A. Field of Invention
The present invention relates to light sources which exhibit lumen depreciation over their operating lives and, in particular, to methods, apparatus, and systems for operating such light sources to compensate, at least partially, for such lumen depreciation. In general, the present invention provides a simple approach for providing constant, or near constant light output from a light source throughout its defined useful life.
B. Problems in the Art
Most high intensity discharge (HID) lamps exhibit what is called lamp lumen depreciation (LLD) characteristic. HID lamps include, but are not limited to, fluorescent, sodium (HPS), metal halide (MH), mercury vapor (HgV), and low pressure sodium (LPS). Each of these specifically mentioned types of HID lamps require a ballast transformer that regulates the operating and starting voltage at the lamp.
One definition of lumen depreciation or LLD is the gradual decline in a source's light output over operation time. Light output from the light source does not stay constant if operated at rated operating wattage. Due to several factors, primarily blackening of the inside of the arc tube from precipitation of chemicals and erosion of electrodes, HID light output usually drops as the lamp is operated. This characteristic is well known in the art. For example, a typical 1500 W MH lamp can lose up to around 50% of its light output over a typical 3000 hour cumulative operation life. See, for example, the graph of
Manufacturers give HID lamps a rated operating wattage (ROW). ROW is the recommended wattage to operate the lamp. Manufacturers do not recommend operation substantially over ROW, as they indicate a belief it could cause failure or, at least, reduce useful life of the lamp. They indicate operation at the ROW will provide the most efficient and long-lasting operation of the lamp.
Operation substantially under ROW is also not recommended because starting the lamp can be a problem. The arc may simply drop out without sufficient power. Also, operation too far below rated wattage can materially affect efficacy of the lamp. It can also reduce light output so much as to make use of the lamp impractical for its cost. Other possible detrimental effects on the lamp or its light output are believed possible.
For example, manufacturers' generally recommend a 1500 W MH lamp not be operated at more than 1750 W (about 15 to 20% above ROW) or less than 1000 W (about 30 to 35% below ROW).
Although LLD is different for each lamp (even lamps of the same type, ROW, and manufacturer), the characteristic is well known and is fairly predictable for the same type of lamps. LLD for a particular lamp can usually be found in the technical information available from manufacturers. Sometimes LLD is expressed in terms of a multiplier factor (lumen depreciation factor or LDF) that can be used in illumination calculations to predict reduction in the light output of a lamp over a period of time caused by lumen depreciation. The LDF is usually determined by dividing the maintained lamp lumens by the published initial lamp lumens, usually yielding a value of less than 1. The LDF therefore is used in the industry as an indication of how much light loss from LLD can be expected for a lamp over its operating life.
Other factors, in addition to lumen depreciation, can contribute to what is called total light loss factor for a light fixture. Some of these factors do not involve operation of the lamp itself, such as ballast factor, ambient fixture temperature, supply voltage variation, optical factor, and surface fixture depreciation. But LLD is a significant contributor to total light loss factor.
A particular example of the LLD problem can be given in the context of sports lighting. MH lamps are commonly used, which have ROWs on the order of at least 700 or 800 watts, and more frequently 1,000 watts, 1,500 watts, or higher. Lamp ROW gives an indication of how much electrical power is needed to run them at a specified operating voltage. Light or lumen output of a lamp is a function of wattage. For example, a 1500 W MH lamp (product ordering code MH1500/U) from Philips Lighting, a division of Philips Electronics N.V. outputs about 155,000 lumens initially and 124,000 lumens on average when operated at 1500 W. A 1000 W MH Philips lamp (product ordering code MH1000/U) outputs about 105,000 lumens initially and 66,000 on average lumens. Wide area, outdoor lighting systems presently tend to favor 1000 W to 1500 W lamps because of the larger light output. Lamps over 1500 W are becoming increasingly available and used.
With reference to
Theoretically, there can be almost an infinite number of ways to light a field to a specified light level. For example, a thousand fixtures containing lower power lamps could be elevated on poles or other superstructures and densely packed together encircling the field. However, this is usually impractical. Not only would the cost of that many fixtures (including lamps) be high, the cost of structures to elevate them would be likewise. The cost of maintenance would also be high. And, over time, the cost of energy to operate them would be high. Since many, if not most, athletic field lighting systems are funded by the public or non-profit organizations (e.g. schools, municipal recreation departments, private recreation leagues), cost is a major factor in selecting such lighting.
Therefore, it is conventional to try to minimize the structure used to elevate fixtures and also minimize the number of fixtures for a lighting application to reduce both capital and operating costs. This has driven HID lamp manufacturers to develop more powerful lamps so that each fixture can output greater amounts of light energy to, in turn, allow fewer fixtures to meet a specified light level for a field. Fewer fixtures require fewer elevating structures (e.g. fewer poles). For example, it has been reported that capital costs for installations with 1000 W fixtures can be at least 30 percent higher over installations with 1500 W fixtures.
However, as previously discussed, MH lamps (and most HID lamps), have an initial light output at rated wattage (after an initial “break in” period), but then, over the life of an HID lamp, the lamp usually slowly loses lumen output from LLD, even if that same level of electrical power or rated wattage is supplied. The practical effect of lumen depreciation is that, by the latter part of normal operating life of the lamp, its light output is a fraction of its starting output. If used in a system which requires a specified light level or output from the light source, the light source may have to be replaced early because it alone, or in combination with other lamps of similar reduced output, may render the light level to the target unacceptable.
One way of dealing with LLD is to do nothing. Even though the LLD characteristic will most likely result in a drop in light level from the light source, in many lighting applications it is not considered worth addressing. The drop in light level over time is simply accepted, or is not deemed significant enough, functionally or economically, to act upon. With HID lamps, the initial rapid drop-off is usually no more than 10-20%. And, subsequent light loss from LLD tends to proceed at a slower rate after that rapid initial lumen depreciation period. The lumen drop-off may not even be noticeable to most observers. However, in applications where light output is specified for a light source or for the area or target to be lighted by the light source, as is the case for wide area sports lighting, lumen depreciation can be a significant problem. As stated, in sports lighting, if light levels drop too much, it can not only be more difficult for spectators to see the activity on the field, it can become dangerous for players. Thus, doing nothing to compensate for LLD is not satisfactory for such lighting applications.
A second approach to the LLD issue is to replace lamps well prior to end of predicted operating life. For example, some specifications call for all lamps to be replaced at 40% of predicted life. While this tries to deal with the light loss from LLD, replacing lamps early during expected life span adds significant cost to the lighting system, and wastes potential usefulness of some lamps.
If lumen depreciation is dealt with in sports lighting, however, the most common way is a third approach, as follows. The designs essentially engineer into the system an excess amount of light fixtures (and thus additional lamps) in anticipation of light output drop-off caused by at least the first, rapid 10-20% depreciation, so that after about 100-200 hours of operation, the light output is at about the specified level for the particular application. These designs conventionally specify that the lamps be operated at rated operating wattages. The excess fixtures, and the higher energy use, add cost to the system (capital and energy) compared to less fixtures (and less lamps), but try to compensate (at least initially) for light loss from LLD. Also, this way of dealing with LLD does not add additional types of components, and the associated cost, to the lamps, or to their luminaires or electrical circuitry. It simply adds additional conventional lamps and fixtures. Therefore, a light designer typically selects a type and number of conventional HID lamps and fixtures that cumulatively may initially exceed the lighting requirements because the designer knows that, over time, the lumen depreciation will drop the lighting level below recommended standards. However, after the initial rapid LLD period, lumen levels decrease (somewhat slowly), but will normally gradually move below the recommended light levels. This latter LLD (after the first more rapid LLD) is many times not adequately accounted for in system design, or is ignored.
Designers may use a lumen depreciation factor or LDF to help decide how much excess light to initially produce. This tries to factor in predicted LLD light loss over whole lamp life, but only uses averages. This approach still uses a number of fixtures which initially produce excess light, but later may not produce enough light. As can be appreciated, this results in added capital and energy costs initially, and added energy and maintenance costs thereafter (e.g. operating additional lamps at ROW over their entire operating lives, and having to replace more lamps over time). It also may result in a deficiency of light later. But this has been the conventional balance adopted by the state of the art.
The state of the art has, therefore, moved in the direction of developing and using higher wattage lamps, and intentionally designing in additional fixtures that produce an initial excess amount of initial light output for an application. This addresses part of the LLD issue, but not all of it. It does not address added cost (capital and operation). Therefore, there is room for improvement in the art.
There are also continuing attempts to make other improvements involving HID lighting. For example, improvements have been made in increasing the efficiency of lighting fixtures to direct more light from each lamp to the field, see, e.g., U.S. Pat. Nos. 4,725,934, 4,816,974, 4,947,303, 5,075,828, 5,134,557, 5,161,883, 5,229,681, and 5,856,721. But, the problem of light loss from lumen depreciation of HID lamps remains a problem in the art.
There are also circuits which enable selective dimming of lights. See, for example, Musco Corporation MULTI-WATT™ system and U.S. Pat. No. 4,994,718. Capacitance is added or deleted to change light output from one or more lamps. However, this provides a user the option to select, at any time, between more or less light to the target. It does not address compensation for LLD.
Special ballasts have also been developed, particularly for fluorescent lamps, to try to keep light output from a lamp uniform over its life. However, these tend to be relatively complex, require significant interfacing components or circuitry with the lighting system, and therefore are relatively expensive and impractical. They also do not address the issues of composite lighting by sets of fixtures, as exists in lighting such as sports lighting or other composite area lighting. Therefore special ballasts of the type mentioned are generally considered too expensive for use in most lighting applications.
Solid-state light sources are known for energy efficiency and long life. They are also known to exhibit LLD. Lumen depreciation of solid state light sources is also often either ignored, or compensated for by over lighting an area such that desired lighting levels are met even as the output of the light source depreciates. These options result in either insufficient light output or wasted light and energy.
There are many different applications for solid-state lighting sources. Some do not require a specific amount of light output be maintained, thus the degradation of the light emission is not much of a concern. For example, LED lights for toys, indicator lights, backlight illumination for small displays, etc. do not require constant light output or a minimum level, except what is viewable. Many other applications do require minimum levels of light. Some examples include task lighting, large area lighting, display lighting, projection system lighting, and others. These applications have traditionally used arc type lamps, such as HID sources. Many of these arc type lamps also experience lumen degradation, as discussed herein (and in U.S. Pat. No. 7,176,635) relating to the commercially available Musco SMART LAMP® product.
Like many of the applications utilizing arc type lamp sources, systems utilizing solid-state light sources overlight an area by the predicted amount of light loss over the useful life. For solid-state light sources, the useful life is generally determined by the degree of degradation that has occurred compared to the amount of energy consumed. At some point in the life of the light source, the amount of light output is not sufficient for the application, or does not warrant the energy cost. This is the end of its useful life, even if the source is still operational. In the case of solid-state light sources, lumen output for individual light sources can be increased by increasing the drive current supplied to the light source rather than increasing the quantity of light sources used for the application. However, this method consumes extra energy and provides excess light early in the life of the light source. Thus, energy and light are wasted. Also, increased drive current to a solid-state light source can shorten the light source's effective life span, therefore the tradeoff between increased lumen output and decreased life span must be carefully managed. Examples of solid-state light sources include light emitting diodes (LEDs), organic light emitting diodes (OLEDs), solid-state lasers, or any other semi-conductor based light source.
For LED light sources, issued U.S. Pat. No. 7,132,805 discusses a controller to drive the LED source and provide constant light output. However, this approach is complex and adds considerable cost in equipment and energy to the system.
Therefore, there is room for improvement using a low cost, simpler approach that is effective in providing constant, or near constant, light output.
Features, advantages or aspects of the invention include a method, apparatus or system which:
These and other features, advantages, and aspects of the invention will become more apparent with reference to the accompanying specification and claims.
Therefore, the inventors identified a need in the art to minimize use of electrical power over at least a substantial portion of operational life of HID lamps, while reasonably compensating for LLD over the life of the lamp in a practical way. In one aspect of the invention, this is accomplished as follows.
Because the lumen depreciation can be fairly well predicted, the relationship between wattage and lumen output can be predicted. Thus, less electrical power is used initially, and LLD compensation is accomplished by one or more increases in wattage to bump light level back to or near desired level during the operational life of the lamp. This saves energy by using lower wattage in the beginning and not using additional wattage until needed to restore lumen output.
Optionally, at subsequent later times, further increases in wattage can be made to return lumen output to at or near the specified level to compensate for LLD. Thus, there can be several increases over the life of the lamp. Preferably, however, there are not more than a few.
In one aspect of the invention relating to sport lighting, the invention attempts to avoid using excess electrical power during a first period of operation (the light(s) will put out approximately what is needed for the field) by initially supplying operating wattage at a level lower than rated wattage for the lamp. Periodically, the wattage will be increased to combat the reduction in lumen output. While the increase in wattage can be done periodically, in one aspect of the invention, it will be done at no more than a handful of intermittent (not necessarily equally spaced-apart) times. One way to designate the times for increases is to use a timer that monitors cumulative operating time of the lamp and, at pre-selected times, changes the tap(s) on the lamp's electrical ballast to increase the amount of current to the lamp. Another way is to add capacitance. Other ways are possible.
Another aspect of the invention includes a method, apparatus, and system for cost and energy savings for lighting applications using one or more lamps having a LLD characteristic by operating a lamp under ROW for a given time period and then incrementally increasing operating wattage towards ROW between one and a few times over normal operating life of the lamp. This aspect also tends to provide a more consistent light level for the application.
Another aspect of the invention is a method of providing approximate or generally near constant light output from a solid-state light source. Lumen depreciation can be compensated for by adjusting the drive current waveform at discrete times determined at least partially from manufacturers' published degradation characteristics or from characteristics based on empirical testing. With knowledge of a light source's lumen depreciation characteristic it is possible to predict approximate times when the lumen level will decay to a particular point. This is a low complexity approach which relies on the accumulation of operating time and a light source's lumen depreciation characteristic to predict discrete times to adjust the operating parameters. This approach could also be used in combination with sensors to regulate the lumen output closer to constant level.
The ability to operate at a constant, or near constant, output is reliant on many factors (temperature, voltage differential, accuracy of curve from manufacture, etc). While these factors may cause the light output to vary from the manufacturers' degradation curve, the adjusted level throughout time will be closer to constant than would otherwise be achieved by doing nothing.
For a better understanding of the present invention, specific exemplary embodiments according to the present invention will be described in detail. These embodiments are by way of example and illustration only, and not by way of limitation. The invention is defined solely by the appended claims.
Frequent reference will be taken in this description to the drawings. Reference numerals and letters will be used to indicate certain parts or locations in the drawings. The same reference numerals or letters will be used to indicate the same parts and locations throughout the drawings, unless otherwise indicated.
A first relatively simple example of the invention will be described in the context of a single HID light source which has an LLD (lumen depreciation) characteristic.
First, how much time the lamp is operating is tracked. This can be done in a number of ways.
Secondly, the lamp can be operated at an operating wattage below ROW, or “bumped down” from an initial operating wattage, for a certain period of operating time. The timing of and amount of bump down can vary. Generally, the magnitude of the bump down is preferred to be substantial enough that there is a material energy savings, at least over the bump down period. However, it is preferable it not be so low as to materially affect lamp performance (e.g. starting, efficacy, color, or lamp life) or reduce light output from the lamp too much. For MH lamps, the bump down would usually be more than 5% but less than 30%. A range of 10% to 20% would be likely. It is unlikely that bumps of less than 2% would be used, or bumps of more than 30%; either decreases (or, as will be discussed later, increases). Although there is usually a reduction in initial light output at the lower operating wattage, and lumen depreciation would proceed, a benefit of the bump down is the savings in energy. Operation of the lamp at the lower wattage uses less energy. Furthermore, indications are that some reduction of initial operating wattage (but not too much) may prolong lamp life. The timing of the bump down can vary from immediately to some time later. For example, there may be reasons to delay the bump down, such as providing ROW for initial starting of the lamp or ROW for an initial “break in” period (e.g. until it reaches “initial lumens” state).
Third, after the bump down period, operating wattage is then increased. The timing of a “bump up” of operating wattage can vary. One criteria could be with reference to the LLD curve of the lamp (e.g.
This simple example shows how the method of the invention allows a creative way to compensate for LLD in a simple, practical way. It balances energy savings with maintenance of light output by making substantial, but not huge, alterations in operating wattage at a few selected times during the life of the lamp. Trade offs are made. For example, even though light level is not maintained continuously, it is restored to at or near initial levels for at least a while. And even though energy savings are not huge in the short term, over time they can become substantial.
In one aspect of the invention, selection of magnitude and timing of wattage changes is made with close reference to the LLD curve for the lamp involved. More than one bump up can be made. By periodically using modest bump ups, light output can repeatedly be restored while continuing to realize energy savings (even if those savings diminish over time). One important result is that the light output is continuously pushed back up towards initial output over the entire life of the lamp, even at the latter part of rated life when otherwise it would be approaching one-half initial output. And, energy savings would most likely be achieved.
As can be appreciated in this example, the number of bump ups can vary. Preferably, they would not exceed perhaps a handful of times. And, as can be appreciated by those skilled in the art, the balancing of operating wattage versus light output can be made case by case, based on the needs or desires of the light or the lighting application and based on the type of lamp and lumen depreciation curve for that lamp.
A more specific example will now be described. It uses the general methodology described above with respect to Example 1. One example of such a light source is the HID lamp 10, like illustrated in
With further reference to the flow chart 200 of
1. Pre-Design Selections
A goal is to provide a reasonable, practical, and cost-effective way to avoid suffering light loss of the magnitude indicated by
The design picks four points along curve 2 for wattage changes. First, a bump down in operating wattage at T0 is designed to save operating energy. A first bump up would occur at T1, the end of initial rapid depreciation (approx. 200 hours), to bring light output back up after that first rather steep loss. Because curve 2 then flattens out, the design picks two rather widely spaced apart times T2 (1000) hours) and T3 (2000 hours) for further increases.
The magnitude of the wattage changes is shown at
The design selects the length of the bump down period to extend until approximately the end of the first rapid depreciation period (until time T1, or approximately 200 hours of operation). At T1, the design bumps up wattage, calculated to basically restore the lamp light level to at or near its initial level. In this example, this is found to require about a 10% bump (see ref no. 33, e.g. 105 W). Operating wattage of approximately 1155 W occurs (ref no. 34) between time T1 (200 hours cumulative operating time for the lamp) and T2 (1000 hours cumulative operating time for the lamp). Additional anticipated energy savings during this time is indicated at
Then, similarly, the design has two more bump ups (ref. nos. 35 and 37) at times T2 and T3. Between T2 and T3 the approximately 10% bump up (ref. no 36, e.g. to approx. 1270 W) is designed to realize further energy savings (ref. no. 39C), as does the approximately 10% bump up after T3 (ref. no. 38, e.g. to approx. 1397 W and ref. no. 39D). All wattage bump ups are still below the 1500 ROW. Thus energy savings over operating the lamp at 1500 W are planned and realized throughout its operating life.
2. Timing Cumulative Lamp Operation.
Referring now to the flow chart of
3. Reduce Initial Operating Wattage.
During operating time T between T0 and T1, operating wattage of lamp 10 is reduced or dropped below its rated operating wattage. This can be done in a number of ways. Specific examples will be discussed later.
In step 214, this reduction or bump down is expressed as the “ROW”, the lamp manufacturer's rated operating wattage, minus “L”, a variable. It is generally indicated to drop initial operating wattage as low as possible to save as much energy as possible, but not too far so that it materially adversely affects the lamp, its efficacy, or its operation. For example, operation too far under ROW is believed to affect ability to start and maintain these types of lamps, as well as some operating characteristics of the lamp. One technique is to limit the initial drop in wattage to no more than the rated operating wattage times the lumen depreciation factor for the particular lamp, or ROW*LDF. In the case of 1500 W MH lamps, LDF tends to be around 0.7 to 0.8. Thus, using this rule would result in the variable L being on the order of 20% to 30% of ROW (rated operating wattage of the lamp). Thus, L might be around 300 to 450 W in such an example; meaning an initial operating wattage of around 1050 to 1200 W for lamp 10 (step 216).
One way to determine the initial reduction offset is by estimating how much it can be reduced and still meet a goal of keeping minimum specified light output and other lighting requirements during initial rapid depreciation period 4 between times T0 and T1. As previously mentioned, some lamps lose as much as 20% light output in first 100-200 hours or so. Based on the previous assumption that lamp 10 produces excess light initially, the initial decrease or offset of operating wattage could be no more than to maintain a light output reasonably close to desired light output for the application. Selection of the amount of bump down should generally be not so much that it materially affects lamp starts, but preferably gives a substantial energy savings. It appears preferable to not run the lamp too low, because the lamp can suffer too much loss of efficiency. It is therefore recommended to start with multiplier that is based on LDF (e.g. between 0.7 to 0.8 or 70% to 80% of normal or mean lumens). For higher powered lamps, 0.7 may be too much because of too much efficiency loss.
As indicated by the cross-hatched area 39A in
4. Increase Operating Wattage.
However, method 200 seeks to compensate for this LLD in the following fashion. At selected time T1, as kept track of by the timer, the operating wattage of lamp 10 will be increased. When the timer indicates T1 has been reached (T=T1, step 214,
The amount of increase can vary. In this example, approximately 10% is added back, so at T1 operating wattage is bumped approximately 105 W (see ref no. 33,
5. Increase Operating Wattage Again, if Desired.
Method 200 repeats the compensation procedure just described. At time T2 (when T=T2, step 218,
This compensation could be repeated a third time at T3 (steps 222 and 226,
Once the third and last increase or bump up as been made, the timer can be turned off (step 228,
If a new lamp is installed for the same application, a similar lamp with similar LLD can be replaced and the timer is reset to zero to begin a new tracking of cumulative operation time for the new lamp to allow the method to provide the pre-selected wattage changes at the pre-selected times.
Thus, under the method of flow chart 200, operation time of lamp 10 is monitored and accumulated. An initial decrease of operating wattage from ROW is followed by three increases back towards ROW. It is to be understood, however, that variations in the method are possible. For example, one bump up in power after an initial “below ROW” operation may be all that is selected. Or, further power bump-ups, over and above the three indicated at
Thus, using method 200, nearer the end of operational life, operating wattage may be brought up to around 1,500 watts. Thus, for at least most of the preceding life, the amount of electricity used is less than used when operating at the normal 1,500 watts ROW. However, lumen output is periodically restored to at or near minimum desired level. Lumen depreciation is thus combated. Therefore both benefits of less initial electricity used and rough maintenance of desired light level are accomplished.
Optionally, the last bump up of wattage might be selected so that operating wattage exceeds 1500 W (e.g. values from just above 1500 W up to 1650 W or maybe somewhat higher). This might be needed to restore light output of lamp 10 to approximately the initial desired output. In other words, late in lamp life, it might take more than ROW 1500 W to drive the lamp to produce an output approximately at its initial lumens. This “overdriving” may result in a little extra cost of energy (as compared to operating it at 1500 W), but there likely was a net energy savings over the early periods, and the benefit of keeping light output near the original output is achieved.
According to preliminary indications, operating an HID lamp of this type initially at a lower wattage may prolong its life. This may be another advantage of method 200.
Of course, different methodologies to that of flowchart 200 could be used with the invention. For example, wattage could be literally raised directly in correspondence with lumen depreciation with appropriate technology (e.g. every 10 hours raise wattage a bit). However, this may be impractical or too costly. It is presently envisioned to have limited number changes to increase wattage; perhaps no more than 2, 3, or 4 changes over the lifetime of the lamp. Compared to attempts to continuously monitor operating wattage and adjust the same (which can require sensors, interfaces with the lighting system, and other components), this would allow low cost electrical or electronic components to be used to change the wattage.
Also, of course, the magnitude and timing of wattage changes could be adjusted for different lumen depreciation curves for different lamps. Based on current understandings and beliefs, the following preferences are can be implemented for various embodiments of the method of
In this example, it is assumed that the light loss during the initial T0-T1 period is accepted, even though it would result in a 20% loss by the end of the period. However, alternatively, lamp 10 can be originally selected, by considering its initial lumens output and its LLD (including its LDF), such that it will provide more than enough initial lumens light output for the application, and roughly sufficient light output lumens at the end of the rapid LLD period (time T1).
Another example of methodology according to one exemplary aspect of the invention will be described in the context of wide-area lighting for sports. One example of such type of lighting installation and system is illustrated in
By referring again to the flow chart of
In this instance, lamps 10 are selected in conventional fashion for sports lighting. Computer programs are well known and available in the art to design a lighting system for field 24 according to specifications for lighting of field, which include a minimum light level at and above field 24. Other methods are possible. From manufacturer information or empirical testing and measurement, initial light output (sometimes defined as output, in lumens, after 100 hours of seasoning; also sometimes referred to as initial lumens) is determined.
The characteristic lumen depreciation (LLD) for the type of lamps 10 used is determined. This can be determined from information from the lamp manufacturer. It can also be empirically derived. From this information a lumen depreciation curve like
As discussed with method 200 of
With this knowledge, using well-known design methods, the designer of the lighting system can select the number and position of fixtures for the application to have sufficient cumulative light for the field, factoring in an initial drop in operating wattage for lamps, based on the offset between initial lumens and mean lumens predicted for the lamp to approximate the light output from each lamp 10 needed initially to create the specified light level for field 24.
Table 1 below indicates one regimen that could be selected according to the following design criteria:
Using the regimen of Table 1, energy savings similar to
With the regimen of Table 1, a similar light output to that depicted in
1. Apparatus
Implementation of the above described LLD compensation method can take many forms and embodiments. One specific exemplary implementation of the above LLD compensation method into the lighting system of
a) Lamp
Lamps 10 are Philips Electric 1500 W MH lamps (product #MH 1500U).
b) Fixture
Conventional aluminum bowl-shaped luminaire with mounting mogul.
c) Power source
Conventional line current (480V to disconnect switch).
d) Power to Lamp
Power is provided to each lamp 10 through a lead-peak ballast (Venture Model 79-18-16410-2). Under state of the art practices, 1500 watts operating power is normally provided to each lamp 10. However, as explained below, altered power levels are provided.
e) Selection of Power Levels
One way to provide four different operating power levels is by circuit 28A of
Each lamp circuit has a conventional lamp ballast (Ballast 1) and lamp 10. The 480V is available to the lamp circuit, through fuses for protection of the subsequent circuitry, to the primary coil of conventional Ballast 1.
Four parallel paths exist between the secondary of ballast 1 and lamp 10. Each path includes a capacitor (Cap 1, 2, 3, or 4) and a switch.
A motor 130 is powered through a 240V, 20 W tap on Ballast 1. Motor 1 therefore only operates when power is supplied to lamp 10. Motor 130, its cams, and the gears in between, are selected and configured so that the cams rotate 360 degrees or one revolution no more than once over the rated life of the lamp. In this example the cams are set to rotate once every 4000 hours of motor operation. Therefore, the motor/cam combination (sometimes called a cam timer) essentially keeps track of cumulative operating time of lamp 10. By appropriate configuration of raised areas or cut-outs on the perimeter of the cams, switches can be closed or opened at appropriate times during the 4000 hours.
Motor 130 turns timing cams (see Cams 1-6,
If following the method of
When the motor has operated the equivalent of 200 hours (until T1), a cam closes S1. This adds in the 1 μf of Cap 2 in parallel with Cap 1, which raises operating wattage of lamp 10 to 1320 W (approx. 5% raise).
When motor has operated the equivalent of an additional 1000 hours (T2—1200 hours total), a cam closes switch S2 to further add Cap 3 (2 μf) in parallel with Caps 1 and 2. This raises operating wattage of lamp 10 to 1440 W (approx. 8% raise).
Finally, when motor has operated an additional 1000 hours (T3—2200 hours total), a cam closes switch S3-1 to further add Cap 4 (2 μf) in parallel with Caps 1-3, to raise operating wattage of lamp 10 to 1560 (approx. 8% raise). Switches S3-1 and S3-2 act in tandem, but oppositely. Therefore, when Cap 4 is added (the last increase), there is no need for further operation of the motor, so switch S3-2 breaks the current to the motor and it stops. Further timing is not needed because the regimen of Table 1 has been designed to make only three wattage bumps. However, Caps 1-4 all remain connected to lamp 10. The remaining further operation of lamp 10 in its operating life after the last bump will be at the operating wattage created by line current and Caps 1-4.
If lamp 10 fails and is replaced (or otherwise is replaced), the switches can be reset to original normal positions, as can the cams and motor. The circuit is ready to repeat the method for the new lamp.
The circuit of
But, importantly, the apparatus to switch in the capacitance operates off of the line voltage needed for the lamps. No separate power source or battery is needed. Also, the electro-mechanical cam timer is highly reliable and long-lasting. The motor rotates at a fraction of a revolution per hour (rph). The motor is the timer. No special timing device is needed. Also, the design is flexible as the levels of lamp operating wattage can be selected by merely selecting the capacitance of the capacitors. The changes in operating wattage do not have to be equal in magnitude. Most ballast boxes have ample room for these components.
f) Timer
As mentioned,
By a typical arrangement, a gear motor rotates cams which operate switches at appropriate times to add the capacitors discussed above. It is relatively low cost, compact, durable, and reliable. It runs off of the electrical power for the lamp, so no extra power source or battery is needed.
Referring to
Gear motor 130 (a combination of an electric motor and gears) turns cam shaft 112 which is rotatably journaled at opposite ends in bearing 116 in end plate 104, and bearing 114 in mounting plate 102. Mounting plate 102 allows mounting of the entire cam timer assembly 100 into ballast box 20. A cover (not shown) can be placed around assembly 100.
Cam shaft 112 is rotated through a set of planetary gears. When motor 130 is on, motor axle 126 rotates pinion 128 (1.2 inch O.D.) at a small fraction of a revolution per hour (rph), specifically at 533 hours per rotation, which drives toothed gear 124 (2½ inch O.D.) which rotates on shaft 122 mounted to end plate 104. Gear 124 has a reduction gear 120 (½ inch O.D. toothed) fixedly mounted on it which abuts and drives cam shaft gear 118 (2½ inch O.D. toothed), which in turn drives cam shaft 112. The gear ratios are pre-designed to translate rotational speed of motor 130 to a desired rotational speed of cam shaft 112 to, in turn, rotate cams 1-6 at a desired rate (e.g. 13,300 hours per single rotation). The gears can be driven frictionally or by intermeshed teeth.
Contactors 1-6 are mounted on rails 106 or 108, as shown in
In this example, contactors 1-6 are normally closed (NC) or conducting. The cam presses down an a spring-loaded plunger component of the contactor to hold it open (i.e. in a non-conducting state) until a cut-out portion of the cam reaches a certain point relative the plunger. At that point, the spring-loaded plunger, which until then had ridden along the cam falls off the cam (is not held down by the cam) and releases, and the contactor closes (becomes conducting). Once the plunger releases, the cut-out is designed so that it will not again lift the plunger back, until the whole cam timer is reset. The cams can be custom made to provide the cut-out at the right point. In this example, the cams are designed to cause three switches, at approximately 200 hours, approximately 1000 hours later, and then approximately another 1000 hours later.
In this way, assembly 100 effectively becomes a timer which monitors cumulative operating hours of its associated lamp 10. Motor 130 is inexpensive, and is low power, long life (e.g. 107 operations), small, light weight, and durable (coil, no armature). It is synchronous for good timing characteristics. It is configured to drive in one direction only (e.g. needle bearing clutch), but like a washing machine cam timer, can be rotated in that direction to reset it to a starting position (e.g. when a lamp is changed). As indicated in
Similarly, the cams are durable, relatively small, light weight and inexpensive. They can be precut using software by the manufacturer or specially ordered. They can also be custom built. They are slideably mounted on square shaft cam shaft 112.
Contactors 1-6 are also relatively inexpensive and small (Square D, either product KA3 for normally closed (N/C) or KA1 for normally open (N/O)). They are push button contactors (protected microswitches) capable of handling the amount of electrical energy supplied to lamp 10. They have environmental protection, including temperature robustness for almost any outdoors application. They also are protected against voltage variations.
Of course, there are a variety of ways such a timer could be configured to produce the functions indicated.
Solid-state light sources are known to have degradation of light output over time. This is undesirable for many applications that require a minimum level of lumen output or require constant lumen output.
Manufacturers' of solid-state light sources publish degradation characteristics of solid-state light sources. For these solid-state light sources, the junction temperature, drive current, voltage differential, and other factors known in the art can impact the rate of degradation. Using manufacturers' data on a solid-state light source's operating parameters, along with good design practices, the output from a solid-state light source can be held constant by adjusting the drive current waveform over time to compensate for lumen depreciation.
The operating time and system operating conditions can be monitored and reported via a remote control system. One such control system is CONTROL-LINK®, U.S. Pat. No. 6,681,110 by Musco Corporation Oskaloosa, Iowa as earlier included by reference.
In a general embodiment of the invention, referring to
An example of a manufacturer's lumen degradation characteristic for Philips Lumileds is shown in
There are a plurality of methods for using time to initiate a change in the operating parameters. One such method uses a microprocessor with an electronic timer which can track the time, and adjust the operating parameters as needed based on the preset limits in the firmware. Another method could use an electro-mechanical timer such as disclosed herein (and in U.S. Pat. No. 7,176,635) relating to the commercially available Musco SMART LAMP® product. Another method could use an electronic timer such as disclosed in provisional patent application U.S. Ser. No. 60/891,392. In yet another method, the operating time could be monitored and stored remotely as part of the control system, and adjustment made to the drive current via commands from the control system. This method would also allow for the operating parameters to be adjusted if conditions change. For example, if temperature or voltage differential are found to be different than expected, then appropriate adjustments could be made to return the light output to constant levels.
The end of life is generally considered to be when the light source is no longer efficient to operate. Upon replacement of the light source, the system is reset to the initial drive current waveform and the cycle starts over. In one embodiment the light is held at nominal level while the energy level gradually increases with each adjustment. Thus, the total energy consumption throughout the life of the light source can be lower than the conventional operating method of using an initial higher drive current for the entire life of the light source. The economy of the system depends on how long a user elects to increase the current to the solid-state light source. A user may elect to increase the current for a period beyond what would be economical from an energy standpoint because of a variety of other factors including, but not limited to, difficulty and cost of replacing the light source.
Referring to the flow chart (
In one embodiment, the current waveform could have a constant amplitude, where the amplitude would remain constant throughout the wave period. This amplitude would correspond to the necessary current needed to drive the solid-state light source to meet the lighting requirements. This amplitude could fall anywhere within a range of currents. It is recognized that amplitudes outside the manufacturers' recommended range of amplitudes could result in negatively impacting the lifespan, efficiency, and color quality of the solid-state light source, as well as other unwanted effects. Therefore, it is preferred that this amplitude fall within the manufacturers' recommended range of currents.
In this embodiment, the amplitude of the current is increased at periodic times (T1, T2, . . . TN), as determined by a timing mechanism, by an amount that will provide a lumen output that would compensate for the lumen depreciation as predicted, at least partially, by the manufacturer's degradation curve. The current increases could stay within the manufacturer's recommended range of drive currents, or it could exceed, or fall below, this range. The current increases would continue until the end of the solid-state light source's effective lifespan, as defined by the point in the life of the light source where the amount of light output is not sufficient for the application, or does not warrant the energy cost.
As can be appreciated, energy savings for each lamp 10 (
A simple example is as follows. If electricity costs 7 cents/KW-hour, and a lamp is on for approximately 4 hours a day for a year, operation of that lamp would cost about $100.00/yr (1460 hours*$0.07). If approximately 20% less energy is used the first year by the lamp, a savings of about $20 would be realized. And, if there were 100 lamps for the lighting installation, a $2000 savings would result. Like compound interest, little gains may not seem significant, but over time, and compounded by multiple similar gains, it can be significant. Over thousands of hours of operation, total savings for each lamp, and for all lamps, would accumulate.
Furthermore, it may be possible to achieve savings by reducing the number of fixtures used in multi-fixture systems. For example, if it is known that later in lamp life light levels will drop substantially, a designer may “over specify” the number of fixtures in the hope that even when LLD has reduced light levels substantially, excess lights at the start will still provide a reasonable amount of light in that situation. With circuit 28A (
Circuit 28A is relatively inexpensive, non-complex, runs off of line power, is uncomplicated, and does not interfere with other parts of lighting system. Furthermore, even if it fails, it would not affect the lighting system and energy savings would be realized for as long as it did work. It is estimated that over normal operating life of such lamps, a 10-15% energy savings over operating the lamp at rated operating wattage is possible on a routine basis.
The output of the solid-state light sources is able to be kept constant, or near constant, through a simple timing mechanism that adjusts the current waveform at key points to compensate for the lumen depreciation at that time as determined, at least partially, by the manufacturer's depreciation characteristic. This constant, or near constant, lighting method uses less energy than prior methods which over light an area, and provides sufficient and more constant light output than prior art methods of ignoring lumen depreciation.
The foregoing examples are made for illustration only, and not to limit the invention. Variations obvious to those skilled in the art are included with the invention. A few examples are given below.
1. Generally
Various specific components can be used to practice the invention, such as is obvious to those skilled in the art. Variations in the regimen to practice the methodology of the invention are also well within the skill of those skilled in the art. A few examples are given below.
2. Lamps
As previously stated, the invention is believed relevant to most HID lights, including the various species of HID lamps (e.g. MH, Fluorescent, etc.), and whether jacketed or not, single or double ended. The invention may be most economically effective for higher powered HID lamps (e.g. at or over 400 W), but may have other advantages regardless of energy cost savings over time. It can be beneficial for an application using a single lamp, or for an application using a plurality of lamps.
The invention is also relevant to most solid-state light sources, especially light emitting diodes (LEDs). These solid-state light sources could have any one or combination of a plurality of substrates, dopants, coatings, casings, or other augmentations that would facilitate efficiency, extended lifespan, color quality, intensity, or directionality from the solid-state light source.
The invention is also believed relevant to any light source exhibiting lumen depreciation, where the lumen depreciation is at least partially predictable, and which has adjustable factors that can contribute to increased lumen output.
3. Method of Setting Wattage Changes
Selection of the times to change wattage can vary according to desire or need. It has been found that time of operation is as predictable as anything upon which to base amount of lumen depreciation (cf. voltage, amperage, temperature, etc.).
Most of these types of lamps are predictable, including what happens when they are under-driven or over-driven. Also, most times the manufacturer will have available information regarding a lamp's LLD, LDF, etc. Therefore, a designer can literally select when to change lamp operating wattage based on a LLD curve for the lamp.
However, allowances can be made for other factors that affect light output of such lamps over time. For example, a designer could consider not only LLD, but also dirt accumulation on the lamp over time when selecting wattage changes and times.
4. Change Wattage
A variety of ways exist to change the wattage, the amount of energy, to such lamps at the desired times.
a) Add Capacitance
In the example of
b) Ballast Taps
In
At the end of the first period (e.g. T1 or 1200 hours), a cam of cam timer 130 would change the state of switch 1, which would open S1-1 but close S1-2 (N/O). Note that switch 1 is configured to close S1-2 before S1-1 breaks so there is assured continuity of power during the switching. Thus, 592V is now supplied to Ballast 1 (instead of 650V). This generates an increased power to lamp 10 of 1215 W during a next, here a second, timed period.
Similarly, at the end of the second timed period (e.g. until T2 or 2200 hours), cam motor 130 operates switch 2 to close S2-2 (N/O) and then open S2-1 (N/C), supplying 533 V to Ballast 1, or 1350 W to lamp 10.
Finally, at the end of the third timed period (T3 or 3200 hours), cam motor 130 closes S3-2 (N/O) and opens S3-1 (N/C), supplying 480V to Ballast 1 and 1500 W to lamp 10. Additionally, S3-3 (N/C) opens, shutting off motor 130.
The table below provides details regarding circuit 28B and its operation.
c) Buck/Boost Transformer
A further example would be use of a buck/boost primary auto transformer (lead-push ballast with taps) (not shown). This is less sensitive to voltage. It can work like a reactor ballast. It may be less expensive than adding capacitors.
d) Linear Reactor Ballast
At the end of the first timed period, like circuit 28B of
Third and fourth wattages are supplied at third and fourth times by switching to Tap 3 (S2-2 (N/O), S3-1 (N/C)), and then Tap 4 (S3-2 (N/O)) of Ballast 1. When switched to tap 4, S3-3 (N/C) also opens or breaks to shut off motor 130.
With this method the reactor ballast taps are physically changed. This method is more sensitive to voltage.
e) Change Primary V
A still further example would be to change transformer taps at the transformer where power comes into the field. In other words, literally change the amount of voltage going to each of the ballast boxes 22 around the field being lighted. Thus, at one place, the operating wattage for all the lamps can be controlled.
Also a tapped transformer could be used for all of the lights on a pole. A time regimen could be used to change voltage to increase power. It could be arbitrarily feed, and bump out at increments such as 480V, 440V, 380V, and 350V.
By reference to
Contactors C2, C3, C4, C5 would be controlled to choose the desired tap. There are three sets of Taps 1-4 and Contactors 2-5; one set for each phase of the primary voltage. Each set of contactors C2 or C3 or C4 or C5 would be controlled together to select one voltage for L1, L2. Thus, similar to the lead peak embodiment of
This differs from circuit 28B of
Switching of contactors C2-5 can be accomplished in a number of ways. One example would be to use a remote control system such as disclosed in co-owned, co-pending U.S. patent application Ser. No. 09/609,000, filed Jun. 30, 2000 (now U.S. Pat. No. 6,681,110), and incorporated by reference herein. The operational status of each lamp can be monitored, e.g., whether each lamp is on or off, and how long the lamp has operated. A computer can keep track of the same and communicate with a remote computer via cellular telephone system control channels. At pre-pre-programmed times, instructions can be sent from the remote computer (after confirmation that no load is on the transformer) and can instruct contactors to open or close. With this method, no cam timer or other timer is required at the lighting site or in each ballast box 22.
Another example of a centralized control system would be CONTROL-LINK® by Musco Corporation. It uses the wireless internet to communicate from a central server to widely distributed controllers associated with lighting systems in different locations across the country, or even the world.
The taps can be selected to have a range of voltages. For example, they could be approximately 10% apart in magnitude of voltage. This would allow incrementally increases in voltage to all lamp circuits, and thus incremental increases in operating wattage, at pre-selected times, preferably timed to LLD. Even if a lamp reaches a time when its operating wattage should be changed, but it can not be changed because it is on (i.e. a load on the transformer exists), by programming and the intelligence of the local controller and the central computer, the system can wait until the lights are turned off to change the transformer taps. The flexibility of the method is such that even if the lamp operates, for example 210 hours instead of the programmed 200 hours, before its operating wattage is changed, it does not have a material effect. Rarely would entire lighting installations be on continuously for more than one half of day.
Therefore, the concept of
This alternative may add some cost and complexity for primary transformer switching, as it may need to be switched while lights are off.
5. Selection of Time of Power Change
a) Cam Timer
The cam timer 130 is a low cost, reliable de facto timer of lamp operation. Like electro-mechanical washer machine timers, cam-based timers with direct switching contacts have been developed over decades and have high reliability.
b) Electronic Timer
However, an electronic timer could be used. It could control relay contacts to effectuate switching. However, it would need to have appropriate components to supply it with electrical power. If based literally on keeping time of day, a battery back up would be needed to run it when the lamps are turned off, and no power to the system is available. A variety of such timers are available commercially.
Electronic or mechanical relays, contactors, or relay energized contacts could be controlled to make the switching changes.
Some disadvantages of electronic devices include susceptibility to damage or error caused by outside environment (e.g. lighting strikes). Also, the components tend to be relatively expensive (e.g. a microprocessor could cost $20 to $40). Associated structure, e.g. contactors, latch relay doubles, also could add to the cost. There is some unreliability inherent in such devices.
c) Computer/Microprocessor Control
Another example was discussed with U.S. Pat. No. 6,681,110 and CONTROL-LINK®. A computer, either local or remote, would keep track of time and cumulative operation time of the lamps. The computers would control switching contactors. They could keep track of events and record when changes are made.
Such devices could be programmed at a factory. They might operate without battery by, like cam timer 130, accumulating timer of lamp operation by the time the electronic controller is operating.
6. Additional Options
Additional features could be used with the invention. There could be a bypass switch that bumps the lamp up to full rated wattage whenever selected. An example would be if there is a tournament when the lamps are brand new. There might be a desire to increase the lumen output for those first several hours, instead of running them at the bumped down wattage. Later the switch could be turned off and the lumen maintenance methodology described above could then take over or continue.
Also, there may be an issue of starting lamps at lower than rated wattage. If a choke is used, the power factor for the lamp may be questionable, especially on starting. There could be an automatic circuit that provides higher starting voltage and then drops back down to the lower operational voltage to overcome this problem (especially in cold weather). For example, the MULTI-WATTT™ circuit by Musco Corporation, mentioned earlier, could be used for this purpose. Essentially higher wattage may be needed to kick in and fire up the lamp to heat up the electrodes (to reduce loss), then bump down. For example with a linear reactor ballast, it might be useful to bump operating wattage up to 125% of rated operating wattage at start to provide a “hot start” in cold weather. This could be accomplished in a number of ways, including many of the ways described in making wattage changes discussed herein. For example, another tap could be put on the reactor ballast.
As further indicated, the methods of the invention may actually also increase lamp life. By running under rated wattage, it is believed to lessen the slope of the LLD curve. This may increase lamp life because it operates without as much light loss over time. This may mean farther wattage bump ups should be made later in lamp life, especially if the lamp life increases because of the method.
Reset of the circuitry can be done in different ways. A reset button or dial (e.g.
The invention is not limited to sports lighting. It is believed relevant to any light subject to lumen depreciation of an analogous nature. It can be applied to a variety of lamps, fixtures, and applications.
One variation of the method according to the invention is as follows. No changes in lamp operation are made during an initial time of operation of the lamp (e.g. the lamp is operated at ROW for the first 100 hours of cumulative operating time). The light output of the lamp, diminished some by LLD, becomes a “base value” output for the lamp. The lamp could then be run at ROW for an additional time (e.g. until 200 cumulative operating hours). At that point, operating wattage of the lamp could be bumped up to restore at least some of the lumen depreciation that has occurred. An alternative to the above method would be operate the lamp at ROW for the first 100 hours, then bump down for hours 100-200, and then bump up at a later time.
Another optional method that could be used with the invention is as follows. Operating wattage could be bumped up whenever light level drops below a predetermined threshold. For example, an average foot-candle (fc) level could be picked for a football field. Some type of measurement, including by automatic sensors, could monitor foot-candle level at the field. A signal could be generated if the fc level drops below the threshold. The signal could actuate an increase in operating wattage to one or more lamps lighting the field. The amount of increase could be selected from empirical testing. One example might be, if the desired light level was 100 fc, each time light level at the measuring point dropped to 90 fc, an increase in operating wattage would be made to bring the light level back to at or near 100 fc. A graph of the light output from the lamps would look like saw-teeth (see, for example,
When it drops to 100 fc, increase wattage to move it back to 110 fc. This way, the field should always have at least the desired lighting level. Other regimens are, of course, possible.
7. Waveform Options
In another embodiment, applicable to at least solid-state light sources, the initial current waveform could be comprised of pulses. These pulses could have a plurality of characteristics that could be modulated in a number of ways, including, pulse width, pulse frequency, pulse amplitude, or pulse shape modulations. It is to be noted that the pulses could be structured such that the pulse is at a constant amplitude throughout the period.
There are tradeoffs between the choices of modulation methods. For example, implementing amplitude modulation with a solid-state light source allows the user to take advantage of driving the light source at a lower current amplitude which results in greater efficiency and lifespan for the light source. However, amplitude modulations can cause the color quality of the emitted light to deteriorate, so these factors must be weighed when determining the appropriate drive current for an application. Frequency and pulse width modulation methods can prevent the emitted light color quality from deteriorating, but they may not have the efficiency increase of amplitude modulation. It is recognized that multiple modulation methods could be implemented.
In one embodiment, as illustrated in
8. Peripherals
This invention does not require any sensors to compensate for lumen depreciation, however, it is envisioned that a variety of sensors could be added to this system. One example could be to implement lumen sensors, for example photo-diodes, at some distance from the light source. These lumen sensors could monitor lumen output and provide corrections to the estimated lumen depreciation characteristic of the light source. For situations where implementing lumen sensors to measure a plurality of light sources is unfavorable, selected light sources could be measured by a lumen sensor from some distance from the light source to help monitor lumen depreciation. Other sensors, including those that measure, current, voltage, temperature, and other relevant metrics, could be implemented in this invention as these metrics can contribute to a lumen depreciation characteristic.
This application is a Continuation application of U.S. Ser. No. 13/092,664 filed Apr. 22, 2011, now U.S. Pat. No. 8,508,152 issued on Aug. 13, 2013, which is a Continuation application of U.S. Ser. No. 11/842,808 filed Aug. 21, 2007, now U.S. Pat. No. 7,956,556 issued on Jun. 7, 2011, which is a continuation-in-part from U.S. Ser. No. 11/559,153 filed Nov. 13, 2006, now U.S. Pat. No. 7,675,251 issued on Mar. 9, 2010, which is a divisional of U.S. Ser. No. 10/785,867 filed Feb. 24, 2004, now U.S. Pat. No. 7,176,635 issued on Feb. 13, 2007, all of which are incorporated herein in their entireties. The entire content of U.S. Pat. No. 6,681,110 is incorporated by reference in its entirety.
Number | Name | Date | Kind |
---|---|---|---|
4005336 | Casella | Jan 1977 | A |
4009387 | Nuver | Feb 1977 | A |
4189664 | Hirschfeld | Feb 1980 | A |
4292570 | Engel | Sep 1981 | A |
4423471 | Gordin et al. | Dec 1983 | A |
4434388 | Carver et al. | Feb 1984 | A |
4442382 | Fleck | Apr 1984 | A |
4475065 | Bhalla et al. | Oct 1984 | A |
4501994 | Spreadbury | Feb 1985 | A |
4712167 | Gordin et al. | Dec 1987 | A |
4725934 | Gordin | Feb 1988 | A |
4729077 | Gordin et al. | Mar 1988 | A |
4816974 | Gordin | Mar 1989 | A |
4891562 | Nuckolls | Jan 1990 | A |
4924109 | Weber | May 1990 | A |
4931701 | Carl | Jun 1990 | A |
4947303 | Gordin | Aug 1990 | A |
4994718 | Gordin | Feb 1991 | A |
5068576 | Hu et al. | Nov 1991 | A |
5075828 | Gordin | Dec 1991 | A |
5103143 | Daub | Apr 1992 | A |
5134557 | Gordin | Jul 1992 | A |
5161883 | Gordin | Nov 1992 | A |
5207747 | Gordin et al. | May 1993 | A |
5229681 | Gordin | Jul 1993 | A |
5313378 | Gordin et al. | May 1994 | A |
5391966 | Garrison | Feb 1995 | A |
5434763 | Hege et al. | Jul 1995 | A |
5442261 | Bank | Aug 1995 | A |
5469027 | Uchihashi et al. | Nov 1995 | A |
5475360 | Guidette et al. | Dec 1995 | A |
5483127 | Widmayer et al. | Jan 1996 | A |
5483535 | McMillen et al. | Jan 1996 | A |
5519286 | Rodrigues et al. | May 1996 | A |
5594740 | La Due | Jan 1997 | A |
5729471 | Jain et al. | Mar 1998 | A |
5745126 | Jain et al. | Apr 1998 | A |
5769527 | Taylor et al. | Jun 1998 | A |
5845126 | Ju et al. | Dec 1998 | A |
5846132 | Junkin | Dec 1998 | A |
5856721 | Gordin | Jan 1999 | A |
5860733 | Stone et al. | Jan 1999 | A |
5882263 | Chung | Mar 1999 | A |
5929849 | Kikinis | Jul 1999 | A |
6002394 | Schein et al. | Dec 1999 | A |
6031340 | Brosius | Feb 2000 | A |
6035304 | Machida et al. | Mar 2000 | A |
6044405 | Driscoll, III et al. | Mar 2000 | A |
6075326 | Nostwick | Jun 2000 | A |
6114816 | Nuckolls | Sep 2000 | A |
6150772 | Crane | Nov 2000 | A |
6172469 | Kern | Jan 2001 | B1 |
6175195 | Janczak et al. | Jan 2001 | B1 |
6188181 | Sinha et al. | Feb 2001 | B1 |
6191568 | Poletti | Feb 2001 | B1 |
6207943 | Smelker | Mar 2001 | B1 |
6215254 | Honda et al. | Apr 2001 | B1 |
6225760 | Moan | May 2001 | B1 |
6295448 | Hayes, Jr. et al. | Sep 2001 | B1 |
6308083 | King | Oct 2001 | B2 |
6316923 | Poletti | Nov 2001 | B1 |
6320323 | Buell | Nov 2001 | B1 |
6369522 | Collins | Apr 2002 | B1 |
6373201 | Morgan | Apr 2002 | B2 |
6376996 | Olson | Apr 2002 | B1 |
6400103 | Adamson | Jun 2002 | B1 |
6415245 | Williams et al. | Jul 2002 | B2 |
6501231 | Hyland | Dec 2002 | B1 |
6515430 | Kayser | Feb 2003 | B2 |
6545429 | Flory, IV | Apr 2003 | B1 |
6545433 | Beij | Apr 2003 | B2 |
6577075 | Romano et al. | Jun 2003 | B2 |
6583574 | Ann | Jun 2003 | B2 |
6681110 | Crookham et al. | Jan 2004 | B1 |
6798153 | Mattos et al. | Sep 2004 | B2 |
7002305 | Kambara et al. | Feb 2006 | B2 |
7176635 | Gordin et al. | Feb 2007 | B2 |
7385360 | Dluzniak | Jun 2008 | B2 |
7675251 | Gordin | Mar 2010 | B2 |
7741786 | Lee | Jun 2010 | B2 |
7956551 | Gordin | Jun 2011 | B1 |
7956556 | Gordin et al. | Jun 2011 | B1 |
7982404 | Gordin | Jul 2011 | B2 |
8098024 | Gordin | Jan 2012 | B1 |
20020089293 | Romano et al. | Jul 2002 | A1 |
20020185980 | Beij et al. | Dec 2002 | A1 |
20030025463 | Mattas et al. | Feb 2003 | A1 |
20030090215 | Beasley | May 2003 | A1 |
20030222605 | Okamoto et al. | Dec 2003 | A1 |
20060071610 | Dluzniak | Apr 2006 | A1 |
20070040513 | Cleland et al. | Feb 2007 | A1 |
20070043540 | Cleland | Feb 2007 | A1 |
20070043541 | Cleland et al. | Feb 2007 | A1 |
20070070571 | Gordin et al. | Mar 2007 | A1 |
20070153524 | Lee | Jul 2007 | A1 |
Number | Date | Country |
---|---|---|
1288803 | Sep 1991 | CA |
195 40 326 | Apr 1997 | DE |
199 12 517 | Sep 2000 | DE |
0 439 358 | Jan 1991 | EP |
0 536 877 | Apr 1993 | EP |
0 669 788 | Aug 1995 | EP |
6163163 | Jun 1994 | JP |
9-180886 | Oct 1996 | JP |
I148059 | Dec 1990 | TW |
I230912 | Apr 2005 | TW |
WO 2005084086 | Sep 2005 | WO |
Entry |
---|
International Search Report for PCT/US2005/005688, International Filing Date Feb. 23, 2005, 3 pages. |
Venture Lighting, Venture Technical Information, BALLASTS, ©2006 and Ballast Types ©2006 (6 pages). |
Venture Lighting International, Range of Metal Halide Maintenace, HID Systems Sourcebook, 2000, p. 143). |
Musco, “MULTI-WATT allows two light levels, reduce energy costs”, copyright 1992, 2002 Musco Lighting, (4 pages). |
English Abstract of JP 9180886, published Oct. 28, 1996 (1 page). |
English Translation of DE 19912517 A1, published Sep. 21, 2000 (8 pages). |
English Translation of DE 19540326 A1, published Apr. 30, 1997 (13 pages). |
English Abstract of JP 6163163 A, published Jun. 10, 1994 (1 page). |
English Abstract of DE 19912517 A1, published Sep. 21, 2000 (1 page). |
English Abstract of DE 19540326 A1, published Apr. 30, 1997 (1 page). |
English Abstract of EP 0669788, published Aug. 30, 1995 (1 page). |
English Abstract of WO 2005/084086, published Sep. 9, 2005 (1 page). |
English translation of Taiwan I230912, published Apr. 11, 2005 (23 pages). |
English translation of Taiwan 148059, date unknown (56 pages). |
Number | Date | Country | |
---|---|---|---|
Parent | 10785867 | Feb 2004 | US |
Child | 11559153 | US |
Number | Date | Country | |
---|---|---|---|
Parent | 13092664 | Apr 2011 | US |
Child | 13611534 | US | |
Parent | 11842808 | Aug 2007 | US |
Child | 13092664 | US |
Number | Date | Country | |
---|---|---|---|
Parent | 11559153 | Nov 2006 | US |
Child | 11842808 | US |