user profile data from the first data repository may include generating a data access request to the second data repository for each group name in the user profile data and retrieving network device data from the second data repository in accordance with the user request may include, for each data access request, searching the second data repository for the group name corresponding to the data access request and retrieving network device data from the second data repository corresponding to the group name if the group name corresponding to the data access request is found in the second data repository. The network device data retrieved from the second data repository may be configured resource data. Retrieving network device data from the second data repository corresponding to the group name may include using the group name to dynamically determine which data in the second data repository is retrieved. The first and second data repositories may be databases and retrieving network device data from the second database corresponding to the group name may include using the group name in a database query to actively filter which data in the second database is retrieved, and generating a data access request to the second database for each group name in the user profile data from the first database may include generating a where clause including the group name and sending the where clause to the second database. The first and second data repositories may be relational databases and the user profile data may be stored in at least one table within the first database and network device data may be stored in at least one table within the second database.
The method may further include generating a user profile logical managed object (LMO) including at least a portion of the user profile data from the first data repository and generating a data access request to the second data repository utilizing the user profile data from the first data repository may include generating a data access request to the second data repository utilizing the user profile data from the user profile LMO. Prior to generating a user profile LMO, the method may further include detecting a user log-on request. Detecting a request from a user for network device data may include detecting the user request through a network management system (NMS) client and sending the user request from the NMS client to an NMS server, where the NMS server generates the data access request to the second data repository utilizing the user profile data from the first data repository and retrieves network device data from the second data repository in accordance with the user request, and the method may further include sending the retrieved network device data from the NMS server to the NMS client. The method may further include generating a user profile logical managed object (LMO) at the NMS server, where the user profile LMO includes at least a portion of the user profile data from the first data repository, sending the NMS client the user profile LMO and, where generating a data access request to the second data repository utilizing the user profile data from the first data repository may include generating a data access request to the second data repository utilizing the user profile data from the user profile LMO. The method may instead include generating a user profile LMO at the NMS server, where the user profile LMO includes at least a portion of the user profile data from the first data repository, generating a client user profile LMO at the NMS server, where the client user profile LMO includes at least a portion of the user profile data from the first data repository in a format expected by the NMS client, sending the client user profile LMO to the NMS client and where generating a data access request to the second data repository utilizing the user profile data from the first data repository may include generating a data access request to the second data repository utilizing the user profile data from the client user profile LMO.
The user request may be a first user request, the network device may be a first network device and the data access request may be a first data access request, and the method may further include storing network device data corresponding to a second network device in the telecommunications network in a third data repository, detecting a second user request from the user for network device data corresponding to the second network device, wherein the second user request is associated with the user profile, generating a second data access request to the third data repository utilizing the user profile data from the first data repository and retrieving network device data from the third data repository in accordance with the second user request. The user profile data may be first user profile data, the user may be a first user, the user request may be a first user request and the data access request may be a first data access request, and the method may further include storing second user profile data corresponding to a second user profile in the first data repository, detecting a second request from a second user for network device data corresponding to the network device, where the second user request is associated with the second user profile, generating a second data access request to the second data repository utilizing the second user profile data from the first data repository and retrieving network device data from the second data repository in accordance with the second user request. The user profile data may be first user profile data, the user may be a first user, the user request may be a first user request, the network device may be a first network device and the data access request may be a first data access request, and the method may further include storing second user profile data corresponding to a second user profile in the first data repository, storing network device data corresponding to a second network device in the telecommunications network in a third data repository, detecting a second request from a second user for network device data corresponding to the second network device, where the second user request is associated with the second user profile, generating a second data access request to the third data repository utilizing the second user profile data from the first data repository and retrieving network device data from the third data repository in accordance with the second user request.
In another aspect, the present invention provides a method of managing a telecommunications network including storing user profile data corresponding to a user profile in a first data repository, wherein the user profile data includes a group name, storing network device data corresponding to a network device in the telecommunications network in a second data repository, detecting a request from a user for network device data corresponding to the network device, where the user request is associated with the user profile, generating a data access request to the second data repository utilizing the user profile data from the first data repository, where the data access request includes the group name, and retrieving network device data from the second data repository in accordance with the group name. The first data repository may be a central data repository and the second data repository may be embedded within the network device, and both the first and second data repositories may be databases. Retrieving network device data from the second data repository in accordance with the group name may include searching the second data repository for the group name and retrieving network device data from the second data repository corresponding to the group name if the group name is found in the second data repository. The network device data retrieved from the second data repository may be configured resource data associated with the group name, and retrieving network device data from the second data repository corresponding to the group name may include using the group name to dynamically determine which data in the second data repository is retrieved. The first and second data repositories may be databases and retrieving network device data from the second database corresponding to the group name may include using the group name in a database query to actively filter which data in the second database is retrieved, and generating a data access request to the second database may include generating a where clause including the group name and sending the where clause to the second database. The user profile data may include group names and generating a data access request to the second data repository utilizing the user profile data from the first data repository may include generating a data access request to the second data repository for each group name in the user profile data, where each data access request includes the corresponding group name, and retrieving network device data from the second data repository in accordance with the group name may include retrieving network device data from the second data repository in accordance with each group name.
In yet another aspect, the present invention provides a method of managing a telecommunications network including storing user profile data corresponding to a user profile in a central data repository, detecting a user log-on request corresponding to the user profile through a network management system (NMS) and generating a user profile logical managed object (LMO) using the user profile data stored in the central data repository. The method may also include storing network device data in a network device data repository embedded within a network device in the telecommunications network, where the data corresponds to configured resources within the network device, detecting through the NMS a request for data corresponding to the configured resources within the network device from a user associated with the user profile and retrieving network device data from the network device data repository in accordance with the user profile data and the request for data. The user profile data may include one or more group names, where the user profile LMO includes the one or more group names, and retrieving network device data from the network device data repository in accordance with the user profile data and the request for data may include searching the network device data repository for a match with each group name in the user profile LMO, returning an empty data set for each group name not found in the network device data repository and retrieving data corresponding to configured resources from the network device data repository for each group name found in the network device data repository. The central data repository and network device data repository may comprise databases.
a-2b are block and flow diagrams of a distributed network management system;
a is a block diagram of a logical system model;
b and 3d-3f are flow diagrams depicting a software build process using a logical system model;
c is a flow diagram illustrating a method for allowing applications to view data within a database;
g is a flow diagram depicting a configuration process;
h and 3j are flow diagrams depicting template driven network services provisioning processes;
i and 3k-3m are screen displays of an OSS client and various templates;
a-4z, 5a-5z, 6a-6p, 7a-7y, 8a-8e, 9a-9n, 10a-10i, 11a-11k, 11n-11o, 11s and 11x are screen displays of graphical user interfaces;
m are tables representing data in a configuration database;
p-11r and 11t-11u are tables representing data in a network management system (NMS) database;
v is a block and flow diagram representing the creation of a user profile logical managed object including one or more groups;
w is a block and flow diagram of a network management system implementing user profiles and groups across multiple databases;
a and 13a are block and flow diagrams of a computer system incorporating a modular system architecture and illustrating a method for accomplishing hardware inventory and setup;
b-12c and 14a-14f are tables representing data in a configuration database;
b is a block and flow diagram of a computer system incorporating a modular system architecture and illustrating a method for configuring the computer system using a network management system;
c and 13d are block and flow diagrams of an accounting subsystem for pushing network device statistics to network management system software;
a-16b are flow diagrams illustrating a method for assigning logical names for inter-process communications;
c is a block and flow diagram of a computer system incorporating a modular system architecture and illustrating a method for using logical names for inter-process communications;
d is a chart representing a message format;
a-31c, 32a-32c, 33a-33d and 34a-34b are block and flow diagrams of a computer system incorporating a distributed redundancy architecture and illustrating methods for accomplishing distributed redundancy and recovery after a failure;
a-41c are front, back and side block diagrams, respectively, of components and modules within the network device of
a-60n are tables representing data in a configuration database;
a is a block diagram representing a physical managed object;
b is a block diagram representing a proxy; and
A modular software architecture solves some of the more common scenarios seen in existing architectures when software is upgraded or new features are deployed. Software modularity involves functionally dividing a software system into individual modules or processes, which are then designed and implemented independently. Inter-process communication (IPC) between the processes is carried out through message passing in accordance with well-defined application programming interfaces (APIs) generated from the same logical system model using the same code generation system. A database process is used to maintain a primary data repository within the computer system/network device, and APIs for the database process are also generated from the same logical system model and using the same code generation system ensuring that all the processes access the same data in the same way. Another database process is used to maintain a secondary data repository external to the computer system/network device; this database receives all of its data by exact database replication from the primary database.
A protected memory feature also helps enforce the separation of modules. Modules are compiled and linked as separate programs, and each program runs in its own protected memory space. In addition, each program is addressed with an abstract communication handle, or logical name. The logical name is location-independent; it can live on any card in the system. The logical name is resolved to a physical card/process during communication. If, for example, a backup process takes over for a failed primary process, it assumes ownership of the logical name and registers its name to allow other processes to re-resolve the logical name to the new physical card/process. Once complete, the processes continue to communicate with the same logical name, unaware of the fact that a switchover just occurred.
Like certain existing architectures, the modular software architecture dynamically loads applications as needed. Beyond prior architectures, however, the modular software architecture removes significant application dependent data from the kernel and minimizes the link between software and hardware. Instead, under the modular software architecture, the applications themselves gather necessary information (i.e., metadata and instance data) from a variety of sources, for example, text files, JAVA class files and database views, which may be provided at run time or through the logical system model.
Metadata facilitates customization of the execution behavior of software processes without modifying the operating system software image. A modular software architecture makes writing applications—especially distributed applications—more difficult, but metadata provides seamless extensibility allowing new software processes to be added and existing software processes to be upgraded or downgraded while the operating system is running. In one embodiment, the kernel includes operating system software, standard system services software and modular system services software. Even portions of the kernel may be hot upgraded under certain circumstances. Examples of metadata include, customization text files used by software device drivers; JAVA class files that are dynamically instantiated using reflection; registration and deregistration protocols that enable the addition and deletion of software services without system disruption; and database view definitions that provide many varied views of the logical system model. Each of these and other examples are described below.
The embodiment described below includes a network computer system with a loosely coupled distributed processing system. It should be understood, however, that the computer system could also be a central processing system or a combination of distributed and central processing and either loosely or tightly coupled. In addition, the computer system described below is a network switch for use in, for example, the Internet, wide area networks (WAN) or local area networks (LAN). It should be understood, however, that the modular software architecture can be implemented on any network device (including routers) or other types of computer systems and is not restricted to a network switch.
A distributed processing system is a collection of independent computers that appear to the user of the system as a single computer. Referring to
Each control processor subsystem includes a processor integrated circuit (chip) 24, 26a-26n, for example, a Motorola 8260 or an Intel Pentium processor. The control processor subsystem also includes a memory subsystem 28, 30a-30n including a combination of non-volatile or persistent (e.g., PROM and flash memory) and volatile (e.g., SRAM and DRAM) memory components. Computer system 10 also includes an internal communication bus 32 connected to each processor 24, 26a-26n. In one embodiment, the communication bus is a switched Fast Ethernet providing 100 Mb of dedicated bandwidth to each processor allowing the distributed processors to exchange control information at high frequencies. A backup or redundant Ethernet switch may also be connected to each board such that if the primary Ethernet switch fails, the boards can fail-over to the backup Ethernet switch.
In this example, Ethernet 32 provides an out-of-band control path, meaning that control information passes over Ethernet 32 but the network data being switched by computer system 10 passes to and from external network connections 31a-31xx over a separate data path 34. External network control data is passed from the line cards to the central processor over Ethernet 32. This external network control data is also assigned a high priority when passed over the Ethernet to ensure that it is not dropped during periods of heavy traffic on the Ethernet.
In addition, another bus 33 is provided for low level system service operations, including, for example, the detection of newly installed (or removed) hardware, reset and interrupt control and real time clock (RTC) synchronization across the system. In one embodiment, this is an Inter-IC communications (I2C) bus.
Alternatively, the control and data may be passed over one common path (in-band).
Network/Element Management System (NMS):
Exponential network growth combined with continuously changing network requirements dictates a need for well thought out network management solutions that can grow and adapt quickly. The present invention provides a massively scalable, highly reliable comprehensive network management system, intended to scale up (and down) to meet varied customer needs.
Within a telecommunications network, element management systems (EMSs) are designed to configure and manage a particular type of network device (e.g., switch, router, hybrid switch-router), and network management systems (NMSs) are used to configure and manage multiple heterogeneous and/or homogeneous network devices. Hereinafter, the term “NMS” will be used for both element and network management systems. To configure a network device, the network administrator uses the NMS to provision services. For example, the administrator may connect a cable to a port of a network device and then use the NMS to enable the port. If the network device supports multiple protocols and services, then the administrator uses the NMS to provision these as well. To manage a network device, the NMS interprets data gathered by programs running on each network device relevant to network configuration, security, accounting, statistics, and fault logging and presents the interpretation of this data to the network administrator. The network administrator may use this data to, for example, determine when to add new hardware and/or services to the network device, to determine when new network devices should be added to the network, and to determine the cause of errors.
Preferably, NMS programs and programs executing on network devices perform in expected ways (i.e., synchronously) and use the same data in the same way. To avoid having to manually synchronize all integration interfaces between the various programs, a logical system model and associated code generation system are used to generate application programming interfaces (APIs)—that is integration interfaces/integration points—for programs running on the network device and programs running within the NMS. In addition, the APIs for the programs managing the data repositories (e.g., database programs) used by the network device and NMS programs are also generated from the same logical system model and associated code generation system to ensure that the programs use the data in the same way. Further, to ensure that the NMS and network device programs for managing and operating the network device use the same data, the programs, including the NMS programs, access a single data repository for configuration information, for example, a configuration database within the network device.
Referring to
The NMS client and server relationship prevents the network administrator from directly accessing the network device. Since several network administrators may be managing the network, this mitigates errors that may result if two administrators attempt to configure the same network device at the same time.
The present invention also includes a configuration relational database 42 within each network device and an NMS relational database 61 external to the network device. The configuration database program may be executed by a centralized processor card or a processor on another card (e.g., 12,
Similarly, any configuration changes made by the network administrator directly through console interface 852 are made to the configuration database and, through active queries, automatically replicated to the NMS database. Maintaining a primary or master repository of data within each network device ensures that the NMS and network device are always synchronized with respect to the state of the configuration. Replicating changes made to the primary database within the network device to any secondary data repositories, for example, NMS database 61, ensures that all secondary data sources are quickly updated and remain in lockstep synchronization.
Instead of automatically replicating changes to the NMS database through active queries, only certain data, as configured by the network administrator, may be replicated. Similarly, instead of immediate replication, the network administrator may configure periodic replication. For example, data from the master embedded database (i.e., the configuration database) can be uploaded daily or hourly. In addition to the periodic, scheduled uploads, backup may be done anytime at the request of the network administrator.
Referring again to
Instead of having a single central processor card (e.g., 12,
The file transfer protocol (FTP) may provide an efficient, reliable transport out of the network device for data intensive operations. Bulk data applications include accounting, historical statistics and logging. An FTP push (to reduce polling) may be used to send accounting, historical statistics and logging data to a data collector server 857, which may be a UNIX server. The data collector server may then generate network device and/or network status reports 858a-858n in, for example, American Standard Code for Information Interchange (ASCII) format and store the data into a database or generate Automatic Message Accounting Format (AMA/BAF) outputs.
Selected data stored within NMS database 61 may also be replicated to one or more remote/central NMS databases 854a-854n, as described below. NMS servers may also access network device statistics and status information stored within the network device using SNMP (multiple versions) traps and standard Management Information Bases (MIBs and MIB-2). The NMS server augments SNMP traps by providing them over the conventional User Datagram Protocol (UDP) as well as over Transmission Control Protocol (TCP), which provides reliable traps. Each event is generated with a sequence number and logged by the data collector server in a system log database for in place context with system log data. These measures significantly improve the likelihood of responding to all events in a timely manner reducing the chance of service disruption.
The various NMS programs—clients, servers, NMS databases, data collector servers and remote NMS databases—are distributed programs and may be executed on the same computer or different computers. The computers may be within the same LAN or WAN or accessible through the Internet. Distribution and hierarchy are fundamental to making any software system scale to meet larger needs over time. Distribution reduces resource locality constraints and facilitates flexible deployment. Since day-to-day management is done in a distributed fashion, it makes sense that the management software should be distributed. Hierarchy provides natural boundaries of management responsibility and minimizes the number of entities that a management tool must be aware of. Both distribution and hierarchy are fundamental to any long-term management solution. The client server model allows for increased scalability as servers and clients may be added as the number of network managers increase and as the network grows.
The various NMS programs may be written in the JAVA programming language to enable the programs to run on both Windows/NT and UNIX platforms, such as Sun Solaris. In fact the code for both platforms may be the same allowing consistent graphical interfaces to be displayed to the network administrator. In addition to being native to JAVA, RMI is attractive as the RMI architecture includes (RMI) over Internet Inter-Orb Protocol (IIOP) which delivers Common Object Request Broker Architecture (CORBA) compliant distributed computing capabilities to JAVA. Like CORBA, RMI over IIOP uses IIOP as its communication protocol. IIOP eases legacy application and platform integration by allowing application components written in C++, SmallTalk, and other CORBA supported languages to communicate with components running on the JAVA platform. For “manage anywhere” purposes and web technology integration, the various NMS programs may also run within a web browser. In addition, the NMS programs may integrate with Hewlett Packard's (HP's) Network Node Manager (NNM™) to provide the convenience of a network map, event aggregation/filtering, and integration with other vendor's networking. From HP NNM a context-sensitive launch into an NMS server may be executed.
The NMS server also keeps track of important statistics including average client/server response times and response times to each network device. By looking at these statistics over time, it is possible for network administrators to determine when it is time to grow the management system by adding another server. In addition, each NMS server gathers the name, IP address and status of other NMS servers in the telecommunication network, determines the number of NMS clients and network devices to which it is connected, tracks its own operation time, the number of transactions it has handled since initialization, determines the “top talkers” (i.e., network devices associated with high numbers of transactions with the server), and the number of communications errors it has experienced. These statistics help the network administrator tune the NMS to provide better overall management service.
NMS database 61 may be remote or local with respect to the network device(s) that it is managing. For example, the NMS database may be maintained on a computer system outside the domain of the network device (i.e., remote) and communications between the network device and the computer system may occur over a wide area network (WAN) or the Internet. Preferably, the NMS database is maintained on a computer system within the same domain as the network device (i.e., local) and communications between the network device and the computer system may occur over a local area network (LAN). This reduces network management traffic over a WAN or the Internet.
Many telecommunications networks include domains in various geographical locations, and network managers often need to see data combined from these different domains to determine how the overall network is performing. To assist with the management of wide spread networks and still minimize the network management traffic sent over WANs and the Internet, each domain may include an NMS database 61 and particular/selected data from each NMS database may be replicated (or “rolled up”) to remote NMS databases 854a-854n that are in particular centralized locations. Referring to
Network administrators use the NMS clients to configure network devices in each of the domains through the NMS servers. The network devices replicate changes made to their internal configuration databases (42,
Logical System Model:
As previously mentioned, to avoid having to manually synchronize all integration interfaces between the various programs, the APIs for both NMS and network device programs are generated using a code generation system from the same logical system model. In addition, the APIs for the data repository software used by the programs are also generated from the same logical system model to ensure that the programs use the data in the same way. Each model within the logical system model contains metadata defining an object/entity, attributes for the object and the object's relationships with other objects. Upgrading/modifying an object is, therefore, much simpler than in current systems, since the relationship between objects, including both hardware and software, and attributes required for each object are clearly defined in one location. When changes are made, the logical system model clearly shows what other programs are affected and, therefore, may also need to be changed. Modeling the hardware and software provides a clean separation of function and form and enables sophisticated dynamic software modularity.
A code generation system uses the attributes and metadata within each model to generate the APIs for each program and ensure lockstep synchronization. The logical model and code generation system may also be used to create test code to test the network device programs and NMS programs. Use of the logical model and code generation system saves development, test and integration time and ensures that all relationships between programs are in lockstep synchronization. In addition, use of the logical model and code generation system facilitates hardware portability, seamless extensibility and unprecedented availability and modularity.
Referring to
Hardware model 284 includes models for all hardware that may be available on computer system 10 (FIG. 1)/network device 540 (
Service endpoint model 314 spans the software and hardware models within logical model 280. It is a parent class including a physical service endpoint model 312 and a logical service endpoint model 316. Since the links between the software model and hardware model are minimal, either may be changed (e.g., upgraded or modified) and easily integrated with the other. In addition, multiple models (e.g., 280) may be created for many different types of managed devices (e.g., 282). The software model may be the same or similar for each different type of managed device even if the hardware—and hardware models—corresponding to the different managed devices are very different. Similarly, the hardware model may be the same or similar for different managed devices but the software models may be different for each. The different software models may reflect different customer needs.
Software model 286 includes models of data objects used by each of the software processes (e.g., applications, device drivers, system services) available on computer system 10/network device 540. All applications and device drivers may not be used in each computer system/network device. As one example, ATM model 318 is shown. It should be understood that software model 286 may also include models for other applications, for example, Internet Protocol (IP) applications, Frame Relay and Multi-Protocol Label Switching (MPLS) applications. Models of other processes (e.g., device drivers and system services) are not shown for convenience.
For each process, models of configurable objects managed by those processes are also created. For example, models of ATM configurable objects are coupled to ATM model 318, including models for a soft permanent virtual path (SPVP) 320, a soft permanent virtual circuit (SPVC) 321, a switch address 322, a cross-connection 323, a permanent virtual path (PVP) cross-connection 324, a permanent virtual circuit (PVC) cross-connection 325, a virtual ATM interface 326, a virtual path link 327, a virtual circuit link 328, logging 329, an ILMI reference 330, PNNI 331, a traffic descriptor 332, an ATM interface 333 and logical service endpoint 316. As described above, logical service endpoint model 316 is coupled to service endpoint model 314. It is also coupled to ATM interface model 333.
The logical model is layered on the physical computer system to add a layer of abstraction between the physical system and the software applications. Adding or removing known (i.e., not new) hardware from the computer system will not require changes to the logical model or the software applications. However, changes to the physical system, for example, adding a new type of board, will require changes to the logical model. In addition, the logical model is modified when new or upgraded processes are created. Changes to an object model within the logical model may require changes to other object models within the logical model. It is possible for the logical model to simultaneously support multiple versions of the same software processes (e.g., upgraded and older). In essence, the logical model insulates software applications from changes to the hardware models and vice-versa.
To further decouple software processes from the logical model—as well as the physical system—another layer of abstraction is added in the form of version-stamped views. A view is a logical slice of the logical model and defines a particular set of data within the logical model to which an associated process has access. Version stamped views allow multiple versions of the same process to be supported by the same logical model since each version-stamped view limits the data that a corresponding process “views” or has access to, to the data relevant to the version of that process. Similarly, views allow multiple different processes to use the same logical model.
Code Generation System:
Referring to
The code generation system also creates a data definition language (DDL) file 344 including structured query language (SQL) commands used to construct the database schema, that is, the various tables and views within a configuration database 346, and a DDL file 348 including SQL commands used to construct various tables and SQL views within a network management (NMS) database 350 (described below). This is also referred to as converting the logical model into a database schema and various SQL views look at particular portions of that schema within the database. If the same database software is used for both the configuration and NMS databases, then one DDL file may be used for both.
The databases do not have to be generated from a logical model for views to work. Instead, database files can be supplied directly without having to generate them using the code generation system. Similarly, instead of using a logical model as an input to the code generation system, a MIB “model” may be used. For example, relationships between various MIBs and MIB objects may be written (i.e., coded) and then this “model” may be used as input to the code generation system.
Referring to
Views also allow the logical model and physical system to be changed, evolved and grown to support new applications and hardware without having to change existing applications. In addition, software applications may be upgraded and downgraded independent of each other and without having to re-boot computer system 10/network device 540. For example, after computer system 10 is shipped to a customer, changes may be made to hardware or software. For instance, a new version of an application, for example, ATM version 2.0, may be created or new hardware may be released requiring a new or upgraded device driver process. To make this a new process and/or hardware available to the user of computer system 10, first the software image including the new process must be re-built.
Referring again to
Again referring to
Prior to shipping computer system 10 to customers, a software build process is initiated to establish the software architecture and processes. The code generation system is the first part of this process. Following the execution of the code generation system, each process when pulled into the build process links the associated view id and API into its image. For example, referring to
Referring to
Referring to
When the computer system is powered-up for the first time, as described below, configuration database software uses DDL file 867 to create a configuration database 42 with the necessary configuration tables and active queries. The NMS database software uses DDL file 868 to create NMS database 61 with corresponding configuration tables. Memory and storage space within network devices is typically very limited. The configuration database software is robust and takes a considerable amount of these limited resources but provides many advantages as described below.
As described above, logical model 280 (
Instead, of providing a logical model (e.g., 280,
In addition to providing view ids and APIs, the code generation system may also provide code used to push data directly into a third party code API. For example, where an API of a third party program expects particular data, the code generation system may provide this data by retrieving the data from the central repository and calling the third-party programs API. In this situation, the code generation system is performing as a “data pump”.
Configuration:
Once the network device programs have been installed on network device 540 (
If the administrator's profile includes the appropriate authority, then the administrator may add new devices to list 898b. To add a new device, the administrator selects Devices branch 898a and clicks the right mouse button to cause a pop-up menu 898c (
To configure a network device, the administrator begins by selecting (step 874,
Referring to
GUI 895 also includes several splitter bars 895a-895c (
Device mimic 896a may also provide one or more visual indications as to whether a card is present in each slot or whether a slot is empty. For example, in one embodiment, the forwarding cards (e.g., 546a and 548e) in the upper portion of the network device are displayed in a dark color to indicate the cards are present while the lower slots (e.g., 928a and 929e) are shown in a lighter color to indicate that the slots are empty. Other visual indications may also be used. For example, a graphical representation of the actual card faceplate may be added to device mimic 896a when a card is present and a blank faceplate may be added when the slot is empty. Moreover, this may be done for any of the cards that may or may not be present in a working network device. For example, the upper cross-connection cards may be displayed in a dark color to indicate they are present while the lower cross-connection card slots may be displayed in a lighter color to indicate the slots are empty.
In addition, a back view and other views of the network device may also be shown. For example, the administrator may use a mouse to move a cursor into an empty portion of graphic window 896b and click the right mouse button to cause a pop-up menu to appear listing the various views available for the network device. In one embodiment, the only other view is a back view and pop-up menu 927 is displayed. Alternatively, short cuts may be set up. For example, double clicking the left mouse button may automatically cause graphic 896a to display the back view of the network device, and another double click may cause graphic 896a to again display the front view. As another alternative, a pull down menu may be provided to allow an administrator to select between various views.
Device mimic 896a is shown in
Since the GUI has limited screen real estate and the network device may be large and loaded with many different types of components (e.g., modules, ports, fan trays, power connections), in addition to the device mimic views described above, GUI 895 may also provide a system view menu option 954 (
Device mimic 896a may also indicate the status of components. For example, ports and/or cards may be green for normal operation, red if there are errors and yellow if there are warnings. In one embodiment, a port may be colored, for example, light green or gray if it is available but not yet configured and colored dark green after being configured. Other colors or graphical textures may also be used show visible status. To further ease a network administrator's tasks, the GUI may present pop-up windows or tool tips containing information about each card and/or port when the administrator moves the cursor over the card or port. For example, when the administrator moves the cursor over universal port card 556f (
The views are used to provide management context. The GUI may also include a configuration/service status window 897 for displaying current configuration and service provisioning details. Again, these details are provided to the NMS client by the NMS server, which reads the data from the network device's configuration database. The status window may include many tabs/folders for displaying various data about the network device configuration. In one embodiment, the status window includes a System tab 934 (
The status window may also include a Modules tab 936 (
The status window may also include a Ports tab 938 (
Another tab in the status window may be a SONET Interface tab 940 (
The System tab data as well as the Modules tab, Ports tab and SONET Interface tab data all represent physical aspects of the network device. The remaining tabs, including SONET Paths tab 942 (
The SONET Path configuration wizard guides the administrator through the task of setting up a SONET Path by presenting the administrator with valid configuration options and inserting default parameter values. As a result, the process of configuring SONET paths is simplified, and required administrator expertise is reduced since the administrator does not need to know or remember to provide each parameter value. In addition, the SONET Path wizard allows the administrator to configure multiple SONET Paths simultaneously, thereby eliminating the repetition of similar configuration process steps required by current network management systems and reducing the time required to configure many SONET Paths. Moreover, the wizard validates configuration requests from the administrator to minimize the potential for mis-configuration.
In one embodiment, the SONET Path wizard displays SONET line data 944a (e.g., slot 4, port 1, OC12) and three configuration choices 944b, 944c and 944d. The first two configuration choices provide “short cuts” to typical configurations. If the administrator selects the first configuration option 944b (
If the administrator selects the second configuration option 944c (
The third configuration option allows the administrator to custom configure a port thereby providing the administrator with more flexibility. If the administrator selects the third configuration option 944d (
In any of the SONET Path windows (
Once the administrator selects the OK button, the NMS client validates the parameters as far as possible within the client's view of the device and passes (step 880,
As just described, the configuration process provides a tiered approach to validation of configuration data. The NMS client validates configuration data received from an administrator according to its view of the network device. Since multiple clients may manage the same network device through the same NMS server, the NMS server re-validates received configuration data. Similarly, because the network device may be managed simultaneously by multiple NMS servers, the network device itself re-validates received configuration data. This tiered validation provides reliability and scalability to the NMS.
The configuration database software then sends (step 884) active query notices, described in more detail below, to appropriate applications executing within the network device to complete the administrator's configuration request (step 885). Active query notices may also be used to update the NMS database with the changes made to the configuration database. In addition, a Configuration Synchronization process running in the network device may also be notified through active queries when any configuration changes are made or, perhaps, only when certain configuration changes are made. As previously mentioned, the network device may be connected to multiple NMS Servers. To maintain synchronization, the Configuration Synchronization program broadcasts configuration changes to each attached NMS server. This may be accomplished by issuing reliable (i.e., over TCP) SNMP configuration change traps to each NMS server. Configuration change traps received by the NMS servers are then multicast/broadcast to all attached NMS clients. Thus, all NMS servers, NMS clients, and databases (both internal and external to the network device) remain synchronized.
Even a simple configuration request from a network administrator may require several changes to one or more configuration database tables. Under certain circumstances, all the changes may not be able to be completed. For example, the connection between the computer system executing the NMS and the network device may go down or the NMS or the network device may crash in the middle of configuring the network device. Current network management systems make configuration changes in a central data repository and pass these changes to network devices using SNMP “sets”. Since changes made through SNMP are committed immediately (i.e., written to the data repository), an uncompleted configuration (series of related “sets”) will leave the network device in a partially configured state (e.g., “dangling” partial configuration records) that is different from the configuration state in the central data repository being used by the NMS. This may cause errors or a network device and/or network failure. To avoid this situation, the configuration database executes groups of SQL commands representing one configuration change as a relational database transaction, such that none of the changes are committed to the configuration database until all commands are successfully executed. The configuration database then notifies the server as to the success or failure of the configuration change and the server notifies the client. If the server receives a communication failure notification, then the server re-sends the SQL commands to re-start the configuration changes. Upon the receipt of any other type of failure, the client notifies the user.
If the administrator now selects the same port 939a (
The SONET path wizard provides the administrator with available and valid configuration options. The options are consistent with constraints imposed by the SONET protocol and the network device itself. The options may be further limited by other constraints, for example, customer subscription limitations. That is, ports or modules may be associated with particular customers and the SONET Path wizard may present the administrator with configuration options that match services to which the customer is entitled and no more. For example, a particular customer may have only purchased service on two STS-3c SONET paths on an OC12 SONET port, and the SONET Path wizard may prevent the administrator from configuring more than these two STS-3c SONET paths for that customer.
By providing default values for SONET Path parameters and providing only configuration options that meet various protocol, network device and other constraints, the process of configuring SONET paths is made simpler and more efficient, the necessary expertise required to configure SONET paths is reduced and the potential for mis-configurations is reduced. In addition, as the administrator provides input to the SONET path configuration wizard, the wizard validates the input and presents the administrator with configuration options consistent with both the original constraints and the administrator's configuration choices. This further reduces the necessary expertise required to configure SONET paths and further minimizes the potential for mis-configurations. Moreover, short cuts presented to the administrator may increase the speed and efficiency of configuring SONET paths.
If the administrator now selects SONET path tab 942 (
Similarly, if the administrator selects an ATM Interfaces button 942c or directly selects the ATM-Interfaces tab 946 (
Referring to
If the administrator selects option 944b (
Now when the administrator selects SONET Paths tab 942 (
Instead of selecting a port in device mimic 896a and then the Configure SONET Paths option from a pop-up menu and instead of selecting a SONET interface in the SONET Interfaces tab and then selecting the Paths button, the SONET Path wizard may be accessed by the administrator from any view in the GUI by simply selecting a Wizard menu button 951 and then selecting a SONET Path option 951a (
To create virtual connections between various ATM Interfaces/SONET Paths within the network device, the administrator first needs to create one or more virtual ATM interfaces for each ATM interface. At least two virtual ATM interfaces are required since two discrete virtual ATM interfaces are required for each virtual connection. In the case of a multipoint connection there will be one root ATM interface and many leafs. To do this, the administrator may select an ATM interface (e.g., 946b) from the inventory in the ATM Interfaces tab and then select a Virtual Interfaces button 946g to cause Virtual Interfaces tab 947 (
The Virtual ATM Interfaces tab also includes a device navigation tree 947a. The navigation tree is linked with the Virtual Interfaces button 946g (
Instead the administrator may directly select Virtual ATM Interfaces tab 947 and then use the device tree 947a to locate the ATM interface they wish to configure with one or more virtual ATM interfaces. In this instance, the NMS client may again automatically request virtual interface data from the NMS server, or instead, the NMS client may simply use data stored in cache.
To return to the ATM Interfaces tab, the administrator may select a Back button 947d or directly select the ATM Interfaces tab. Once the appropriate ATM interface has been selected (e.g., ATM-Path2—11/4/1) in the Virtual ATM Interfaces tab device tree 947a, then the administrator may select an ADD button 947b to cause a virtual ATM (V-ATM) Interfaces dialog box 950 (
GUI 895 automatically fills in dialog box 950 with default values for Connection type 950a, Version 950b and Administration Status 950c. The administrator may provide a Name or Alias 950d and may modify the other three parameters by selecting from the options provided in pull down menus. This and other dialog boxes may also have wizard-like properties. For example, only valid connection types, versions and administrative status choices are made available in corresponding pull-down menus. For instance, Version may be UNI Network 3.1, UNI Network 4.0, IISP User 3.0, IISP User 3.1, PNNI, IISP Network 3.0 or IISP Network 3.1, and Administration Status may be Up or Down. When Down is selected, the virtual ATM interface is created but not enabled. With regard to connection type, for the first virtual ATM interface created for a particular ATM interface, the connection type choices include Direct Link or Virtual Uni. However, for any additional virtual ATM interfaces for the same ATM interface the connection type choices include only Logical Link. Hence the dialog box provides valid options to further assist the administrator. When finished, the administrator selects an OK button 950e to accept the values in the dialog box and cause the virtual ATM interface (e.g., 947c,
The administrator may then select ADD button 947b again to add another virtual ATM interface to the selected ATM interface (ATM-Path2—11/4/1). Instead, the administrator may use device tree 947a to select another ATM interface, for example, ATM path 946c (
To create a virtual connection, the administrator selects a virtual ATM interface (e.g., 947c,
The Virtual Connection configuration wizard includes a Connection Topology panel 952a and a Connection Type panel 952b. Within the Connection Topology panel the administrator is asked whether they want a point-to-point or point-to-multipoint connection, and within the Connection Type panel, the administrator is asked whether they want a Virtual Path Connection (VPC) or a Virtual Channel Connection (VCC). In addition, the administrator may indicate that they want the VPC or VCC made soft (SPVPC/SPVCC). Where the administrator chooses a point-to-point, VPC connection, the Virtual Connection wizard presents dialog box 953 (
The source (e.g., test1 in End Point 1 window 953a) for the point-to-point connection is automatically set to the virtual ATM interface (e.g., 947c,
The virtual Connection wizard also contains a Connections Parameters window 953e, an End Point 1 Parameters window 953f and an End Point 2 Parameters window 953g. Again for point-to-multipoint, there will be multiple End Point 2 Parameters windows. Within the Connections Parameters window, the administrator may provide a Connection name (e.g., test). The administrator also determines whether the connection will be configured in an Up or Down Administration Status, and may provide a Customer Name (e.g., Walmart) or select one from a customer list, which may be displayed by selecting Customer List button 953h.
Within the End Point 1 and 2 Parameters windows, the administrator provides a Virtual Path Identifier (VPI) in window 953i, 953j or selects a Use Any VPI Value indicator 953k, 9531. If the administrator chooses a VCC connection in Connection Type window 952b (
Within the Virtual Connection wizard, the administrator may select a Back button 953u (
The Virtual Connections tab also includes a device navigation tree 948c. The device tree is linked with Virtual Connections button 947d such that the device tree highlights the virtual ATM interface that was selected in Virtual ATM Interfaces tab 947 when the Virtual Connections button was selected. The Virtual Connections tab then only displays data relevant to the highlighted portion of the device tree.
As described above, the SONET Paths tab, ATM Interfaces tab, Virtual ATM Interfaces tab and Virtual Connections tabs are configuration tabs that are chained together providing wizard-like properties. Both the order of the tabs from right to left and the forward buttons (e.g., ATM Interfaces button 942c) and back buttons (e.g., Back button 946h) allow an administrator to easily and quickly sequence through the steps necessary to provision services. Although device navigation trees were shown in only the Virtual ATM Interface tab and the Virtual Connection tab, a device navigation tree may be included in each tab and only data relevant to the highlighted portion of the navigation tree may be displayed.
In addition to the SONET Interface and SONET Paths tabs, the status window may include tabs for other physical layer protocols, for example, Ethernet. Moreover, in addition to the ATM Interfaces and Virtual ATM Interfaces tabs, the status window may include tabs for other upper layer protocols, including MPLS, IP and Frame Relay. Importantly, other configuration wizards in addition to the SONET Path configuration wizard and Virtual Connection configuration wizard may also be used to simplify service provisioning.
Custom Navigator:
In typical network management systems, the graphical user interface (GUI) provides static choices and is not flexible. That is, the screen flow provided by the GUI is predetermined and the administrator must walk through a predetermined set of screens each time a service is to be provisioned. To provide flexibility and further simplify the steps required to provision services within a network device, GUI 895, described in detail above, may also include a custom navigator tool that facilitates “dynamic menus”. When the administrator selects the custom navigator menu button 958 (
When the administrator selects a particular screen mark, the custom navigator shortcuts the configuration process by jumping forward past various configuration screens to a particular configuration screen corresponding to the screen mark. For example, if the administrator selects a Virtual ATM IF screen mark 958b, the custom navigator presents the Virtual ATM Interface tab (
Moreover, the custom navigator allows the administrator to create unique screen marks. For example, the administrator may provision SONET paths and ATM interfaces as described above, then select an ATM interface (e.g., 946b,
As a result, the administrator is provided with configuration short cuts, both default short cuts and ones created by the administrator himself. Many other screen marks may be created through GUI 895, and in each case, the screen marks may simplify the configuration process and save the administrator configuration time.
Custom Wizard:
To provide additional flexibility and efficiency, an administrator may use a custom wizard tool to create unique custom wizards to reflect common screen sequences used by the administrator. To create a custom wizard, the administrator begins by selecting a Custom Wizard menu button 960 (
The administrator may continue to select further screens to add to the new custom wizard (for example, by selecting an ATM interface from device tree 947a and then selecting the Add button 947b to cause the Add V-ATM Interface dialog box 950 (
To access a custom wizard, the administrator again selects Custom Wizard 960 menu button and then selects a Select Wizard option 960e to cause an inventory 960f of custom wizards to be displayed. The administrator then selects a custom wizard (e.g., test), and the custom wizard automatically presents the administrator with the first screen of that wizard. In the continuing example, the custom navigator presents SONET Path configuration wizard screen 961 (
Off-Line Configuration:
There may be times when a network manager/administrator wishes to jump-start initial configuration of a new network device before the network device is connected into the network. For example, a new network device may have been purchased and be in the process of being delivered to a particular site. Generally, a network manager will already know how they plan to use the network device to meet customer needs and, therefore, how they would like to configure the network device. Because configuring an entire network device may take considerable time once the device arrives and because the network manager may need to get the network device configured as soon as possible to meet network customer needs, many network managers would like the ability to perform preparatory configuration work prior to the network device being connected into the network.
In the current invention, network device configuration data is stored in a configuration database within the network device and all changes to the configuration database are copied in the same format to an external NMS database. Since the data in both databases (i.e., configuration and NMS) is in the same format, the present invention allows a network device to be completely configured “off-line” by entering all configuration data into an NMS database using GUI 895 in an off-line mode. When the network device is connected to the network, the data from the NMS database is reliably downloaded to the network device as a group of SQL commands using a relational database transaction. The network device then executes the SQL commands to enter the data into the internal configuration database, and through the active query process (described below), the network device may be completely and reliably configured.
Referring to
Referring to
Again, the cursor provides context sensitive pop-up windows. For example, the network manager may move the cursor over a particular slot (e.g., 896c,
If there are multiple types of modules that may be inserted in a particular slot, then a dialog box will appear after the network manager selects the Add Module option and the network manager will select the particular module that the network device will include in this slot upon delivery. For example, while viewing the back of the chassis (
Typically, a network device may include many similar modules, for example, many 16 port OC3 universal port cards and many forwarding cards. Instead of having the network manager repeat each of the steps described above to add a universal port card or a forwarding card, the network manager may simply select an inserted module (e.g., 16 port OC3 universal port card 556h,
Once the network manager is finished adding appropriate modules into the empty slots such that the device mimic represents the physical hardware that will be present in the new network device, then the network manager may configure/provision services within the network device. Off-line configuration is the same as on-line configuration, however, instead of sending the configuration data to the configuration database within the network device, the NMS server stores the configuration data in an external NMS database. After the network device arrives and the network manager connects the network device's ports into the network, the network manager selects the device (e.g., 192.168.9.201,
The NMS client notifies the NMS server that the device is now to be managed on-line. The NMS server first reconciles the physical configuration created by the network manager and stored in the NMS database against the physical configuration of the actual network device and stored in the internal configuration database. If there are any mis-matches, the NMS server notifies the NMS client, which then displays any discrepancies to the network manager. After the network manager fixes any discrepancies, the network manager may again select the Manage On-Line option in pop-up menu 898o. If there are no mis-matches between the physical device tables in the NMS database and the configuration database, then the NMS server reconciles all service provisioning data in the NMS database against the service provisioning data in the configuration database. In this example, the network device is new and thus, the configuration database has no service provisioning data. Thus, the reconciliation will be successful.
The NMS server then instructs the network device to stop replication between the primary configuration database within the network device and the backup configuration database within the network device. The NMS server then pushes the NMS database data into the backup configuration database, and then instructs the network device to switchover from the primary configuration database to the backup configuration database. If any errors occur after the switchover, the network device may automatically switch back to the original primary configuration database. If there are no errors, then the network device is quickly and completely configured to work properly within the network while maximizing network device availability.
In the previous example, the network manager configured one new network device off-line. However, a network manager may configure many new network devices off-line. For example, a network manager may be expecting the receipt of five or more new network devices. Referring to
A network manager may also choose to re-configure an operational device in off-line mode without affecting the operation of the network device. For example, the network manager may want to add one or more new modules or provision services in a network device during a time when the network sees the least amount of activity, for example, midnight. Through the off-line mode, the network manager may prepare the configuration data ahead of time.
Referring to
The NMS client notifies the NMS server that the device is now to be managed on-line. The NMS server first reconciles the physical configuration stored in the NMS database (or the temporary NMS database) against the physical configuration of the actual network device stored in the internal configuration database. If there are any mismatches, the NMS server notifies the NMS client, which then displays any discrepancies to the network manager. After the network manager fixes any discrepancies, the network manager may again select the Manage On-Line option in pop-up menu 898o. If there are no mismatches between the physical device tables in the NMS database and the configuration database, then the NMS server reconciles all service provisioning data in the NMS database (or the temporary NMS database) against the service provisioning data in the configuration database. If any conflicts are discovered, the NMS server notifies the NMS client, which displays the discrepancies to the network manager. After fixing any discrepancies, the network manager may again select the Manage On-Line option in pop-up menu 898o.
If there are no conflicts, the NMS server instructs the network device to stop replication between the primary configuration database within the network device and the backup configuration database within the network device. The NMS server then pushes the NMS database data into the backup configuration database, and then instructs the network device to switchover from the primary configuration database to the backup configuration database. If any errors occur after the switchover, the network device may automatically switch back to the original primary configuration database. If there are no errors, then the network device is quickly re-configured to work properly within the network.
Off-line configuration, therefore, provides a powerful tool to allow network managers to prepare configuration data prior to actually implementing any configuration changes. Such preparation, allows a network manager to carefully configure a network device when they have time to consider all their options and requirements, and once the network manager is ready, the configuration changes are implemented quickly and efficiently.
FCAPS Management:
Fault, Configuration, Accounting, Performance and Security (FCAPS) management are the five functional areas of network management as defined by the International Organization for Standardization (ISO). Fault management is for detecting and resolving network faults, configuration management is for configuring and upgrading the network, accounting management is for accounting and billing for network usage, performance management is for overseeing and tuning network performance, and security management is for ensuring network security. Referring to
Each FCAP button may be colored according to a hierarchical color code where, for example, green means normal operation, red indicates a serious error and yellow indicates a warning status. Today there are many NMSs that indicate faults through color coded icons or other graphics. However, current NMSs do not categorize the errors or warnings into the ISO five functional areas of network management—that is, FCAPS. The color-coding and order of the FCAPS buttons provide a “status bar code” allowing a network administrator to quickly determine the category of error or warning and quickly take action to address the error or warning.
As with current NMSs, a network administrator may actively monitor the FCAPS buttons by sitting in front of the computer screen displaying the GUI. Unfortunately, network administrators do not have time to actively monitor the status of each network device—passive monitoring is required. To assist passive monitoring, the FCAPS buttons may be enlarged or “stretched” to fill a large portion of the screen, as shown in
The network administrator may set the FCAPS buttons to represent a single network device or multiple network devices or all the network devices in a particular network. Alternatively, the network administrator may have the GUI display two or more FCAPS status bars each of which represents one or more network devices.
Although the FCAPS buttons have been described as a string of multiple stretched bars, many different types of graphics may be used to display FCAPS status. For example, different colors may be used to represent normal operation, warnings and errors, and additional colors may be added to represent particular warnings and/or errors. Instead of a bar, each letter (e.g., F) may be stretched and color-coded. Instead of a solid color, each FCAPS button may repeatedly flash or strobe a color. For example, green FCAPS buttons may remain solid (i.e., not flashing) while red errors and yellow warnings are displayed as a flashing FCAPS button to quickly catch a network administrator's attention. As another example, green/normal operation FCAPS buttons may be a different size relative to yellow/warnings and red/errors FCAPS buttons. For example, an FCAPS button may be automatically enlarged if status changes from good operation to a warning status or an error status. In addition, the FCAPS buttons may be different sizes to allow the network administrator to distinguish between each FCAPS button from a further distance. For example, the buttons may have a graduated scale where the F button is the largest and each button is smaller down to the S button, which is the smallest. Alternatively, the F button may be the smallest while the S button is the largest, or the A button in the middle is the largest, the C and P buttons are smaller and the F and S buttons are smallest. Many variations are possible for quickly alerting a network administrator of the status of each functional area.
Referring to
Events tab 957a (
Referring to
If ATM protocol branch 958c is selected, then tabs/folders holding ATM protocol information are displayed, for example, Private Network-to-Network Interface (PNNI) tab 959 (
If Virtual Connections branch 958e is selected, then tabs/folders holding virtual connection information are displayed, for example, Soft Permanent Virtual Circuit (PVC) tab 960a (
For detailed accounting information, the administrator may select Accounting branch 898r (
For detailed performance information, the administrator may select Performance branch 898s (
If the administrator selects ATM sub-branch 958g (
If the administrator selects Connections sub-branch 958h (
If the administrator selects Interfaces sub-branch 958i (
Referring to
Referring to
Dynamic Bulletin Boards:
Graphical User Interface (GUI) 895 described in detail above provides a great deal of information to a network administrator to assist the administrator in managing each network device in a telecommunications network. As shown, however, this information is contained in a large number of GUI screens/tabs. There may be many instances when a network administrator may want to simultaneously view multiple screens/tabs. To provide network managers with more control and flexibility personal application bulletin boards (PABBs, i.e., dynamic bulletin boards) are provided that allow the network administrator to customize the information they view by dragging and dropping various GUI screens/tabs (e.g., windows, table entries, dialog boxes, panels, device mimics, etc.) from GUI 895 onto one or more dynamic bulletin boards. This allows the administrator to consolidate several GUI screens and/or dialog boxes into a single view. The information in the dynamic bulletin board remains linked to the GUI such that both the GUI and the bulletin boards are dynamically updated if the screens in either the. GUI or in the bulletin boards are changed. As a result, the administrator may manage and/or configure network devices through the GUI screens or the dynamic bulletin board. Within the dynamic bulletin boards, the administrator may change the format of the data and, perhaps, view the same data in multiple formats simultaneously. Moreover, the administrator may add information to one dynamic bulletin board from multiple different network devices to allow the administrator to simultaneously manage and/or configure the multiple network devices. The dynamic bulletin boards provide an alternative viewing environment, and administrators can, therefore, choose what they want to view, when they want to view it and how they want to view it.
Referring to
Referring to
The administrator may then select other GUI data to drag and drop onto bulletin board 970a. Referring to
The administrator may then select other GUI data from the same network device (e.g., system 192.168.9.201) to drag and drop to the bulletin board or the administrator may select a different network device (e.g., system 192.168.9.202,
As shown in
An administrator may wish to view an item dragged to a bulletin board in a different format than that displayed in the GUI. The different format may, for example, have more meaning to them or provide more clarity to the task at hand. For instance, after dragging and dropping ATM Stats In tab 963a to bulletin board 970a (
Referring to
Although the above examples used the ATM Stats In and Out tabs, it is to be understood that any of the tabs or entries within tabs in status window 897 may be capable of being dragged and dropped into one or more dynamic bulletin boards. In addition, an administrator may drag and drop one or more of the FCAPS buttons 899a-899e (
Referring to
Referring to
A network administrator may save one or more dynamic bulletin boards before exiting out of the NMS client, and the NMS client may persist this data in the administrator's profile (described below). When the administrator logs in to the same or a different NMS client and selects Bulletin Bd option 968a (
Through saved bulletin boards, a senior administrator may guide and instruct junior administrators through various tasks. For example, a senior administrator may drag and drop a sequence of GUI screens onto one or more bulletin boards where the sequence of GUI screens represent a series of steps that the senior administrator wants the junior administrator to take to complete a particular task (e.g., provisioning a SONET path). In addition to providing the series of steps, the senior administrator may fill in various parameters (e.g., traffic descriptors) to indicate to junior administrators the default parameters the senior administrator wants them to use. The saved bulletin board may then be added to the junior administrator's profile or put in a master profile accessible by multiple users. The junior administrator may then use a saved bulletin board to interactively complete provisioning tasks similar to the task shown in the saved bulletin board. For example, the junior administrator may use the saved SONET path bulletin board to provision one or more different SONET paths. In effect, then saved bulletin boards behave as custom wizards.
As described above, the dynamic bulletin boards allow a network administrator to actively monitor—simultaneously—specific information about one or more operational network devices. This provides a powerful customization tool for the administrator of large, complex network devices in large, complex telecommunications networks. By customizing views of one or more devices, the administrator may view only the data they need to see and in a format that best meets their needs.
Custom Object Collections:
As described above with respect to FCAPS management, a network device (e.g., 10,
Referring to
Referring to
Referring to
Alternatively, the network manager may add an object to a collection by dragging and dropping an object from an FCAPs tab onto a collection branch in a navigation tree. Referring to
When a collection is selected by a network manager, customer or other user, for example, by double clicking on the collection name in a navigation tree or pull down menu, the tabs in service status window 897 are changed to include only objects in the selected collection. For instance, if the collection includes only SONET path objects, then only the SONET Paths tab will include objects once the collection is selected and all other tabs will not include any objects. Alternatively, the other tabs in service status window 897 may include objects corresponding to or related to the objects in the selected collection.
Referring to
To remove an object from a collection, the network manager selects an object and then selects a Remove button 982. The network manager may also select an object and double click the left mouse button to cause a dialog box to appear. The network manager may edit certain parameters and then exit from the dialog box. Any changes made to an object in a collection are automatically updated in GUI 895. Similarly, any changes made to an object in GUI 895 are automatically updated in any and all collections including that object.
Custom object collections allow a user to view only those objects that are of interest. These may be a few objects from an otherwise very large object list in the same FCAPS tab (that is, the collection acts as a filter), and these may be a few objects from different FCAPS tabs (that is, the collection acts as an aggregator). Consequently, both flexibility and scalability are provided through custom object collections.
Custom object collections may also be used to restrict access to network objects. For example, a senior network administrator may establish a collection of objects and provide access to that collection to a junior network manager through the junior network manager's profile. In one embodiment, the junior network manager may not be provided with the full navigation tree 898 (
Similarly, collections may be created that include objects corresponding to a particular customer, for example, Walmart or Kmart. A customer profile may be established for each customer and one or more collections containing only objects relevant to each customer may be assigned to the relevant customer profile. Consequently, each customer is limited to viewing only those objects corresponding to their own accounts and not the accounts of any other customers. This permits Customer Network Management (CNM) without breaching the security provided to each customer account.
Profiles:
Profiles may be used by the NMS client to provide individual users (e.g., network managers and customers) with customized graphical user interfaces (GUIs) or views of their network and with defined management capabilities. For example, some network managers are only responsible for a certain set of devices in the network. Displaying all network devices makes their management tasks more difficult and may inadvertently provide them with management capabilities over network devices for which they are not responsible or authorized to perform. With respect to customers, profiles limit access to only those network device resources in a particular customer's network—that is, only those network device resources for which the customer has subscribed/paid. This is crucial to protecting the proprietary nature of each customer's network. Profiles also allow each network manager and customer to customize the GUI into a presentation format that is most efficient or easy for them to use. For example, even two users with access to the same network devices and having the same management capabilities may have different GUI customizations through their profiles. In addition, profiles may be used to provide other important information, for example, SNMP community strings to allow an NMS server to communicate with a network device over SNMP, SNMP retry and timeout values, and which NMS servers to use, for example, primary and secondary servers may be identified.
A network administrator is typically someone who powers up a network device for the first time, installs necessary software on the new network device as well as installs any NMS software on an NMS computer system, and adds any additional hardware and/or software to a network device. The network administrator is also the person that attaches physical network cables to network device ports. The first time GUI 895 is displayed to a network administrator, an NMS client application uses a default profile including a set of default values. Referring again to
To save a network manager's time, the profiles tab may also include a copy button 906. By selecting a profile 904 and clicking on the copy button, an existing profile is copied. The network manager may then change the parameters within the copied profile. This is helpful where two user profiles are to include the same or similar parameters.
To change the parameters in the network administrator's profile or any other existing profile, including a copied profile, the user double clicks on one of the profiles 904. To add a new profile, the user clicks on an Add button 905. In either case, the NMS client displays a profile dialog box 907 (
A group level access field 908d enables/disables various management capabilities (i.e., functionality available through the NMS client). Clicking on the group level access field may provide a list of available access levels. In one embodiment, access levels may include administrator, provisioner and viewer (e.g., customer), with administrator having the highest level of management capabilities and viewer having the lowest level of management capabilities (described in more detail below). In one embodiment, users can create profiles for other users at or below their own group access level. For example, a user at the provisioner access level can create user profiles for users at either the provisioner or viewer level but cannot create an administrator user profile.
A description may be added in a description field 908e, including, for example, a description of the user, phone number, fax number and/or e-mail address. A group name may be added to group field 908f, and a list of network device IP addresses may be provided in a device list field 908g. Alternatively, a domain name server (DNS) name may be provided and a host look up may be used to access the IP address of the corresponding device. Where a group name is provided, the list of network devices is associated with the group such that if the same group name is assigned to multiple user profiles, the users will be presented with the same view—that is, the same list of network devices in device list field 908g. For example, users from the same customer may share a group name corresponding to that customer. A wildcard feature is available for the group field. For example, perhaps an * or ALL may be used as a wildcard to indicate that a particular user is authorized to see all network devices. In most instances, the wildcard feature will only be used for a high-level network administrator. The list of devices indicates which network devices the user may manage or view, for example, configuration status and statistics data may be viewed.
Within a profile certain policy flags (i.e., attributes) may also be set. For example, a flag 908h may be set to indicate that the user is not allowed to change his/her password, and an account disable flag 908i may be set to disable a particular profile/account. In addition, a flag 908j may be set to allow the user to add network device IP addresses to device list field 908g, and a number may be added to a timeout field 908k to specify a number of minutes after which a user will be automatically logged out due to inactivity. A zero in this field or no value in this field may be used to indicate unlimited activity, that is, the user will never be automatically logged out.
The profile may also be used to indicate with which NMS servers the NMS client should communicate. An IP address or DNS name may be added to a primary server field 9081 and a secondary server field 908m. If the primary server fails, the client will access the secondary server. A port number may be added to primary server port field 908n and to secondary server port field 908o to indicate the particular ports that should be used for RMI connectivity to the primary and secondary NMS servers.
As described below, the information provided in a user profile is stored in tables within the NMS database, and when a user logs onto the network through an NMS client, the NMS client connects to an NMS server that retrieves the user's profile information and sends the information to the NMS client. The NMS client automatically saves the NMS server primary and secondary IP addresses and port numbers from the user's profile to a team session file associated with the user's username and password in a memory 986 (
The first time a user accesses an NMS client, however, no team session file or cookie will be available. Consequently, during the initial access of the NMS client, the NMS client may use a default IP address to connect with an NMS server or a pop-up menu 1034 (
User profiles and team session files/cookies allow a network administrator or provisioner to push down new NMS server IP addresses, port numbers and other information to users simply by changing those values in the user profiles. For example, an NMS server may be over loaded and a network administrator may wish to move some users from this NMS server to another less utilized NMS server. The administrator need only change the NMS server IP addresses and port numbers in the users' profiles to affect the switch. The NMS server sends the new IP addresses and port numbers to the one or more NMS clients through which the users are logged in, and the NMS clients save the new IP addresses and port numbers in each user's team session file or cookie. The next time the users log in, the NMS client(s) use the new IP addresses and port numbers in the team session files or cookies to access the appropriate NMS server. Thus, the users selected by the administrator are automatically moved to a different NMS server without the need to notify those users or take additional steps. In addition to saving IP addresses and perhaps port numbers in team session files/cookies, other information from the user profile may also be saved in team session files/cookies and changes to that information may be pushed down by the administrator simply by changing a user profile.
Referring again to
Instead of providing all the parameters and fields in a single profile dialog box, they may be separated into a variety of a tabbed dialog boxes (
In one embodiment, an administrator level user has both read and write access to the physical and logical objects of the NMS client. Thus, all screens and functionality are available to an administrator level user, and an administrator after physically attaching an external network attachment to a particular network device port may then enable that port and provision SONET paths on that port. All screens are available to a provisioner level user, however, they do not have access to all functionality as they are limited to read-only access of physical objects. For example, a provisioner can see SONET ports available on a device and can provision SONET paths on a port, but the provisioner cannot enable/disable a SONET port. In other words, a provisioner's power begins at the start of logical objects (not physical objects), for example, SONET paths, ATM interfaces, virtual ATM interfaces, and PVCs, and continues through all the configuration aspects of any object or entity that can be stacked on top of either a SONET path or ATM interface. A viewer (e.g., customer) level user has read-only access to logical entities and only those logical entities corresponding to their group name or listed in the device list field. A viewer may or may not have access to Fault, Configuration, Accounting, and Security categories of FCAPS relative to their devices.
A customer may install an NMS client at a customer site or, preferably, the customer will use a web browser to access the NMS client. To use the web browser, a service provider gives the customer an IP address corresponding to the service provider's site. The customer supplies the IP address to their web browser and while at the service provider site, the customer logs in with their username and password. The NMS client then displays the customer level GUI corresponding to that username and password.
Referring to
As an alternative to providing a Group Name 908f (
Each group may include one or more configured resources (e.g., SONET paths, VATM interfaces, ATM PVCs) within the network device, and the resources in each group may be related in some way. For instance, a group may include resources configured by a particular provisioner. As another example, a group may include configured resources purchased by a particular customer. For instance, Walmart Corporation may be a customer of a network service provider and each network device resource paid for/subscribed to by Walmart may be included in a Walmart group. In addition, if Walmart subscribes to a larger number of configured resources, the network service provider may create several groups within the same network device for Walmart, for example, Walmart-East may include network device resources associated with Walmart activities in the eastern half of the United States and Walmart-West may include network device resources associated with Walmart activities in the western half of the United States. In addition, the network service provider may create a Walmart-Total group including all configured resources within the network device paid for by Walmart. Various users may be given access to one or more groups. For example, a Walmart employee responsible for network service in the eastern half of the United States may be given access to only the Walmart-East group while another higher level Walmart employee is given access to both the Walmart-East and Walmart-West groups. In addition, the same group name may be used in multiple network devices to simplify tracking. Through profiles multiple users may be given access to the same or different groups of configured resources within each network device, and users may be given access to multiple groups of configured resources in different network devices.
When an administrator or a provisioner configures a network device resource, they may assign that resource to a particular group. For example, when an administrator or provisioner configures one or more SONET paths, they may assign each SONET path to a particular group. Referring to
In addition, the NMS server searches a Managed Resource Group table 1008 (
The NMS server also uses the SONET path data from the NMS client to add a row in a Managed Resource Table 1007 (
Just as each SONET path may be assigned to a group, each other type of configured resource/manageable entity within the network device may be assigned to a group. For example, when an administrator or provisioner configures a virtual ATM (VATM) interface, they may also assign the VATM interface to a group. Referring to
Instead of using a Managed Resource Group table and a Managed Resource table, the configured network device resource tables (e.g., SONET path table, Virtual ATM IF table, etc.) could include a group name field. However, the Managed Resource Group adds a layer of abstraction, which may allow each configured resource to belong to multiple groups. Moreover, the Managed Resource table provides scalability and modularity by not being tied to a particular resource type. That is, the Managed Resource table will include a row for each different type of configured resource and if the network device is upgraded to include new types of configurable resources, they too may be added to the Managed Resource table without having to upgrade other processes. If each configurable resource is limited to belonging to only one group, then the Managed Resource Table 1007 (
Referring again to
The NMS server also adds a row to a User Managed Device table 1012 (
The Administration Managed Device table includes a row for each network device (i.e., managed device) in the telecommunications network. To add a network device to the network, an administrator selects an Add Device option in a pop-up menu 898c (
The Administration Managed Device table, therefore, provides a centralized set of device records shared by all NMS servers, and since the records are centralized, the Administration Managed Device table facilitates centralized changes to the devices in the network. For example, a network device may be added to the network by adding a record and removed from the network by deleting a record. As another example, a network device's parameters (e.g., IP address) may be changed by modifying data in a record. Because the changes are made to centralized records accessed by all NMS servers, no change notifications need to be sent and the NMS servers may automatically receive the changed data during the next access of the table. Alternatively, the NMS server that makes a change to the central database may send notices out to each connected NMS client and other NMS servers in the network.
For newly added devices, after the information is input in the dialog box, the administrator selects an Add button 1013h causing the NMS client to send the data from the dialog box to the NMS server. Similarly, for changes to device data, after the information is changed in the dialog box, the administrator selects an OK button 1013i to cause the NMS client to send the data from the dialog box to the NMS server. For new devices, the NMS server uses the received information to add a row to Administration Managed Device table 1014 in NMS database 61, and for existing devices, the NMS server uses the received information to update a previously entered row in the Administration Managed Device table. For each managed device/row, the NMS server assigns a host LID (e.g., 9046) and inserts it in LID column 1014a.
When the NMS server adds a new row to the User Managed Device table 1012 (
After receiving user profile information from an NMS client, the NMS server also updates a User Resource Group Map table 1016 (
For each group name received by the NMS server, the NMS server searches a User Resource Group table 1018 (
After a user's profile is created, the user may log in through an NMS client (e.g., 850a,
In one embodiment, the user profile LMO is a JAVA object and a JAVA persistence layer within the NMS server creates the user profile LMO. For each persistent JAVA class/object, metadata is stored in a class table 1020 (
Referring to
The NMS server first retrieves metadata from class table 1020 associated with the user managed device properties LMO 1026. The metadata includes two simple attributes (retry 1026b and timeout 1026c) and one association attribute (managed device 1026a). The metadata causes the NMS server to search User Managed Device table 1012 (
In response to the managed device associated attribute, the NMS server retrieves metadata from class table 1020 associated with administration managed device properties LMO 1028. The metadata includes a list of simple attributes including host address 1028a, port address 1028b, SNMP retry value 1028c, SNMP timeout value 1028d and a database port address 1028e for connecting to the configuration database §within the network device. The metadata also includes simple attributes corresponding to passwords for each of the possible group access levels, for example, an administrator password 1028f, a provisioner password 1028g and a viewer password 1028h.
The NMS server uses the host LID (e.g., 9046) from column 1012c in the User Managed Device table (
The NMS server then inserts the newly created Administration Managed Device LMO 1028 into the corresponding User Managed Device Properties LMO 1026, and the NMS server also inserts each newly created User Managed Devices Properties LMO 1026 into User Profile LMO 1022. Thus, the information necessary for connecting to each network device listed in the user profile is made available within user LMO 1022.
The resource group maps association attribute 1022d (
In response to user resource group associated attribute 1030b, the NMS server creates a User Resource Group LMO 1032. The NMS server begins by retrieving metadata from class table 1020 corresponding to the User Resource Group LMO. The metadata includes three simple attributes: host address 1032a, port address 1032b and group name 1032c. The NMS server searches User Resource Group Map table 1016 (
The NMS server sends data from the user profile LMO to the NMS client to allow the NMS client to present the user with a graphical user interface such as GUI 895 shown in
Alternatively, a more robust set of data may be sent from the NMS server to the NMS client such that for each transaction issued by the NMS client, the data provided with the transaction eliminates the need for the NMS server to access the user profile LMO in its local memory. This reduces the workload of the NMS server, which will likely be sent transactions from many NMS clients. In one embodiment, the NMS server may send the NMS client the entire user profile LMO. Instead, the server may create a separate client user profile LMO that may present the data in a format expected by the NMS client and perhaps include only some of the data from the user profile LMO stored locally to the NMS server. In the preferred embodiment, the client user profile LMO includes at least data corresponding to each device in the user profile and each group selected within the user profile for each device. If the user selects one of the network devices listed in navigation tree 898, the NMS client includes the selected network device's IP address, the password corresponding to the user's group access level and the database port number in the “Get Network Device” transaction sent to the NMS server. The NMS server uses this information to connect to the network device and return the network device's physical data to the NMS client.
If the user selects a tab in configuration status window 897 that includes logical data corresponding to configured network device resources (e.g., SONET Paths tab 942 (
For example, if a user selects SONET Paths tab 942 (
The NMS server then searches column 1007c in the Managed Resource table 1007 (
When data is stored in tables within the same database, references from one table to another may provide a direct binding and referential integrity may be maintained by only deleting the upper most record—that is, not leaving any dangling records. Referential integrity prevents references from being orphaned, which may lead to data loss or other more severe problems, such as a system crash. In the current embodiment, tables are stored across multiple databases. Certain tables are stored in NMS database 61 and certain other tables are stored in the configuration database within each network device in the network. Direct binding between tables cannot be maintained since a database may be removed or a record deleted without maintaining referential integrity. To address this issue, group names are used to provide a “dynamic binding” between the User Resource Group table 1018 (
Through a user profile, a user may log-on to the network with a single, secure username and password through any NMS client, access any network device in their user profile and access configured resources corresponding to groups in their user profile. Since the tables including the data necessary for the creation of user profile LMOs are stored in the NMS database, any NMS server capable of connecting to the NMS database—that is, any NMS server in the network—may access the tables and generate a user LMO. As a result, users may log-on with a single, secure username and password through any NMS client that may be connected to an NMS server capable of connecting to the NMS database. Essentially, users may log on through any computer system/workstation (e.g., 984,
In addition, user profiles provide a level of indirection to better protect the passwords used to access each network device. For example, access to the passwords may be limited to only those users capable of adding network devices to the network, for example, users with the administrator group access level. Other users would not see the passwords since they are automatically added to their user profile LMO, which is not accessible by users. The level of indirection provided by user profiles also allows network device passwords to be easily changed across the entire network. Periodically the passwords for access to the network devices in a network may be changed for security. The network device passwords may be quickly changed in the Administration Managed Device table 1014 (
User profiles and group names also simplify network management tasks. For example, if an administrator adds a newly configured resource to a group, all users having access to that group will automatically be able to access the newly configured resource. The administrator need not send out a notice or take other steps to update each user.
Group names in a user profile define what the user can view. For instance, one customer may not view the configured resources subscribed for by another customer if their resources are assigned to different groups. Thus, groups allow for a granular way to “slice” up each network device according to its resources.
The user access level in a user profile determines how the NMS server behaves and affects what the user can do. For example, the viewer user access level provides the user with read-only capability and, thus, prevents the NMS server from modifying data in tables. In addition, the user access level may be used to restrict access—even read access—to certain tables or columns in certain tables.
Network Device Power-Up:
Referring again to
In one embodiment, the operating system software and system services software are the OSE operating system and system services from Enea OSE Systems, Inc. in Dallas, Tex. The OSE operating system is a pre-emptive multi-tasking operating system that provides a set of services that together support the development of distributed applications (i.e., dynamic loading). The OSE approach uses a layered architecture that builds a high level set of services around kernel primitives. The operating system, system services, and modular system services provide support for the creation and management of processes; inter-process communication (IPC) through a process-to-process messaging model; standard semaphore creation and manipulation services; the ability to locate and communicate with a process regardless of its location in the system; the ability to determine when another process has terminated; and the ability to locate the provider of a service by name.
These services support the construction of a distributed system wherein applications can be located by name and processes can use a single form of communication regardless of their location. By using these services, distributed applications may be designed to allow services to transparently move from one location to another such as during a fail over.
The OSE operating system and system services provide a single inter-process communications mechanism that allows processes to communicate regardless of their location in the system. OSE IPC differs from the traditional IPC model in that there are no explicit IPC queues to be managed by the application. Instead each process is assigned a unique process identification that all IPC messages use. Because OSE IPC supports inter-board communication the process identification includes a path component. Processes locate each other by performing an OSE Hunt call on the process identification. The Hunt call will return the Process ID of the process that maps to the specified path/name. Inter-board communication is carried over some number of communication links. Each link interface is assigned to an OSE Link Handler. The path component of a process path/name is the concatenation of the Link Handler names that one must transverse in order to reach the process.
In addition, the OSE operating system includes memory management that supports a “protected memory model”. The protected memory model dedicates a memory block (i.e., defined memory space) to each process and erects “walls” around each memory block to prevent access by processes outside the “wall”. This prevents one process from corrupting the memory space used by another process. For example, a corrupt software memory pointer in a first process may incorrectly point to the memory space of a second processor and cause the first process to corrupt the second processor's memory space. The protected memory model prevents the first process with the corrupted memory pointer from corrupting the memory space or block assigned to the second process. As a result, if a process fails, only the memory block assigned to that process is assumed corrupted while the remaining memory space is considered uncorrupted.
The modular software architecture takes advantage of the isolation provided to each process (e.g., device driver or application) by the protected memory model. Because each process is assigned a unique or separate protected memory block, processes may be started, upgraded or restarted independently of other processes.
Referring to
Also within the modular system services is a configuration service program 35 that downloads a configuration database program 42 and its corresponding DDL file from persistent storage into non-persistent memory 40 on central processor 12. In one embodiment, configuration database 42 is a Polyhedra database from Polyhedra, Inc. in the United Kingdom.
Hardware Inventory and Set-Up:
Master MCD 38 begins by taking a physical inventory of computer system 10 (over the I2C bus) and assigning a unique physical identification number (PID) to each item. Despite the name, the PID is a logical number unrelated to any physical aspect of the component being numbered. In one embodiment, pull-down/pull-up resistors on the chassis mid-plane provide the number space of Slot Identifiers. The master MCD may read a register for each slot that allows it to get the bit pattern produced by these resistors. MCD 38 assigns a unique PID to the chassis, each shelf in the chassis, each slot in each shelf, each line card 16a-16n inserted in each slot, and each port on each line card. (Other items or components may also be inventoried.)
Typically, the number of line cards and ports on each line card in a computer system is variable but the number of chassis, shelves and slots is fixed. Consequently, a PID could be permanently assigned to the chassis, shelves and slots and stored in a file. To add flexibility, however, MCD 38 assigns a PID even to the chassis, shelves and slots to allow the modular software architecture to be ported to another computer system with a different physical construction (i.e., multiple chassis and/or a different number of shelves and slots) without having to change the PID numbering scheme.
Referring to
Even after initial power-up, master MCD 38 will continue to take physical inventories to determine if hardware has been added or removed from computer system 10. For example, line cards may be added to empty slots or removed from slots. When changes are detected, master MCD 38 will update CT 47 and PT 49 accordingly.
For each line card 16a-16n, master MCD 38 searches a physical module description (PMD) file 48 in memory 40 for a record that matches the card type and version number retrieved from that line card. The PMD file may include multiple files. The PMD file includes a table that corresponds card type and version number with name of the mission kernel image executable file (MKI.exe) that needs to be loaded on that line card. Once determined, master MCD 38 passes the name of each MKI executable file to master SRM 36. Master SRM 36 requests a bootserver (not shown) to download the MKI executable files 50a-50n from persistent storage 21 into memory 40 (i.e., dynamic loading) and passes each MKI executable file 50a-50n to a bootloader (not shown) running on each board (central processor and each line card). The bootloaders execute the received MKI executable file.
Once all the line cards are executing the appropriate MKI, slave MCDs 39a-39n and slave SRMs 37a-37n on each line card need to download device driver software corresponding to the particular devices on each card. Referring to
In order to understand the significance of the PMD file (i.e., metadata), note that the MCD software does not have knowledge of board types built into it. Instead, the MCD parameterizes its operations on a particular board by looking up the card type and version number in the PMD file and acting accordingly. Consequently, the MCD software does not need to be modified, rebuilt, tested and distributed with new hardware. The changes required in the software system infrastructure to support new hardware are simpler modify logical model 280 (
Network Management System (NMS):
Referring to
During installation, an NMS database 61 is established on, for example, work-station 62 using a DDL executable file corresponding to the NMS database. The DDL file may be downloaded from persistent storage 21 in computer system 10 or supplied separately with other NMS programs as part of an NMS installation kit. The NMS database mirrors the configuration database through an active query feature (described below). In one embodiment, the NMS database is an Oracle database from Oracle Corporation in Boston, Mass.
The NMS and central processor 12 pass control and data over Ethernet 41 using, for example, the Java Database Connectivity (JDBC) protocol. Use of the JDBC protocol allows the NMS to communicate with the configuration database in the same manner that it communicates with its own internal storage mechanisms, including the NMS database. Changes made to the configuration database are passed to the NMS database to ensure that both databases store the same data. This synchronization process is much more efficient, less error-prone and timely than older methods that require the NMS to periodically poll the network device to determine whether configuration changes have been made. In these systems, NMS polling is unnecessary and wasteful if the configuration has not been changed. Additionally, if a configuration change is made through some other means, for example, a command line interface, and not through the NMS, the NMS will not be updated until the next poll, and if the network device crashes prior to the NMS poll, then the configuration change will be lost. In computer system 10, however, command line interface changes made to configuration database 42 are passed immediately to the NMS database through the active query feature ensuring that the NMS, through both the configuration database and NMS database, is immediately aware of any configuration changes.
Asynchronously Providing Network Device Management Data:
Typically, work-station 62 (
In addition, instead of having the NMS interpret each network device's management data in the same fashion, flexibility is added by having each system send the NMS (e.g., data collector server 857,
Referring to
When device drivers are first started, upgraded or re-booted, the device driver makes a call into the UDML to notify the UDML as to which statistical data the device driver is able to gather. For example, an ATM device driver may be able to gather virtual circuit (VC) accounting statistics and Virtual ATM (VATM) interface statistics while a SONET device driver may be able to gather SONET statistics. The device driver then makes a call into the UDML to notify the UDML as to each interface (including virtual circuits) for which the device driver will be gathering data and the types of data the device driver will provide for each interface.
The UDML sends a registration packet to the UDS providing one or more string names corresponding to the types of data that the UDML will send to the UDS. For example, for ATM drivers the UDML may register “Acct_PVC” to track permanent virtual circuit statistics, “Acct_SVC” to track soft permanent virtual circuit statistics, “Vir_Intf” to track quality of service (QoS) statistics corresponding to virtual interfaces, and “Bw_Util” to track bandwidth utilization. As another example, for SONET drivers the UDML may register “Section” to track section statistics, “Line” to track line statistics and “Path” to track path statistics. The UDML need only register each string name with the UDS once, for example, for the first interface registered, and not for each interface since the UDML will package up the data from multiple interfaces corresponding to the same string name before sending the data with the appropriate string name to the UDS.
The UDML includes a polling timer to cause each driver to periodically poll its hardware for “current” statistical/accounting data samples 411a. The current data samples are typically gathered on a frequent interval of, for example, 15 minutes, as specified by the polling timer. The UDML also causes each driver to put the binary data in a particular format, time stamp the data and store the current data sample locally. When a current data sample for each interface managed by the device driver and corresponding to a particular string name is stored locally, the UDML packages all of the current data samples corresponding to the same string name into one or more packets containing binary data and sends the packets to the UDS with the registered string name.
In addition, the UDML adds each gathered current data sample 411a to a local data summary 411b. The UDML clears the data summary periodically, for example, every twenty-four hours, and then adds newly gathered current data samples to the cleared data summary. Thus, the data summary represents an accumulation of current data samples gathered over the period (e.g., 24 hours).
The UDS maintains a list of UDMLs expected to send current data samples and data summaries corresponding to each string name. For each poll, the UDS combines the data sent from each UDML with the same string name into a common binary data file (e.g., binary data files 416a-416n) associated with that string name in non-volatile memory, for example, a hard drive 421 located on internal control processor 542a. When all UDMLs in the list corresponding to a particular string name have reported their current data samples or data summaries, the UDS closes the common data file, thus ending the data collecting period. Preferably, the data is maintained in binary form to keep the data files smaller than translating it into other forms such as ASCII. Smaller binary files require less space to store and less bandwidth to transfer.
If after a predetermined period of time has passed, for example, 5 minutes, one or more of the UDMLs in a list has not sent binary data with the corresponding string name, the UDS closes the common data file, ending the data collecting period. The UDS then sends a notice to the non-responsive UDML(s). The UDS will repeat this sequence a predetermined number of times, for example, three, and if no binary data with the corresponding string name is received, the UDS will delete the UDML(s) from the list and send a trap to the NMS indicating which specific UDML is not responsive. As a result, maintaining the list of UDMLs that will be sending data corresponding to each string name allows the UDS to know when to close each common data file and also allows the UDS to notify the NMS when a UDML becomes non-responsive. This provides for increased availability including fault tolerance—that is, a fault on one card or in one application cannot interrupt the statistics gathering from each of the other cards or other applications on one card—and also including hot swapping where a card and its local UDMLs may no longer be inserted within the network device.
Since a large number of UDMLs may be sending data to the UDS, the potential exists for the data transfer rate to the UDS to be larger than the amount of data that the UDS can process and larger than local buffering can support. Such a situation may result in lost data or worse, for example, a network device crash. A need exists, therefore, to be able to “throttle” the amount of data being sent from the UDMLs to the UDS depending upon the current backlog of data at the UDS.
In one embodiment, the UDML is allowed to send up to a maximum number of packets to the UDS before the UDML must wait for an acknowledge (ACK) packet from the UDS. For example, the UDML may be allowed to send three packets of data to the UDS and in the third packet the UDML must include an acknowledge request. Alternatively, the UDML may follow the third packet with a separate packet including an acknowledge request. Once the third packet is sent, the UDML must delay sending any additional packets to the UDS until an acknowledge packet is received from the UDS. The UDML may negotiate the maximum number of packets that can be sent in its initial registration with the UDS. Otherwise, a default value may be used.
Many packets may be required to completely transfer a binary current data sample or data summary to the UDS. Once the acknowledge packet is received, the UDML may again send up to the maximum number (e.g., 3) of packets to the UDS again including an acknowledge request in the last packet. Requiring the UDML to wait for an acknowledge packet from the UDS, allows the UDS to throttle back the data received from UDMLs when the UDS has a large backlog of data to process.
A simple mechanism to accomplish this throttling is to have the UDS send an acknowledge packet each time it processes a packet containing an acknowledge request. Since the UDS is processing the packet that is a good indication that it is steadily processing packets. If the number of packets received by the UDS is large, it will take longer to process the packets and, thus, longer to process packets containing acknowledge requests. Thus, the UDMLs must wait longer to send more packets. On the other hand, if the number of packets is small, the UDS will quickly process each packet received and more quickly send back the acknowledge request and the UDMLs will not have to wait as long to send more packets.
Instead of immediately returning an acknowledge packet when the UDS processes a packet containing an acknowledge request, the UDS may first compare the number of packets waiting to be processed against a predetermined threshold. If the number of packets waiting to be processed is less than the predetermined threshold, then the UDS immediately sends the acknowledge packet to the UDML. If the number of packets waiting to be processed is more than the predetermined threshold, then the UDS may delay sending the acknowledge packet until enough packets have been processed that the number of packets waiting to be processed is reduced to less than the predetermined threshold. Instead, the UDS may estimate the amount of time that it will need to process enough packets to reduce the number of packets waiting to be processed to less than the threshold and send an acknowledge packet to the UDML including a future time at which the UDML may again send packets. In other words, the UDS does not wait until the backlog is diminished to notify the UDMLs but instead notifies the UDMLs prior to reducing the backlog and based on an estimate of when the backlog will be diminished.
Another embodiment for a throttling mechanism requires polls for different statistical data to be scheduled at different times to load balance the amount of statistical traffic across the control plane. For example, the UDML for each ATM driver polls and sends data to the UDS corresponding to PVC accounting statistics (i.e., Acct_PVC) at a first time, the UDML for each ATM driver polls and sends data to the UDS corresponding to SPVC accounting statistics (i.e., Acct_SPVC) at a second time, and the UDML for each ATM driver and each SONET driver polls and sends data to the UDS corresponding to other statistics at other times. This may be accomplished by having multiple polling timers within the UDML corresponding to the type of data being gathered. Load balancing and staggered reporting provides distributed data throttling which may smooth out control plane bandwidth utilization (i.e., prevent large data bursts) and reduce data buffering and data loss.
Referring to
As mentioned, the UDML causes the device driver to periodically gather the current statistical management data samples for each interface and corresponding to each string name. The period may be relatively frequent, for example, every 15 minutes. In addition, the UDML causes the device driver or separate packaging program to add the current data sample to a data summary corresponding to the same string name each time a current data sample is gathered. The UDML clears the data summary periodically, for example, every twenty-four hours. To reduce bandwidth utilization, the data summary and corresponding string name is sent to the UDS periodically but with an infrequent time period of, for example, every 6 to 12 hours. The data summary provides resiliency such that if any of the current data samples are lost in any of the various transfers, the data summary is still available. Local resiliency may be provided by storing a backlog of both current data sample files and summary data files in hard drive 421. For example, the four most recent current data sample files and the two most recent summary data files corresponding to each string name may be stored.
If FTP client 412b cannot send data from hard drive 421 to file system 425 for a predetermined period of time, for example, 15 minutes, the FTP client may notify the UDS and the UDS may notify each UDML. Each UDML then continues to cause the device driver to gather current statistical management data samples and add them to the data summaries at the same periodic interval (i.e., current data interval, e.g., 15 minutes), however, the UDML stops sending the current data samples to the UDS. Instead, the UDML sends only the data summaries to the UDS but at the more frequent current data interval (e.g., 15 minutes) instead of the longer time period (e.g., 6 to 12 hours). The UDS may then update the data summaries stored in hard drive 421 and cease collecting and storing current data samples. This will save space in the hard drive and minimize any data loss.
To reduce the amount of statistical management data being transferred to the UDS, a network manager may selectively configure only certain of the applications (e.g., device drivers) and certain of the interfaces to provide this data. As each UDML registers with the UDS, the UDS may then inform each UDML with respect to each interface as to whether or not statistical management data should be gathered and sent to the UDS. There may be many circumstances in which gathering this data is unnecessary. For example, each ATM device driver may manage multiple virtual interfaces (VATMs) and within each VATM there may be several virtual circuits. A network manager may choose not to receive statistics for virtual circuits on which a customer has ordered only Variable Bit Rate (VBR) real time (VBR-rt) and VBR non-real time (VBR-nrt) service. For VBR-rt and VBR-nrt, the network service provider may provide the customer only with available/extra bandwidth and charge a simple flat fee per month. However, a network manager may need to receive statistics for virtual circuits on which a customer has ordered a high quality of service such as Constant Bit Rate (CBR) to ensure that the customer is getting the appropriate level of service and to appropriately charge the customer. In addition, a network manager may want to receive statistics for virtual circuits on which a customer has ordered Unspecified Bit Rate (UBR) service to police the customer's usage and ensure they are not receiving more network bandwidth than what they are paying for. Allowing a network manager to indicate that certain applications or certain interfaces managed by an application (e.g., a VATM) need not provide statistical management data or some portion of that data to the UDS reduces the amount of data transferred to the UDS —that is, reduces internal bandwidth utilization —, reduces the amount of storage space required in the hard drive, and reduces the processing power required to transfer the statistical management data from remote cards to external file system 425.
For each binary data file, the UDS creates a data summary file (e.g., data summary files 414a-414n) and stores it in, for example, hard drive 421. The data summary file defines the binary file format, including the type based on the string name, the length, the number of records and the version number. The UDS does not need to understand the binary data sent to it by each of the device drivers. The UDS need only combine data corresponding to similar string names into the same file and create a summary file based on the string name and the amount of data in the binary data file. The version number is passed to the UDS by the device driver, and the UDS includes the version number in the data summary file.
Periodically, FTP client 412b asynchronously reads each binary data file and corresponding data summary file from hard drive 421. Preferably, the FTP client reads these files from the hard drive through an out-of-band Ethernet connection, for example, Ethernet 32 (
In one embodiment, the data collector server is a JAVA program, and each different type of binary data file has a corresponding JAVA class file (e.g., class file 410a) that defines how the data collector server should process the binary data file. When a device driver is loaded into the network device, a corresponding JAVA class file is also loaded and stored in hard drive 421. The FTP client periodically polls the hard drive for new JAVA class files and uses an FTP push to send them to file system 425. The data collector server uses the binary file type in the data summary file to determine which JAVA class file it should use to interpret the binary data file. The data collector server then converts the binary data into ASCII or AMA/BAF format and stores the ASCII or AMA/BAF files in the file system. The data collector server may use a set of worker threads for concurrency.
As described, the data collector server is completely independent of and asynchronous with the FTP client, which is also independent and asynchronous of the UDS. The separation of the data collector server and FTP client avoids data loss due to process synchronization problems, since there is no synchronization, and reduces the burden on the network device by not requiring the network device to maintain synchronization between the processes. In addition, if the data collector server goes down or is busy for some time, the FTP client and UDS continue working and continue sending binary data files and data summary files to the file system. When the data collector server is again available, it simply accesses the data summary files and processes the binary files as described above. Thus, there is no data loss and the limited storage capacity within the network device is not strained by storing data until the data collector server is available. In addition, if the FTP client or UDS goes down, the data collector server may continue working.
An NMS server (e.g., NMS server 851a), which may or may not be executing on the same computer system 62 as the data collector server, may periodically retrieve the ASCII or AMA/BAF files from the file system. The files may represent accounting, statistics, security, logging and/or other types of data gathered from hardware within the network device. The NMS server may also access the corresponding class files from the file system to learn how the data should be presented to a user, for example, how a graphical user interface (GUI) should be displayed, what data and format to display, or perhaps which one of many GUIs should be used. The NMS server may use the data to, for example, monitor network device performance, including quality of service guarantees and service level agreements, as well as bill customers for network usage. Alternatively, a separate billing server 423a or statistics server 423b, which may or may not be executing on the same computer system 62 as the data collector server and/or the NMS server, may periodically retrieve the ASCII or AMA/BAF files from the file system in order to monitor network device performance, including quality of service guarantees and service level agreements, and/or bill customers for network usage. One or more of the data collector server, the NMS server, the billing server and the statistics server may be combined into one server. Moreover, management files created by the data collector server may be combined with data from the configuration or NMS databases to generate billing records for each of the network provider's customers.
The data collector server may convert the ASCII or AMA/BAF files into other data formats, for example, Excel spread sheets, for use by the NMS server, billing server and/or statistics server. In addition, the application class file for each data type may be modified to go beyond conversion, including direct integration into a database or an OSS system. For example, many OSS systems use a Portal billing system available from Portal Software, Inc. in Cupertino, Calif. The JAVA class file associated with a particular binary data file and data summary file may cause the data collector server to convert the binary data file into ASCII data and then issue a Portal API call to give the ASCII data directly to the Portal billing system. As a result, accounting, statistics, logging and/or security data may be directly integrated into any other process, including third party processes, through JAVA class files.
Through JAVA class files, new device drivers may be added to a network device without having to change UDS 412a or FTP client 412b and without having to re-boot the network device and without having to upgrade/modify external processes. For example, a new forwarding card (e.g., forwarding card 552a) may be added to an operating network device and this new forwarding card may support MPLS. An MPLS device driver 419, linked within the UDML, is downloaded to the network device as well as a corresponding class file (e.g., class file 410e). When the FTP client discovers the new class file in hard drive 421, it uses an FTP push to send it to file system 425. The FTP client does not need to understand the data within the class file it simply needs to push it to the file system. Just as with other device drivers, the UDML causes the MPLS driver to register appropriate string names with the UDS and poll and send data to the UDS with a registered string name. The UDS stores binary data files (e.g., binary data file 416e) and corresponding data summary files (e.g., data summary file 414e) in the hard drive without having to understand the data within the binary data file. The FTP client then pushes these files to the file system again without having to understand the data. When the data summary file is discovered by the data collector server, the data collector server uses the binary file type in the data summary file to locate the new MPLS class file 410e in the file system and then uses the class file to convert the binary data in the corresponding binary data file into ASCII format and perhaps other data formats. Thus, a new device driver is added and statistical information may be gathered without having to change any of the other software and without having to re-boot the network device. As described, having the data collector server be completely independent of and asynchronous with the FTP client avoids the typical problems encountered when internal and external management programs are synchronized. Moreover, modularity of device drivers and internal management programs is maintained by providing metadata through class files that instruct the external management programs as to how the management data should be processed. Consequently, device drivers may be modified, upgraded and added to an operating network device without disrupting the operation of any of the other device drivers or the management programs.
Configuration:
As described above, unlike a monolithic software architecture which is directly linked to the hardware of the computer system on which it runs, a modular software architecture includes independent applications that are significantly decoupled from the hardware through the use of a logical model of the computer system. Using the logical model and a code generation system, a view id and API are generated for each application to define each application's access to particular data in a configuration database and programming interfaces between the different applications. The configuration database is established using a data definition language (DDL) file also generated by the code generation system from the logical model. As a result, there is only a limited connection between the computer system's software and hardware, which allows for multiple versions of the same application to run on the computer system simultaneously and different types of applications to run simultaneously on the computer system. In addition, while the computer system is running, application upgrades and downgrades may be executed without affecting other applications and new hardware and software may be added to the system also without affecting other applications.
Referring again to
The user chooses the desired redundancy structure and instructs the NMS as to which boards are primary boards and which boards are backup boards. For example, the NMS may assign LID 30 to line card 16a—previously assigned PID 500 by the MCD—as a user defined primary card, and the NMS may assign LID 30 to line card 16n—previously assigned PID 513 by the MCD—as a user defined back-up card (see row 106,
In a 1:1 redundant system, each backup line card backs-up only one other line card and the NMS assigns a unique primary PID and a unique backup PID to each LID (no LIDs share the same PIDs). In a 1:N redundant system, each backup line card backs-up at least two other line cards and the NMS assigns a different primary PID to each LID and the same backup PID to at least two LIDs. For example, if computer system 10 is a 1:N redundant system, then one line card, for example, line card 16n, serves as the hardware backup card for at least two other line cards, for example, line cards 16a and 16b. If the NMS assigns an LID of 31 to line card 16b, then in logical to physical card table 100 (see row 109,
The logical to physical card table provides the user with maximum flexibility in choosing a redundancy structure. In the same computer system, the user may provide full redundancy (1:1), partial redundancy (1:N), no redundancy or a combination of these redundancy structures. For example, a network manager (user) may have certain customers that are willing to pay more to ensure their network availability, and the user may provide a backup line card for each of that customer's primary line cards (1:1). Other customers may be willing to pay for some redundancy but not full redundancy, and the user may provide one backup line card for all of that customer's primary line cards (1:N). Still other customers may not need any redundancy, and the user will not provide any backup line cards for that customer's primary line cards. For no redundancy, the NMS would leave the backup PID field in the logical to physical table blank. Each of these customers may be serviced by separate computer systems or the same computer system. Redundancy is discussed in more detail below.
The NMS and MCD use the same numbering space for LIDs, PIDs and other assigned numbers to ensure that the numbers are different (no collisions).
The configuration database, for example, a Polyhedra relational database, supports an “active query” feature. Through the active query feature, other software applications can be notified of changes to configuration database records in which they are interested. The NMS database establishes an active query for all configuration database records to insure it is updated with all changes. The master SRM establishes an active query with configuration database 42 for LPCT 100 and LPPT 101. Consequently, when the NMS adds to or changes these tables, configuration database 42 sends a notification to the master SRM and includes the change. In this example, configuration database 42 notifies master SRM 36 that LID 30 has been assigned to PID 500 and 513 and LID 31 has been assigned to PID 501 and 513. The master SRM then uses card table 47 to determine the physical location of boards associated with new or changed LIDs and then tells the corresponding slave SRM of its assigned LID(s). In the continuing example, master SRM reads CT 47 to learn that PID 500 is line card 16a, PID 501 is line card 16b and PID 513 is line card 16n. The master SRM then notifies slave SRM 37b on line card 16a that it has been assigned LID 30 and is a primary line card, SRM 37c on line card 16b that it has been assigned LID 31 and is a primary line card and SRM 37o on line card 16n that it has been assigned LIDs 30 and 31 and is a backup line card. All three slave SRMs 37b, 37c and 37o then set up active queries with configuration database 42 to insure that they are notified of any software load records (SLRs) created for their LIDs. A similar process is followed for the LIDs assigned to each port.
The NMS informs the user of the hardware available in computer system 10. This information may be provided as a text list, as a logical picture in a graphical user interface (GUI), or in a variety of other formats. The user then uses the GUI to tell the NMS (e.g., NMS client 850a,
The user will select which ports (e.g., 44a-44d, 46a-46f, 68a-68n) the NMS should enable. There may be instances where some ports are not currently needed and, therefore, not enabled. The user also needs to provide the NMS with information about the type of network connection (e.g., connection 70a-70d, 72a-72f, 74a-74n). For example, the user may want all ports 44a-44d on line card 16a enabled to run ATM over SONET. The NMS may start one ATM application to control all four ports, or, for resiliency, the NMS may start one ATM application for each port. Alternatively, each port may be enabled to run a different protocol (e.g., MPLS, IP, Frame Relay).
In the example given above, the user must also indicate the type of SONET fiber they have connected to each port and what paths to expect. For example, the user may indicate that each port 44a-44d is connected to a SONET optical fiber carrying an OC-48 stream. A channelized OC-48 stream is capable of carrying forty-eight STS-1 paths, sixteen STS-3c paths, four STS-12c paths or a combination of STS-1, STS-3c and STS-12c paths. A clear channel OC-48c stream carries one concatenated STS-48 path. In the example, the user may indicate that the network connection to port 44a is a clear channel OC-48 SONET stream having one STS-48 path, the network connection to port 44b is a channelized OC-48 SONET stream having three STS-12c paths (i.e., the SONET fiber is not at full capacity—more paths may be added later), the network connection to port 44c is a channelized OC-48 SONET stream having two STS-3c paths (not at full capacity) and the network connection to port 44d is a channelized OC-48 SONET stream having three STS-12c paths (not at full capacity). In the current example, all paths within each stream carry data transmitted according to the ATM protocol. Alternatively, each path within a stream may carry data transmitted according to a different protocol.
The NMS (e.g., NMS server 851a-851n) uses the information received from the user (through the GUI/NMS client) to create records in several tables in the configuration database, which are then copied to the NMS database. These tables are accessed by other applications to configure computer system 10. One table, the service endpoint table (SET) 76 (see also
Service endpoint managers (SEMs) within the modular system services of the kernel software running on each line card use the service endpoint numbers assigned by the NMS to enable ports and to link instances of applications, for example, ATM, running on the line cards with the correct port. The kernel may start one SEM to handle all ports on one line card, or, for resiliency, the kernel may start one SEM for each particular port. For example, SEMs 96a-96d are spawned to independently control ports 44a-44d.
The service endpoint managers (SEMs) running on each board establish active queries with the configuration database for SET 76. Thus, when the NMS changes or adds to the service endpoint table (SET), the configuration database sends the service endpoint manager associated with the port PID in the SET a change notification including information on the change that was made. In the continuing example, configuration database 42 notifies SEM 96a that SET 76 has been changed and that SE 1 was assigned to port 44a (PID 1500). Configuration database 42 notifies SEM 96b that SE 2, 3, and 4 were assigned to port 44b (PID 1501), SEM 96c that SE 5 and 6 were assigned to port 44c (PID 1502) and SEM 96d that SE 7, 8, and 9 were assigned to port 44d (PID 1503). When a service endpoint is assigned to a port, the SEM associated with that port passes the assigned SE number to the port driver for that port using the port PID number associated with the SE number.
To load instances of software applications on the correct boards, the NMS creates software load records (SLR) 128a-128n in configuration database 42. The SLR includes the name 130 (
For each application that needs to be spawned, for example, an ATM application and a SONET application, the NMS creates an application group table. Referring to
In the above example, one instance of ATM was started for each port on the line card. This provides resiliency and fault isolation should one instance of ATM fail or should one port suffer a failure. An even more resilient scheme would include multiple instances of ATM for each port. For example, one instance of ATM may be started for each path received by a port.
The application controllers on each board now need to know how many instances of the corresponding application they need to spawn. This information is in the application group table in the configuration database. Through the active query feature, the configuration database notifies the application controller of records associated with the board's LID from corresponding application group tables. In the continuing example, configuration database 42 sends ATM controller 136 records from ATM group table 108 that correspond to LID 30 (line card 16a). With these records, ATM controller 136 learns that there are four ATM groups associated with LID 30 meaning ATM must be instantiated four times on line card 16a. ATM controller 136 asks slave SRM 37b to download and execute four instances (ATM 110-113,
Once spawned, each instantiation of ATM 110-113 sends an active database query to search ATM interface table 114 for its corresponding group number and to retrieve associated records. The data in the records indicates how many ATM interfaces each instantiation of ATM needs to spawn. Alternatively, a master ATM application (not shown) running on central processor 12 may perform active queries of the configuration database and pass information to each slave ATM application running on the various line cards regarding the number of ATM interfaces each slave ATM application needs to spawn.
Referring to
Computer system 10 is now ready to operate as a network switch using line card 16a and ports 44a-44d. The user will likely provide the NMS with further instructions to configure more of computer system 10. For example, instances of other software applications, such as an IP application, and additional instances of ATM may be spawned (as described above) on line cards 16a or other boards in computer system 10.
As shown above, all application dependent data resides in memory 40 and not in kernel software. Consequently, changes may be made to applications and configuration data in memory 40 to allow hot (while computer system 10 is running) upgrades of software and hardware and configuration changes. Although the above described power-up and configuration of computer system 10 is complex, it provides massive flexibility as described in more detail below.
Template Driven Service Provisioning:
Instead of using the GUI to interactively provision services on one network device in real time, a user may provision services on one or more network devices in one or more networks controlled by one or more network management systems (NMSs) interactively and non-interactively using an Operations Support Services (OSS) client and templates. At the heart of any carrier's network is the OSS, which provides the overall network management infrastructure and the main user interface for network managers/administrators. The OSS is responsible for consolidating a diverse set of element/network management systems and third-party applications into a single system that is used, for example, to detect and resolve network faults (Fault Management), configure and upgrade the network (Configuration Management), account and bill for network usage (Accounting Management), oversee and tune network performance (Performance Management), and ensure ironclad network security (Security Management). FCAPS are the five functional areas of network management as defined by the International Organization for Standardization (ISO). Through templates one or more NMSs may be integrated with a telecommunication network carrier's OSS.
Templates are metadata and include scripts of instructions and parameters. In one embodiment, instructions within templates are written in ASCII text to be human readable. There are three general categories of templates, provisioning templates, control templates and batch templates. A user may interactively connect the OSS client with a particular NMS server and then cause the NMS server to connect to a particular device. Instead, the user may create a control template that non-interactively establishes these connections. Once the connections are established, whether interactively or non-interactively, provisioning templates may be used to complete particular provisioning tasks. The instructions within a provisioning template cause the OSS client to issue appropriate calls to the NMS server which cause the NMS server to complete the provisioning task, for example, by writing/modifying data within the network device's configuration database. Batch templates may be used to concatenate a series of templates and template modifications (i.e., one or more control and provisioning templates) to provision one or more network devices. Through the client/server based architecture, multiple OSS clients may work with one or more NMS servers. Database view ids and APIs for the OSS client may be generated using the logical model and code generation system (
Interactively, a network manager may have an OSS client execute many provisioning templates to complete many provisioning tasks. Instead, the network manager may order and sequence the execution of many provisioning templates within a batch template to non-interactively complete the many provisioning tasks and build custom services. In addition, execution commands followed by control template names may be included within batch templates to non-interactively cause an OSS client to establish connections with particular NMS servers and network devices. For example, a first control template may designate a network device to which the current OSS client and NMS server are not connected. Including an execution command followed by the first control template name in a batch template will cause the OSS client to issue calls to the NMS server to cause the NMS server to access the different network device. As another example, a second control template may designate an NMS server and a network device to which the OSS client is not currently connected. Including an execution command followed by the second control template name will cause the OSS client to set up connections to both the different NMS server and the different network device. Moreover, batch templates may include execution commands followed by provisioning template names after each execution command and control template to provision services within the network devices designated by the control templates. Through batch templates, therefore, multiple control templates and provisioning templates may be ordered and sequenced to provision services within multiple network devices in multiple networks controlled by multiple NMSs.
Calls issued by the OSS client to the NMS server may cause the NMS server to immediately provision services or delay provisioning services until a predetermined time, for example, a time when the network device is less likely to be busy. Templates may be written to apply to different types of network devices.
A “command line” interactive interpreter within the OSS client may be used by a network manager to select and modify existing templates or to create new templates. Templates may be generated for many various provisioning tasks, for example, setting up a permanent virtual circuit (PVC), a switched virtual circuit (SVC), a SONET path (SPATH), a traffic descriptor (TD) or a virtual ATM interface (VAIF). Once a template is created, a network manager change default parameters within the template to complete particular provisioning tasks. A network manager may also copy a template and modify it to create a new template.
Referring to
Referring to
As shown, the help command alone causes the interactive interpreter to display the list of commands. The help command followed by another command provides help information about that command. The load command followed by a template type and a named template loads the named template into the OSS client such that any commands followed by the template type will use the named/loaded template. The manage command followed by an IP address of a network device causes the OSS client to issue a call to an NMS server to establish a connection between the NMS server and that network device. Alternatively, a username and password may also need to be supplied. The open command followed by an NMS server IP address causes the OSS client to open a connection with that NMS server, and again, the network manager may also need to supply a username and password. Instead of an IP address, a domain name server (DNS) name may be provided and a host look up may be used to determine the IP address and access the corresponding device.
The showCurrent command followed by a template type will cause the interactive interpreter to display current parameter values for the loaded template corresponding to that template type. For example, showCurrent SPATH 914 displays a list 915 of parameters and current parameter values for the loaded template corresponding to the SPATH template type. The showTemplate command followed by a template type will cause the OSS client to display available parameters and acceptable parameter values for each parameter within the loaded template. For example, showTemplate SPATH 916 causes the interactive interpreter to display the available parameters 917 within the loaded template corresponding to the SPATH template type. The set command followed by a template type, a parameter name and a value will change the named parameter to the designated value within the loaded template, and a subsequent showCurrent command followed by that template type will show the new parameter value within the loaded.
The status command 918 will cause the interactive interpreter to display a status of the current interactive interpreter session. For example, the interactive interpreter may display the name 919 of an NMS server to which the OSS client is currently connected (as shown in
Referring to
The network manager may now provision services within that network device by typing in an execute command 921f followed by a template type. For example, the network manager may type “execute SPATH” at the Enetcli> prompt to cause the OSS client to execute the instructions 921g within the loaded SPATH template using the parameter values within the loaded SPATH template. Executing the instructions causes the OSS client to issue calls to the NMS server, and these calls cause the NMS server to complete the provisioning task 921h. For example, following an execute SPATH command, the NMS server will set up a SONET path in the network device using the parameter values passed to the NMS server by the OSS client from the template.
At any time from the Enetcli> prompt, a network manager may change the parameter values within a template. Again, the network manager may use showCurrent followed by a template type to see the current parameter values within the loaded template or showTemplate to see the available parameters within the loaded template. The network manager may then use the set command followed by the template type, parameter name and new parameter value to change a parameter value within the loaded template. For example, after the network manager sets up a SONET path within the network device, the network manager may change one or more parameter values within the loaded SPATH template and re-execute the SPATH template to set up a different SONET path within the same network device.
Once a connection to a network device is open, the network manager may interactively execute any template any number of times to provision services within that network device. The network manager may also create new templates and execute those. The network manager may simply write a new template or use the writeCurrent or writeTemplate commands to copy an existing template into a new template name and then edit the instructions within the new template.
After provisioning services within a first network device, the network manager may open a connection with a second network device to provision services within that second network device. If the NMS server currently connected to the OSS client is capable of establishing a connection with the second network device, then the network manager may simply open a connection to the second network device. If the NMS server currently connected to the OSS client is not capable of establishing a connection with the second network device, then the network manager closes the connections with the NMS server and then opens connections with a second NMS server and the second network device. Thus, a network manager may easily manage/provision services within multiple network devices within multiple networks even if they are managed by different NMS servers. In addition, other network managers may provision services on the same network devices through the same NMS servers using other OSS clients that are perhaps running on other computer systems. That is, multiple OSS clients may be connected to multiple NMS servers.
Instead of interactively establishing connections with NMS servers and network devices, control templates may be used to non-interactively establish these connections. Referring to
The template may also include an output file name 923f where any output/status information generated in response to the execution of the CONTROL template will be sent. The template may also include a version number 923g. Version numbers allow a new template to be created with the same name as an old template but with a new version number, and the new template may include additional/different parameters and/or instructions. Using version numbers, both old (e.g., not upgraded) and new OSS clients may use the templates but only access those templates having particular version numbers that correspond to the functionality of each OSS client.
Once connections with an NMS server and network device are established (either interactively or non-interactively through a control template), services within the network device may be provisioned. As described above, a network manager may interactively provision services by issuing execute commands followed by provisioning template types. Alternatively, a network manager may provision services non-interactively through batch templates, which include an ordered list of tasks, including execute commands followed by provisioning template types.
Referring to
If multiple similar provisioning tasks are needed, then the network manager may use writeCurrent or writeTemplate to create multiple similar templates (i.e., same template type with different template names), change or add parameter values within these multiple similar templates using the set command, and sequentially load and execute each of the different named templates. For example, SPVC is the template type and task3 causes the OSS to execute instructions within the previously loaded named template. Spvc1 and spvc2 are two different named templates (or template instantiations) corresponding to the SPVC template type for setting up soft permanent virtual circuits having different parameters from each other and the loaded template to set up different SPVCs. In this example, the BATCH template then includes task4924d including “load SPVC spvc1” to load the spvc1 template and then task5924e “execute SPVC” to cause the OSS client to execute the loaded spvc1 template and set up a different SPVC. Similarly, task6924f includes “load SPVC spvc2” and task7924e includes “execute SPVC” to cause the OSS client to execute the loaded spvc2 template and set up yet another different SPVC.
Alternatively, the batch template may include commands for altering an existing template such that multiple similar templates are not necessary. For example, the loaded BATCH template may include task50924g “set SPATH PortID 3” to cause the OSS client to change the PortID parameter within the SPATH template to 3. The BATCH template then includes task51924h “execute SPATH” 924g to cause the OSS client to execute the SPATH template including the new parameter value which sets up a different SONET path. A BATCH template may include many set commands to change parameter values followed by execute commands to provision multiple similar services within the same network device. For example, the BATCH template may further include task52924i “set SPATH SlotID 2” followed by task53924j “execute SPATH” to set up yet another different SONET path. Using this combination of set and execute commands eliminates the need to write, store and keep track of multiple similar templates.
Batch templates may also be used to non-interactively provision services within multiple different network devices by ordering and sequencing tasks including execute commands followed by control template types and then execute commands followed by provisioning template types. Referring to
If the network manager wishes to provision a network device coupled with another NMS server, then the BATCH template includes, for example, task108925h including “close” to drop the connection between the OSS client and localhost NMS server. The BATCH template may then have, for example, task109925i including “set CONTROL Server Server1” to change the server parameter within the loaded CONTROL template to Server1 and task110925j including “set CONTROL System 192.168.8.200” to change the network device parameter within the loaded CONTROL template to the IP address of the new network device. The BATCH template may then have task111925k including “execute CONTROL” to cause the OSS client to set up connections to the Server1 NMS server and to network device 192.168.8.200. The BATCH template may then include tasks with execute commands followed by provisioning template types to provision services within the network device, for example, task112925L includes “execute SPATH”.
The templates and interactive interpreter/OSS client may be loaded and executed on a central OSS computer system(s) and used to provision services in one or more network devices in one or more network domains. A network administrator may install an OSS client at various locations and/or for “manage anywhere” purposes, web technology may be used to allow a network manager to download an OSS client program from a web accessible server onto a computer at any location. The network manager may then use the OSS client in the same manner as when it is loaded onto a central OSS computer system. Thus, the network manager may provision services from any computer at any location.
Provisioning templates may be written to apply to different types of network devices. The network administrator does not need to know details of the network device being provisioned as the parameters required and available for modification are listed in the various templates. Consequently, the templates allow for multifaceted integration of different network management systems (NMS) into existing OSS infrastructures.
Instead of using template executable files and an OSS client, network managers may prefer to use their standard OSS interface to provision services in various network devices. In one embodiment, therefore, a single OSS client application programming interface (API) and a library of compiled code may be linked directly into the OSS software. The library of compiled code is a subset of the compiled code used to create the OSS client, with built-in templates including provisioning, control, batch and other types of templates. The OSS software then uses the supported templates as documentation of the necessary parameters needed for each provisioning task and presents template streams (null terminated arrays of arguments that serialize the totality of arguments required to construct a supported template) via the single API for potential alteration through the OSS standard interface. Since the network managers are comfortable working with the OSS interface, provisioning services may be made more efficient and simple by directly linking the OSS client API and templates into the OSS software.
Typically, OSS software is written in C or C++ programming language. In one embodiment, the OSS client and templates are written in JAVA, and JAVA Native Interface (JNI) is used by the OSS software to access the JAVA OSS client API and templates.
Inter-Process Communication:
As described above, the operating system assigns a unique process identification number (proc_id) to each spawned process. Each process has a name, and each process knows the names of other processes with which it needs to communicate. The operating system keeps a list of process names and the assigned process identification numbers. Processes send messages to other processes using the assigned process identification numbers without regard to what board is executing each process (i.e., process location). Application Programming Interfaces (APIs) define the format and type of information included in the messages.
The modular software architecture configuration model requires a single software process to support multiple configurable objects. For example, as described above, an ATM application may support configurations requiring multiple ATM interfaces and thousands of permanent virtual connections per ATM interface. The number of processes and configurable objects in a modular software architecture can quickly grow especially in a distributed processing system. If the operating system assigns a new process for each configurable object, the operating system's capabilities may be quickly exceeded.
For example, the operating system may be unable to assign a process for each ATM interface, each service endpoint, each permanent virtual circuit, etc. In some instances, the process identification numbering scheme itself may not be large enough. Where protected memory is supported, the system may have insufficient memory to assign each process and configurable object a separate memory block. In addition, supporting a large number of independent processes may reduce the operating system's efficiency and slow the operation of the entire computer system.
One alternative is to assign a unique process identification number to only certain high level processes. Referring to
One possible solution is to hard code the name of device driver 248 into ATM 240. ATM 240 then knows it must communicate with device driver 248 to learn about the existence of any service endpoints within device driver 248 that may be needed by ATM IF 242, 243 or 244. Unfortunately, this can lead to scalability issues. For instance, each instantiation of ATM (e.g., ATM 240, 241) needs to know the name of all device drivers (e.g., device drivers 248, 250, 252) and must query each device driver to locate each needed service endpoint. An ATM query to a device driver that does not include a necessary service endpoint is a waste of time and resources. In addition, each high level process must periodically poll other high level processes to determine whether objects within them are still active (i.e., not terminated) and whether new objects have been started. If the object status has not changed between polls, then the poll wasted resources. If the status did change, then communications have been stalled for the length of time between polls. In addition, if a new device driver is added (e.g., device driver 262), then ATM 240 and 241 cannot communicate with it or any of the service endpoints within it until they have been upgraded to include the new device driver's name.
Preferably, computer system 10 implements a name server process and a flexible naming procedure. The name server process allows high level processes to register information about the objects within them and to subscribe for information about the objects with which they need to communicate. The flexible naming procedure is used instead of hard coding names in processes. Each process, for example, applications and device drivers, use tables in the configuration database to derive the names of other configurable objects with which they need to communicate. For example, both an ATM application and a device driver process may use an assigned service endpoint number from the service endpoint table (SET) to derive the name of the service endpoint that is registered by the device driver and subscribed for by the ATM application. Since the service endpoint numbers are assigned by the NMS during configuration, stored in SET 76 and passed to local SEMs, they will not be changed if device drivers or applications are upgraded or restarted.
Referring to
Referring to
Applications, for example, ATM 224, also use SE numbers to generate the names of device drivers with which they need to communicate and subscribe to NS 220b for those device driver names, for example, atm.se1. If the device driver has published its name and process identification with NS 220b, then NS 220b notifies ATM 224 of the process identification number associated with atm.se1 and the name of its service endpoints. ATM 224 can then use the process identification to communicate with DD 222 and, hence, any objects within DD 222. If device driver 222 is restarted or upgraded, SEM 96a will again notify DD 222 that its associated service endpoint is SE 1 which will cause DD 222 to generate the same name of atm.se1. DD 222 will then re-publish with NS 220b and include the newly assigned process identification number. NS 220b will provide the new process identification number to ATM 224 to allow the processes to continue to communicate. Similarly, if ATM 224 is restarted or upgraded, it will use the service endpoint numbers from ATM interface table 114 and, as a result, derive the same name of atm.se1 for DD 222. ATM 224 will then re-subscribe with NS 220b.
Computer system 10 includes a distributed name server (NS) application including a name server process 220a-220n on each board (central processor and line card). Each name server process handles the registration and subscription for the processes on its corresponding board. For distributed applications, after each application (e.g., ATM 224a-224n) registers with its local name server (e.g., 220b-220n), the name server registers the application with each of the other name servers. In this way, only distributed applications are registered/subscribed system wide which avoids wasting system resources by registering local processes system wide.
The operating system, through the use of assigned process identification numbers, allows for inter-process communication (IPC) regardless of the location of the processes within the computer system. The flexible naming process allows applications to use data in the configuration database to determine the names of other applications and configurable objects, thus, alleviating the need for hard coded process names. The name server notifies individual processes of the existence of the processes and objects with which they need to communicate and the process identification numbers needed for that communication. The termination, re-start or upgrade of an object or process is, therefore, transparent to other processes, with the exception of being notified of new process identification numbers. For example, due to a configuration change initiated by the user of the computer system, service endpoint 253 (
The name server or a separate binding object manager (BOM) process may allow processes and configurable objects to pass additional information adding further flexibility to inter-process communications. For example, flexibility may be added to the application programming interfaces (APIs) used between processes. As discussed above, once a process is given a process identification number by the name server corresponding to an object with which it needs to communicate, the process can then send messages to the other process in accordance with a predefined application programming interface (API). Instead of having a predefined API, the API could have variables defined by data passed through the name server or BOM, and instead of having a single API, multiple APIs may be available and the selection of the API may be dependent upon information passed by the name server or BOM to the subscribed application.
Referring to
In addition to adding flexibility to the size of fields in a message format, flexibility may be added to the overall message format including the type of fields included in the message. When a process registers its name and process identification number, it may also register a version number indicating which API version should be used by other processes wishing to communicate with it. For example, device driver 250 (
This also allows an application, for example, ATM, to be upgraded to support new configurable objects, for example, new ATM interfaces, while still being backward compatible by supporting older configurable objects, for example, old ATM interfaces. Backward compatibility has been provided in the past through revision numbers, however, initial communication between processes involved polling to determine version numbers and where multiple applications need to communicate, each would need to poll the other. The name server/BOM eliminates the need for polling.
As described above, the name server notifies subscriber applications each time a subscribed for process is terminated. Instead, the name server/BOM may not send such a notification unless the System Resiliency Manager (SRM) tells the name server /BOM to send such a notification. For example, depending upon the fault policy/resiliency of the system, a particular software fault may simply require that a process be restarted. In such a situation, the name server/BOM may not notify subscriber applications of the termination of the failed process and instead simply notify the subscriber applications of the newly assigned process identification number after the failed process has been restarted. Data that is sent by the subscriber processes after the termination of the failed process and prior to the notification of the new process identification number may be lost but the recovery of this data (if any) may be less problematic than notifying the subscriber processes of the failure and having them hold all transmissions. For other faults, or after a particular software fault occurs a predetermined number of times, the SRM may then require the name server/BOM to notify all subscriber processes of the termination of the failed process. Alternatively, if a terminated process does not re-register within a predetermined amount of time, the name server/BOM may then notify all subscriber processes of the termination of the failed process.
Configuration Change:
Over time the user will likely make hardware changes to the computer system that require configuration changes. For example, the user may plug a fiber or cable (i.e., network connection) into an as yet unused port, in which case, the port must be enabled and, if not already enabled, then the port's line card must also be enabled. As other examples, the user may add another path to an already enabled port that was not fully utilized, and the user may add another line card to the computer system. Many types of configuration changes are possible, and the modular software architecture allows them to be made while the computer system is running (hot changes). Configuration changes may be automatically copied to persistent storage as they are made so that if the computer system is shut down and rebooted, the memory and configuration database will reflect the last known state of the hardware.
To make a configuration change, the user informs the NMS (e.g., NMS client 850a,
Referring to
Configuration database 42 also notifies (through the active query process) SEM 96c that a new service endpoint (SE 10) was added to the SET corresponding to its port (PID 1502), and configuration database 42 also notifies ATM instantiation 112 that a new ATM interface (ATM-IF 166) was added to the ATM interface table corresponding to ATM group 3. ATM 112 establishes ATM interface 166 and SEM 96c notifies port driver 142 that it has been assigned SE10. A communication link is established through NS 220b. Device driver 142 generates a service endpoint name using the assigned SE number and publishes this name and its process identification number with NS 220b. ATM interface 166 generates the same service endpoint name and subscribes to NS 220b for that service endpoint name. NS 220b provides ATM interface 166 with the process identification assigned to DD 142 allowing ATM interface 166 to communicate with device driver 142.
Certain board changes to computer system 10 are also configuration changes. After power-up and configuration, a user may plug another board into an empty computer system slot or remove an enabled board and replace it with a different board. In the case where applications and drivers for a line card added to computer system 10 are already loaded, the configuration change is similar to initial configuration. The additional line card may be identical to an already enabled line card, for example, line card 16a or if the additional line card requires different drivers (for different components) or different applications (e.g., IP), the different drivers and applications are already loaded because computer system 10 expects such cards to be inserted.
Referring to
Referring to
When master MCD 38 updates card table 47, configuration database 42 updated NMS database 61 which sends NMS 60 (e.g., NMS Server 851a,
Logical Model Change:
Where applications and device drivers for a new line card are not already loaded and where changes or upgrades to already loaded applications and device drivers are needed, logical model 280 (
New and upgraded applications and device drivers are being used by way of an example, and it should be understood that other processes, for example, modular system services and new Mission Kernel Images (MKIs), may be changed or upgraded in the same fashion.
Referring to
Application Upgrade:
For new applications and application upgrades, the NMS works with a software management system (SMS) service to implement the change while the computer system is running (hot upgrades or additions). The SMS is one of the modular system services, and like the MCD and the SRM, the SMS is a distributed application. Referring to
Upgrading a distributed application that is running on multiple boards is more complicated than upgrading an application running on only one board. As an example of a distributed application upgrade, the user may want to upgrade all ATM applications running on various boards in the system using new ATM version two 360. This is by way of example, and it should be understood, that only one ATM application may be upgraded so long as it is compatible with the other versions of ATM running on other boards. ATM version two 360 may include many sub-processes, for example, an upgraded ATM application executable file (ATMv2.exe 189), an upgraded ATM control executable file (ATMv2_cntrl.exe 190) and an ATM configuration control file (ATMv2_cnfg_cntrl.exe). The NMS downloads ATMv2.exe 189, ATMv2_cntrl.exe and ATMv2_cnfg_cntrl.exe to memory 40 on central processor 12.
The NMS then writes a new record into SMS table 192 indicating the scope of the configuration update. The scope of an upgrade may be indicated in a variety of ways. In one embodiment, the SMS table includes a field for the name of the application to be changed and other fields indicating the changes to be made. In another embodiment, the SMS table includes a revision number field 194 (
During initial configuration, the SMS establishes an active query on SMS table 192. Consequently, when the NMS changes the SMS table, the configuration database sends a notification to master SMS 184 including the change. In some instances, the change to an application may require changes to configuration database 42. The SMS determines the need for configuration conversion based on the scope of the release or update. If the configuration database needs to be changed, then the software, for example, ATM version two 360, provided by the user and downloaded by the NMS also includes a configuration control executable file, for example, ATMv2_cnfig_cntrl.exe 191, and the name of this file will be in the SMS table record. The master SMS then directs slave SRM 37a on central processor 12 to execute the configuration control file which uses DDL file 344′ to upgrade old configuration database 42 into new configuration database 42′ by creating new tables, for example, ATM group table 108′ and ATM interface table 114′.
Existing processes using their view ids and APIs to access new configuration database 42′ in the same manner as they accessed old configuration database 42. However, when new processes (e.g., ATM version two 360 and device driver 362) access new configuration database 42′, their view ids and APIs allow them to access new tables and data within new configuration database 42′.
The master SMS also reads ATM group table 108′ to determine that instances of ATM are being executed on line cards 16a-16n. In order to upgrade a distributed application, in this instance, ATM, the Master SMS will use a lock step procedure. Master SMS 184 tells each slave SMS 186b-186n to stall the current versions of ATM. When each slave responds, Master SMS 184 then tells slave SMSs 186b-186n to download and execute ATMv2_cntrl.exe 190 from memory 40. Upon instructions from the slave SMSs, slave SRMs 37b-37n download and execute copies of ATMv2_cntrl.exe 204a-204n. The slave SMSs also pass data to the ATMv2cntrl.exe file through the SRM. The data instructs the control shim to start in upgrade mode and passes required configuration information. The upgraded ATMv2 controllers 204a-204n then use ATM group table 108′ and ATM interface table 114′ as described above to implement ATMv2 206a-206n on each of the line cards. In this example, each ATM controller is shown implementing one instance of ATM on each line card, but as explained below, the ATM controller may implement multiple instances of ATM on each line card.
As part of the upgrade mode, the updated versions of ATMv2 206a-206n retrieve active state from the current versions of ATM 188a-188n. The retrieval of active state can be accomplished in the same manner that a redundant or backup instantiation of ATM retrieves active state from the primary instantiation of ATM. When the upgraded instances of ATMv2 are executing and updated with active state, the ATMv2 controllers notify the slave SMSs 186b-186n on their board and each slave SMS 186b-186n notifies master SMS 184. When all boards have notified the master SMS, the master SMS tells the slave SMSs to switchover to ATMv2 206a-206n. The slave SMSs tell the slave SRMs running on their board, and the slave SRMs transition the new ATMv2 processes to the primary role. This is termed “lock step upgrade” because each of the line cards is switched over to the new ATMv2 processes simultaneously.
There may be upgrades that require changes to multiple applications and to the APIs for those applications. For example, a new feature may be added to ATM that also requires additional functionality to be added to the Multi-Protocol Label Switching (MPLS) application. The additionally functionality may change the peer-to-peer API for ATM, the peer-to-peer API for MPLS and the API between ATM and MPLS. In this scenario, the upgrade operation must avoid allowing the “new” version of ATM to communicate with itself or the “old” version of MPLS and vice versa. The master SMS will use the release number scheme to determine the requirements for the individual upgrade. For example, the upgrade may be from release 1.0.0.0 to 1.0.1.3 where the release differs by the subsystem compatibility level. The SMS implements the upgrade in a lock step fashion. All instances of ATM and MPLS are upgraded first. The slave SMS on each line card then directs the slave SRM on its board to terminate all “old” instances of ATM and MPLS and switchover to the new instances of MPLS and ATM. The simultaneous switchover to new versions of both MPLS and ATM eliminate any API compatibility errors.
Referring to
The upgrade is begun as discussed above with the NMS downloading ATM version two 360—including ATMv2.exe 189, ATMv2_cntrl.exe and ATMv2_cnfg_cntrl.exe—and DDL file 344′ to memory on central processor 12. Simultaneously, because central processor 13 is in backup mode, the application and DDL file are also copied to memory on central processor 13. The NMS also creates a software load record in SMS table 192, 192′ indicating the upgrade. In this embodiment, when the SMS determines that the scope of the upgrade requires an upgrade to the configuration database, the master SMS instructs slave SMS 186e on central processor 13 to perform the upgrade. Slave SMS 186e works with slave SRM 37e to cause backup processor 13 to change from backup mode to upgrade mode.
In upgrade mode, backup processor 13 stops replicating the active state of central processor 12. Any changes made to new configuration database 420 are copied to new NMS database 61′. Slave SMS 186e then directs slave SRM 37e to execute the configuration control file which uses DDL file 344′ to upgrade configuration database 420.
Once configuration database 420 is upgraded, a fail-over or switch-over from central processor 12 to backup central processor 13 is initiated. Central processor 13 then begins acting as the primary central processor and applications running on central processor 13 and other boards throughout computer system 10 begin using upgraded configuration database 420.
Central processor 12 may not become the backup central processor right away. Instead, central processor 12 with its older copy of configuration database 42 stays dormant in case an automatic downgrade is necessary (described below). If the upgrade goes smoothly and is committed (described below), then central processor 12 will begin operating in backup mode and replace old configuration database 42 with new configuration database 420.
Device Driver Upgrade:
Device driver software may also be upgraded and the implementation of device driver upgrades is similar to the implementation of application upgrades. The user informs the NMS of the device driver change and provides a copy of the new software (e.g., DD^.exe 362,
The master SMS notifies each slave SMS running on boards to be upgraded of the name of the device driver executable file to download and execute. In the example, master SMS 184 sends slave SMS 186f the name of the upgraded device driver (DD^.exe 362) to download. Slave SMS 186f tells slave SRM to download and execute DD^.exe 362 in upgrade mode. Once downloaded, DD^.exe 363 (copy of DD^.exe 362) gathers active state information from the currently running DD.exe 212 in a similar fashion as a redundant or backup device driver would gather active state. DD^.exe 362 then notifies slave SRM 37f that active state has been gathered, and slave SRM 37f stops the current DD.exe 212 process and transitions the upgraded DD^.exe 362 process to the primary role.
Automatic Downgrade:
Often, implementation of an upgrade, can cause unexpected errors in the upgraded software, in other applications or in hardware. As described above, a new configuration database 42′ (
Because the operating system provides a protected memory model that assigns different process blocks to different processes, including upgraded applications, the original applications will not share memory space with the upgraded applications and, therefore, cannot corrupt or change the memory used by the original application. Similarly, memory 40 is capable of simultaneously maintaining the original and upgraded versions of the configuration database records and executable files as well as the original and upgraded versions of the applications (e.g., ATM 188a-188n). As a result, the SMS is capable of an automatic downgrade on the detection of an error. To allow for automatic downgrade, the SRMs pass error information to the SMS. The SMS may cause the system to revert to the old configuration and application (i.e., automatic downgrade) on any error or only for particular errors.
As mentioned, often upgrades to one application may cause unexpected faults or errors in other software. If the problem causes a system shut down and the configuration upgrade was stored in persistent storage, then the system, when powered back up, will experience the error again and shut down again. Since, the upgrade changes to the configuration database are not copied to persistent storage 21 until the upgrade is committed, if the computer system is shut down, when it is powered back up, it will use the original version of the configuration database and the original executable files, that is, the computer system will experience an automatic downgrade.
Additionally, a fault induced by an upgrade may cause the system to hang, that is, the computer system will not shut down but will also become inaccessible by the NMS and inoperable. To address this concern, in one embodiment, the NMS and the master SMS periodically send messages to each other indicating they are executing appropriately. If the SMS does not receive one of these messages in a predetermined period of time, then the SMS knows the system has hung. The master SMS may then tell the slave SMSs to revert to the old configuration (i.e., previously executing copies of ATM 188a-188n) and if that does not work, the master SMS may re-start/re-boot computer system 10. Again, because the configuration changes were not saved in persistent storage, when the computer system powers back up, the old configuration will be the one implemented.
Evaluation Mode:
Instead of implementing a change to a distributed application across the entire computer system, an evaluation mode allows the SMS to implement the change in only a portion of the computer system. If the evaluation mode is successful, then the SMS may fully implement the change system wide. If the evaluation mode is unsuccessful, then service interruption is limited to only that portion of the computer system on which the upgrade was deployed. In the above example, instead of executing the upgraded ATMv2 189 on each of the line cards, the ATMv2 configuration convert file 191 will create an ATMv2 group table 108′ indicating an upgrade only to one line card, for example, line card 16a. Moreover, if multiple instantiations of ATM are running on line card 16a (e.g., one instantiation per port), the ATMv2 configuration convert file may indicate through ATMv2 interface table 114′ that the upgrade is for only one instantiation (e.g., one port) on line card 16a. Consequently, a failure is likely to only disrupt service on that one port, and again, the SMS can further minimize the disruption by automatically downgrading the configuration of that port on the detection of an error. If no error is detected during the evaluation mode, then the upgrade can be implemented over the entire computer system.
Upgrade Commitment:
Upgrades are made permanent by saving the new application software and new configuration database and DDL file in persistent storage and removing the old configuration data from memory 40 as well as persistent storage. As mentioned above, changes may be automatically saved in persistent storage as they are made in non-persistent memory (no automatic downgrade), or the user may choose to automatically commit an upgrade after a successful time interval lapses (evaluation mode). The time interval from upgrade to commitment may be significant. During this time, configuration changes may be made to the system. Since these changes are typically made in non-persistent memory, they will be lost if the system is rebooted prior to upgrade commitment. Instead, to maintain the changes, the user may request that certain configuration changes made prior to upgrade commitment be copied into the old configuration database in persistent memory. Alternatively, the user may choose to manually commit the upgrade at his or her leisure. In the manual mode, the user would ask the NMS to commit the upgrade and the NMS would inform the master SMS, for example, through a record in the SMS table.
Independent Process Failure and Restart:
Depending upon the fault policy managed by the slave SRMs on each board, the failure of an application or device driver may not immediately cause an automatic downgrade during an upgrade process. Similarly, the failure of an application or device driver during normal operation may not immediately cause the fail over to a backup or redundant board. Instead, the slave SRM running on the board may simply restart the failing process. After multiple failures by the same process, the fault policy may cause the SRM to take more aggressive measures such as automatic downgrade or fail-over.
Referring to
For network devices, this separation of the control plane and data plane means that the connections previously established by the ATM application are not lost when ATM fails and hardware controlled by the device drivers continue to pass data through connections previously established by the ATM application. Until the ATM application is restarted and re-synchronized (e.g., through an audit process, described below) with the active state of the device drivers, no new network connections may be established but the device drivers continue to pass data through the previously established connections to allow the network device to minimize disruption and maintain high availability.
Local Backup:
If a device driver, for example, device driver 234, fails instead of an application, for example, ATM 230, then data cannot be passed. For a network device, it is critical to continue to pass data and not lose network connections. Hence, the failed device driver must be brought back up (i.e., recovered) as soon as possible. In addition, the failing device driver may have corrupted the hardware it controls, therefore, that hardware must be reset and reinitialized. The hardware may be reset as soon as the device driver terminates or the hardware may be reset later when the device driver is restarted.
Resetting the hardware stops data flow. In some instances, therefore, resetting the hardware will be delayed until the device driver is restarted to minimize the time period during which data is not flowing. Alternatively, the failing device driver may have corrupted the hardware, thus, resetting the hardware as soon as the device driver is terminated may be important to prevent data corruption. In either case, the device driver re-initializes the hardware during its recovery.
Again, because applications and device drivers are assigned independent memory blocks, a failed device driver can be restarted without having to restart associated applications and device drivers. Independent recovery may save significant time as described above for applications. In addition, restoring the data plane (i.e., device drivers) can be simpler and faster than restoring the control plane (i.e., applications). While it may be just as challenging in terms of raw data size, device driver recovery may simply require that critical state data be copied into place in a few large blocks, as opposed to application recovery which requires the successive application of individual configuration elements and considerable parsing, checking and analyzing. In addition, the application may require data stored in the configuration database on the central processor or data stored in the memory of other boards. The configuration database may be slow to access especially since many other applications also access this database. The application may also need time to access a management information base (MIB) interface.
To increase the speed with which a device driver is brought back up, the restarted device driver program accesses local backup 236. In one example, local backup is a simple storage/retrieval process that maintains the data in simple lists in physical memory (e.g., random access memory, RAM) for quick access. Alternatively, local backup may be a database process, for example, a Polyhedra database, similar to the configuration database.
Local backup 236 stores the last snap shot of critical state information used by the original device driver before it failed. The data in local backup 236 is in the format required by the device driver. In the case of a network device, local back up data may include path information, for example, service endpoint, path width and path location. Local back up data may also include virtual interface information, for example, which virtual interfaces were configured on which paths and virtual circuit (VC) information, for example, whether each VC is switched or passed through segmentation and reassembly (SAR), whether each VC is a virtual channel or virtual path and whether each VC is multicast or merge. The data may also include traffic parameters for each VC, for example, service class, bandwidth and/or delay requirements.
Using the data in the local backup allows the device driver to quickly recover. An Audit process resynchronizes the restarted device driver with associated applications and other device drivers such that the data plane can again transfer network data. Having the backup be local reduces recovery time. Alternatively, the backup could be stored remotely on another board but the recovery time would be increased by the amount of time required to download the information from the remote location.
Audit Process:
It is virtually impossible to ensure that a failed process is synchronized with other processes when it restarts, even when backup data is available. For example, an ATM application may have set up or torn down a connection with a device driver but the device driver failed before it updated corresponding backup data. When the device driver is restarted, it will have a different list of established connections than the corresponding ATM application (i.e., out of synchronization). The audit process allows processes like device drivers and ATM applications to compare information, for example, connection tables, and resolve differences. For instance, connections included in the driver's connection table and not in the ATM connection table were likely torn down by ATM prior to the device driver crash and are, therefore, deleted from the device driver connection table. Connections that exist in the ATM connection table and not in the device driver connection table were likely set up prior to the device driver failure and may be copied into the device driver connection table or deleted from the ATM connection table and re-set up later. If an ATM application fails and is restarted, it must execute an audit procedure with its corresponding device driver or drivers as well as with other ATM applications since this is a distributed application.
Vertical Fault Isolation:
Typically, a single instance of an application executes on a single card or in a system. Fault isolation, therefore, occurs at the card level or the system level, and if a fault occurs, an entire card—and all the ports on that card—or the entire system—and all the ports in the system—is affected. In a large communications platform, thousands of customers may experience service outages due to a single process failure.
For resiliency and fault isolation one or more instances of an application and/or device driver may be started per port on each line card. Multiple instances of applications and device drivers are more difficult to manage and require more processor cycles than a single instance of each but if an application or device driver fails, only the port those processes are associated with is affected. Other applications and associated ports—as well as the customers serviced by those ports—will not experience service outages. Similarly, a hardware failure associated with only one port will only affect the processes associated with that port. This is referred to as vertical fault isolation.
Referring to
Vertical fault isolation allows processes to be deployed in a fashion supportive of the underlying hardware architecture and allows processes associated with particular hardware (e.g., a port) to be isolated from processes associated with other hardware (e.g., other ports) on the same or a different line card. Any single hardware or software failure will affect only those customers serviced by the same vertical stack. Vertical fault isolation provides a fine grain of fault isolation and containment. In addition, recovery time is reduced to only the time required to re-start a particular application or driver instead of the time required to re-start all the processes associated with a line card or the entire system.
Fault/Event Detection:
Traditionally, fault detection and monitoring does not receive a great deal of attention from network equipment designers. Hardware components are subjected to a suite of diagnostic tests when the system powers up. After that, the only way to detect a hardware failure is to watch for a red light on a board or wait for a software component to fail when it attempts to use the faulty hardware. Software monitoring is also reactive. When a program fails, the operating system usually detects the failure and records minimal debug information.
Current methods provide only sporadic coverage for a narrow set of hard faults. Many subtler failures and events often go undetected. For example, hardware components sometimes suffer a minor deterioration in functionality, and changing network conditions stress the software in ways that were never expected by the designers. At times, the software may be equipped with the appropriate instrumentation to detect these problems before they become hard failures, but even then, network operators are responsible for manually detecting and repairing the conditions.
Systems with high availability goals must adopt a more proactive approach to fault and event monitoring. In order to provide comprehensive fault and event detection, different hierarchical levels of fault/event management software are provided that intelligently monitor hardware and software and proactively take action in accordance with a defined fault policy. A fault policy based on hierarchical scopes ensures that for each particular type of failure the most appropriate action is taken. This is important because over-reacting to a failure, for example, re-booting an entire computer system or re-starting an entire line card, may severely and unnecessarily impact service to customers not affected by the failure, and under-reacting to failures, for example, restarting only one process, may not completely resolve the fault and lead to additional, larger failures. Monitoring and proactively responding to events may also allow the computer system and network operators to address issues before they become failures. For example, additional memory may be assigned to programs or added to the computer system before a lack of memory causes a failure.
Hierarchical Scopes and Escalation:
Referring to
A master logging entity 431 also runs on central processor 12 and slave logging entities 433a-433n run on each board. Notifications of failures and other events are sent by the master SRM, slave SRMs and LRMs to their local logging entity which then notifies the master logging entity. The master logging entity enters the event in a master event log file 435. Each local logging entity may also log local events in a local event log file 435a-435n.
In addition, a fault policy table 429 may be created in configuration database 42 by the NMS when the user wishes to over-ride some or all of the default fault policy (see configurable fault policy below), and the master and slave SRMs are notified of the fault policies through the active query process.
Referring to
If, for example, SSCOP 439 detects a fault, it notifies LRM 436. LRM 436 passes the fault to local slave SRM 37b, which catalogs the fault in the ATM application's fault history and sends a notice to local slave logging entity 433b. The slave logging entity sends a notice to master logging entity 431, which may log the event in master log event file 435. The local logging entity may also log the failure in local event log 435a. LRM 436 also determines, based on the type of failure, whether it can fully resolve the error and do so without affecting other processes outside its scope, for example, ATM 111-113, device drivers 43a-43d and their sub-processes and processes running on other boards. If yes, then the LRM takes corrective action in accordance with its fault policy. Corrective action may include restarting SSCOP 439 or resetting it to a known state.
Since all sub-processes within an application, including the LRM sub-process, share the same memory space, it may be insufficient to restart or reset a failing sub-process (e.g., SSCOP 439). Hence, for most failures, the fault policy will cause the LRM to escalate the failure to the local slave SRM. In addition, many failures will not be presented to the LRM but will, instead, be presented directly to the local slave SRM. These failures are likely to have been detected by either processor exceptions, OS errors or low-level system service errors. Instead of failures, however, the sub-processes may notify the LRM of events that may require action. For example, the LRM may be notified that the PNNI message queue is growing quickly. The LRM's fault policy may direct it to request more memory from the operating system. The LRM will also pass the event to the local slave SRM as a non-fatal fault. The local slave SRM will catalog the event and log it with the local logging entity, which may also log it with the master logging entity. The local slave SRM may take more severe action to recover from an excessive number of these non-fatal faults that result in memory requests.
If the event or fault (or the actions required to handle either) will affect processes outside the LRM's scope, then the LRM notifies slave SRM 37b of the event or failure. In addition, if the LRM detects and logs the same failure or event multiple times and in excess of a predetermined threshold set within the fault policy, the LRM may escalate the failure or event to the next hierarchical scope by notifying slave SRM 37b. Alternatively or in addition, the slave SRM may use the fault history for the application instance to determine when a threshold is exceeded and automatically execute its fault policy.
When slave SRM 37b detects or is notified of a failure or event, it notifies slave logging entity 435b. The slave logging entity notifies master logging entity 431, which may log the failure or event in master event log 435, and the slave logging entity may also log the failure or event in local event log 435b. Slave SRM 37b also determines, based on the type of failure or event, whether it can handle the error without affecting other processes outside its scope, for example, processes running on other boards. If yes, then slave SRM 37b takes corrective action in accordance with its fault policy and logs the fault. Corrective action may include re-starting one or more applications on line card 16a.
If the fault or recovery actions will affect processes outside the slave SRM's scope, then the slave SRM notifies master SRM 36. In addition, if the slave SRM has detected and logged the same failure multiple times and in excess of a predetermined threshold, then the slave SRM may escalate the failure to the next hierarchical scope by notifying master SRM 36 of the failure. Alternatively, the master SRM may use its fault history for a particular line card to determine when a threshold is exceeded and automatically execute its fault policy.
When master SRM 36 detects or receives notice of a failure or event, it notifies slave logging entity 433a, which notifies master logging entity 431. The master logging entity 431 may log the failure or event in master log file 435 and the slave logging entity may log the failure or event in local event log 435a. Master SRM 36 also determines the appropriate corrective action based on the type of failure or event and its fault policy. Corrective action may require failing-over one or more line cards 16a-16n or other boards, including central processor 12, to redundant backup boards or, where backup boards are not available, simply shutting particular boards down. Some failures may require the master SRM to re-boot the entire computer system.
An example of a common error is a memory access error. As described above, when the slave SRM starts a newinstance of an application, it requests a protected memory block from the local operating system. The local operating systems assign each instance of an application one block of local memory and then program the local memory management unit (MMU) hardware with which processes have access (read and/or write) to each block of memory. An MMU detects a memory access error when a process attempts to access a memory block not assigned to that process. This type of error may result when the process generates an invalid memory pointer. The MMU prevents the failing process from corrupting memory blocks used by other processes (i.e., protected memory model) and sends a hardware exception to the local processor. A local operating system fault handler detects the hardware exception and determines which process attempted the invalid memory access. The fault handler then notifies the local slave SRM of the hardware exception and the process that caused it. The slave SRM determines the application instance within which the fault occurred and then goes through the process described above to determine whether to take corrective action, such as restarting the application, or escalate the fault to the master SRM.
As another example, a device driver, for example, device driver 43a may determine that the hardware associated with its port, for example, port 44a, is in a bad state. Since the failure may require the hardware to be swapped out or failed-over to redundant hardware or the device driver itself to be re-started, the device driver notifies slave SRM 37b. The slave SRM then goes through the process described above to determine whether to take corrective action or escalate the fault to the master SRM.
As a third example, if a particular application instance repeatedly experiences the same software error but other similar application instances running on different ports do not experience the same error, the slave SRM may determine that it is likely a hardware error. The slave SRM would then notify the master SRM which may initiate a fail-over to a backup board or, if no backup board exists, simply shut down that board or only the failing port on that board. Similarly, if the master SRM receives failure reports from multiple boards indicating Ethernet failures, the master SRM may determine that the Ethernet hardware is the problem and initiate a fail-over to backup Ethernet hardware.
Consequently, the failure type and the failure policy determine at what scope recovery action will be taken. The higher the scope of the recovery action, the larger the temporary loss of services. Speed of recovery is one of the primary considerations when establishing a fault policy. Restarting a single software process is much faster than switching over an entire board to a redundant board or re-booting the entire computer system. When a single process is restarted, only a fraction of a card's services are affected. Allowing failures to be handled at appropriate hierarchical levels avoids unnecessary recovery actions while ensuring that sufficient recovery actions are taken, both of which minimize service disruption to customers.
Hierarchical Descriptors:
Hierarchical descriptors may be used to provide information specific to each failure or event. The hierarchical descriptors provide granularity with which to report faults, take action based on fault history and apply fault recovery policies. The descriptors can be stored in master event log file 435 or local event log files 435a-435n through which faults and events may be tracked and displayed to the user and allow for fault detection at a fine granular level and proactive response to events. In addition, the descriptors can be matched with descriptors in the fault policy to determine the recovery action to be taken.
Referring to
The type field more specifically defines the subclass failure or event. For example, if a hardware class, Ethernet subclass failure has occurred, the type field may indicate a more specific type of Ethernet failure, for instance, a cyclic redundancy check (CRC) error or a runt packet error. Similarly, if a software class, ATM failure or event has occurred, the type field may indicate a more specific type of ATM failure or event, for instance, a private network-to-network interface (PNNI) error or a growing message queue event. The instance field identifies the actual hardware or software that failed or generated the event. For example, with regard to a hardware class, Ethernet subclass, CRC type failure, the instance indicates the actual Ethernet port that experienced the failure. Similarly, with regard to a software class, ATM subclass, PNNI type, the instance indicates the actual PNNI sub-program that experienced the failure or generated the event.
When a fault or event occurs, the hierarchical scope that first detects the failure or event creates a descriptor by filling in the fields described above. In some cases, however, the Instance field is not applicable. The descriptor is sent to the local logging entity, which may log it in the local event log file before notifying the master logging entity, which may log it in the master event log file 435. The descriptor may also be sent to the local slave SRM, which tracks fault history based on the descriptor contents per application instance. If the fault or event is escalated, then the descriptor is passed to the next higher hierarchical scope.
When slave SRM 37b receives the fault/event notification and the descriptor, it compares it to descriptors in the fault policy for the particular scope in which the fault occurred looking for a match or a best case match which will indicate the recovery procedure to follow. Fault descriptors within the fault policy can either be complete descriptors or have wildcards in one or more fields. Since the descriptors are hierarchical from left to right, wildcards in descriptor fields only make sense from right to left. The fewer the fields with wildcards, the more specific the descriptor. For example, a particular fault policy may apply to all software faults and would, therefore, include a fault descriptor having the class field set to “software” and the remaining fields—subclass, type, and instance—set to wildcard or “match all.” The slave SRM searches the fault policy for the best match (i.e., the most fields matched) with the descriptor to determine the recovery action to be taken.
Configurable Fault Policy:
In actual use, a computer system is likely to encounter scenarios that differ from those in which the system was designed and tested. Consequently, it is nearly impossible to determine all the ways in which a computer system might fail, and in the face of an unexpected error, the default fault policy that was shipped with the computer system may cause the hierarchical scope (master SRM, slave SRM or LRM) to under-react or over-react. Even for expected errors, after a computer system ships, certain recovery actions in the default fault policy may be determined to be over aggressive or too lenient. Similar issues may arise as new software and hardware is released and/or upgraded.
A configurable fault policy allows the default fault policy to be modified to address behavior specific to a particular upgrade or release or to address behavior that was learned after the implementation was released. In addition, a configurable fault policy allows users to perform manual overrides to suit their specific requirements and to tailor their policies based on the individual failure scenarios that they are experiencing.
The modification may cause the hierarchical scope to react more or less aggressively to particular known faults or events, and the modification may add recovery actions to handle newly learned faults or events. The modification may also provide a temporary patch while a software or hardware upgrade is developed to fix a particular error.
If an application runs out of memory space, it notifies the operating system and asks for more memory. For certain applications, this is standard operating procedure. As an example, an ATM application may have set up a large number of virtual circuits and to continue setting up more, additional memory is needed. For other applications, a request for more memory indicates a memory leak error. The fault policy may require that the application be re-started causing some service disruption. It may be that re-starting the application eventually leads to the same error due to a bug in the software. In this instance, while a software upgrade to fix the bug is developed, a temporary patch to the fault policy may be necessary to allow the memory leak to continue and prevent repeated application re-starts that may escalate to line card re-start or fail-over and eventually to a re-boot of the entire computer system. A temporary patch to the default fault policy may simply allow the hierarchical scope, for example, the local resiliency manager or the slave SRM, to assign additional memory to the application. Of course, an eventual re-start of the application is likely to be required if the application's leak consumes too much memory.
A temporary patch may also be needed while a hardware upgrade or fix is developed for a particular hardware fault. For instance, under the default fault policy, when a particular hardware fault occurs, the recovery policy may be to fail-over to a backup board. If the backup board includes the same hardware with the same hardware bug, for example, a particular semiconductor chip, then the same error will occur on the backup board. To prevent a repetitive fail-over while a hardware fix is developed, the temporary patch to the default fault policy may be to restart the device driver associated with the particular hardware instead of failing-over to the backup board.
In addition to the above needs, a configurable fault policy also allows purchasers of computer system 10 (e.g., network service providers) to define their own policies. For example, a network service provider may have a high priority customer on a particular port and may want all errors and events (even minor ones) to be reported to the NMS and displayed to the network manager. Watching all errors and events might give the network manager early notice of growing resource consumption and the need to plan to dedicate additional resources to this customer.
As another example, a user of computer system 10 may want to be notified when any process requests more memory. This may give the user early notice of the need to add more memory to their system or to move some customers to different line cards.
Referring again to
Alternatively, active queries may be established with the configuration database for configuration fault policies specific to each board type such that the slave SRMs are notified directly of changes to their default fault policies.
A fault policy (whether default or configured) is specific to a particular scope and descriptor and indicates a particular recovery action to take. As one example, a temporary patch may be required to handle hardware faults specific to a known bug in an integrated circuit chip. The configured fault policy, therefore, may indicate a scope of all line cards, if the component is on all line cards, or only a specific type of line card that includes that component. The configured fault policy may also indicate that it is to be applied to all hardware faults with that scope, for example, the class will indicate hardware (HW) and all other fields will include wildcards (e.g., HW.*.*.*). Instead, the configured fault policy may only indicate a particular type of hardware failure, for example, CRC errors on transmitted Ethernet packets (e.g., HW.Ethernet.TxCRC.*).
Redundancy:
As previously mentioned, a major concern for service providers is network downtime. In pursuit of “five 9's availability” or 99.999% network up time, service providers must minimize network outages due to equipment (i.e., hardware) and all too common software failures. Developers of computer systems often use redundancy measures to minimize downtime and enhance system resiliency. Redundant designs rely on alternate or backup resources to overcome hardware and/or software faults. Ideally, the redundancy architecture allows the computer system to continue operating in the face of a fault with minimal service disruption, for example, in a manner transparent to the service provider's customer.
Generally, redundancy designs come in two forms: 1:1 and 1:N. In a so-called “1:1 redundancy” design, a backup element exists for every active or primary element (i.e., hardware backup). In the event that a fault affects a primary element, a corresponding backup element is substituted for the primary element. If the backup element has not been in a “hot” state (i.e., software backup), then the backup element must be booted, configured to operate as a substitute for the failing element, and also provided with the “active state” of the failing element to allow the backup element to take over where the failed primary element left off. The time required to bring the software on the backup element to an “active state” is referred to as synchronization time. A long synchronization time can significantly disrupt system service, and in the case of a computer network device, if synchronization is not done quickly enough, then hundreds or thousands of network connections may be lost which directly impacts the service provider's availability statistics and angers network customers.
To minimize synchronization time, many 1:1 redundancy schemes support hot backup of software, which means that the software on the backup elements mirror the software on the primary elements at some level. The “hotter” the backup element—that is, the closer the backup mirrors the primary—the faster a failed primary can be switched over or failed over to the backup. The “hottest” backup element is one that runs hardware and software simultaneously with a primary element conducting all operations in parallel with the primary element. This is referred to as a “1+1 redundancy” design and provides the fastest synchronization.
Significant costs are associated with 1:1 and 1+1 redundancy. For example, additional hardware costs may include duplicate memory components and printed circuit boards including all the components on those boards. The additional hardware may also require a larger supporting chassis. Space is often limited, especially in the case of network service providers who may maintain hundreds of network devices. Although 1:1 redundancy improves system reliability, it decreases service density and decreases the mean time between failures. Service density refers to the proportionality between the net output of a particular device and its gross hardware capability. Net output, in the case of a network device (e.g., switch or router), might include, for example, the number of calls handled per second. Redundancy adds to gross hardware capability but not to the net output and, thus, decreases service density. Adding hardware increases the likelihood of a failure and, thus, decreases the mean time between failures. Likewise, hot backup comes at the expense of system power. Each active element consumes some amount of the limited power available to the system. In general, the 1+1 or 1:1 redundancy designs provide the highest reliability but at a relatively high cost. Due to the importance of network availability, most network service providers prefer the 1+1 redundancy design to minimize network downtime.
In a 1:N redundancy design, instead of having one backup element per primary element, a single backup element or spare is used to backup multiple (N) primary elements. As a result, the 1:N design is generally less expensive to manufacture, offers greater service density and better mean time between failures than the 1:1 design and requires a smaller chassis/less space than a 1:1 design. One disadvantage of such a system, however, is that once a primary element fails over to the backup element, the system is no longer redundant (i.e., no available backup element for any primary element). Another disadvantage relates to hot state backup. Because one backup element must support multiple primary elements, the typical 1:N design provides no hot state on the backup element leading to long synchronization times and, for network devices, the likelihood that connections will be dropped and availability reduced.
Even where the backup element provides some level of hot state backup it generally lacks the processing power and memory to provide a full hot state backup (i.e., 1+N) for all primary elements. To enable some level of hot state backup for each primary element, the backup element is generally a “mega spare” equipped with a more powerful processor and additional memory. This requires customers to stock more hardware than in a design with identical backup and primary elements. For instance, users typically maintain extra hardware in the case of a failure. If a primary fails over to the backup, the failed primary may be replaced with a new primary. If the primary and backup elements are identical, then users need only stock that one type of board, that is, a failed backup is also replaced with the same hardware used to replace the failed primary. If they are different, then the user must stock each type of board, thereby increasing the user's cost.
Distributed Redundancy:
A distributed redundancy architecture spreads software backup (hot state) across multiple elements. Each element may provide software backup for one or more other elements. For software backup alone, therefore, the distributed redundancy architecture eliminates the need for hardware backup elements (i.e., spare hardware). Where hardware backup is also provided, spreading resource demands across multiple elements makes it possible to have significant (perhaps full) hot state backup without the need for a mega spare. Identical backup (spare) and primary hardware provides manufacturing advantages and customer inventory advantages. A distributed redundancy design is less expensive than many 1:1 designs and a distributed redundancy architecture also permits the location of the hardware backup element to float, that is, if a primary element fails over to the backup element, when the failed primary element is replaced, that new hardware may serve as the hardware backup.
Software Redundancy:
In its simplest form, a distributed redundancy system provides software redundancy (i.e., backup) with or without redundant (i.e., backup) hardware, for example, with or without using backup line card 16n as discussed earlier with reference to the logical to physical card table (
As one example, NMS 60 creates SLR 128a including the executable name atm_cntrl.exe and card LID 30 (line card 16a), SLR 128b including atm_cntrl.exe and LID 31 (line card 16b) and SLR 128c including atm_cntrl.exe and LID 32 (line card 16c). The configuration database detects LID 30, 31 and 32 in SLRs 128a, 128b and 128c, respectively, and sends slave SRMs 37b, 37c and 37d (line cards 16a, 16b, and 16c) notifications including the name of the executable file (e.g., atm_cntrl.exe) to be loaded. The slave SRMs then download and execute a copy of atm_cntrl.exe 135 from memory 40 to spawn ATM controllers 136a, 136b and 136c.
Through the active query feature, the ATM controllers are sent records from group table (GT) 108′ (
Each primary instantiation registers with its local name server 220b-220d, as described above, and each backup instantiation subscribes to its local name server 220b-220d for information about its corresponding primary instantiation. The name server passes each backup instantiation at least the process identification number assigned to its corresponding primary instantiation, and with this, the backup instantiation sends a message to the primary instantiation to set up a dynamic state check-pointing procedure. Periodically or asynchronously as state changes, the primary instantiation passes dynamic state information to the backup instantiation (i.e., check-pointing). In one embodiment, a Redundancy Manager Service available from Harris and Jefferies of Dedham, Mass. may be used to allow backup and primary instantiations to pass dynamic state information. If the primary instantiation fails, it can be re-started, retrieve its last known dynamic state from the backup instantiation and then initiate an audit procedure (as described above) to resynchronize with other processes. The retrieval and audit process will normally be completed very quickly, resulting in no discernable service disruption.
Although each line card in the example above is instructed by the group table to start four instantiations of ATM, this is by way of example only. The user could instruct the NMS to set up the group table to have each line card start one or more instantiations and to have each line card start a different number of instantiations.
Referring to
If, instead of restarting a particular application, the software fault experienced by line card 16a requires the entire element to be shut down and rebooted, then all of the processes executing on line card 16a will be terminated including backup processes ATM 468-471. When the primary processes are restarted, backup state information is retrieved from backup processes executing on line card 16b as explained above. Simultaneously, the restarted backup processes on line card 16a again initiate the check-pointing procedure with primary ATM processes 480-483 executing on line card 16c to again serve as backup processes for these primary processes. Referring to
Since the operating system assigns each process its own memory block, each primary process may be backed-up by a backup process running on the same line card. This would minimize the time required to retrieve backup state and resynchronize if a primary process fails and is restarted. In a computer system that includes a spare or backup line card (described below), the backup state is best saved on another line card such that in the event of a hardware fault, the backup state is not lost and can be copied from the other line card. If memory and processor limitations permit, backup processes may run simultaneously on the same line card as the primary process and on another line card such that software faults are recovered from using local backup state and hardware faults are recovered from using remote backup state.
Where limitations on processing power or memory make full hot state backup impossible or impractical, only certain hot state data will be stored as backup. The level of hot state backup is inversely proportional to the resynchronization time, that is, as the level of hot state backup increases, resynchronization time decreases. For a network device, backup state may include critical information that allows the primary process to quickly re-synchronize.
Critical information for a network device may include connection data relevant to established network connections (e.g., call set up information and virtual circuit information). For example, after primary ATM applications 464-467, executing on line card 16a, establish network connections, those applications send critical state information relevant to those connections to backup ATM applications 479-476 executing on line card 16b. Retrieving connection data allows the hardware (i.e., line card 16a) to send and receive network data over the previously established network connections preventing these connections from being terminated/dropped.
Although ATM applications were used in the examples above, this is by way of example only. Any application (e.g., IP or MPLS), process (e.g., MCD or NS) or device driver (e.g., port driver) may have a backup process started on another line card to store backup state through a check-pointing procedure.
Hardware and Software Backup:
By adding one or more hardware backup elements (e.g., line card 16n) to the computer system, the distributed redundancy architecture provides both hardware and software backup. Software backup may be spread across all of the line cards or only some of the line cards. For example, software backup may be spread only across the primary line cards, only on one or more backup line cards or on a combination of both primary and backup line cards.
Referring to
There are many levels at which a backup line card may be partially operational. For example, the backup line card's hardware may be configured and device driver processes 490 loaded and ready to execute. In addition, the active state of the device drivers 492, 494, and 496 on each of the primary line cards may be stored as backup device driver state (DDS) 498, 500, 502 on backup line card 16n such that after a primary line card fails, the backup device driver state corresponding to that primary element is used by device driver processes 490 to quickly synchronize the hardware on backup line card 16n. In addition, data reflecting the network connections established by each primary process may be stored within each of the backup processes or independently on backup line card 16n, for example, connection data (CD) 504, 506, 508. Having a copy of the connection data on the backup line card allows the hardware to quickly begin transmitting network data over previously established connections to avoid the loss of these connections and minimize service disruption. The more operational (i.e., hotter) backup line card 16n is the faster it will be able to transfer data over network connections previously established by the failed primary line card and resynchronize with the rest of the system.
In the case of a primary line card hardware fault, the backup or spare line card takes the place of the failed primary line card. The backup line card starts new primary processes that register with the name server on the backup line card and begin retrieving active state from backup processes associated with the original primary processes. As described above, the same may also be true for software faults. Referring to
As discussed above, preferably, backup line card 16n is partially operational. While active state is being retrieved from backup processes on line card 16b, device driver processes 490 use device driver state 502 and connection data 508 corresponding to failed primary line card 16a to quickly continue passing network data over previously established connections. Once the active state is retrieved then the ATM applications resynchronize and may begin establishing new connections and tearing down old connections.
Floating Backup Element:
Referring to
Instead of failing-over from line card 16n back to line card 16a or 16a′ and risking further service disruption, line card 16a or 16a′ may serve as the new backup line card with line card 16n serving as the primary line card. If line cards 16b, 16c or 16n experience a fault, a fail-over to line card 16a is initiated as discussed above and the primary line card that failed (or a replacement of that line card) serves as the new backup line card. This is referred to as a “floating” backup element. Referring to
Alternatively, computer system 10 may be physically configured to only allow a line card in a particular chassis slot, for example, line card 16n, to serve as the backup line card. This may be the case where physically, the slot line card 16n is inserted within is wired to provide the necessary connections to allow line card 16n to communicate with each of the other line cards but no other slot provides these connections. In addition, even where the computer system is capable of allowing line cards in other chassis slots to act as the backup line card, the person acting as network manager, may prefer to have the backup line card in each of his computer systems in the same slot. In either case, where only line card 16n serves as the backup line card, once line card 16a (or any other failed primary line card) is ready to act as a primary line card again, a fail-over, as described above, is initiated from line card 16n to the primary line card to allow line card 16n to again serve as a backup line card to each of the primary line cards.
Balancing Resources:
Typically, multiple processes or applications are executed on each primary line card. Referring to
For instance, primary line card 16a executes backup processes 510 and 512 corresponding to primary processes 474 and 475 executing on primary line card 16b. Primary line card 16b executes backup processes 514 and 516 corresponding to primary processes 482 and 483 executing on primary line card 16c, and primary line card 16c executes backup processes 518 and 520 corresponding to primary processes 466 and 467 executing on primary line card 16a. Backup line card 16n executes backup processes 520, 522, 524, 526, 528 and 530 corresponding to primary processes 464, 465, 472, 473, 480 and 481 executing on each of the primary line cards. Having each primary line card execute backup processes for only two primary processes executing on another primary line card reduces the primary line card resources required for backup. Since backup line card 16n is not executing primary processes, more resources are available for backup. Hence, backup line card 16n executes six backup processes corresponding to six primary processes executing on primary line cards. In addition, backup line card 16n is partially operational and is executing device driver processes 490 and storing device driver backup state 498, 500 and 502 corresponding to the device drivers on each of the primary elements and network connection data 504, 506 and 508 corresponding to the network connections established by each of the primary line cards.
Alternatively, each primary line card could execute more or less than two backup processes. Similarly, each primary line card could execute no backup processes and backup line card 16n could execute all backup processes. Many alternatives are possible and backup processes need not be spread evenly across all primary line cards or all primary line cards and the backup line card.
Referring to
Multiple Backup Elements:
In the examples given above, one backup line card is shown. Alternatively, multiple backup line cards may be provided in a computer system. In one embodiment, a computer system includes multiple different primary line cards. For example, some primary line cards may support the Asynchronous Transfer Mode (ATM) protocol while others support the Multi-Protocol Label Switching (MPLS) protocol, and one backup line card may be provided for the ATM primary line cards and another backup line card may be provided for the MPLS primary line cards. As another example, some primary line cards may support four ports while others support eight ports and one backup line card may be provided for the four port primaries and another backup line card may be provided for the eight port primaries. One or more backup line cards may be provided for each different type of primary line card.
Data Plane:
Referring to
In one embodiment, the forwarding cards have a 1:4 hardware redundancy structure and distributed software redundancy as described above. For example, forwarding card 546e is the hardware backup for primary forwarding cards 546a-546d and each of the forwarding cards provide software backup. The cross-connection cards are 1:1 redundant. For example, cross-connection card 562b provides both hardware and software backup for cross-connection card 562a. Each port on the universal port cards may be 1:1, 1+1, 1:N redundant or not redundant at all depending upon the quality of service paid for by the customer associated with that port. For example, port cards 554e-554h may be the hardware and software backup cards for port cards 554a-554d in which case the port cards are 1:1 or 1+1 redundant. As another example, one or more ports on port card 554a may be backed-up by separate ports on one or more port cards (e.g., port cards 554b and 554c) such that each port is 1:1 or 1+1 redundant, one or more ports on port card 554a may not be backed-up at all (i.e., not redundant) and two or more ports on 554a may be backed-up by one port on another port card (e.g., port card 554b) such that those ports are 1:N redundant. Many redundancy structures are possible using the LID to PID Card table (LPCT) 100 (
Each port card includes one or more ports for connecting to external network connections. One type of network connection is an optical fiber carrying an OC-48 SONET stream, and as described above, an OC-48 SONET stream may include connections to one or more end points using one or more paths. A SONET fiber carries a time division multiplexed (TDM) byte stream of aggregated time slots (TS). A time slot has a bandwidth of 51 Mbps and is the fundamental unit of bandwidth for SONET. An STS-1 path has one time slot within the byte stream dedicated to it, while an STS-3c path (i.e., three concatenated STS-1s) has three time slots within the byte stream dedicated to it. The same or different protocols may be carried over different paths within the same TDM byte stream. In other words, ATM over SONET may be carried on an STS-1 path within a TDM byte stream that also includes IP over SONET on another STS-1 path or on an STS-3c path.
Through network management system 60 on workstation 62, after a user connects an external network connection to a port, the user may enable that port and one or more paths within that port (described below). Data received on a port card path is passed to the cross-connection card in the same quadrant as the port card, and the cross-connection card passes the path data to one of the five forwarding cards or eight port cards also within the same quadrant. The forwarding card determines whether the payload (e.g., packets, frames or cells) it is receiving includes user payload data or network control information. The forwarding card itself processes certain network control information and sends certain other network control information to the central processor over the Fast Ethernet control bus. The forwarding card also generates network control payloads and receives network control payloads from the central processor. The forwarding card sends any user data payloads from the cross-connection card or control information from itself or the central processor as path data to the switch fabric card. The switch fabric card then passes the path data to one of the forwarding cards in any quadrant, including the forwarding card that just sent the data to the switch fabric card. That forwarding card then sends the path data to the cross-connection card within its quadrant, which passes the path data to one of the port cards within its quadrant.
Referring to
Each cross-connection card is a switch that provides connections between port cards and forwarding cards within its quadrant. Each cross-connection card is programmed to transfer each serial line on each port card within its quadrant to a forwarding card within its quadrant or to serial line on a port card, including the port card that transmitted the data to the cross-connection card. The programming of the cross-connect card is discussed in more detail below under Policy Based Provisioning.
Each forwarding card (e.g., forwarding card 546c) receives SONET frames over serial lines from the cross-connection card in its quadrant through a payload extractor chip (e.g., payload extractor 582a). In one embodiment, each forwarding card includes four payload extractor chips where each payload extractor chip represents a “slice” and each serial line input represents a forwarding card “port”. Each payload extractor chip receives four serial line inputs, and since each serial line includes twelve STS-1 time slots, the payload extractor chips combine and separate time slots where necessary to output data paths with the appropriate number of time slots. Each STS-1 time slot may represent a separate data path, or multiple STS-1 time slots may need to be combined to form a data path. For example, an STS-3c path requires the combination of three STS-1 time slots to form a data path while an STS-48c path requires the combination of all forty-eight STS-1 time slots. Each path represents a separate network connection, for example, an ATM cell stream.
The payload extractor chip also strips off all vestigial SONET frame information and transfers the data path to an ingress interface chip. The ingress interface chip will be specific to the protocol of the data within the path. As one example, the data may be formatted in accordance with the ATM protocol and the ingress interface chip is an ATM interface chip (e.g., ATM IF 584a). Other protocols can also be implemented including, for example, Internet Protocol (IP), Multi-Protocol Label Switching (MPLS) protocol or Frame Relay.
The ingress ATM IF chip performs many functions including determining connection information (e.g., virtual circuit or virtual path information) from the ATM header in the payload. The ATM IF chip uses the connection information as well as a forwarding table to perform an address translation from the external address to an internal address. The ATM IF chip passes ATM cells to an ingress bridge chip (e.g., BG 586a-586b) which serves as an interface to an ingress traffic management chip or chip set (e.g., TM 588a-588n).
The traffic management chips ensure that high priority traffic, for example, voice data, is passed to switch fabric card 570a faster than lower priority traffic, for example, e-mail data. The traffic management chips may buffer lower priority traffic while higher priority traffic is transmitted, and in times of traffic congestion, the traffic management chips will ensure that low priority traffic is dropped prior to any high priority traffic. The traffic management chips also perform an address translation to add the address of the traffic management chip to which the data is going to be sent by the switch fabric card. The address corresponds to internal virtual circuits set up between forwarding cards by the software and available to the traffic management chips in tables.
The traffic management chips send the modified ATM cells to switch fabric interface chips (SFIF) 589a-589n that then transfer the ATM cells to switch fabric card 570a. The switch fabric card uses the address provided by the ingress traffic management chips to pass ATM cells to the appropriate egress traffic management chips (e.g., TM 590a-590n) on the various forwarding cards. In one embodiment, the switch fabric card 570a is a 320 Gbps, non-blocking fabric. Since each forwarding card serves as both an ingress and egress, the switching fabric card provides a high degree of flexibility in directing the data between any of the forwarding cards, including the forwarding card that sent the data to the switch fabric card.
When a forwarding card (e.g., forwarding card 546c) receives ATM cells from switch fabric card 570a, the egress traffic management chips re-translate the address of each cell and pass the cells to egress bridge chips (e.g., BG 592a-592b). The bridge chips pass the cells to egress ATM interface chips (e.g., ATM IF 594a-594n), and the ATM interface chips add a re-translated address to the payload representing an ATM virtual circuit. The ATM interface chips then send the data to the payload extractor chips (e.g., payload extractor 582a-582n) that separate, where necessary, the path data into STS-1 time slots and combine twelve STS-1 time slots into four serial lines and send the serial lines back through the cross-connection card to the appropriate port card.
The port card SERDES chips receive the serial lines from the cross-connection card and de-serialize the data and send it to SONET framer chips 574a-574n. The Framers properly format the SONET overhead and send the data back through the transceivers that change the data from electrical to optical before sending it to the appropriate port and SONET fiber.
Although the port card ports above were described as connected to a SONET fiber carrying an OC-48 stream, other SONET fibers carrying other streams (e.g., OC-12) and other types of fibers and cables, for example, Ethernet, may be used instead. The transceivers are standard parts available from many companies, including Hewlett Packard Company and Sumitomo Corporation. The SONET framer may be a Spectra chip available from PMC-Sierra, Inc. in British Columbia. A Spectra 2488 has a maximum bandwidth of 2488 Mbps and may be coupled with a 1xOC48 transceiver coupled with a port connected to a SONET optical fiber carrying an OC-48 stream also having a maximum bandwidth of 2488 Mbps. Instead, four SONET optical fibers carrying OC-12 streams each having a maximum bandwidth of 622 Mbps may be connected to four 1xOC12 transceivers and coupled with one Spectra 2488. Alternatively, a Spectra 4x155 may be coupled with four OC-3 transceivers that are coupled with ports connected to four SONET fibers carrying OC-3 streams each having a maximum bandwidth of 155 Mbps. Many variables are possible.
The SERDES chip may be a Telecommunications Bus Serializer (TBS) chip from PMC-Sierra, and each cross-connection card may include a Time Switch Element (TSE) from PMC-Sierra, Inc. Similarly, the payload extractor chips may be MACH 48 chips and the ATM interface chips may be ATLAS chips both of which are available from PMC-Sierra. Several chips are available from Extreme Packet Devices (EPD), a subsidiary of PMC-Sierra, including PP3 bridge chips and Data Path Element (DPE) traffic management chips. The switch fabric interface chips may include a Switch Fabric Interface (SIF) chip also from EPD. Other switch fabric interface chips are available from Abrizio, also a subsidiary of PMC-Sierra, including a data slice chip and an enhanced port processor (EPP) chip. The switch fabric card may also include chips from Abrizio, including a cross-bar chip and a scheduler chip.
Although the port cards, cross-connection cards and forwarding cards have been shown as separate cards, this is by way of example only and they may be combined into one or more different cards.
Multiple Redundancy Schemes:
Coupling universal port cards to forwarding cards through a cross-connection card provides flexibility in data transmission by allowing data to be transmitted from any path on any port to any port on any forwarding card. In addition, decoupling the universal port cards and the forwarding cards enables redundancy schemes (e.g., 1:1, 1+1, 1:N, no redundancy) to be set up separately for the forwarding cards and universal port cards. The same redundancy scheme may be set up for both or they may be different. As described above, the LID to PID card and port tables are used to setup the various redundancy schemes for the line cards (forwarding or universal port cards) and ports. Network devices often implement industry standard redundancy schemes, such as those defined by the Automatic Protection Switching (APS) standard. In network device 540 (
Referring again to
Alternatively, the cross-connection cards in each quadrant may be coupled only with cross-connection cards in one other quadrant. For example, cross-connection cards in quadrants 1 and 2 may be connected and cross-connection cards in quadrants 3 and 4 may be connected. Similarly, the cross-connection cards in each quadrant may be coupled with cross-connection cards in only two other quadrants, or only the cross-connection cards in one quadrant (e.g., quadrant 1) may be connected to cross-connection cards in another quadrant (e.g., quadrant 2) while the cross-connection cards in the other quadrants (e.g., quadrants 3 and 4) are not connected to other cross-connection cards or are connected only to cross-connection cards in one quadrant (e.g., quadrant 2). Many variations are possible. Although these connections do not provide the flexibility of having all cross-connection cards inter-connected, these connections require less routing resources and still provide some increase in the data transmission flexibility of the network device.
The additional flexibility provided by inter-connecting one or more cross-connection cards may be used to optimize the efficiency of network device 540. For instance, a redundant forwarding card in one quadrant may be used as a backup for primary forwarding cards in other quadrants thereby reducing the number of backup modules and increasing the network device's service density. Similarly, a redundant universal port card or a redundant port on a universal port card in one quadrant may be used as a backup for primary universal port cards or ports in other quadrants. As previously mentioned, each primary forwarding card may support a different protocol (e.g., ATM, MPLS, IP, Frame Relay). Similarly, each universal port card may support a different protocol (e.g., SONET, Ethernet). A backup or spare forwarding card or universal port card must support the same protocol as the primary card or cards. If forwarding or universal port cards in one quadrant support multiple protocols and the cross-connection cards are not interconnected, then each quadrant may need multiple backup forwarding and universal port cards (i.e., one for each protocol supported). If each of the quadrants includes forwarding and universal port cards that support different protocols then each quadrant may include multiple backup forwarding and universal port cards further decreasing the network device's service density.
By inter-connecting the cross-connection cards, a forwarding card in one quadrant may serve as a backup for primary forwarding cards in its own quadrant and in other quadrants. Similarly, a universal port card or port in one quadrant may serve as a backup for a primary universal port card or port in its own quadrant and in other quadrants. For example, forwarding card 546e in quadrant 1 that supports a particular protocol (e.g., the ATM protocol) may serve as the backup forwarding card for primary forwarding cards supporting ATM in its own quadrant (e.g., forwarding cards 546a-546b) as well as for primary forwarding cards supporting ATM in quadrant 2 (e.g., forwarding cards 548b-548c) or all quadrants (e.g., forwarding card 550c in quadrant 3 and forwarding cards 552b-552d in quadrant 4). Similarly, forwarding card 548e in quadrant 2 that supports a different protocol (e.g., the MPLS protocol) may serve as the backup forwarding card for primary forwarding cards supporting MPLS in its own quadrant (e.g., forwarding cards 548a and 548d) as well as for primary forwarding cards supporting MPLS in quadrant 1 (e.g., forwarding card 546c) or all quadrants (e.g., forwarding card 550a in quadrant 3 and forwarding card 552a in quadrant 4). Even with this flexibility, to provide sufficient redundancy, multiple backup modules supporting the same protocol may be used, especially where a large number of primary modules support one protocol.
As previously discussed, each port on a universal port card may be connected to an external network connection, for example, an optical fiber transmitting data according to the SONET protocol. Each external network connection may provide multiple streams or paths and each stream or path may include data being transmitted according to a different protocol over SONET. For example, one path may include data being transmitted according to ATM over SONET while another path may include data being transmitted according to MPLS over SONET. The cross-connection cards may be programmed (as described below) to transmit protocol specific data (e.g., ATM, MPLS, IP, Frame Relay) from ports on universal port cards within their quadrants to forwarding cards within any quadrant that support the specific protocol. Because the traffic management chips on the forwarding cards provide protocol-independent addresses to be used by switch fabric cards 570a-570b, the switch fabric cards may transmit data between any of the forwarding cards regardless of the underlying protocol.
Alternatively, the network manager may dedicate each quadrant to a specific protocol by putting forwarding cards in each quadrant according to the protocol they support. Within each quadrant then, one forwarding card may be a backup card for each of the other forwarding cards (1:N, for network device 540, 1:4). Protocol specific data received from ports or paths on ports on universal port cards within any quadrant may then be forwarded by one or more cross-connection cards to forwarding cards within the protocol specific quadrant. For instance, quadrant 1 may include forwarding cards for processing data transmissions using the ATM protocol, quadrant 2 may include forwarding cards for processing data transmissions using the IP protocol, quadrant 3 may include forwarding cards for processing data transmissions using the MPLS protocol and quadrant 4 may be used for processing data transmissions using the Frame Relay protocol. ATM data received on a port path is then transmitted by one or more cross-connection cards to a forwarding card in quadrant 1, while MPLS data received on another path on that same port or on a path in another port is transmitted by one or more cross-connection cards to a forwarding card in quadrant 3.
Policy Based Provisioning:
Unlike the switch fabric card, the cross-connection card does not examine header information in a payload to determine where to send the data. Instead, the cross-connection card is programmed to transmit payloads, for example, SONET frames, between a particular serial line on a universal port card port and a particular serial line on a forwarding card port regardless of the information in the payload. As a result, one port card serial line and one forwarding card serial line will transmit data to each other through the cross-connection card until that programmed connection is changed.
In one embodiment, connections established through a path table and service endpoint table (SET) in a configuration database are passed to path managers on port cards and service endpoint managers (SEMs) on forwarding cards, respectively. The path managers and service endpoint managers then communicate with a cross-connect manager (CCM) on the cross-connection card in their quadrant to provide connection information. The CCM uses the connection information to generate a connection program table that is used by one or more components (e.g., a TSE chip 563) to program internal connection paths through the cross-connection card.
Typically, connections are fixed or are generated according to a predetermined map with a fixed set of rules. Unfortunately, a fixed set of rules may not provide flexibility for future network device changes or the different needs of different users/customers. Instead, within network device 540, each time a user wishes to enable/configure a path on a port on a universal port card, a Policy Provisioning Manager (PPM) 599 (
When a user connects an external network connection to a particular port on a universal port card, the user notifies the NMS as to which port on which universal port card should be enabled, which path or paths should be enabled, and the number of time slots in each path. The user may also notify the NMS as to a new path and its number of time slots on an already enabled port that was not fully utilized or the user may notify the NMS of a modification to one or more paths on already enabled ports and the number of time slots required for that path or paths. With this information, the NMS fills in a Path table 600 (
When a record in the path table is filled in, the configuration database sends an active query notification to a path manager (e.g., path manager 597) executing on a universal port card (e.g., port card 554a) corresponding to the universal port card port LID (e.g., port 1231,
Leaving some fields in the SET blank or assigning a particular value (e.g., zero), causes the configuration database to send an active query notification to Policy Provisioning Manager (PPM) 599. The PPM then determines—using provisioning policy 603—which forwarding card (FC) port or ports to assign to the new path or paths. For example, the PPM may first compare the new path's requirements, including its protocol (e.g., ATM over SONET), the number of time slots, the number of virtual circuits and virtual circuit scheduling restrictions, to the available forwarding card resources in the quadrant containing the universal port card port and path. The PPM also takes other factors into consideration including quality of service, for example, redundancy requirements or dedicated resource requirements, and balancing resource usage (i.e., load balancing) evenly within a quadrant.
As an example, a user connects SONET optical fiber 576a (
The NMS also partially fills in a record (e.g., row 604) in SET 76′ by filling in the quadrant number—in this example, 1—and the assigned path LID 1666 and by assigning a service endpoint number 878. The SET table also includes other fields, for example, a forwarding card LID field 606, a forwarding card slice 608 (i.e., port) and a forwarding card serial line 610. In one embodiment, the NMS fills in these fields with a particular value (e.g., zero), and in another embodiment, the NMS leaves these fields blank.
In either case, the particular value or a blank field causes the configuration database to send an active query notice to the PPM indicating a new path LID, quadrant number and service endpoint number. It is up to the PPM to decide which forwarding card, slice (i.e., payload extractor chip) and time slot (i.e., port) to assign to the new universal port card path. Once decided, the PPM fills in the SET Table fields. Since the user and NMS do not completely fill in the SET record, this may be referred to as a “self-completing configuration record.” Self-completing configuration records reduce the administrative workload of provisioning a network.
The SET and path table records may be automatically copied to persistent storage 21 to insure that if network device 540 is re-booted these configuration records are maintained. If the network device shuts down prior to the PPM filling in the SET record fields and having those fields saved in persistent storage, when the network device is rebooted, the SET will still include blank fields or fields with particular values which will cause the configuration database to again send an active query to the PPM.
When the forwarding card LID (e.g., 1667) corresponding, for example, to forwarding card 546c, is filled into the SET table, the configuration database sends an active query notification to an SEM (e.g., SEM 96i) executing on that forwarding card and corresponding to the assigned slice and/or time slots. The active query notifies the SEM of the newly assigned service endpoint number (e.g., SE 878) and the forwarding card slice (e.g., payload extractor 582a) and time slots (i.e., 3 time slots from one of the serial line inputs to payload extractor 582a) dedicated to the new path.
Path manager 597 and SEM 96i both send connection information to a cross-connection manager 605 executing on cross-connection card 562a—the cross-connection card within their quadrant. The CCM uses the connection information to generate a connection program table 601 and uses this table to program internal connections through one or more components (e.g., a TSE chip 563) on the cross-connection card. Once programmed, cross-connection card 562a transmits data between new path LID 1666 on SONET fiber 576a connected to port 571a on universal port card 554a and the serial line input to payload extractor 582a on forwarding card 546c.
An active query notification is also sent to NMS database 61, and the NMS then displays the new system configuration to the user.
Alternatively, the user may choose which forwarding card to assign to the new path and notify the NMS. The NMS would then fill in the forwarding card LID in the SET, and the PPM would only determine which time slots and slice within the forwarding card to assign.
In the description above, when the PPM is notified of a new path, it compares the requirements of the new path to the available/unused forwarding card resources. If the necessary resources are not available, the PPM may signal an error. Alternatively, the PPM could move existing forwarding card resources to make the necessary forwarding card resources available for the new path. For example, if no payload extractor chip is completely available in the entire quadrant, one path requiring only one time slot is assigned to payload extractor chip 582a and a new path requires forty-eight time slots, the one path assigned to payload extractor chip 582a may be moved to another payload extractor chip, for example, payload extractor chip 582b that has at least one time slot available and the new path may be assigned all of the time slots on payload extractor chip 582a. Moving the existing path is accomplished by having the PPM modify an existing SET record. The new path is configured as described above.
Moving existing paths may result in some service disruption. To avoid this, the provisioning policy may include certain guidelines to hypothesize about future growth. For example, the policy may require small paths—for example, three or less time slots—to be assigned to payload extractor chips that already have some paths assigned instead of to completely unassigned payload extractor chips to provide a higher likelihood that forwarding card resources will be available for large paths—for example, sixteen or more time slots—added in the future.
Multi-Layer Network Device in One Telco Rack:
Referring again to
In other embodiments, each port card includes one port capable of being connected to an OC-192 SONET fiber. Since OC-192 SONET fibers are capable of transferring data at 10 Gbps, a fully redundant network device 540 is again capable of transferring 160 Gbps. In the embodiment employing one OC-192 connection per port card, each port card may include one hundred and ninety-two logical DS3 connections using sub-rate data multiplexing (SDRM). In addition, each port card may differ in its number and type of ports to provide more or less data through put. As previously mentioned, ports other than SONET ports may be provided, for example, Ethernet ports, Plesiochronous Digital Hierarchy ports (i.e., DS0, DS1, DS3, E0, E1, E3, J0, J1, J3) and Synchronous Digital Hierarchy (SDH) ports (i.e., STM1, STM4, STM16, STM64).
The universal port cards and cross-connect cards in each quadrant are in effect a physical layer switch, and the forwarding cards and switch fabric cards are effectively an upper layer switch. Prior systems have packaged these two switches into separate network devices. One reason for this is the large number of signals that need to be routed. Taken separately, each cross-connect card 562a-562b, 564a-564b, 566a-566b and 568a-568b is essentially a switch fabric or mesh allowing switching between any path on any universal port card to any serial input line on any forwarding card in its quadrant and each switch fabric card 570a-570b allows switching between any paths on any forwarding cards. Approximately six thousand, seven hundred and twenty etches are required to support a 200 Gbps switch fabric, and about eight hundred and thirty-two etches are required to support an 80 Gbps cross-connect. Combining such high capacity multi-layer switches into one network device in a single telco rack (seven feet by nineteen inches by 24 inches) has not been thought possible by those skilled in the art of telecommunications network devices.
To fit network device 540 into a single telco rack, dual mid-planes are used. All of the functional printed circuit boards connect to at least one of the mid-planes, and the switch fabric cards and certain control cards connect to both mid-planes thereby providing connections between the two mid-planes. In addition, to efficiently utilize routing resources, instead of providing a single cross-connection card, the cross-connection functionality is separated into four cross-connection cards—one for each quadrant—(as shown in
Referring to
The chassis also supports switch fabric cards 570a and 570b. As shown, each switch fabric card may include multiple switch fabric (SF) cards and a switch scheduler (SS) card. In addition, the chassis supports multiple central processor cards (542 and 543,
The chassis also support two mid-plane printed circuit boards 622a and 622b (
Mid-plane 622a is also connected to external control processor cards 542b and 543b and management interface card 621. Mid-plane 622b is also connected to auxiliary processor cards 542c and 543c.
Switch fabric cards 570a and 570b are located in the back portion of chassis 620, approximately mid-way between the top and bottom of the chassis. The switch fabric cards are connected to both mid-planes 622a and 622b to allow the switch fabric cards to transfer signals between any of the forwarding cards in any quadrant. In addition, the cross-connection cards in quadrants 1 and 2 may be connected through the mid-planes and switch fabric cards to the cross-connection cards in quadrants 3 and 4 to enable network packets to be transferred between any universal port card and any forwarding card.
To provide for better routing efficiency through mid-plane 622b, forwarding cards 550a-550e and 552a-552e and cross-connection cards 566a-566b and 568a-568b in quadrants 3 and 4, located in the bottom portion of the chassis, are flipped over when plugged into mid-plane 622b. This permits the switch fabric interface 589a-589n on each of the lower forwarding cards to be oriented nearest the switch fabric cards and the cross-connection interface 582a-582n on each of the lower forwarding cards to be oriented nearest the cross-connection cards in quadrants 3 and 4. This orientation avoids having to cross switch fabric and cross-connection etches in mid-plane 622b.
Typically, airflow for cooling a network device is brought in at the bottom of the device and released at the top of the device. For example, in the back portion of chassis 620, a fan tray (FT) 626 pulls air into the device from the bottom portion of the device and a fan tray 628 blows air out of the top portion of the device. When the lower forwarding cards are flipped over, the airflow/cooling pattern is reversed. To accommodate this reversal, fan trays 630 and 632 pull air into the middle portion of the device and then fan trays 634 and 636 pull the air upwards and downwards, respectively, and blow the heated air out the top and bottom of the device, respectively.
The quadrant 3 and 4 universal port cards 558a-558h and 560a-560h may also be flipped over to orient the port card's cross-connection interface nearest the cross-connection cards and more efficiently use the routing resources. It is preferred, however, not to flip the universal port cards for serviceability reasons and airflow issues. The network managers at the telco site expect network attachments/cables to be in a certain pattern. Reversing this pattern could cause confusion in a large telco site with many different types of network devices. Also, flipping the port cards will change the airflow and cooling pattern and require a similar airflow pattern and fan tray configuration as implemented in the front of the chassis. However, with the switch fabric and internal control processor cards in the middle of the back portion of the chassis, it may be impossible to implement this fan tray configuration.
Referring to
Both mid-planes 622a and 622b include back mounted connectors 648a-648d for the switch fabric cards and back mounted connectors 650a-650d for the internal control cards. Mid-plane 622b further includes front, reverse mounted connectors 652a-652j for the quadrant 3 and 4 forwarding cards and back mounted connectors 654a-654p for the quadrant 3 and 4 universal port cards. In addition, mid-plane 622b also includes front, reverse mounted connectors 656a-656d for the quadrant 3 and 4 cross-connection cards and front mounted connectors 658a-658b for the auxiliary processor cards.
Combining both physical layer switch/router subsystems and upper layer switch/router subsystems in one network device allows for intelligent layer 1 switching. For example, the network device may be used to establish dynamic network connections on the layer 1 network to better utilize resources as service subscriptions change. In addition, network management is greatly simplified since the layer 1 and multiple upper layer networks may be managed by the same network management system and grooming fees are eliminated. Combining the physical layer switch/router and upper layer switch/routers into a network device that fits into one telco rack provides a less expensive network device and saves valuable telco site space.
Splitting the cross-connection function into four separate cards/quadrants enables the cross-connection routing requirements to be spread between the two mid-planes and alleviates the need to route cross-connection signals through the center of the device where the switch fabric is routed. In addition, segmenting the cross-connection function into multiple, independent subsystems allows customers/network managers to add functionality to network device 540 in pieces and in accordance with network service subscriptions. When a network device is first installed, a network manager may need only a few port cards and forwarding cards to service network customers. The modularity of network device 540 allows the network manager to purchase and install only one cross-connection card and the required number of port and forwarding cards. As the network becomes more subscribed, the network manager may add forwarding cards and port cards and eventually additional cross-connection cards. Since network devices are often very expensive, this modularity allows network managers to spread the cost of the system out in accordance with new service requests. The fees paid by customers to the network manager for the new services can then be applied to the cost of the new cards.
Although the embodiment describes the use of two mid-planes, it should be understood that more than two mid-planes may be used. Similarly, although the embodiment described flipped/reversed the forwarding cards and cross-connection cards in the lower half of the chassis, alternatively, the forwarding cards and cross-connection cards in the upper half of the chassis could be flipped.
Distributed Switch Fabric:
A network device having a distributed switch fabric locates a portion of the switch fabric functionality on cards separate from the remaining/central switch fabric functionality. For example, a portion of the switch fabric may be distributed on each forwarding card. There are a number of difficulties associated with distributing a portion of the switch fabric. For instance, distributing the switch fabric makes mid-plane/back-plane routing more difficult which further increases the difficulty of fitting the network device into one telco rack, switch fabric redundancy and timing are also made more difficult, valuable forwarding card space must be allocated for switch fabric components and the cost of each forwarding card is increased. However, since the entire switch fabric need not be included in a minimally configured network device, the cost of the minimal configuration is reduced allowing network service providers to more quickly recover the initial cost of the device. As new services are requested, additional functionality, including both forwarding cards (with additional switch fabric functionality) and universal port cards may be added to the network device to handle the new requests, and the fees for the new services may be applied to the cost of the additional functionality. Consequently, the cost of the network device more closely tracks the service fees received by network providers.
Referring again to
Referring also to
Due to the size and complexity of the switch fabric, each switch fabric card 570a-570b may include multiple separate cards. In one embodiment, each switch fabric card 570a-570b includes a control card 666 and four data cards 668a-668d. A scheduler chip 670 on control card 666 works with the EPP chips on each of the forwarding cards to transfer network data between the data slice chips on the forwarding cards through cross-bar chips 672a-6721 (only chips 672a-672f are shown) on data cards 668a-668d. Each of the data slice chips on each of the forwarding cards is connected to two of the cross-bar chips on the data cards. Switch fabric control card 666 and each of the switch fabric data cards 668a-668d also include a switch fabric local timing subsystem (LTS) 665, and a switch fabric central timing subsystem (CTS) 673 on control card 666 provides a start of segment (SOS) reference signal to each LTS 665 on each of the forwarding cards and switch fabric cards.
The traffic management chips perform upper level network traffic management within the network device while scheduler chip 670 on control card 666 performs the lower level data transfer between forwarding cards. The traffic management chips determine the priority of received network data and then forward the highest priority data to SIF chips 661. The traffic management chips include large buffers to store lower priority data until higher priority data has been transferred. The traffic management chips also store data in these buffers when the local EPP chip indicates that data transfers are to be stopped (i.e., back pressure). The scheduler chip works with the EPP chips to stop or hold-off data transfers when necessary, for example, when buffers on one forwarding card are close to fill, the local EPP chip sends notice to each of the other EPP chips and the scheduler to hold off sending more data. Back pressure may be applied to all forwarding cards when a new switch fabric control card is added to the network device, as described below.
The traffic management chips forward network data in predefined segments to the SIF chips. In the case of ATM data, each ATM cell is a segment. In the case of IP and MPLS, where the amount of network data in each packet may vary, the data is first arranged into appropriately sized segments before being sent to the SIF chips. This may be accomplished through segmentation and reassembly (SAR) chips (not shown).
When the SIF chip receives a segment of network data, it organizes the data into a segment consistent with that expected by the switch fabric components, including any required header information. The SIF chip may be a PMC9324-TC chip available from Extreme Packet Devices (EPD), a subsidiary of PMC-Sierra, and the data slice chips may be PM9313-HC chips and the EPP chip may be a PM9315-HC chip available from Abrizio, also a subsidiary of PMC-Sierra. In this case, the SIF chip organizes each segment of data—including header information—in accordance with a line-card-to-switch two (LCS-2) protocol. The SIF chip then divides each data segment into twelve slices and sends two slices to each data slice chip 662a-662f. Two slices are sent because each data slice chip includes the functionality of two data slices.
When the data slice chips receive the LCS segments, the data slice chips strip off the header information, including both a destination address and quality of service (QoS) information, and send the header information to the local EPP chip. Alternatively, the SIF chip may send the header information directly to the EPP chip and send only data to the data slice chips. However, the manufacturer teaches that the SIF chip should be on the forwarding card and the EPP and data slice chips should be on a separate switch fabric card within the network device or in a separate box connected to the network device. Minimizing connections between cards is important, and where the EPP and data slice chips are not on the same card as the SIF chips, the header information is sent with the data by the SIF chip to reduce the required inter-card connections, and the data slice chips then strip off this information and send it to the EPP chip.
The EPP chips on all of the forwarding cards communicate and synchronize through cross-bar chips 674a-674b on control card 666. For each time interval (e.g., every 40 nanoseconds, “ns”), the EPP chips inform the scheduler chip as to which data segment they would like to send and the data slice chips send a segment of data previously set up by the scheduler and EPP chips. The EPP chips and the scheduler use the destination addresses to determine if there are any conflicts, for example, to determine if two or more forwarding cards are trying to send data to the same forwarding card. If a conflict is found, then the quality of service information is used to determine which forwarding card is trying to send the higher priority data. The highest priority data will likely be sent first. However, the scheduler chips include an algorithm that takes into account both the quality of service and a need to keep the switch fabric data cards 668a-668d full (maximum data through put). Where a conflict exists, the scheduler chip may inform the EPP chip to send a different, for example, lower priority, data segment from the data slice chip buffers or to send an empty data segment during the time interval.
Scheduler chip 670 informs each of the EPP chips which data segment is to be sent and received in each time interval. The EPP chips then inform their local data slice chips as to which data segments are to be sent in each interval and which data segments will be received in each interval. As previously mentioned, the forwarding cards each send and receive data. The data slice chips include small buffers to hold certain data (e.g., lower priority) while other data (e.g., higher priority) data is sent and small buffers to store received data. The data slice chips also include header information with each segment of data sent to the switch fabric cards. The header information is used by cross-bar chips 672a-6721 (only cross-bar chips 672a-672f are shown) to switch the data to the correct forwarding card. The cross-bar chips may be PM9312-UC chips and the scheduler chip may be a PM9311-UC chip both of which are available from Abrizio.
Distributed Switch Fabric Timing:
As previously mentioned, a segment of data (e.g., an ATM cell) is transferred between the data slice chips through the cross-bar chips every predetermined time interval. In one embodiment, this time interval is 40 ns and is established by a 25 MHz start of segment (SOS) signal. A higher frequency clock (e.g., 200 MHz, having a 5 ns time interval) is used by the data slice and cross-bar chips to transfer the bits of data within each segment such that all the bits of data in a segment are transferred within one 40 ns interval. More specifically, in one embodiment, each switch fabric component multiplies the 200 MHz clock signal by four to provide an 800 MHz internal clock signal allowing data to be transferred through the data slice and cross-bar components at 320 Gbps. As a result, every 40 ns one segment of data (e.g., an ATM cell) is transferred. It is crucial that the EPP, scheduler, data slice and cross-bar chips transfer data according to the same/synchronized timing signals (e.g., clock and SOS), including both frequency and phase. Transferring data at different times, even slightly different times, may lead to data corruption, the wrong data being sent and/or a network device crash.
When distributed signals (e.g., reference SOS or clock signals) are used to synchronize actions across multiple components (e.g., the transmission of data through a switch fabric), any time-difference in events (e.g., clock pulse) on the distributed signals is generally termed “skew”. Skew between distributed signals may result in the actions not occurring at the same time, and in the case of transmission of data through a switch fabric, skew can cause data corruption and other errors. Many variables can introduce skew into these signals. For example, components used to distribute the clock signal introduce skew, and etches on the mid-plane(s) introduce skew in proportion to the differences in their length (e.g., about 180 picoseconds per inch of etch in FR 4 printed circuit board material).
To minimize skew, one manufacturer teaches that all switch fabric components (i.e., scheduler, EPP, data slice and cross-bar chips) should be located on centralized switch fabric cards. That manufacturer also suggests distributing a central clock reference signal (e.g., 200 MHz) and a separate SOS signal (e.g., 25 MHz) to the switch fabric components on the switch fabric cards. Such a timing distribution scheme is difficult but possible where all the components are on one switch fabric card or on a limited number of switch fabric cards that are located near each other within the network device or in a separate box connected to the network device. Locating the boards near each other within the network device or in a separate box allows etch lengths on the mid-plane for the reference timing signals to be more easily matched and, thus, introduce less skew.
When the switch fabric components are distributed, maintaining a very tight skew becomes difficult due to the long lengths of etches required to reach some of the distributed cards and the routing difficulties that arise in trying to match the lengths of all the etches across the mid-plane(s). Because the clock signal needs to be distributed not only to the five switch fabric cards but also the forwarding cards (e.g., twenty), it becomes a significant routing problem to distribute all clocks to all loads with a fixed etch length.
Since timing is so critical to network device operation, typical network devices include redundant central timing subsystems. Certainly, the additional reference timing signals from a redundant central timing subsystem to each of the forwarding cards and switch fabric cards create further routing difficulties. In addition, if the two central timing subsystems (i.e., sources) are not synchronous with matched distribution etches, then all of the loads (i.e., LTSs) must use the same reference clock source to avoid introducing clock skew—that is, unless both sources are synchronous and have matched distribution networks, the reference timing signals from both sources are likely to be skewed with respect to each other and, thus, all loads must use the same source/reference timing signal or be skewed with respect to each other.
A redundant, distributed switch fabric greatly increases the number of reference timing signals that must be routed over the mid-planes and yet remain accurately synchronized. In addition, since the timing signals must be sent to each card having a distributed switch fabric, the distance between the cards may vary greatly and, thus, make matching the lengths of timing signal etches on the mid-planes difficult. Further, the lengths of the etches for the reference timing signals from both the primary and redundant central timing subsystems must be matched. Compounding this with a fast clock signal and low skew component requirements makes distributing the timing very difficult.
The network device of the present invention, though difficult, includes two synchronized central timing subsystems (CTS) 673 (one is shown in
Both electro-magnetic radiation and electro-physical limitations prevent the 200 MHz reference clock signal from being widely distributed as required in a network device implementing distributed switch fabric subsystems. Such a fast reference clock increases the overall noise level generated by the network device and wide distribution may cause the network device to exceed Electro-Magnetic Interference (EMI) limitations. Clock errors are often measured as a percentage of the clock period, the smaller the clock period (5 ns for a 200 MHz clock), the larger the percentage of error a small skew can cause. For example, a skew of 3 ns represents a 60% error for a 5 ns clock period but only a 7.5% error for a 40 ns clock period. Higher frequency clock signals (e.g., 200 MHz) are susceptible to noise error and clock skew. The SOS signal has a larger clock period than the reference clock signal (40 ns versus 5 ns) and, thus, is less susceptible to noise error and reduces the percentage of error resulting from clock skew.
As previously mentioned, the network device may include redundant switch fabric cards 570a and 570b (
Still referring to
Each of the CTS reference SOS signals sent to the LTSs and the other CTS over mid-plane etches are the same length (i.e., matched) to avoid introducing skew. The CTS may be on its own independent card or any other card in the system. Even when it is located on a switch fabric card, such as the control card, that has an LTS, the reference SOS signal is routed through the mid-plane with the same length etch as the other reference SOS signals to avoid adding skew.
Central Timing Subsystem (CTS):
Referring to
VCXO 676 may be a VF596ES50 25 MHz LVPECL available from Conner-Winfield. Positive Emitter Coupled Logic (PECL) is preferred over Transistor-Transistor Logic (TTL) for its lower skew properties. In addition, though it requires two etches to transfer a single clock reference—significantly increasing routing resources—, differential PECL is preferred over PECL for its lower skew properties and high noise immunity. The clock drivers are also differential PECL and may be one to ten (1:10) MC100 LVEP111 clock drivers available from On Semiconductor. A test header 681 may be connected to clock driver 680 to allow a test clock to be input into the system.
Hardware control logic 684 determines (as described below) whether the CTS is the master or slave, and hardware control logic 684 is connected to a multiplexor (MUX) 686 to select between a predetermined voltage input (i.e., master voltage input) 688a and a slave VCXO voltage input 688b. When the CTS is the master, hardware control logic 684 selects predetermined voltage input 688a from discrete bias circuit 690 and slave VCXO voltage input 688b is ignored. The predetermined voltage input causes VCXO 676 to generate a constant 25 MHz SOS signal; that is, the VCXO operates as a simple oscillator.
Hardware control logic may be implemented in a field programmable gate array (FPGA) or a programmable logic device (PLD). MUX 686 may be a 74CBTLV3257 FET 2:1 MUX available from Texas Instruments.
When the CTS is the slave, hardware control logic 684 selects slave VCXO voltage signal 688b. This provides a variable voltage level to the VCXO that causes the output of the VCXO to track or follow the SOS reference signal from the master CTS. Referring still to
The reference output 700a and the feedback output 700b are then sent from the MUX to phase detector circuit 702. The phase detector compares the rising edge of the two input signals to determine the magnitude of any phase shift between the two. The phase detector then generates variable voltage pulses on outputs 704a and 704b representing the magnitude of the phase shift. The phase detector outputs are used by discrete logic circuit 706 to generate a voltage on a slave VCXO voltage signal 688b representing the magnitude of the phase shift. The voltage is used to speed up or slow down (i.e., change the phase of) the VCXO's output SOS signal to allow the output SOS signal to track any phase change in the reference SOS signal from the other CTS (i.e., SFC_SYNC). The discrete logic components implement filters that determine how quickly or slowly the VCXO's output will track the change in phase detected on the reference signal. The combination of the dual MUX, phase detector, discrete logic, VCXO, clock drivers and feedback signal forms a phase locked loop (PLL) circuit allowing the slave CTS to synchronize its reference SOS signal to the master CTS reference SOS signal. MUX 686 and discrete bias circuit 690 are not found in phase locked loop circuits.
The phase detector circuit may be implemented in a programmable logic device (PLD), for example a MACH4LV-32 available from Lattice/Vantis Semiconductor. Dual MUX 694 may be implemented in the same PLD. Preferably, however, dual MUX 694 is an SN74CBTLV3253 available from Texas Instruments, which has better skew properties than the PLD. The differential PECL to TTL translators may be MC100EPT23 dual differential PECL/TTL translators available from On Semiconductor.
Since quick, large phase shifts in the reference signal are likely to be the results of failures, the discrete logic implements a filter, and for any detected phase shift, only small incremental changes over time are made to the voltage provided on slave VCXO control signal 688b. As one example, if the reference signal from the master CTS dies, the slave VCXO control signal 688b only changes phase slowly over time meaning that the VCXO will continue to provide a reference SOS signal. If the reference signal from the master CTS is suddenly returned, the slave VCXO control signal 688b again only changes phase slowly over time to cause the VCXO signal to re-synchronize with the reference signal from the master CTS. This is a significant improvement over distributing a clock signal directly to components that use the signal because, in the case of direct clock distribution, if one clock signal dies (e.g., broken wire), then the components connected to that signal stop functioning causing the entire switch fabric to fail.
Slow phase changes on the reference SOS signals from both the master and slave CTSs are also important when LTSs switch over from using the master CTS reference signal to using the slave CTS reference signal. For example, if the reference SOS signal from the master CTS dies or other problems are detected (e.g., a clock driver dies), then the slave CTS switches over to become the master CTS and each of the LTSs begin using the slave CTS′ reference SOS signal. For these reasons, it is important that the slave CTS reference SOS signal be synchronized to the master reference signal but not quickly follow large phase shifts in the master reference signal.
It is not necessary for every LTS to use the reference SOS signals from the same CTS. In fact, some LTSs may use reference SOS signals from the master CTS while one or more are using the reference SOS signals from the slave CTS. In general, this is a transitional state prior to or during switch over. For example, one or more LTSs may start using the slave CTS's reference SOS signal prior to the slave CTS switching over to become the master CTS.
It is important for both the CTSs and the LTSs to monitor the activity of the reference SOS signals from both CTSs such that if there is a problem with one, the LTSs can begin using the other SOS signal immediately and/or the slave CTS can quickly become master. Reference output signal 700a—the translated reference SOS signal sent from the other CTS and received on SFC_SYNC—is sent to an activity detector circuit 708. The activity detector circuit determines whether the signal is active—that is, whether the signal is “stuck at” logic 1 or logic 0. If the signal is not active (i.e., stuck at logic 1 or 0), the activity detector sends a signal 683a to hardware control logic 684 indicating that the signal died. The hardware control logic may immediately select input 688a to MUX 686 to change the CTS from slave to master. The hardware control logic also sends an interrupt to a local processor 710 and software being executed by the processor detects the interrupt. Hardware control allows the CTS switch over to happen very quickly before a bad clock signal can disrupt the system.
Similarly, an activity detector 709 monitors the output of the first level clock driver 680 regardless of whether the CTS is master or slave. Instead, the output of one the second level clock drivers could be monitored, however, a failure of a different second level clock will not be detected. SFC_REF_ACTIVITY is sent from the first level clock driver to differential PECL to TTL translator 693 and then as FABRIC_REF_ACTIVITY to activity detector 709. If activity detector 709 determines that the signal is not active, which may indicate that the clock driver, oscillator or other component(s) within the CTS have failed, then it sends a signal 683b to the hardware control logic. The hardware control logic asserts KILL_CLKTREE to stop the clock drivers from sending any signals and notifies a processor chip 710 on the switch fabric control card through an interrupt. Software being executed by the processor chip detects the interrupt. The slave CTS activity detector 708 detects a dead signal from the master CTS either before or after the hardware control logic sends KILL_CLKTREE and asserts error signal 683a to cause the hardware control logic to change the input selection on MUX 686 from 688b to 688a to become the master CTS. As described below, the LTSs also detect a dead signal from the master CTS either before or after the hardware control logic sends KILL_CLKTREE and switch over to the reference SOS signal from the slave CTS either before or after the slave CTS switches over to become the master.
As previously mentioned, in the past, a separate, common clock selection signal or etch was sent to each card in the network device to indicate whether to use the master or slave clock reference signal. This approach required significant routing resources, was under software control and resulted in every load selecting the same source at any given time. Hence, if a clock signal problem was detected, components had to wait for the software to change the separate clock selection signal before beginning to use the standby clock signal and all components (i.e., loads) were always locked to the same source. This delay can cause data corruption errors, switch fabric failure and a network device crash.
Forcing a constant logic one or zero (i.e., “killing”) clock signals from a failed source and having hardware in each LTS and CTS detect inactive (i.e., “dead” or stuck at logic one or zero) signals allows the hardware to quickly begin using the standby clock without the need for software intervention. In addition, if only one clock driver (e.g., 682b) dies in the master CTS, LTSs receiving output signals from that clock driver may immediately begin using signals from the slave CTS clock driver while the other LTSs continue to use the master CTS. Interrupts to the processor from each of the LTSs connected to the failed master CTS clock driver allow software, specifically the SRM, to detect the failure and initiate a switch over of the slave CTS to the master CTS. The software may also override the hardware control and force the LTSs to use the slave or master reference SOS signal.
When the slave CTS switches over to become the master CTS, the remaining switch fabric control card functionality (e.g., scheduler and cross-bar components) continue operating. The SRM (described above) decides—based on a failure policy—whether to switch over from the primary switch fabric control card to the secondary switch fabric control card. There may be instances where the CTS on the secondary switch fabric control card operates as the master CTS for a period of time before the network device switches over from the primary to the secondary switch fabric control card, or instead, there may be instances where the CTS on the secondary switch fabric control card operates as the master CTS for a period of time and then the software directs the hardware control logic on both switch fabric control cards to switch back such that the CTS on the primary switch fabric control card is again master. Many variations are possible since the CTS is independent of the remaining functionality on the switch fabric control card.
Phase detector 702 also includes an out of lock detector that determines whether the magnitude of change between the reference signal and the feedback signal is larger than a predetermined threshold. When the CTS is the slave, this circuit detects errors that may not be detected by activity detector 708 such as where the reference SOS signal from the master CTS is failing but is not dead. If the magnitude of the phase change exceeds the predetermined threshold, then the phase detector asserts an OOL signal to the hardware control logic. The hardware control logic may immediately change the input to MUX 686 to cause the slave CTS to switch over to Master CTS and send an interrupt to the processor, or the hardware control logic may only send the interrupt and wait for software (e.g., the SRM) to determine whether the slave CTS should switch over to master.
Master/Slave CTS Control:
In order to determine which CTS is the master and which is the slave, hardware control logic 684 implements a state machine. Each hardware control logic 684 sends an IM_THE_MASTER signal to the other hardware control logic 684 which is received as a YOU_THE_MASTER signal. If the IM_THE_MASTER signal—and, hence, the received YOU_THE_MASTER signal—is asserted then the CTS sending the signal is the master (and selects input 688a to MUX 686,
Referring to
While in INIT/RESET state 0, if the SLOT_ID signals indicate that the control card is inserted in a non-preferred slot, (e.g., slot 0), then the state machine will enter STANDBY state 2 as the slave CTS and the hardware control logic will not assert IM_THE_MASTER and will select input 688b to MUX 686. While in INIT/RESET state 0, even if the SLOT_ID signals indicate that the control card is inserted in the preferred slot, if YOU_THE_MASTER is asserted, indicating that the other CTS is master, then the state machine transfers to STANDBY state 2. This situation may arise after a failure and recovery of the CTS in the preferred slot (e.g., reboot, reset or new control card).
While in the STANDBY state 2, if the YOU_THE_MASTER signal becomes zero (i.e., not asserted), indicating that the master CTS is no longer master, the state machine will transition to ONLINE state 3 and the hardware control logic will assert IM_THE_MASTER and select input 688a to MUX 686 to become master. While in ONLINE state 3, if the YOU_THE_MASTER signal is asserted and SLOT_ID indicating slot 0 the state machine enters STANDBY state 2 and the hardware control logic stops asserting IM_THE_MASTER and selects input 688b to MUX 686. This is the situation where the original master CTS is back up and running. The software may reset the state machine at any time or set the state machine to a particular state at any time.
Local Timing Subsystem:
Referring to
A phase detector 722 receives the feedback (FB) and reference (REF) signals from the dual MUX and, as explained above, generates an output in accordance with the magnitude of any phase shift detected between the two signals. Discrete logic circuit 724 is used to filter the output of the phase detector, in a manner similar to discrete logic 706 in the CTS, and provide a signal to VCXO 726 representing a smaller change in phase than that output from the phase detector. Within the LTSs, the VCXO is a 200 MHz oscillator as opposed to the 25 MHz oscillator used in the CTS. The output of the VCXO is the reference switch fabric clock. It is sent to clock driver 728, which fans the signal out to each of the local switch fabric components. For example, on the forwarding cards, the LTSs supply the 200 MHz reference clock signal to the EPP and data slice chips, and on the switch fabric data cards, the LTSs supply the 200 MHz reference clock signal to the cross-bar chips. On the switch fabric control card, the LTSs supply the 200 MHz clock signal to the scheduler and cross-bar components.
The 200 MHz reference clock signal from the VCXO is also sent to a divider circuit or component 730 that divides the clock by eight to produce a 25 MHz reference SOS signal 731. This signal is sent to clock driver 732, which fans the signal out to each of the same local switch fabric components that the 200 MHz reference clock signal was sent to. In addition, reference SOS signal 731 is provided as feedback signal SFC_FB to translator 714b. The combination of the dual MUX, phase detector, discrete logic, VCXO, clock drivers and feedback signal forms a phase locked loop circuit allowing the 200 MHz and 25 MHz signals generated by the LTS to be synchronized to either of the reference SOS signals sent from the CTSs.
The divider component may be a SY100EL34L divider by Synergy Semiconductor Corporation.
Reference signals 716a and 716b from translator 714a are also sent to activity detectors 734a and 734b, respectively. These activity detectors perform the same function as the activity detectors in the CTSs and assert error signals ref_a_los or ref_b_los to the LTS hardware control logic if reference signal 716a or 716b, respectively, die. On power-up, reset or reboot, a state machine (
While in REF_A state 2, if activity detector 734a detects a loss of reference signal 716a and asserts ref_a_los, the state machine will change to REF_B state 1 and change REF_SEL(1:0) and FB_SEL(1:0) to select inputs 716b and 719b. Similarly, while in REF_B state 1, if activity detector 734b detects a loss of signal 716b and asserts ref_b_los, the state machine will change to REF_A state 2 and change REF_SEL(1:0) and FB_SEL(1:0) to select inputs 716a and 719a. While in either REF_A state 2 or REF_B state 1, if both ref_a_los and ref_b_los are asserted, indicating that both reference SOS signals have died, the state machine changes back to INIT/RESET state 0 and change REF_SEL(1:0) and FB_SEL(1:0) to select no inputs or test inputs 736a and 736b or ground 738. For a period of time, the LTS will continue to supply a clock and SOS signal to the switch fabric components even though it is receiving no input reference signal.
When ref_a_los and/or ref_b_los are asserted, the LTS hardware control logic notifies its local processor 740 through an interrupt. The SRM will decide, based on a failure policy, what actions to take, including whether to switch over from the master to slave CTS. Just as the phase detector in the CTS sends an out of lock signal to the CTS hardware control logic, the phase detector 722 also sends an out of lock signal OOL to the LTS hardware control logic if the magnitude of the phase difference between the reference and feedback signals exceeds a predetermined threshold. If the LTS hardware receives an asserted OOL signal, it notifies its local processor (e.g., 740) through an interrupt. The SRM will decide based on a failure policy what actions to take.
Shared LTS Hardware:
In the embodiment described above, the switch fabric data cards are four independent cards. More data cards may also be used. Alternatively, all of the cross-bar components may be located on one card. As another alternative, half of the cross-bar components may be located on two separate cards and yet attached to the same network device faceplate and share certain components. A network device faceplate is something the network manager can unlatch and pull on to remove cards from the network device. Attaching two switch fabric data cards to the same faceplate effectively makes them one board since they are added to and removed from the network device together. Since they are effectively one board, they may share certain hardware as if all components were on one physical card. In one embodiment, they may share a processor, hardware control logic and activity detectors. This means that these components will be on one of the physical cards but not on the other and signals connected to the two cards allow activity detectors on the one card to monitor the reference and feedback signals on the other card and allow the hardware control logic on the one card to select the inputs for dual MUX 718 on the other card.
Scheduler:
Another difficulty with distributing a portion of the switch fabric functionality involves the scheduler component on the switch fabric control cards. In current systems, the entire switch fabric, including all EPP chips, are always present in a network device. Registers in the scheduler component are configured on power-up or re-boot to indicate how many EPP chips are present in the current network device, and in one embodiment, the scheduler component detects an error and switches over to the redundant switch fabric control card when one of those EPP chips is no longer active. When the EPP chips are distributed to different cards (e.g., forwarding cards) within the network device, an EPP chip may be removed from a running network device when the printed circuit board on which it is located is removed (“hot swap”, “hot removal”) from the network device. To prevent the scheduler chip from detecting the missing EPP chip as an error (e.g., a CRC error) and switching over to the redundant switch fabric control card, prior to the board being removed from the network device, software running on the switch fabric control card re-configures the scheduler chip to disable the scheduler chip's links to the EPP chip that is being removed.
To accomplish this, a latch 547 (
Similarly, when a forwarding card is added to the network device, circuit 742 detects the closing of the latch and sends an interrupt to the processor. The slave SRM running on the local processor sends a notice to the Master SRM which then sends a notice to the slave SRMs being executed by the processors on the switch fabric control cards, data cards and forwarding cards indicating the presence of the new forwarding card. The slave SRM on the cross-connection cards may be re-configured, and the slave SRM on the switch fabric control card may re-configure the scheduler chip to establish links with the new EPP chip to allow data to be transferred to the newly added forwarding card.
Switch Fabric Control Card Switch-Over:
Typically, the primary and secondary scheduler components receive the same inputs, maintain the same state and generate the same outputs. The EPP chips are connected to both scheduler chips but only respond to the master/primary scheduler chip. If the primary scheduler or control card experiences a failure a switch over is initiated to allow the secondary scheduler to become the primary. When the failed switch fabric control card is re-booted, re-initialized or replaced, it and its scheduler component serve as the secondary switch fabric control card and scheduler component.
In currently available systems, a complex sequence of steps is required to “refresh” or synchronize the state of the newly added scheduler component to the primary scheduler component and for many of these steps, network data transfer through the switch fabric is temporarily stopped (i.e., back pressure). Stopping network data transfer may affect the availability of the network device. When the switch fabric is centralized and all on one board or only a few boards or in its own box, the refresh steps are quickly completed by one or only a few processors limiting the amount of time that network data is not transferred. When the switch fabric includes distributed switch fabric subsystems, the processors that are local to each of the distributed switch fabric subsystems must take part in the series of steps. This may increase the amount of time that data transfer is stopped further affecting network device availability.
To limit the amount of time that data transfer is stopped in a network device including distributed switch fabric subsystems, the local processors each set up for a refresh while data is still being transferred. Communications between the processors take place over the Ethernet bus (e.g., 32,
During the time in which the data transfer is stopped, the buffers in the traffic management chips are used to store data coming from external network devices. It is important that the data transfer be complete quickly to avoid overrunning the traffic management chip buffers.
Since the switch over of the switch fabric control cards is very complex and requires that data transfer be stopped, even if briefly, it is important that the CTSs on each switch fabric control card be independent of the switch fabric functionality. This independence allows the master CTS to switch over to the slave CTS quickly and without interrupting the switch fabric functionality or data transmission.
As described above, locating the EPP chips and data slice chips of the switch fabric subsystem on the forwarding cards is difficult and against the teachings of a manufacturer of these components. However, locating these components on the forwarding cards allows the base network device—that is, the minimal configuration—to include only a necessary portion of the switching fabric reducing the cost of a minimally configured network device. As additional forwarding cards are added to the minimal configuration—to track an increase in customer demand—additional portions of the switch fabric are simultaneously added since a portion of the switch fabric is located on each forwarding card. Consequently, switch fabric growth tracks the growth in customer demands and fees. Also, typical network devices include 1:1 redundant switch fabric subsystems. However, as previously mentioned, the forwarding cards may be 1:N redundant and, thus, the distributed switch fabric on each forwarding card is also 1:N redundant further reducing the cost of a minimally configured network device.
External Network Data Transfer Timing:
In addition to internal switch fabric timing, a network device must also include external network data transfer timing to allow the network device to transfer network data synchronously with other network devices. Generally, multiple network devices in the same service provider site synchronize themselves to Building Integrated Timing Supply (BITS) lines provided by a network service provider. BITS lines are typically from highly accurate stratum two clock sources. In the United States, standard T1 BITS lines (2.048 MHz) are provided, and in Europe, standard E1 BITS lines (1.544 MHz) are provided. Typically, a network service provider provides two T1 lines or two E1 lines from different sources for redundancy. Alternatively, if there are no BITS lines or when network devices in different sites want to synchronously transfer data, one network device may extract a timing signal received on a port connected to the other network device and use that timing signal to synchronize its data transfers with the other network device.
Referring to
One of the EX CTSs behaves as a master and the other EX CTS behaves as a slave. The master EX CTS may synchronize its output external reference timing signals to one of BITS lines 751 or one of the port timing signals 753, while the slave EX CTS synchronizes its output external reference timing signals to the received master external reference timing signal 755. Upon a master EX CTS failure, the slave EX CTS may automatically switch over to become the master EX CTS or software may upon an error or at any time force the slave EX CTS to switch over to become the master EX CTS.
An external reference timing signal from each EX CTS is sent to each external local timing subsystem (EX LTS) 756 on cards throughout the network device, and each EX LTS generates local external timing signals synchronized to one of the received external reference timing signals. Generally, external reference timing signals are sent only to cards including external data transfer functionality, for example, cross connection cards 562a-562b, 564a-564b, 566a-566b and 568a-568b (
In network devices having multiple processor components, an additional central processor timing subsystem is needed to generate processor timing reference signals to allow the multiple processors to synchronize certain processes and functions. The addition of both external reference timing signals (primary and secondary) and processor timing reference signals (primary and secondary) require significant routing resources. In one embodiment of the invention, the EX CTSs embed a processor timing reference signal within each external timing reference signal to reduce the number of timing reference signals needed to be routed across the mid-plane(s). The external reference timing signals are then sent to EX LTSs on each card in the network device having a processor component, for example, cross connection cards 562a-562b, 564a-564b, 566a-566b, 568a-568b, universal port cards 554a-554h, 556a-556h, 558a-558h, 560a-560h, forwarding cards 546a-546e, 548a-548e, 550a-550e, 552a-552e, switch fabric cards 666, 667, 668a-668d, 669a-669d (
All of the EX LTSs extract out the embedded processor reference timing signal and send it to their local processor component. Only the cross-connection cards and port cards use the external reference timing signal to synchronize external network data transfers. As a result, the EX LTSs include extra circuitry not necessary to the function of cards not including external data transfer functionality, for example, forwarding cards, switch fabric cards and internal controller cards. The benefit of reducing the necessary routing resources, however, out weighs any disadvantage related to the excess circuitry. In addition, for the cards including external data transfer functionality, having one EX LTS that provides both local signals actually saves resources on those cards, and separate processor central timing subsystems are not necessary. Moreover, embedding the processor timing reference signal within the highly accurate, redundant external timing reference signal provides a highly accurate and redundant processor timing reference signal. Furthermore having a common EX LTS on each card allows access to the external timing signal for future modifications and having a common EX LTS, as opposed to different LTSs for each reference timing signal, results in less design time, less debug time, less risk, design re-use and simulation re-use.
Although the EX CTSs are described as being located on the external controllers 542b and 543b, similar to the switch fabric CTSs described above, the EX CTSs may be located on their own independent cards or on any other cards in the network device, for example, internal controllers 542a and 543a. In fact, one EX CTS could be located on an internal controller while the other is located on an external controller. Many variations are possible. In addition, just as the switch fabric CTSs may switch over from master to slave without affecting or requiring any other functionality on the local printed circuit board, the EX CTSs may also switch over from master to slave without affecting or requiring any other functionality on the local printed circuit board.
External Central Timing Subsystem (EX CTS):
Referring to
Port timing signals 753 are also sent to dual MUXs 762a and 762b. The network administrator also notifies the NMS as to which timing reference signals should be used, the BITS lines or the port timing signals. The NMS again notifies software running on the network device and through signals 761, the local processor configures the hardware control logic. The hardware control logic then uses select signals 764a and 764b to select the appropriate output signals from the dual MUXs.
Activity detectors 766a and 766b provide status signals 767a and 767b to the hardware control logic indicating whether the PRI_REF signal and the SEC_REF signal are active or inactive (i.e., stuck at 1 or 0). The PRI_REF and SEC_REF signals are sent to a stratum 3 or stratum 3E timing module 768. Timing module 768 includes an internal MUX for selecting between the PRI_REF and SEC_REF signals, and the timing module receives control and status signals 769 from the hardware control logic indicating whether PRI_REF or SEC_REF should be used. If one of the activity detectors 766a or 766b indicates an inactive status to the hardware control logic, then the hardware control logic sends appropriate information over control and status signals 769 to cause the timing module to select the active one of PRI_REF or SEC_REF.
The timing module also includes an internal phase locked loop (PLL) circuit and an internal stratum 3 or 3E oscillator. The timing module synchronizes its output signal 770 to the selected input signal (PRI_REF or SEC_REF). The timing module may be an MSTM-S3 available from Conner-Winfield or an ATIMe-s or ATIMe-3E available from TF systems. The hardware control logic, activity detectors and dual MUXs may be implemented in an FPGA. The timing module also includes a Free-run mode and a Hold-Over mode. When there is no input signal to synchronize to, the timing module enter a free-run mode and uses the internal oscillator to generate a clock output signal. If the signal being synchronized to is lost, then the timing module enters a hold-over mode and maintains the frequency of the last known clock output signal for a period of time.
The EX CTS 750 also receives an external timing reference signal from the other EX CTS on STRAT_SYNC 755 (one of STRAT_REF1-STRAT_REFN from the other EX CTS). STRAT_SYNC and output 770 from the timing module are sent to a MUX 772a. REF_SEL(1:0) selection signals are sent from the hardware control logic to MUX 772a to select STRAT_SYNC when the EX CTS is the slave and output 770 when the EX CTS is the master. When in a test mode, the hardware control logic may also select a test input from a test header 771a.
An activity detector 774a monitors the status of output 770 from the timing module and provides a status signal to the hardware control logic. Similarly, an activity detector 774b monitors the status of STRAT_SYNC and provides a status signal to the hardware control logic. When the EX CTS is master, if the hardware control logic receives an inactive status from activity detector 774a, then the hardware control logic automatically changes the REF_SEL signals to select STRAT_SYNC forcing the EX CTS to switch over and become the slave. When the EX CTS is slave, if the hardware control logic receives an inactive status from activity detector 774b, then the hardware control logic may automatically change the REF_SEL signals to select output 770 from the timing module forcing the EX CTS to switch over and become master.
A MUX 772b receives feedback signals from the EX CTS itself BENCH_FB is an external timing reference signal from the EX CTS that is routed back to the MUX on the local printed circuit board. STRAT_FB 754 is an external timing reference signal from the EX CTS (one of STRAT_REF1-STRAT_REFN) that is routed onto the mid-plane(s) and back onto the local printed circuit board such that is most closely resembles the external timing reference signals sent to the EX LTSs and the other EX CTS in order to minimize skew. The hardware control logic sends FB_SEL(1:0) signals to MUX 772b to select STRAT_FB in regular use or BENCH_FB or an input from a test header 771b in test mode.
The outputs of both MUX 772a and 772b are provided to a phase detector 776. The phase detector compares the rising edge of the two input signals to determine the magnitude of any phase shift between the two. The phase detector then generates variable voltage pulses on outputs 777a and 777b representing the magnitude of the phase shift. The phase detector outputs are used by discrete logic circuit 778 to generate a voltage on signal 779 representing the magnitude of the phase shift. The voltage is used to speed up or slow down (i.e., change the phase of) a VCXO 780 to allow the output signal 781 to track any phase change in the external timing reference signal received from the other EX CTS (i.e., STRAT_SYNC) or to allow the output signal 781 to track any phase change in the output signal 770 from the timing module. The discrete logic components implement a filter that determines how quickly or slowly the VCXO's output tracks the change in phase detected on the reference signal.
The phase detector circuit may be implemented in a programmable logic device (PLD).
The output 781 of the VCXO is sent to an External Reference Clock (ERC) circuit 782 which may also be implemented in a PLD. ERC_STRAT_SYNC is also sent to ERC 782 from the output of MUX 772a. When the EX CTS is the master, the ERC circuit generates the external timing reference signal 784 with an embedded processor timing reference signal, as described below, based on the output signal 781 and synchronous with ERC_STRAT_SYNC (corresponding to timing module output 770). When the EX CTS is the slave, the ERC generates the external timing reference signal 784 based on the output signal 781 and synchronous with ERC_STRAT_SYNC (corresponding to STRAT_SYNC 755 from the other EX CTS).
External reference signal 784 is then sent to a first level clock driver 785 and from there to second level clock drivers 786a-786d which provide external timing reference signals (STRAT_REF1-STRAT_REFN) that are distributed across the mid-plane(s) to EX LTSs on the other network device cards and the EX LTS on the same network device card, the other EX CTS and the EX CTS itself. The ERC circuit also generates BITS1_TXREF and BITS2_TXREF signals that are provided to BITS T1/E1 framer 758.
The hardware control logic also includes an activity detector 788 that receives STRAT_REF_ACTIVITY from clock driver 785. Activity detector 788 sends a status signal to the hardware control logic, and if the status indicates that STRAT_REF_ACTIVITY is inactive, then the hardware control logic asserts KILL_CLKTREE. Whenever KILL_CLKTREE is asserted, the activity detector 774b in the other EX CTS detects inactivity on STRAT_SYNC and may become the master by selecting the output of the timing module as the input to MUX 772a.
Similar to hardware control logic 684 (
In one embodiment, ports (e.g., 571a-571n,
In one embodiment, the embedded processor timing reference signal within the 19.44 MHz external timing reference signal is 8 KHz. Since the processor timing reference signal and the SONET framing pulse are both 8 KHz, the embedded processor timing reference signal may used to supply both. In addition, the embedded processor timing reference signal may also be used to supply BITS1_TXREF and BITS2_TXREF signals to BITS T1/E1 framer 758.
Referring to
External Reference Clock (ERC) circuit:
Referring to
The rollover counter increments on each 77.76 MHz clock tick and at 9720-1 (9720-1 times 77.76 MHz=8 KHz), the counter rolls over to zero. Load circuit 800 detects when the counter value is zero and loads a logic 1 into embedding registers 794a, 794b and 794c and a logic zero into embedding register 794d. As a result, the output of embedding register 794d is held high for three 77.76 MHz clock pulses (since logic ones are loaded into three embedding registers) which forces the duty cycle distortion into the 19.44 MHz output signal 784.
BITS circuits 802a and 802b also monitor the value of the rollover counter. While the value is less than or equal to 4860-1 (half of 8 KHz), the BITS circuits provide a logic one to 8 KHz output registers 798a and 798b, respectively. When the value changes to 4860, the BITS circuits toggle from a logic one to a logic zero and continue to send a logic zero to 8 KHz output registers 798a and 798b, respectively, until the rollover counter rolls over. As a result, 8 KHz output registers 798a and 798b provide 8 KHz signals with a 50% duty cycle on BITS1_TXREF and BITS2_TXREF to the BITS T1/E1 framer.
As long as a clock signal is received over signal 781 (77.76 MHz), rollover counter 796 continues to count causing BITS circuits 802a and 802b to continue toggling 8 KHz registers 798a and 798b and causing load circuit 800 to continue to load logic 1110 into the embedding registers every 8 KHz. As a result, the embedding registers will continue to provide a 19 MHz clock signal with an embedded 8 KHz signal on line 784. This is often referred to as “fly wheeling.”
Referring to
8 KHz output signal 808 is passed to extractor circuit 804 and used to reset the rollover counter to synchronize the rollover counter to the embedded 8 KHz signal within ERC_STRAT_SYNC when the EX CTS is the slave. As a result, the 8 KHz embedded signal generated by both EX CTSs are synchronized.
External Local Timing Subsystem (EX LTS):
Referring to
A second MUX 810b receives a feed back signal 816 from the EX LTS itself. Hardware control logic 812 uses FB_SEL(1:0) to select either a feedback signal input to MUX 810b or a test header 818b input to MUX 810b. The test header input is only used in a test mode. In regular use, feedback signal 816 is selected. Similarly, in a test mode, the hardware control logic may use REF_SEL(1:0) to select a test header 818a input to MUX 810a.
Output signals 820a and 820b from MUXs 810a and 810b, respectively, are provided to phase detector 822. The phase detector compares the rising edge of the two input signals to determine the magnitude of any phase shift between the two. The phase detector then generates variable voltage pulses on outputs 821a and 821b representing the magnitude of the phase shift. The phase detector outputs are used by discrete logic circuit 822 to generate a voltage on signal 823 representing the magnitude of the phase shift. The voltage is used to speed up or slow down (i.e., change the phase of) of an output 825 of a VCXO 824 to track any phase change in STRAT_REF_A or STRAT_REF_B. The discrete logic components implement filters that determine how quickly or slowly the VCXO's output will track the change in phase detected on the reference signal.
In one embodiment, the VCXO is a 155.51 MHz or a 622 MHz VCXO. This value is dependent upon the clock speeds required by components, outside the EX LTS but on the local card, that are responsible for transferring network data over the optical fibers in accordance with the SONET protocol. On at least the universal port card, the VCXO output 825 signal is sent to a clock driver 830 for providing local data transfer components with a 622 MHz or 155.52 MHz clock signal 831.
The VCXO output 825 is also sent to a divider chip 826 for dividing the signal down and outputting a 77.76 MHz output signal 827 to a clock driver chip 828. Clock driver chip 828 provides 77.76 MHz output signals 829a for use by components on the local printed circuit board and provides 77.76 MHz output signal 829b to ERC circuit 782. The ERC circuit also receives input signal 832 corresponding to the EX LTS selected input signal either STRAT_REF_B or STRAT_REF_A. As shown, the same ERC circuit that is used in the EX CTS may be used in the EX LTS to extract an 8 KHz J0FP pulse for use by data transfer components on the local printed circuit board. Alternatively, the ERC circuit could include only a portion of the logic in ERC circuit 782 on the EX CTS.
Similar to hardware control logic 712 (
External Reference Clock (ERC) circuit:
Referring again to
Again, as long as a clock signal is received over signal 829b (77.76 MHz), rollover counter 796 continues to count causing circuit 834 to continue pulsing 8 KHz register 798c.
External Central Timing Subsystem (EX CTS) Alternate Embodiment:
Referring to
It is still necessary to send one of the STRAT_REF1-STRAT_REFN signals to the other EX CTS (received as STRAT_SYNC 755) in order to provide ERC 782 with a 19.44 MHz signal with an embedded 8 KHz clock for use when the EX CTS is a slave. The ERC circuit only uses ERC_STRAT_SYNC in this instance when the EX CTS is the slave.
Layer One Test Port:
The present invention provides programmable physical layer (i.e., layer one) test ports within an upper layer network device (e.g., network device 540,
Referring to
Referring to
For many reasons, including error diagnosis, a service administrator may wish to monitor the data received on a particular path or paths at a particular port, for example, port 571a, and/or the data transmitted on a particular path or paths from port 571a. To accomplish this, the network administrator may connect test equipment, for example, an analyzer 840 (e.g., an Omniber analyzer available from Hewlett Packard Company), to the transmit connection of port 571b to monitor data received at port 571a and/or to the transmit connection of port 571c to monitor data transmitted from port 571a. The network administrator then notifies the NMS (e.g., NMS 60 running on PC 62,
Similar to the process of enabling a working port through path table 600 (
Through the test path table, the path manager learns that the transmitters of ports 571b and 571c need to be enabled and which path or paths are to be transferred to each port. As shown in path table 600 (
The path manager passes the path connection information to cross-connection manager 605 executing on the cross-connection card 562a. The CCM uses the connection information to generate a new connection program table 601 and uses this table to program internal connections through one or more components (e.g., a TSE chip 563) on the cross-connection card. After re-programming, cross-connection card 562a continues to transmit data corresponding to path LID 1666 between port 571a on universal port card 554a and the serial line input to payload extractor 582a on forwarding card 546c. However, after reprogramming, cross-connection card 562a also multicasts the data corresponding to path LID 1666 and received on port 571a to port 571b and data corresponding to path LID 1666 and transmitted to port 571a by forwarding card 546c to port 571c.
Analyzer 840 may then be used to monitor both the network data received on port 571a and the network data being transmitted from port 571a. Alternatively, analyzer 840 may only be connected to one test port to monitor either the data received on port 571a or the data transmitted from port 571a. The data received on port 571a may be altered by the components on the port card(s) and the cross-connection cards before the data reaches the test port but any modification is minimal. For example, where the external network attachment 576a is a SONET optical fiber, the port card components may convert the optical signals into electrical signals that are passed to the cross-connection card and then back to the test ports, which reconvert the electrical signals into optical signals before the signals are passed to analyzer 840. Since the data received at port 571a has not been processed or translated by the upper layer processing components on the forwarding card, the data accurately reflects the data received at the port. For example, the physical layer (e.g., SONET) information and format is accurately reflected in the data received.
To passively monitor both the data received and transmitted by a particular port, two transmitters are necessary and, thus, two ports are consumed for testing and cannot be used for normal data transfer. Because the test ports are programmable through the cross-connection card, however, the test ports may be re-programmed at any time to be used for normal data transfer. In addition, redundant ports may be used as test ports to avoid consuming ports needed for normal data transfer. Current network devices often have a dedicated test port that can provide both the data received and transmitted by a working port. The dedicated test port, however, contains specialized hardware that is different from the working ports and, thus, cannot be used as a working port. Hence, although two ports may be consumed for monitoring the input and output of one working port, they are only temporarily consumed and may be re-programmed at any time. Similarly, if the port card on which a test port is located fails, the test port(s) may be quickly and easily reprogrammed to another port on another port card that has not failed.
Instead of passively monitoring the data received at port 571a, test equipment 840 may be connected to the receiver of a test port and used to drive data to network device 540. For example, the network administrator may connect test equipment 840 to the receiver of test port 571c and then notify the NMS to enable the receiver on port 571c to receive path 1666. With this information, the NMS modifies test path table 841. For example, record 844 (
After re-programming, cross-connection card 562a data is sent from test equipment 840 to test port 571c and then through the cross-connection card to forwarding card 546c. The cross-connection card may multicast the data from forwarding card 546c to both working port 571a and to test port 571c, or just to test port 571c or just working port 571a.
Instead of having test equipment 840 drive data to the network device over a test port, internal components on a port card, cross-connection card or forwarding card within the network device may drive data to the other cards and to other network devices over external physical attachments connected to working ports and/or test ports. For example, the internal components may be capable of generating a pseudo-random bit sequence (PRBS). Test equipment 840 connected to one or more test ports may then be used to passively monitor the data sent from and/or received by the working port, and the internal components may be capable of detecting a PRBS over the working port and/or test port(s).
Although the test ports have been shown on the same port card as the working port being tested, it should be understood, that the test ports may be on any port card in the same quadrant as the working port. Where cross-connection cards are interconnected, the test ports may be on any port card in a different quadrant so long as the cross-connection card in the different quadrant is connected to the cross-connection card in same quadrant as the working port. Similarly, the test ports may be located on different port cards with respect to each other. A different working port may be tested by re-programming the cross-connection card to multicast data corresponding to the different working port to the test port(s). In addition, multiple working ports may be tested simultaneously by re-programming the cross-connection card to multicast data from different paths on different working ports to the same test port(s) or to multiple different test ports. A network administrator may choose to dedicate certain ports as test ports prior to any testing needing to be done or the network administrator may choose certain ports as test ports when problems arise.
The programmable physical layer test port or ports allow a network administrator to test data received at or transmitted from any working port or ports and also to drive data to any upper layer card (i.e., forwarding card) within the network device. Only the port card(s) and cross-connection card need be working properly to passively monitor data received at and sent from a working port. Testing and re-programming test ports may take place during normal operation without disrupting data transfer through the network device to allow for diagnosis without network device disruption.
NMS Server Scalability
As described above, a network device (e.g., 10,
If multiple NMS clients request access to multiple different network devices and the NMS server is required to retrieve and store data for all managed objects corresponding to each network device, then the NMS server's local memory will likely be quickly filled and repeated retrievals of data from each network device will likely be necessary. Retrieval of a large amount of data from each network device limits the scalability of the NMS server and reduces the NMS server's response time to NMS client requests.
To improve the scalability of the NMS server and improve data request response times, only physical managed objects are initially retrieved from a selected network device and logical managed objects are retrieved only when necessary. To further increase NMS server scalability and response time, proxies for managed objects (preferably physical managed objects and only a limited number of global logical managed objects) are stored in memory local to each NMS client. Moreover, to increase NMS server scalability and response time, unique identification numbers corresponding to each managed object are also stored in memory local to the NMS client (for example, in proxies or GUI tables) and used by the NMS server to quickly retrieve data requested by the NMS client. Each NMS client, therefore, maintains its user context of interest, eliminating the need for client-specific device context management by the NMS server.
Referring to
If the user selects one of the IP addresses (e.g., 192.168.9.202,
In one embodiment, data is stored within configuration database 42 as a series of containers. Since the configuration database is a relational database, data is stored in tables and containment is accomplished using pointers from lower level tables (children) to upper level tables (parents). As previously discussed with reference to
The MCD then fills in tables for each type of physical component, such tables being provided by a default configuration within the configuration database. Alternatively, the MCD could create and fill in each table. In one embodiment, the configuration database includes a managed device table 983 (
Referring to
Referring to
Even after initial power-up, master MCD 38 continues to take physical inventories of the network device to determine if physical components have been added or removed. For example, cards may be added to empty slots or removed from slots. When changes are detected, master MCD 38 updates the tables (e.g., card table 47′ and port table 49′) accordingly, and through the active query feature, the configuration database updates an external NMS database (e.g., 61,
In this embodiment, therefore, when the server sends database access commands to the configuration database within the network device to retrieve all data corresponding to physical components of the network device, the database access commands request data from each row in each of the physical tables (e.g., managed device table 983, chassis table 988, shelf table 989, slot table 990, card table 47′ and port table 49′). The data from these tables is then sent to the NMS server, and the server creates physical managed objects (PMO1-PMOn,
Referring to
In one embodiment, all physical managed objects include a “Get Parent” 991e function call to cause the NMS server to retrieve data corresponding to the parent physical component. A Get Parent function call to the managed device managed object receives a null message since the managed device does not have a parent component. The Get Parent function call may be used for constraint checking. For example, prior to configuring a particular card as a backup for another card, the Get Parent function call may be placed twice by the NMS server to ensure that both cards are within the same shelf—that is, the network device may have a constraint that redundant boards must be within the same shelf. The first Get Parent function call determines which slot each card is in and the second Get Parent function call determines which shelf each slot is in. If the shelves match, then the constraint is met.
In one embodiment, all physical managed objects include a “Get Children” 991f function call to cause the NMS server to retrieve data from the configuration database for children physical components related to the physical managed object. A Get Children function call to a port managed object receives a null message since the port does not have any physical children components. The data retrieved with the Get Children function call is used to fill in the tables in the physical tabs (e.g., system tab 934 (
In addition to Get Children and Get Parent function calls, each physical managed object includes a “Get Config” 991g and a “Set Config” 991h function call. The Get Config function call is used to retrieve data for dialog boxes when a user double clicks the left mouse button on an entry in one of the tabs in status window 897. The Set Config function call is used to implement changes to managed objects received from a user through a dialog box.
Instead of a “Get Children” function call, the port managed object includes a “Get SONET Path Table” function call to cause the server to retrieve all SONET paths (logical managed objects) configured for that particular port for display in SONET Paths tab 942 (
Each managed object 991 also includes a “Get Proxy” function call 991d, and after creating each managed object, the NMS server places a get proxy function call to the managed object. Placing the get proxy call causes the NMS server to create a proxy (PX) for the managed object and send the proxy (e.g., PX1-PXn) to memory 986 local to the NMS client that requested the network device access. Referring to
In addition, each proxy may include function calls 992c similar to one or more function calls in the corresponding managed object, with the exception of the “Get Proxy” function call. Unlike the managed object function calls, however, the proxy function calls cause the NMS client to send messages to the NMS server in, for example, JAVA RMI. For instance, the SONET Port proxy like the SONET Port managed object includes the “Get SONET Path Table”, “Create SONET Paths” and “Delete SONET Paths” function calls. However, proxy function calls cause the NMS client to send JAVA RMI messages to the NMS server to cause the server to place similar function calls to the managed object. The managed object function calls cause the server to generate database access commands to the configuration database in the network device.
Initially, the NMS client uses data from the received proxies (PX1-PXn,
If a user selects a different network device from navigation tree 898 (
In addition to reducing the time required to display physical information through GUI 895, limiting the initial data retrieval to only physical data reduces the amount of memory 987a local to the NMS server required to store the managed objects. Moreover, once the data from the proxies are added to the GUI tables, the GUI can respond to a user request for any of the device views within the mimic (as shown in
If the proxies include all of the attribute data from the managed objects, then once the proxies are transferred to the NMS client, it is not necessary for the NMS server to continue storing the corresponding physical managed objects. If, however, a proxy includes only some of the attribute data from its corresponding managed object, then continuing to store the managed object at the NMS server saves time if the user requests access to data not included in the proxy. For example, a proxy may only include data for attributes displayed in a tab in status window 897. If a user desires more data, the user may double click the left mouse button on an entry in the tab to cause a dialog box to be displayed including additional attribute data. This causes the NMS client to place a Get Config function call to the corresponding proxy which causes the NMS client to send JAVA RMI messages to the NMS server. If the managed object is still in local memory 987a, then the response time to the client is faster than if the server needs to access the configuration database again to retrieve the data.
Maintaining the managed objects for a particular network device in local memory 987a is also advantageous if another NMS client requests access to the same network device. As previously mentioned, when the NMS server receives a network device access request, it first checks local memory 987a. If the managed objects are already present, then the NMS server may respond more quickly than if the server again needs to retrieve the data from the network device.
Due to the advantages described above, in one embodiment, the NMS server does not automatically delete managed objects from its local memory after proxies are sent to the NMS client. However, because the NMS server's local memory is a limited resource, as clients request access to more and more different network devices, it may become necessary for the NMS server to overwrite managed objects within local memory 987a such that they are no longer available. As previously mentioned, sending proxies to the NMS clients allows the clients to display physical data through GUI 895 without accessing the NMS server. Thus, even when the NMS server is forced to overwrite corresponding managed objects in local memory 987a, the client is able to continue displaying physical data through GUI 895.
Importantly, through the unique PID and the function calls, the proxies also provide an improved mechanism for accessing logical data and physical data not included within the proxies. As mentioned above, if the user requests access to physical data not in the proxy, then the NMS client places a Get Config function call to the NMS server. The function call is made more efficient by including the unique PID stored in the proxy. The NMS server uses the PID to first search local memory 987a-perhaps the NMS server searches a hash table in cache. If the PID is found, then the NMS quickly sends the data from the corresponding managed object to the NMS client. If the PID is not found in local memory 987a, then the NMS server uses the PID as a primary key to retrieve the physical data from the configuration database within the network device and again builds the corresponding physical managed object. The NMS server then sends the data from the managed object to the NMS client.
Without the PID, the NMS server would be forced to walk through the hierarchical physical tables until the correct physical component was found. For example, if the NMS server needs data relevant to a particular port, the NMS server would begin by locating the managed device, the chassis, then the correct shelf within the chassis, then the correct slot within the chassis, then the module within the slot and then finally the correct port on the module. This will likely take several database accesses and will certainly take more time than directly accessing the port data using a primary key that provides absolute context.
The process is similar if the data requested is logical. For example, if a user selects a particular port (e.g., port 939a,
Similar to the physical data, logical data is stored in tables within configuration database 42 (
The database access commands corresponding to the Get SONET Path Table function call include the port PID (from the proxy/JAVA RMI messages) associated with the selected port. When the database access commands corresponding to the Get SONET Path Table function call are received by the configuration database, the configuration database locates each row in SONET Path Table 600′ (
For each row of data the NMS server formats the data according to the SONET Paths tab display and sends it to the NMS client. The NMS client adds the data to the GUI tables which causes the GUI tables to display the SONET paths (e.g., 942a and 942b,
As previously discussed, to retrieve additional attribute data or change attribute data for a managed object, the user may simply double click the left mouse button on an entry in a tab in configuration/status window 897 (
For example, if a user selects SONET path 942a (
The database access commands cause the configuration database to retrieve all the attribute data in the row in SONET Path Table 600′ (
If the user then selects a Cancel button 997a or OK button 997b, then the NMS client closes the dialog box. If the user selects Cancel button 997a, then the NMS client closes and deletes GUI dialog 998 and takes no further action. If the user selects OK button 997b, then it is assumed that the user made changes to one or more SONET path attributes and now wants those changes implemented. To implement any changes made to the SONET path attributes, when the NMS client detects the selection of the OK button, the NMS client places a “Set Config” function call to the corresponding port proxy. The function call causes the NMS client to send JAVA RMI messages to the NMS server including both the port PID from the proxy and the SONET path LID from the GUI table and the attributes for the SONET path. The NMS server first searches local memory 987a for the port PID. If a managed object including the port PID is found, then the NMS server issues a “Set Config” function call to the managed object including the SONET Path LID. If the port PID is not found, then the NMS server uses the port PID as a primary key into the configuration database to retrieve data from the row/record corresponding to the port. The NMS server then creates the port managed object, stores it in local memory and issues the “Set Config” function call. The function call causes the NMS server to generate database access commands and send them to the configuration database within the selected network device.
The database access commands cause the configuration database to locate the row in SONET Path Table 600′ (
Alternatively, proxies may be created for each logical managed object and sent to the NMS client. In a typical network device, however, there may be millions of logical managed objects making storage of all logical proxies in memory local to an NMS client difficult if not impossible. Moreover, since logical managed objects change frequently (as opposed to physical managed objects which do not change as frequently), the stored logical proxies would need to be updated frequently leading to an increased burden on both the NMS server and NMS client. Thus, in the preferred embodiment, only physical proxies are created and stored local to the NMS client.
Using the unique PIDs as primary keys allows for faster response times by the NMS server. First the PIDs are used to quickly check local memory 987a-perhaps hash tables in a cache. If the data is not in local memory, the PIDS are used as primary keys to perform a fast data retrieval from configuration database 42. If the PIDs were not used, the NMS server would need to navigate through the hierarchy of tables—possibly performing multiple database accesses—to locate the data of interest and, thus, response time would be much slower. As primary keys, the PIDs allow the NMS server to directly retrieve required data (i.e., table rows/records) without having to navigate through upper level tables.
Since logical data corresponds to configured objects, rows are added to the tables when logical objects are configured. In addition, the NMS server assigns a unique logical identification number (LID) for each configured object and inserts this within each corresponding row. The LID, like the PID, is used as a primary key within the configuration database for the row/data corresponding to each logical component. The NMS server and MCD use the same numbering space for LIDs, PIDs and other assigned numbers to ensure that the numbers are different (no collisions). In each row, the NMS server also inserts a unique PID or LID corresponding to a parent table (i.e., a foreign key for association) to provide data “containment”.
As described above with reference to
The database access commands cause the configuration database to add a row in SONET Path Table 600′ (
As previously discussed, each SONET path corresponds to a port (e.g., 571a,
For each service endpoint created, the database access commands also cause the configuration database to add a row in an interface table. For example, for each service endpoint corresponding to a SONET path configured for ATM service—that is, service field 942h (
Again, when tables in the configuration database are updated an active query feature is used to notify other processes including NMS database 61 (
Similarly, a user may select Virtual ATM Interfaces tab 947 (
The database access commands cause the configuration database to add a row in Virtual ATM Interfaces Table 993 (
Because there may be many upper layer network protocol interfaces in network device 540, the port managed object and port proxy may become very large as more and more function calls (e.g., Add Virtual ATM Interface, Add Virtual MPLS Interface, etc.) are added for each type of interface. To limit the size of the port managed object and port proxy, all interface function calls may be added to logical proxies corresponding to logical upper layer protocol nodes. For example, an ATM node table 999 (
Thus, after the user selects OK button 950e (
The database access commands cause the configuration database to add a row in Virtual ATM Interfaces Table 993 (
In the discussion below, virtual connections are added using the ATM node proxy. It should be understood, however, that a port proxy including the virtual connection function calls could be used instead.
As explained above, to add a virtual connection, the user may select a port (e.g., 941a,
The database access commands cause the configuration database to add a row in Virtual Connection Table 994 (
In addition to adding a row to Virtual Connection table 994, when a virtual connection is created one or more rows are also added to Virtual Link Table 995 (
Each row/record in Cross-Connection Table 60g, represents the relationship between the various endpoints and virtual connections. One row is created for each point-to-point connection while multiple rows are created for each point-to-multipoint connection. The NMS server assigns a unique cross-connection LID 996a (i.e., primary key) to each cross-connection and inserts each cross-connection LID within a row in the Cross-Connection Table. The NMS server also enters data in each row representing attributes (e.g., A1-An) for the corresponding cross-connection. The NMS server then enters two foreign keys for association: Virtual Link 1 LID 996b and Virtual Link 2 LID 996c. Within Virtual Link 1 LID 996b the NMS server inserts the source endpoint LID for the virtual connection. Within Virtual Link 2 LID 996c, the NMS server inserts a destination endpoint LID for the virtual connection. For each of these Virtual Link LIDs in Virtual Link Table 995, the NMS server also inserts Cross-Connection LID 995c (corresponding to Cross-Connection LID 996a in Cross-Connection Table 996). Since a point-to-point connection includes only one destination endpoint, only one row in the Cross-Connection table is needed to fully represent the connection. One or more rows are necessary, however, to represent a point-to-multipoint connection. In each of the other rows, Virtual Link 1 LID 996b representing the source endpoint remains the same but in each row a different Virtual Link 2 LID 996c is added representing the various destination endpoints.
Again, through the active query feature, the NMS database and NMS server are notified of the changes made to the Virtual Connection Table, Virtual Link Table and Cross-Connection Table in the configuration database. The NMS server creates configuration objects for each changed row and sends the configuration objects to the NMS client which updates the GUI tables to display the added virtual connection (e.g., 948a,
In addition to adding rows to tables when logical managed objects are configured, rows are also removed from tables when logical managed objects are deleted. For example, if a user selects a SONET path (e.g., 942a,
The database access commands cause the configuration database to directly delete the specific row within SONET Path Table 600′ (
Many different function calls may be generated by the NMS client and NMS server to carry out configuration changes requested by users.
As described above, memory local to each NMS client is utilized to store proxies corresponding to managed objects associated with physical components within a network device selected by a user. Proxies for logical managed objects corresponding to upper layer network protocol nodes (e.g., ATM node, IP node, MPLS node, Frame Relay node, etc.) may also be stored in memory local to each NMS client to limit the size of physical port proxies. The proxies reduce the load on the network/NMS server by allowing the NMS client to respond to user requests for physical network device data and views without having to access the NMS server. Storing data local to the NMS client improves the scalability of the NMS server by not requiring the NMS server to maintain the managed objects in memory local to the server. Thus, as multiple NMS clients request access to different network devices, the NMS server may, if necessary, overwrite managed objects within its local memory without disrupting the NMS client's ability to display physical network device information to the user and issue function calls to the NMS server. Response time to a user's request for access to a network device is also improved by initially only retrieving physical data as opposed to retrieving both physical and logical data.
In addition, unique identification numbers—both PIDs and LIDs—may also be stored in memory local to the NMS client (e.g., within proxies or GUI tables) to provide improved data request response times. Instead of navigating through the hierarchy of tables within the relational configuration database internal to the network device, the NMS server is able to use the unique identification numbers as primary keys to directly retrieve the specific data needed. Providing the unique identification numbers from the NMS client to the NMS server insures that even if the NMS server needed to overwrite managed objects within memory local to the NMS server, the NMS server will be able to quickly re-generate the managed objects and quickly retrieve the necessary data.
The unique identification numbers—both PIDs and LIDs—may be used in a variety of ways. For example, as previously mentioned, the device mimic 896a (
It will be understood that variations and modifications of the above described methods and apparatuses will be apparent to those of ordinary skill in the art and may be made without departing from the inventive concepts described herein. Accordingly, the embodiments described herein are to be viewed merely as illustrative, and not limiting, and the inventions are to be limited solely by the scope and spirit of the appended claims.
This application is a continuation-in-part of U.S. Ser. No. 09/687,191, filed Oct. 12, 2000, entitled “Utilizing Managed Object Proxies in Network Management Systems”, abandoned, which is a CIP of 09/663,947, filed Sep. 18, 2000, abandoned, which is a CIP of 09/656,123, filed Sep. 6, 2000, abandoned, which is a CIP of 09/653,700, filed Aug. 31, 2000, abandoned, which is a CIP of 09/637,800, filed Aug. 11, 2000 now U.S. Pat. No. 7,222,147, which is a CIP of 09/633,675, filed Aug. 7, 2000, U.S. Pat. No. 7,111,053 which is a CIP of 09/625,101, filed Jul. 24, 2000, abandoned, which is a CIP of 09/616,477, filed Jul. 14, 2000, U.S. Pat. No. 7,054,272 which is a CIP of 09/613,940, filed Jul. 11, 2000, U.S. Pat. No. 7,039,046 which is a CIP of 09/596,055, filed Jun. 16, 2000, U.S. Pat. No. 6,760,339* which is a CIP of 09/593,034, filed Jun. 13, 2000, abandoned, which is a CIP of 09/591,193, filed Jun. 9, 2000, U.S. Pat. No. 6,332,198, which is a CIP of 09/588,398, filed Jun. 6, 2000, abandoned, which is a CIP of 09/574,341, filed May 20, 2000, U.S. Pat. No. 7,062,642, and is a CIP of 09/574,343, filed May 20, 2000, U.S. Pat. No. 6,639,910, and said 09/593,034, filed Jun. 13, 2000 is a CIP of 09/574,440 May 20, 2000, U.S. Pat. No. 6,654,903.
Number | Name | Date | Kind |
---|---|---|---|
4750136 | Arpin et al. | Jun 1988 | A |
4942540 | Black et al. | Jul 1990 | A |
5515403 | Sloan et al. | May 1996 | A |
5638410 | Kuddes | Jun 1997 | A |
5726607 | Brede et al. | Mar 1998 | A |
5850399 | Ganmukhi et al. | Dec 1998 | A |
5903564 | Ganmukhi et al. | May 1999 | A |
5905730 | Yang et al. | May 1999 | A |
5926463 | Ahearn et al. | Jul 1999 | A |
5953314 | Ganmukhi et al. | Sep 1999 | A |
5958016 | Chang et al. | Sep 1999 | A |
5991163 | Marconi et al. | Nov 1999 | A |
5991297 | Palnati et al. | Nov 1999 | A |
5995511 | Zhou et al. | Nov 1999 | A |
6008805 | Land et al. | Dec 1999 | A |
6008995 | Pusateri et al. | Dec 1999 | A |
6015300 | Schmidt, Jr. et al. | Jan 2000 | A |
6021116 | Chiussi et al. | Feb 2000 | A |
6021263 | Kujoory et al. | Feb 2000 | A |
6033259 | Daoud | Mar 2000 | A |
6041307 | Ahuja et al. | Mar 2000 | A |
6044540 | Fontana | Apr 2000 | A |
6078595 | Jones et al. | Jun 2000 | A |
6233618 | Shannon | May 2001 | B1 |
6362836 | Shaw et al. | Mar 2002 | B1 |
6434619 | Lim et al. | Aug 2002 | B1 |
6470386 | Combar et al. | Oct 2002 | B1 |
6505245 | North et al. | Jan 2003 | B1 |
6631407 | Mukaiyama et al. | Oct 2003 | B1 |
6678827 | Rothermel et al. | Jan 2004 | B1 |
Number | Date | Country |
---|---|---|
9826611 | Jun 1998 | WO |
9905826 | Feb 1999 | WO |
9911095 | Mar 1999 | WO |
9914876 | Mar 1999 | WO |
9927688 | Jun 1999 | WO |
9930530 | Jun 1999 | WO |
9935577 | Jul 1999 | WO |
Number | Date | Country | |
---|---|---|---|
Parent | 09687191 | Oct 2000 | US |
Child | 09703856 | US | |
Parent | 09663947 | Sep 2000 | US |
Child | 09687191 | US | |
Parent | 09656123 | Sep 2000 | US |
Child | 09663947 | US | |
Parent | 09653700 | Aug 2000 | US |
Child | 09656123 | US | |
Parent | 09637800 | Aug 2000 | US |
Child | 09653700 | US | |
Parent | 09633675 | Aug 2000 | US |
Child | 09637800 | US | |
Parent | 09625101 | Jul 2000 | US |
Child | 09633675 | US | |
Parent | 09616477 | Jul 2000 | US |
Child | 09625101 | US | |
Parent | 09613940 | Jul 2000 | US |
Child | 09616477 | US | |
Parent | 09593034 | Jun 2000 | US |
Child | 09613940 | US | |
Parent | 09596055 | Jun 2000 | US |
Child | 09593034 | US | |
Parent | 09591193 | Jun 2000 | US |
Child | 09596055 | US | |
Parent | 09588398 | Jun 2000 | US |
Child | 09591193 | US | |
Parent | 09574341 | May 2000 | US |
Child | 09588398 | US | |
Parent | 09574343 | May 2000 | US |
Child | 09574341 | US | |
Parent | 09574440 | May 2000 | US |
Child | 09593034 | US |