This invention relates to grid power management.
It is a critical requirement to ensure the power system frequency stability in order to provide reliable and secure power supply to the customers. The system frequency deviation is resulted as a mismatch between the load demand and the power generation due to the loss of generators, tripping of transmission lines, fluctuation of load demands, variation of the renewable generations, etc. In recent years, with the increasing penetration of power electronics interfaced generators, intermittency of the renewable generations, and arising cyber-physical threats, it becomes more challenging to maintain the frequency stability. For example, if a large generator or a tie-line carrying gigawatts of power is suddenly tripped due to lighting, grounding fault, or cyberattack, there will be a huge power imbalance in the power grid, the frequency will drop rapidly and may cause great blackouts, like happened in the 2003 Northeast Blackout in the US and Canada.
In the past, many frequency control schemes have been developed at/under different time scales and scenarios. Conventional hierarchical control including primary, secondary, and tertiary loops was designed to deal with trivial/mild disturbances, but they often become ineffective in the case of great disturbances or contingencies. Under-frequency load shedding (UFLS) schemes belong to special protection systems, and can cut off the load of an entire area connected to a substation or a feeder when the frequency drops to a pre-defined value, but such UFLS schemes suffer from the problem of low granularity as they could not distinguish the critical loads from the trivial loads. Also, UFLS schemes are passive methods, and could not actively respond upon the occurrence of a major disturbance before the frequency drops severely.
Recently, some demand response strategies including direct load control were instant as alternative frequency regulation approaches. However, their control strategies were usually centralized and heavily rely on the communication network to transfer the commands when needed, which is a heavy burden of the communication network, and make them unable to rapidly response to major contingencies, e.g., the sudden tripping of an HVDC line or major generator that can cause severe system frequency drop within seconds. While there are some distributed frequency control methods in the literature [3], they are often not adaptive to the variation of power system states and lack adequate coordination between the devices.
Thus, in this invention, a practical hybrid strategy is instant, and the principle is online contingency estimation and centralized parameter setting for the cloud-based control center, and real-time measurement and decentralized decision making for the locally/remotely controlled outlet. The instant hybrid strategy is robust and adaptive, and its performance is validated by numerical simulations.
In one aspect, systems and methods are disclosed for power management by estimating power contingency of a grid at a cloud control center; performing decentralized real-time measurement and making local decisions at one more computer controlled outlets connected to the grid; and aggregating distributed loads to provide emergency frequency support to the grid.
In another aspect, an adaptive method for aggregation of distributed loads to provide emergency frequency support is described. This method consists of centralized online contingency estimation and parameter setting of the cloud control center, as well as the decentralized real-time measurement and local decision-making of the smart outlets. The instant method works with a smart outlet network consisting of a large number of smart outlets, the communication network and a cloud control center. In the cloud control center, the decision-making for frequency control involves two major steps: (1) calculate the amount of flexible loads that need to shed based on the power system state, total amount of flexible loads, importance of the flexible loads, as well as the possible contingencies; (2) analyze the switching-off conditions of the smart outlets and send these conditions to the smart outlets. The decision-making of the control center is usually conducted every few minutes. For the smart outlets, the control involves two major steps: (1) Continuously measure the frequency of the power system; (2) Switch off the appliances when the switching-off conditions are satisfied, or when the switching-off commands sent from the cloud control center is received. The decision-making of the control center is usually conducted in milliseconds/seconds after the disturbance.
Advantages of the system may include one or more of the following. The instant method is adaptive, robust, cost-effective, and fast-responsive. This method can adapt to different power system operation states, rapidly respond to frequency disturbances with fast local frequency tracking and control decision-making. Also, the cost of load shedding is reduced due to the wide-area smart outlet coordination and global optimization in the cloud control center. The system can respond quickly to the increasing load demand, intermittent renewable integration, and potential risks from cyber-physical threats, and can work with aggregated flexible load demands to perform frequency regulation service, especially emergency frequency support in case of a major generator/line loss. The system provides adaptive method for aggregation of distributed loads to provide emergency frequency support. This method combines the centralized online contingency estimation and parameter setting of the cloud control center, and the decentralized real-time measurement and local decision-making of the smart outlets. The system is fast, robust and cost-effective compared with the existing techniques like UFLS and centralized direct load control.
For simplicity, the following adaptive frequency control method for utilizing aggregated flexible load demand to provide emergency frequency support service is based on the smart outlet network illustrated in
Based on the smart outlet network, an adaptive method for aggregation of distributed loads to provide emergency frequency support is instant. It combines the centralized online contingency estimation and parameter setting at the cloud control center, with the decentralized real-time measurement and local decision-making of smart outlets. The detail is explained as follows.
Determination of Minimal Controllable Load Required
This section presents the calculation of the amount of load curtailment in case of a serious contingency, e.g., a sudden loss of the generator or increase of the load. Based on the frequency response model of the power system in
When a power mismatch between the generation and load demand suddenly happens, the system frequency will experience a dynamic change until a new equilibrium is reached. Using the Laplace transform, the frequency response to the power imbalance in the frequency domain can be calculated as
Based on (1), the frequency response in the time domain can be computed by inverse Laplace transform,
When there are multiple sudden power changes at different times, the frequency response is
where ΔP(tj) is the sudden power loss at time tj.
Given the initial power loss ΔP at time t0=0, the rate of frequency change (ROFC) g(t) can be calculated as
When the ROFC is zero, the minimum frequency fnadir is obtained. Thus, the time tnadir taken to reach fnadir can be computed as follows
Thus, fnadir can be obtained based on the following equation [5].
where fn is the pre-contingency frequency of the steady state, and it is typically 1 in per unit.
One principle of the instant method is to ensure the system frequency does not drop to the point of conventional under frequency load shedding (UFLS) while minimizing the amount of load shedding by the smart outlets. The starting frequency of the UFLS can be different for different systems. For safety, a frequency slightly higher than the starting frequency of the UFLS, denoted as fs, is chosen as the objective for the frequency control. Hence, the threshold power loss ΔPs which makes the frequency drop to fs as the nadir frequency can be calculated as
The cloud control center can receive the measurements from the widely distributed smart outlets and predict the possible contingencies. Assume the maximum amount of sudden power deficit that could be induced among all the contingencies is ΔPmax. The minimal controllable power ΔPv that needs to be shed to prevent the frequency from dropping below fs is calculated as
Switching-Off Conditions of Smart Outlets
An adaptive and robust control strategy for the smart outlets is instant. A typical relationship between the ROFC and the frequency can be represented as shown in
Thus, the control strategy of the smart outlets in response to the frequency drop is described as follows. If the real-time frequency measurement is fx, and at the same time the ROFC measurement is lower than gx, the switching-off condition is satisfied. For robustness, the smart outlet will switch off when the switching-off condition is satisfied for multiple times.
Further, the control strategy is elaborated considering more practical factors as follows. (1) The power system frequency may fluctuate in the normal operation. The smart outlets should not switch off within this normal range in order to avoid the mis-tripping caused by noises or measurement errors. (2) In the curve shown in
Overall Control Strategy
The overall control strategy consisting of the cloud control center and the smart outlets are explained as follows. The smart outlets measure the voltage, current, active power, reactive power, frequency, ROFC and switch status, etc. of the plugged-in appliances in real-time continuously. Also, the smart outlets periodically send the measurements to the cloud to keep the control center updated about the statuses of smart outlets. The control center aggregates the widely distributed smart outlets into hierarchical blocks considering the types of appliances and their locations. Based on the measurements sent from the smart outlets, the total power of each block, as well as the total power Ptotal of all the blocks, can be obtained. These blocks serve as the basis for the control and management of the smart outlets. The blocks are not fixed but can dynamically change, merge or divide as needed.
The cloud control center has communication with the control center of the power system and can even be regarded as part of the power system energy management system (EMS). Based on the information from the control center of the power system, the cloud control center can update its power system model and parameters, including the equations (1)-(14).
The major control strategy of the cloud control center is described in
Based on the parameter setting sent from the control center, the flow chart of the smart outlet control is shown in
Case Studies
In order to verify the performance of the instant control method for emergency frequency support, case studies are performed using a modified IEEE 24-bus system. The original system [6] has 32 generators, and in this modified system the three generators on bus 23 are removed and an interconnection line between bus 23 and an external system is added. Assume the rated power of the interconnection line is 1000 MVA, thus the tripping of the interconnection line is often most serious single contingency.
The parameters used in the power system frequency dynamics model are explained as follows. The inertia constant H and the constant of the governor speed-droop control R are 5.8 s and 1/17 for a generator whose rated power is less than 100 MW, respectively; 8.1 s and 1/20 for rated power between 100 MW and 200 MW, respectively; 9.3 s and 1/22 for rated power larger than 200 MW, respectively. D is 2.5, FH is 0.3, TR is 8 and Km is 0.95. Based on the above parameters, it is calculated that tnadir is 3.72 seconds. 49.1 Hz is chosen as the desired nadir frequency, the threshold power loss ΔPs is 633 MW which makes the frequency drop to the minimum frequency 49.1 Hz, as shown in
The sensitivity analysis for the relationship between the ROFC and the frequency drop is conducted for different power loss cases, as shown in
Thus, the specific switching-off conditions of the smart outlets can be obtained as in Table II.
The developed smart outlets in Section III reports a frequency and a related ROFC value every 16 ms, and based on them check if any of the switching-off conditions is satisfied. The smart outlet will turn off the switch when the switching-off conditions are satisfied for 3 times.
Based on Table II, the response of the smart outlets in case of a sudden power loss can be analyzed. A random frequency measurement error is added to each point of the frequency drop curve in
Case studies are conducted to verify the frequency regulation performance of the instant method when the available load is sufficient, as in
Also, sensitivity studies are carried out to check the influence of different amount of controllable power on the contingency. Assume a sudden power loss of 1000 MW, the system frequency dynamics in case of different amounts of controllable load is presented in
Number | Date | Country | |
---|---|---|---|
62681806 | Jun 2018 | US |