The claimed invention relates to centrifugal fan design and control, and more particularly to a system, method, and computer program to a control system for a backward inclined centrifugal fan assembly to allow for a wider range of operation of the fan system by controlling the effective width of the fan wheel.
Backward inclined centrifugal fans are typically selected for maximum static efficiency when operating at design conditions. This results in the lowest power requirement, as the fan is operating near the stall region. However, if the fan system needs to operate a reduced flow rate, like those found in variable air volume distribution systems in office buildings, university buildings, etc., then, the fan is prone to stalling at a relatively high percentage of the design volume (cubic feet per minute (CFM)).
There are adverse effects to operating a backward inclined centrifugal fan system in the stall region such as excessive vibration in the fan and attached systems, and in extreme cases, mechanical failure of the fan assembly.
To overcome this limitation when selecting a fan system, it may be necessary to select a fan with a lower than desired peak static efficiency to allow for the required reduction in flow rate. This results in a higher peak power requirement for the fan system than would otherwise be possible. To select a fan with a lower peak static pressure, some possible methods are to select larger diameter fans at a slower speed, or to reduce the width of the fan wheel. Some issues with these approaches are that larger fans may not fit in the required space and are more expensive, and reducing the width of the fan wheel causes reduction in the peak efficiency of the fan.
An alternate method for reducing the air flow is to design a fan system consisting of multiple individual fan assemblies in parallel to allow for shutting down individual fans when low flow rates are required. This means using many smaller fans to allow for the large volume turndowns required of large fan systems. Smaller fans are generally less efficient than larger fans of the same design, so this again results in increased power consumption when running at design conditions. This method also limits the ability to provide a smooth delivery of air when the fans are cycled on and off.
An ideal solution to this problem is prevention of fan stall when operating at low volume deliveries and elevated static pressures, while maintaining a high efficiency system. The presently claimed invention allows for easy field tuning, positive shutoff, and monitoring of valve position during operation.
The presently claimed invention solves the ongoing problems addressed above by providing a system, method, and computer program for adjusting the width of the wheel of a centrifugal fan and a control system to determine when to adjust the width of the wheel. The device for adjusting the width of the fan wheel consists of a conical valve that is allowed to move within the fan wheel on a linear guide. The valve is moved by a linear operator under direction of a controls system. Historically a valve of this type has been used on a fixed speed fan to adjust the volume of air being delivered. However, in the presently claimed invention, this device is used on a variable speed fan when volume delivery is controlled by adjusting the speed of the fan and the valve is being used to tune the effective width of the wheel to allow for efficient operation and to prevent stalling of the fan over a wide range of operating conditions.
The control system consists of a microprocessor based controller that monitors the flow rate of each fan in a fan system, and the total static pressure at which the fan is operating. Based on the performance data for the fan the controller is able to determine if the fan is too close to stall and adjust the position of the valve.
The accompanying drawings, which are incorporated into and form a part of the specification, illustrate several embodiments of the presently claimed invention and, together with the description, explain the principles of the presently claimed invention. The drawings are only for illustrating a preferred embodiment of the presently claimed invention and are not to be construed as limiting the presently claimed invention. In the drawings:
The claimed invention comprises a device for adjusting the width of the wheel of a centrifugal fan and a control system to determine when to adjust the width of the wheel. The control system may or may not be a module within a larger control system.
A single fan assembly 10 is shown in
Control system or controller 32′ and alternative controller 32″ preferably comprises of a microprocessor based controller that monitors the flow rate of each fan in a fan system, and the total calculated static pressure of which the fan is operating. Controller 32′ can be disposed on the fan system or located remotely 32″. Controller 32″ can also be part of the fan speed controller. Monitoring the flow rate can accomplished by several methods. Preferably, a measurement of the pressure differential between a sensor 34 disposed on the narrowest part of the inlet cone 38 and another a measurement of second sensor upstream of the fan, with the measurement converted into a flow rate.
There are other ways to measure fan flow as well. Alternative methods for obtaining the flow rate are to mount a device at the inlet of the fan cone that provides a CFM measurement using two thermistors and air temp and power loss, calculating fan flow from fan revolutions per minute (RPM), fan power, and by using any number of methods for duct flow measuring that are well known in the art. Based on the performance data the fan controller 32 is able to determine if fan 26 is too close to stall, and automatically adjusts the position of valve 16.
Based on the current flow rate measurement the controller calculates the current static pressure the fan will stall at using formula 1:
SPs is the current stall pressure
SPb is the fans specified stall pressure
Qb is the volume flow at the specified pressure
Qc is the currently measured fan volume.
Graph 1 seen in
Reference is made to
Controller 32 uses current stall pressure 104, along with a predefined and adjustable open percentage offset 106 and intermediate percentage offset 108 from the current stall pressure 104, to determine in what position valve 16 should be. If the measured total static pressure is above the current stall pressure 104 minus the intermediate percentage 108, controller 32 will move valve 16 to the predefined and adjustable intermediate position. Once the measured total static pressure falls below the current stall pressure 104 minus the open percentage 106, controller 32 shall fully open valve 16. Although the above method describes three valve positions, this disclosure is not limited to this number but intended to include any number of valve positions.
The valve movement 36 can either be a closed loop system for precise control of the valve position, or in open loop to provide a lower cost system provided valve 16 remains in position when not commanded to move.
It is possible to operate the system in a continuous mode where controller 32 calculates the current stall pressure based on both the measured flow and the current valve position, and adjusts valve 16 continuously to maintain fan 26 at peak efficiency across a large range of operating conditions.
An additional, optional, function of the claimed invention is to stop reverse flow through fan 26 when it has failed, and to allow that fan to restart even if other fans in the array are running. When a fan failure is detected by control system 32, control system 32 fully closes the valve 16 on the failed fan. Control system 32 leaves the valve 16 closed until the fault is cleared. Once cleared, if there is a call for fan 26 to run, control system 32 starts the fan 26 and holds the valve 16 closed for a predetermined user defined time to allow fan 26 to pre-spin-up in the correct direction. After the predetermined time, the valve 16 is moved to the location determined by the flow and static pressure (Graph 1), as described above.
Typically, the claimed invention is installed on a fan system within HVAC air handlers (AHU) and are attached to a variable air volume (VAV) air delivery system to various zones within a building. In these systems as the zones call for heating or cooling the zone controls will open a damper. As this damper opens the pressure in the supply duct to all zones will drop. As the pressure drops, the fan within the AHU will increase in speed to match the request for additional airflow.
When there are only a few zones calling for cooling or heating the AHU needs to be able to supply a small volume of air at a sufficient pressure. Since there is a minimum pressure required at each zone, the total static pressure across the fans is not proportional to required flow, and the total static pressure across the fan system is higher than would be predicted by a square of the change in flow curve. This normally results in the fan system operating in the stall area. The invention allows adjusting the fan wheel width, which increases the pressure for a given flow at which the fan will stall (as shown in Graph 1 of
Below is an example of a system using the claimed system, method, and computer program to adjust the width of a conical fan wheel to optimize the operation of a fan.
Start/Stop
The unit shall have the following options to start/stop the unit.
Hardwires
BMS
Local Time Clock
Keypad (keypad stop command overrides the Hardwire, BMS and time clock commands)
Normal Start
The unit is called to run there will be a 30 (adj.) second delay time before the flow valves 16 are opened and then the supply fans 26 started.
Normal Stop
The supply fans 26 are stopped. Minimum on timers is respected. All flow valves 16 are driven to the fully closed position after a 30 (adj.) second delay after fans 26 are stopped.
Emergency Stop
The emergency stop input is intended for use by life safety systems to stop fans 26 rapidly. This shall bypass all minimum on timers and other safeties that would prevent supply fans 26 from being stopped. All flow valves 16 shall be driven to the fully closed position.
Supply Fan
The high static safety and door interlocks are wired to the VFD emergency input. If either of these faults is active, fans 26 will immediately shut down and controller 32 will indicate a VFD Fault.
Supply Fan (BMS)
Supply fan speed to be controlled by the BMS. The BMS control signal shall be overridden at the keypad to allow time for the unit to normalize temperatures. Supply fan 26 shall remain on for 30 seconds (adj.) after a unit stop command. If the unit is equipped with supply air isolation dampers, the dampers shall remain open until supply fan 26 stops.
Supply Fan (Supply Duct Static Pressure)
The duct static pressure input shall be used to control the supply fan speed. If the measured duct static pressure falls below 0.2″ w.c. (adj.) controller 32 shall switch the pressure input to the discharge plenum static pressure input. It shall continue to use the discharge plenum static pressure input until the measured supply duct static pressure rises above 0.75″ w.c. (adj.). Supply fan speed is controlled to maintain supply duct static pressure. A PI loop shall be used to control the speed of supply fan 26 to a supply duct static pressure set point of 1.5-inch w.c. (adj.). This PI loop shall be capable of override at the keypad to allow time for the unit to normalize temperatures. Supply fan 26 shall remain on for 30 seconds (adj.) after a unit stop command. If the unit is equipped with supply air isolation dampers the dampers must remain open until supply fan 26 stops.
Supply Fan (Supply CFM)
Supply fan speed is controlled to supply CFM as measured by airflow station. A PI loop shall be used to control the speed of supply fan 26 to a supply CFM set point (adj.). This PI loop shall be capable of override at the keypad to allow time for the unit to normalize temperatures. Supply fan 26 shall remain on for 30 seconds (adj.) after a unit stop command. If the unit is equipped with supply air isolation dampers the dampers shall remain open until the supply fan stops.
Supply Fan Flow (Flowtrac—One Device to Each Fan)
Each fan 26 in the array of fans shall have a Flowtrac fan flow sensor. The pressure reading from this device shall be converted to a flow via the following formula:
CFM=Fc*√ΔPressure
The Fc (flow coefficient) factor shall be adjustable. All fans shall use a common Fc factor. The CFM from each sensor shall be summed to present a total flow.
Supply Fan Flow Valve
Each fan is equipped with a flow valve 16. This valve 16 allows the effective width of the wheel to be adjusted. The controller shall monitor the CFM and TSP across fan 26, and adjust flow valve 16 on all the fans in the array to the same position and fan speed to prevent fans 16 from stalling at low flows. If a fan fails, the flow valve for that fan shall be driven closed to prevent recirculation of air.
Variables
FanLine: “ELPF”, “Optiline”, “Optiflow”
The ELPF, Optiline, and Optiflow numbers in this example are the designations for different fan sizes that applicant Energy Labs, Inc., makes in each fan line. This is used to look up the correct flow coefficient to use in the pressure to flow calculation. Instead of having an editable field for the flow coefficient it is far easier for the users to specify the type and size of fan.
ELPF: 135, 150, 165, 182, 200, 222, 245, 270, 300, 330, 365, 402, 445, 490, 542, 600
Optiline: 165, 182, 200, 222, 245, 270, 300, 330, 365
Optiflow: 165, 182, 200, 222, 245, 270, 300, 330, 365
StallPressure: Lookup based on fan selection
StallCFM: Lookup based on fan selection
StallSafetyIntermediate: 10%, Technician adjustable, 0-100%.
StallSafetyFull: 25%, Technician adjustable, 0-100%, must be greater than, or equal to StallSafetyIntermediate.
IntermediatePosition: 40%, Technician adjustable 0-100%
FlowControlDelay: 120 Seconds, Factory adjustable 0-600 seconds
CFMAverage: The flow from all active fans shall summed and divided by the quantity of active fans.
StallPressureIntermediate:
StallPressureIntermediate:
StallPressureFull:
Valve Control
The actuator has an open stroke time of 60 seconds (adj.). The actuator has a closed stroke time of 60 seconds (adj.). An opened and closed output moves the valve while the output is held on in the desired direction. The stroke time shall be used to determine how long to hold the opened or closed output on to get to the desired opening position. The actuator has internal end switches for the fully closed and fully opened positions, so a small amount of overdriving should be used to ensure that the valve is correctly positioned when driven to the fully open or fully closed positions.
Valve Position
When the fans are called to start, all valves shall be driven to the fully opened position and the fan start shall be delayed for zero (0) seconds (adj.). The valve shall be held in the fully open position for the first 120 seconds (adj.) of fan run time. If the measured total static pressure (TSP) rises above StallPressureIntermediate for the current average flow (CFMAverage), all flow valves on active fans shall be driven to the intermediate position. Once the measured TSP falls below StallPressureFull for the current average CFM (CFMAverage), all flow valves on active fans shall be driven to the fully opened position.
Failed Fan Valve Control and Fan Restart
If a fan fails, the flow valve to that fan shall be driven to the fully closed position and held closed until the fault is clears. When the fault clears, the valve shall be held closed for 30 seconds (adj.) to allow the fan to spin up prior to opening the flow valve. After the delay the flow valve shall be driven to the same position as all the other valves.
Dual Power Supplies
The unit is equipped with dual power supplies. The controller, all flow valve actuators, and some of the fans are connected to power supply #1 (PS1). The remaining fans are connected to power supply #2 (PS2). If the status input of a power supply indicates an issue with the power, the fans on that power supply shall be stopped. Once power is signaled good again for 120 seconds (adj.) the fans on that power supply shall be restarted.
Network Points
At a minimum the following points shall be available via network communications:
Start/Stop input from BMS
Supply duct static pressure setpoint input
CFM output for each fan
Status for each fan
1=Off, 2=ON—Intermediate, 3=On—Fully open, 4=Off—Alarm
Total Array CFM
VFD failure alarm for each VFD
Power Supply 1 Failure Alarm
Power Supply 2 Failure Alarm
High Duct Static Pressure Alarm
External Shutdown Alarm
Fan speed (0-100% speed)
While various embodiments of the disclosed method and apparatus have been described above, it is understood that they have been presented by way of example only, and should not limit the claimed invention. Likewise, the various diagrams may depict an example, architectural or other configuration, for the disclosed method and apparatus. This is done to aid in understanding the features and functionality that can be included in the disclosed method and apparatus. The claimed invention is not restricted to the illustrated example, architectures or configurations, rather the desired features can be implemented using a variety of alternative architectures and configurations. Indeed, it will be apparent to one of skill in the art how alternative functional, logical, or physical partitioning, and configurations can be implemented to realize the desired features of the disclosed method and apparatus. In addition, a multitude of different constituent module names other than those depicted herein can be applied to the various partitions. Additionally, regarding flow diagrams, operational descriptions, and method claims, the order in which the steps are presented herein shall not mandate that various embodiments be implemented to perform the recited functionality in the same order unless the context dictates otherwise.
Although the disclosed method and apparatus is described above in terms of various exemplary embodiments and implementations, it is understood that the various features, aspects, and functionality described in one or more of the individual embodiments are not limited in their applicability to the particular embodiment with which they are described. Thus, the breadth and scope of the claimed invention should not be limited by any of the above-described exemplary embodiments.
Terms and phrases used in this document, and variations thereof, unless otherwise expressly stated, should be construed as open ended, as opposed to limiting. As examples of the foregoing: the term “including” should be read as meaning “including, without limitation” or the like; the term “example” is used to provide exemplary instances of the item in discussion, not an exhaustive or limiting list thereof; the terms “a” or “an” should be read as meaning “at least one,” “one or more” or the like; and adjectives such as “conventional,” “traditional,” “normal,” “standard,” “known,” and terms of similar meaning should not be construed as limiting the item described to a given time period or to an item available as of a given time, but instead should be read to encompass conventional, traditional, normal, or standard technologies that may be available or known now or at any time in the future. Likewise, where this document refers to technologies that would be apparent or known to one of ordinary skill in the art, such technologies encompass those apparent or known to the skilled artisan now or at any time in the future.
A group of items linked with the conjunction “and” should not be read as requiring that each and every one of those items be present in the grouping, but rather should be read as “and/or” unless expressly stated otherwise. Similarly, a group of items linked with the conjunction “or” should not be read as requiring mutual exclusivity among that group, but rather should also be read as “and/or” unless expressly stated otherwise. Furthermore, although items, elements, or components of the disclosed method and apparatus may be described or claimed in the singular, the plural is contemplated to be within the scope thereof unless limitation to the singular is explicitly stated.
The presence of broadening words and phrases such as “one or more,” “at least,” “but not limited to” or other like phrases, in some instances shall not be read to mean that the narrower case is intended or required in instances where such broadening phrases may be absent. The use of the term “module” does not imply that the components or functionality described or claimed as part of the module are all configured in a common package. Indeed, any or all the various components of a module, whether control logic or other components, can be combined in a single package or separately maintained and can further be distributed in multiple groupings or packages or across multiple locations.
Additionally, the various embodiments set forth herein are described in terms of exemplary block diagrams, flow charts and other illustrations. As will become apparent to one of ordinary skill in the art after reading this document, the illustrated embodiments and their various alternatives can be implemented without confinement to the illustrated examples. For example, “block diagrams” and their accompanying description should not be construed as mandating a particular architecture or configuration.
In one or more exemplary embodiments, the functions described may be implemented in hardware, software, firmware, or any combination thereof. If implemented in software, the functions may be stored on or transmitted over as one or more instructions or code on a computer-readable medium. Computer-readable media includes both computer storage media and communication media including any medium that facilitates transfer of a computer program from one place to another. A storage media may be any available media that can be accessed by a computer. By way of example, and not limitation, such computer-readable media can comprise RAM, ROM, EEPROM, CD-ROM or other optical disk storage, magnetic disk storage or other magnetic storage devices, or any other medium that can be used to carry or store desired program code in the form of instructions or data structures, and that can be accessed by a computer. Also, any connection is properly termed a computer-readable medium. For example, if the software is transmitted from a website, server, or other remote source using a coaxial cable, fiber optic cable, twisted pair, digital subscriber line (DSL), or wireless technologies such as infrared, radio, and microwave, then the coaxial cable, fiber optic cable, twisted pair, DSL, or wireless technologies such as infrared, radio, and microwave are included in the definition of medium. Disk and disc, as used herein, includes compact disc (CD), laser disc, optical disc, digital versatile disc (DVD), floppy disk and BLU-RAY disc where disks usually reproduce data magnetically, while discs reproduce data optically with lasers. Combinations of the above should also be included within the scope of computer-readable media.
Although the embodiments of the claimed invention have been described in detail with particular reference to these preferred embodiments, other embodiments can achieve the same results. It is anticipated that the software that utilizes the method will continue to change the appearance of its user interface and evolve. Variations and modifications of the presently claimed invention will be obvious to those skilled in the art, and it is intended to cover in the appended claims all such modifications and equivalents. The entire disclosures of all references, applications, patents, and publications cited above, are hereby incorporated by reference.
This application claims the benefit of U.S. Provisional Patent Application No. 62/450,461, filed Jan. 25, 2017, entitled “Active Stall Prevention in Centrifugal Fans,” the specification of which is incorporated herein by reference.
Number | Date | Country | |
---|---|---|---|
62450461 | Jan 2017 | US |