1. Technical Field
This invention relates to a heating/cooling system and, more particularly, to installation by unlicensed personnel of a pre-charged, ductless heating/cooling system.
2. Description of the Prior Art
Providing heat in the winter and cooling in the summer has been a concern to man since the earliest of recorded time. About one hundred years ago, electric energy came into common use as a means of providing air conditioning and heating. While initially air conditioning or heating was performed by separate devices, after a period of time, reverse cycling units were developed to provide heating, ventilation, and air conditioning, which systems were referred to as HVAC systems.
In a typical HVAC system, there is an indoor coil and an outdoor coil with an expansion valve and compressor located there between. A reversing valve is also included between the outdoor coil and the indoor coil so the system can be switched between cooling or heating. In the cooling cycle, the outdoor coil is the condenser and the indoor coil is the evaporator. In the heating cycle, the outdoor coil is the evaporator and the indoor coil is the condenser. Fans will move the air through both the indoor coil and the outdoor coil. If neither heating or cooling is necessary, the fan for the indoor unit can still provide air circulation within the enclosed space.
In a typical central HVAC unit, air is drawn through the indoor coil and flows into a duct system for delivery throughout the enclosed space. The ducts will have outlets that can be opened or closed as desired to provide the appropriate amount of conditioned air. The connection of the ducts from the indoor coil to the various rooms in the enclosed space to be heated or cooled has always required a lot of manpower and effort. In recent years, especially in countries having relaxed laws and regulations, there has been a trend to provide ductless HVAC systems. In the ductless systems, the refrigerant lines would run between the indoor and outdoor units, but there would not be ducts inside the conditioned space to deliver air from the indoor coil to the various rooms being conditioned. Instead, a fan would draw air through the indoor coil to be discharged directly into the room. If more than one room was to be conditioned, multiple indoor coils would be used. The multiple indoor coils could be connected in parallel so that each could act as an evaporator if cooling is necessary or a condenser if heating is necessary.
In the more developed countries that have codes and regulations covering how HVAC systems are to be wired and operated, electrical codes and regulations mandate the use of an electric disconnecting means for safety reasons. To put in the electrical connection requires a licensed electrician. Also, to charge an HVAC system with a refrigerant once it is installed requires another licensed individual. If a need for these licensed individuals can be eliminated while meeting necessary codes and regulations, then an HVAC system could be installed by unlicensed personnel.
It is an object of the present invention to provide a ductless HVAC system.
It is another object of the present invention to eliminate the need for licensed individuals when installing a ductless HVAC system.
It is another object of the present invention to provide a pre-packaged, pre-charged ductless HVAC system for installation by unlicensed personnel.
It is still another object of the present invention to provide a method and apparatus for connecting the outdoor unit of an HVAC system that would eliminate the need for licensed personnel but, instead, can be installed by unlicensed personnel.
A pre-packaged HVAC system is provided that has an outdoor unit complete with a mounting skid. The outdoor unit will include an outdoor coil, compressor and reversing valve. The outdoor unit will be pre-charged with a refrigerant and connects to a dual-refrigerant connector that is accessible under a covering box. Also under the covering box is a clamped-down male electrical connection. An electrical disconnect cover will clamp any connecting electrical cable in place. The electrical cable when clamped in place cannot accidentally fall down into water or any other substance to create a danger of electrocution of individuals working thereon.
The outdoor unit is shipped on a lightweight pad, which lightweight pad can then be used to mount the outdoor unit thereon outside of the conditioned space. The lightweight pad may rest directly on the ground or any other desired location by the user.
The inside unit has a mounting bracket that can be attached to the wall. The inside unit will have a cable sheath, which cable sheath will include inside thereof a pair of refrigerant lines and an electrical cable. A drainage line may or may not be included within the sheath, depending upon the desires of the end-user.
Typically, the indoor unit is mounted on the wall with a hole through the wall located immediately there behind. The mounting bracket is secured to the wall adjacent to the hole. The cable sheath is inserted through the hole and the indoor unit is secured to the mounting bracket. The pair of refrigerant lines would be connected to the dual-refrigerant connector on the outdoor unit. The electrical cable would be clamped down by the electrical disconnect cover. The female connector on the end of the electrical cable is connected to the male electrical connector inside of the electrical disconnect cover.
If filters have not already been inserted inside of the inside unit, filters are inserted. Thereafter, the inside unit is plugged in and turn ON, either with a switch thereon or with a remote control. The electrical connection from the inside unit connects through the electrical cable, the female connector, the male electrical connector to the outside unit. Because the electrical cable is clamped down by the electrical disconnect cover so that the electrical cable cannot fall into water or other fluids to cause electrocution or shock, and because the connection is contained within an electrical disconnect cover, the regulatory authorities will approve this unit acting as the factory installed disconnect.
The drain line may go all the way to the end of the cable sheath and drip any condensation on the ground, or the drain line could extend to any other location desired by the end user.
Referring now to
Within the outdoor unit 12, behind the grill 16 is located the outdoor coil. The outdoor unit 12 includes a compressor (not shown) and/or a reversing valve (not shown). On one end of the outdoor unit 12 is mounted an electrical disconnect cover 18 and dual-refrigerant connector 20. Dual-refrigerant connector 20 is held in position by mounting bracket 22. The dual-refrigerant connector 20 is contained inside of covering box 24. Covering box 24 is held in position by tabs (not shown) inserted into slots 26.
The system also includes a mounting bracket 28 that is attached to the inside wall wherever the inside unit 30 is mounted. Extending from the back of the inside unit 30 is a cable sheath 32. A hole is cut in the wall directly behind the inside unit 30 to allow the cable sheath 32 to extend there through. Extending from the lower end 34 of the cable sheath 32 is the electrical cable 36, dual refrigerant lines 38 and drain line 40. Drain line 40 may or may not be included within the cable sheath 32, but in this preferred embodiment, the drain line 40 extends to the lower end 34 of the cable sheath 32. On the end of the electrical cable 36 is a female locking connector 42.
Inside the enclosed space (not shown in
Referring now to
In operation, a fan (not shown) will draw air up through the inside unit 30, which air is conditioned (either heated or cooled) and discharged into the enclosed space through inside louvers 56. Likewise, a fan (not shown) will draw air through the grill 16 of the outside unit 12, which air will subsequently be discharged to the atmosphere.
Referring now to
The dual-refrigerant connector 20, which is held in position by mounting bracket 22 connects to the dual-refrigerant line 38 by quick refrigerant connector 60. By use of the quick refrigerant connector 60 with the locking lever 62, the dual-refrigerant connector 20 can be connected to the dual refrigerant lines 38, even though both are fully charged.
Referring now to
After the electrical disconnect cover 18 has been secured in position, electrical cable 36 is clamped by rubber grommet 66 and clamp 72 and the female locking connector 42 mated with the male locking connector 76, the lid 78 may be secured on the electrical disconnect cover 18 (see
Referring now to
While the preferred embodiment has shown the inside unit 30 to be mounted on the wall, the inside unit 30 could be anywhere that is convenient, including a stand-alone unit inside the enclosed space. The inside unit 30 could even be mounted in the ceiling. All that the unlicensed person would have to do to install the present system 10 is to cut a single hole of approximately 3 inches in diameter in the wall to extend the cable sheath there through. Immediately outside, the cable sheath can be clamped to the wall and connected to the outside unit. Since the outside unit 12 and inside unit 30 are both pre-charged, there is no need for refrigeration service personnel to come to charge the unit. Also because no electrical box is installed outside, no electrician is necessary to install the system 10. The only “construction” that would have to be done would be to cut the 3 inch hole in the wall for the cable sheath and mount the mounting bracket 28 on the wall 52. Thereafter, it is simply a matter of connecting the dual-refrigeration lines 38 and the electrical cable 36.
If the hole cut in the wall behind the inside unit 30 is too large, it may be weather-sealed with a rubber grommet there around or caulked with suitable caulking material.
While the present system 10 has been described as an HVAC system, it could be just air conditioning or just heating, depending upon the preference of the individual user.
Also, if the individual user desires to bring the drain line 40 out someway other than through the cable sheath 32, that also can be done. For example, the drain line could come straight out through the same hole as the cable sheath 32, but not be inside of cable sheath 32.
By use of the system as just described, a ductless HVAC system can be provided to as many indoor units 30 as are desired with indoor units 30 being located in different rooms. However, if indoor units 30 are connected in parallel, then a licensed refrigerant person might be necessary to recharge the system. However, for systems using a single indoor unit, recharging is not necessary.
Concerning the running of the cable sheath 32, the preferred embodiment shows the cable sheath 32 going through the wall 52 immediately behind the inside unit 30. The cable sheath 32 can go through the wall 52 at any desired location.