The present invention is directed to the field of air systems for heating, ventilating, and/or air-conditioning (HVAC) system, and, in particular, for dedicated outdoor air systems.
It is known that the air outside of buildings is generally healthier for human respiration than the air inside of buildings. But humans are most comfortable in somewhat neutral air conditions of temperature and humidity that are not found in the outside environment in which humans choose to live. It is possible to introduce or duct in outside air to the inside of a building or enclosure, with energy then needing to be expended to condition the air to the proper temperature and humidity. Based on the amount and type of human activity, more or less outside air is required to satisfy the ventilation need. To solve this problem, the HVAC market has responded with modifications of traditional equipment meant to recondition recirculated indoor air. These solutions are either packaged (self-contained) and large (both cabinet volume and footprint) for a particular quantity of air being conditioned and/or the amount of energy being removed from the air for cooling or added to the air for heating, and require exterior mounting, such as on a roof, or if they are smaller, containing components that are meant to use less interior building volume/space but split, needing separate remotely located components that require field layout and connections. Due to traditional manufacturing processes, these units are assembled in such a way that one of the major serviceable components, such as a compressor, requires skilled labor in a fire-hazard situation to be serviced. To improve the overall safety of this process, various codes have been developed to require certain protocols be followed. Compliance with these codes may require what is sometimes referred to as a “hot work permit.” For example, when working on a compressor in a municipal building, the permit might require the presence of two knowledgeable persons, with a fire extinguisher, including appropriate documentation as to the day and time of work. Another problem is that the outside conditions change with time and location. There is a benefit in having the HVAC equipment handling this ventilation air to be able to adapt in some way to changes in some combination of input conditions and customer requirements, and be able to measure, with some reasonable accuracy, the amount of air being brought into the equipment. At the same time, a combination of various efficiency codes has been developed to aid in standardizing and enforcing the commercial HVAC market's response to the outside air ventilation need. Similar to miles-per-gallon for automobiles, these metrics aim to make equipment produce a certain beneficial effect with minimal energy use. Lastly, having that same piece of equipment both heat the incoming air in winter and cool the incoming air in summer without auxiliary inputs, such as electric heaters, has been a problem for some time, as the outside air has a much larger swing in temperature than the air that stays in the building.
There is a need in the art for an air system that does not suffer from these deficiencies.
In an embodiment, an air system includes an enclosure. The air system further includes a compressor, a first energy exchange device, an expansion device, and a second energy exchange device each positioned in or along the enclosure and connected in a closed refrigerant loop. The air system further includes a first inlet formed in the enclosure for receiving air from a first source, the air received from the first source being psychrometrically controlled in the enclosure. The air system further includes a first outlet formed in the enclosure for removing the psychrometrically controlled air from the enclosure. The air system further includes a second inlet formed in the enclosure for receiving air from a second source, the air received from the second source being non-psychrometrically controlled in the enclosure. The air system further includes a second outlet formed in the enclosure for removing the non-psychrometrically controlled air from the enclosure. The air system further includes a third energy exchange device positioned in or along the enclosure for exchanging energy between the psychrometrically controlled air and the non-psychrometrically controlled air. The enclosure is adapted for insertion through an opening having opposed parallel sides having a dimension of 36 inches or less.
In another embodiment, an air system includes an enclosure. The air system further includes a compressor, a first energy exchange device, an expansion device, and a second energy exchange device each positioned in or along the enclosure and connected in a closed refrigerant loop. The air system further includes a first inlet formed in the enclosure for receiving air from a first source, the air received from the first source being psychrometrically controlled in the enclosure. The air system further includes a first outlet formed in the enclosure for removing the psychrometrically controlled air from the enclosure. The air system further includes a second inlet formed in the enclosure for receiving air from a second source, the air received from the second source being non-psychrometrically controlled in the enclosure. The air system further includes a second outlet formed in the enclosure for removing the non-psychrometrically controlled air from the enclosure. The air system further includes a third energy exchange device positioned in or along the enclosure for exchanging energy between the psychrometrically controlled air and the non-psychrometrically controlled air. The air system further includes the enclosure having a cross section having outside dimensions of less than 36 inches in two perpendicular directions.
In a further embodiment, a compressor includes a first fitting connected to a first pressure port of the compressor or to one end of a first tube connected to the first pressure port, and a second fitting connected to a second pressure port of the compressor or to one end of a second tube connected to the second pressure port. The compressor further includes the first fitting and the second fitting being threadedly engageable with a corresponding first fitting to form a first fitting pair, and a second fitting pair, respectively, the corresponding first fitting and corresponding second fitting being in fluid communication with a closed refrigerant loop, the first fittings of the first fitting pair and the second fittings of the second fitting pair each being adapted to be repeatably threadedly disconnected from one another. In response to each instance of the first fitting and the corresponding first fitting of the first fitting pair and the second fitting and the corresponding second fitting of the second fitting pair being threadedly disconnected from one another, each first fitting, corresponding first fitting, second fitting, and corresponding second fitting forming a fluid tight seal preventing refrigerant flow therethrough.
Other features and advantages of the present invention will be apparent from the following more detailed description, taken in conjunction with the accompanying drawings which illustrate, by way of example, the principles of the invention. Skilled artisans will appreciate that elements in the figures are illustrated for simplicity and clarity and have not necessarily been drawn to scale. For example, the dimensions of some of the elements in the figures may be exaggerated relative to other elements to help to improve understanding of various embodiments of the present application. Also, common but well-understood elements that are useful or necessary in a commercially feasible embodiment are typically not depicted in order to facilitate a less obstructed view of these various embodiments of the present application.
Wherever possible, the same reference numbers will be used throughout the drawings to represent the same parts.
The description of illustrative embodiments according to principles of the present invention is intended to be read in connection with the accompanying drawings, which are to be considered part of the entire written description. In the description of embodiments of the invention disclosed herein, any reference to direction or orientation is merely intended for convenience of description and is not intended in any way to limit the scope of the present invention. Relative terms such as “lower,” “upper,” “horizontal,” “vertical,” “above,” “below,” “up,” “down,” “top,” and “bottom” as well as derivative thereof (e.g., “horizontally,” “downwardly,” “upwardly,” etc.) should be construed to refer to the orientation as then described or as shown in the drawing under discussion. These relative terms are for convenience of description only and do not require that the apparatus be constructed or operated in a particular orientation unless explicitly indicated as such. Terms such as “attached,” “affixed,” “connected,” “coupled,” “interconnected,” and similar refer to a relationship wherein structures are secured or attached to one another either directly or indirectly through intervening structures, as well as both movable or rigid attachments or relationships, unless expressly described otherwise. Moreover, the features and benefits of the invention are illustrated by reference to the preferred embodiments. Accordingly, the invention expressly should not be limited to such preferred embodiments illustrating some possible non-limiting combination of features that may exist alone or in other combinations of features, the scope of the invention being defined by the claims appended hereto.
As shown in
This compact construction is especially beneficial for buildings with minimal roof space, such as high-rise buildings. This unit or air system 10 is also packaged. That is, an installer does not need to layout and field assemble different components, such as field refrigerant lines or tubes extending between sections, typically involving two electrical hook-ups, two condensation hook-ups, and/or two separate installations (e.g., removing ceiling tiles, etc.) for a conventional unit having separately located condenser and evaporator sections, sometimes referred to as a “split” unit. Another solution this air system 10 offers is that the major serviceable component, such as a compressor 20 is replaceable without needing a “hot work permit.” This is accomplished by a specific piping layout with valves that manages or controls the flow of refrigerant. The air flow measurement conundrum is solved via utilizing a physical phenomenon of the air through a certain device within the cabinet or enclosure that allows the air flow to be easily and accurately correlated with simple tools commonly carried by field technicians, or, alternatively, measured and controlled by building management systems. The efficiency problem is solved in part by the arrangement of devices within the unit or air system, the order of which the air must pass through, and refrigeration management using certain valves and thermodynamic processes utilized in vapor compression refrigeration systems. This also allows the unit or air system to heat and cool incoming outside air without the need for auxiliary heating devices over a wider range of natural conditions compared to other air systems presently in the market.
As shown in
For purposes herein, the term “psychrometrically controlled” means that parameters such as humidity and temperature are to be controlled for air 36, for purposes such as being introduced in a structure (not shown) for climate control within the structure. That is, the humidity and temperature of air 36 exiting enclosure 22 via the outlet 32 is controlled more tightly compared to the range of humidity and temperature of air 36 of air entering enclosure 22 from source 34.
For purposes herein, the term “non-psychrometrically controlled” means that parameters such as humidity and temperature are not to be controlled. That is, although air 44 is utilized to exchange energy or energy and moisture with air 36, it is not an object of the invention to control the humidity or the temperature of air 44 exiting enclosure 22 via outlet 40, but for air system 10 to efficiently exchange energy or energy and moisture between air 44 with air 36 so that air 36 exits enclosure 22 via outlet 32 at a desired humidity and temperature.
For purposes herein, the terms “psychrometrically controlled air 36” and “air 36” and the like may be used interchangeably.
For purposes herein, the terms “non-psychrometrically controlled air 44” and “air 44” and the like may be used interchangeably.
It is to be understood that components, including refrigerant lines or tubes deliverable as part of the assembled enclosure may be secured in or along enclosure 22, such as extending along the exterior of the enclosure, such as extending outside of the enclosure dimensions 24, 26, 28, so long as enclosure 22 may be inserted through opening 12 (
As further shown in
As further shown in
For purposes of illustration, if a desired flow rate is 350 CFM, a technician (not shown) utilizing curve 50 (
It is to be understood that while only one curve 50 is shown in
In one embodiment, the sensor output voltage is directly accessible via a display (not shown), not requiring a technician to carry a voltmeter to measure the sensor output voltage, also permitting independent flow rate (CFM) adjustability of each of psychrometrically controlled air 36 and non-psychrometrically controlled air 44 in enclosure 22. In one embodiment, a well known microprocessor control system 11 calculates and directly displays flow rate (CFM), also permitting independent flow rate (CFM) adjustability of each of psychrometrically controlled air 36 and non-psychrometrically controlled air 44 in enclosure 22.
Referring back to
As further shown in
In one embodiment, turbomachine 52 may be positioned anywhere along the flow path of psychrometrically controlled air 36 between inlet 30, energy exchange device 46, energy exchange device 60, energy exchange device 68, energy exchange device 80 and outlet 32, including being at least partially exterior of enclosure 22, such as extending exterior of enclosure 22 near inlet 30 or outlet 32, so long as such positioning does not require disassembly of turbomachine 52 from enclosure 22 in order to permit insertion of enclosure 22 through opening 12 (
Returning to
Returning to
In one embodiment, energy exchange device 60 may be a heat pipe.
In one embodiment, a single expansion device 104 may be utilized for use with both energy exchange devices 54, 68.
In one embodiment, air system 10 (
1. Ventilating (turbomachines 52 (
2. Ventilating (turbomachines 52 (
3. Ventilating (turbomachines 52 (
In one embodiment, air system 10 (
As further shown in
As further shown in
As further shown in
As further shown in
Returning to
In one embodiment, a second, independently operated air system may be used in combination with the air system of the present invention, if desired.
Referring now to
In one embodiment, port 84 may be directly threadedly connected to fitting 88. In one embodiment, port 130 may be directly threadedly connected to fitting 88.
The fittings 88, 94, such as Series 5505 fittings manufactured by Parker Hannifin headquartered in Cleveland, Ohio, of respective fitting pairs 96, 97 are adapted to be repeatably, e.g., at least twice, threadedly connected and disconnected to/from each other. When fittings 88, 94 are threadedly connected, the resulting fitting pairs 96, 97 form a fluid tight seal to prevent refrigerant flow therethrough, i.e., preventing leakage of refrigerant from between the fittings 88, 94. Additionally, when fittings 88, 94 are threadedly disconnected from one another, each disconnected side of fittings 88, 94 fitting forming a fluid tight seal preventing refrigerant flow therethrough. Stated another way, the disconnected fittings are self-sealing. In other words, during service, fitting pairs 96, 97 may be opened without loss of refrigerant, allowing compressor 20 to be removed without evacuating refrigerant and un-brazing refrigeration tubing. Compressor 20 may be pre-charged with refrigerant using service ports 128, which service ports 128, in one embodiment, may be re-sealed after charging the compressor.
As a result of fitting pairs 96, 97, compressor 20 can be replaced inside of a sealed refrigerant loop 70 without the requirement of an open flame or other high temp (>600° F.) heating process, such as solder or braze, in addition to not requiring refrigerant recovery and evacuation.
The compressor is arguably, the largest and most complex device to have a possibility of failure in a refrigeration system. A typical compressor replacement requires several (common to all refrigeration circuits) processes to occur by international, national, local and some safety policies. Currently, these processes minimally include the following steps currently if a compressor has failed.
First, the refrigerant from the refrigeration circuit must be recovered using specialty tools that must be approved by the Environmental Protection Agency (EPA), and EPA licensed technicians must also follow strict EPA rules while recovering the refrigerant. This process requires a minimum of a recovery cylinder, a refrigeration gauge set, a recovery machine, and the associated additional hoses or lines or tubes typically required to tie all of these components and the refrigeration circuit in need of repair together.
Second, the compressor must be removed from the circuit. Once the refrigerant is recovered and there is no additional refrigerant inside the system, the compressor can be removed. Some compressors may have what is commonly referred to as “roto-lock” fittings. A roto lock fitting may be mounted directly on a compressor and allows for removal of the compressor without a brazing torch. However, the components described as “roto-locks” are not self-sealing, and once the compressor is removed, the entire refrigeration system is subject to refrigerant leakage to the atmosphere.
If there are no “roto-locks” available on the compressor, the compressor must be removed via an open flame torch, at minimal using a gas such as methylacetylene-propadiene propane (MAPP) gas and usually with an oxyacetylene torch kit. In order to braze safely and to follow EPA and typically unit manufacturers suggestions, nitrogen must be blown through the system where brazing is occurring to remove oxygen from the brazing area preventing oxidation during the heating process. The act of “sweating”/brazing a compressor out of a unit requires at minimal a torch kit of various types, nitrogen bottle or other inert gas that prevents oxidation. Normally many local codes and building ownership safety guidelines exist, that also require the following, a fire extinguisher placed within 6 feet of the technician, as well as a second person known as the “fire watch”. The “fire watch” is dedicated additional personnel whose sole task is to oversee from a reasonable distance and at minimum in the same room and in sight as the technician performing the brazing, to look for any flames that may be catching flammable media of any type on fire. Depending on codes or most building safety guidelines, the “fire watch” must actually be holding a fire extinguisher. This provides improved response time and ability to divert a fire hazard if a fire is in its earliest stages.
Once the compressor is removed the same brazing and nitrogen procedure is used to install the new compressor.
Once the new compressor is installed the technician typically performs a leak test, which per EPA guidelines, requires a pressure of nitrogen or other inert gas to be pressurized to manufacturer specifications in the system for 20 minutes to 30 minutes and review if the pressure has dropped since time of pressurization.
The technician must use another EPA approved device referred to as a vacuum pump. The system must be evacuated for a recommended minimum of a half-hour and must achieve a vacuum of 500 microns or below vacuum. This is measured by a (generally observed as required) tool referred to as a micron gauge.
Once the unit has achieved and held the sufficient vacuum, the system can be recharged with refrigerant. The technician must use a refrigerant scale, and a bottle of the specified equipment's refrigerant to achieve the desired charge.
The pre-charged compressor of the present invention in the field only requires loosening or threadedly disconnecting fittings 88, 94 from fitting pairs 96, 97 in order to disconnect the failed compressor 20 from the system.
The new compressor 20 can then be placed in location tied into the system by threadedly connecting fittings 88, 94 to form fitting pairs 96, 97. No recovery machine, no nitrogen, no brazing, no pressure test, no evacuation, and no charging are required. There is virtually no refrigerant release.
A conventional compressor replacement process is commonly quoted at 6-8 labor hours. However, a replacement of the compressor of the present invention requires about 20 minutes, with none of the specialized equipment discussed above.
In one embodiment, any one or all of energy exchange devices 54, 68, 80, expansion device(s) 104, vessels 110, 118, filter 124 may be threadedly connected to refrigerant loop 70 by fittings 88, 94 of fitting pairs 96, 97.
While the invention has been described with reference to a preferred embodiment, it will be understood by those skilled in the art that various changes may be made and equivalents may be substituted for elements thereof without departing from the scope of the invention. In addition, many modifications may be made to adapt a particular situation or material to the teachings of the invention without departing from the essential scope thereof. Therefore, it is intended that the invention not be limited to the particular embodiment disclosed as the best mode contemplated for carrying out this invention, but that the invention will include all embodiments falling within the scope of the appended claims.
Number | Name | Date | Kind |
---|---|---|---|
5024263 | Laine | Jun 1991 | A |
7231967 | Haglid | Jun 2007 | B2 |
9395097 | McKie | Jul 2016 | B2 |
20100170655 | Kronvall | Jul 2010 | A1 |
20140262125 | Erb | Sep 2014 | A1 |
Number | Date | Country | |
---|---|---|---|
20190170379 A1 | Jun 2019 | US |
Number | Date | Country | |
---|---|---|---|
62594321 | Dec 2017 | US |