This invention relates to the safe and simple distribution of electrical power, from a portable or auxiliary generator, to specific circuits in a home or building during a power outage. This invention includes a means of easily connecting the portable/emergency generator to an auxiliary distribution box that is installed adjacent or close to the home's main circuit breaker—distribution panel. Programming, timing, control and protection are also included in this invention.
It is desirable, when living in an area that has frequent power outages, to have a means of portable emergency power. The distribution of this power can be confusing. First, safety is a concern, load distribution can be a problem, and “how and where to make a connection” can all be confusing to the homeowner. Also, the homeowner often drags multiple cords throughout the house to connect the desired appliances to the portable generator which can create a tripping hazard.
The main concerns when dealing with electricity is first of all safety. The primary issue deals with personal and personnel safety. The second issue is safety in preventing short circuits, overloads, property destruction, and possible fire hazards. Therefore, a safe but useable connection and distribution scheme has to be utilized.
The standard, typical setup in most American households and businesses is a dual single phase 220-240 vac system. Three wires, two hot and one neutral, enter the box from the utility company. The two “hot wires” measure 110-120 vac between each wire and neutral. The “neutral” becomes a reference. It is usually the white wire and is grounded to “earth ground” at or near the distribution box. Building codes now require an additional ground wire that is run to each receptacle, appliance, and light fixture. This provides another layer of protection and a means of utilizing ground fault protection, which will disconnect the circuit if a fault is detected. An auxiliary/emergency generator is compatible with these electrical requirements. This invention ties the generator to the existing distribution system.
A means is provided to connect a generator to an “auxiliary distribution box” that is permanently attached to the main distribution box in a home or building. The “auxiliary distribution box” contains circuit breakers, current and voltage sensing, a disconnect system utilizing relay contacts, and programmable controls to properly monitor and control the power distribution.
Some of the obstacles of utilizing portable generator systems have to do with extension cords and plugging in the various appliances that need to be energized. Another problem is how much load the generator can tolerate, and how many appliances can be run at the same time? For example, can the refrigerator and freezer be run at the same time? Can the heater or air conditioner be run? If these questions are answered before power outages, then an appropriate plan can be made and appropriate connections implemented. Using simple switches allows the user to make the appropriate connections and decisions for connections without dragging cords and creating an unsafe scenario. To complete the design, current sensing, relay contacts, circuit breaker switches, connection methods to the existing distribution, and programmable control features are described.
In the typical setup of most American households and businesses, the distribution panel is a dual single phase 220-240 vac system. Three wires enter the box from the utility company. Two wires are considered “hot” and measure 220-240 vac between them and the other is called “neutral”. The two “hot wires” also measure 110-120 vac between each wire and neutral. The “neutral” becomes a reference. It is usually the white wire and is grounded to “earth ground” at or near the distribution box. This is usually done by attaching it to a stake or pipe that is driven well into the earth. All 240 vac appliances operate from the two “hot” wires, and all 120 vac appliances operate from one “hot” wire to neutral. The 240 vac outputs typically go to stoves, ovens, hot water heaters, dryers, and air conditioning systems. The two 120 vac circuits are distributed to the remaining 120 vac lights, receptacles and appliances. There are many scenarios of circuits and distribution schemes, so this figure in no way represents any one particular method.
The generator is connected to the Auxiliary Distribution Box 300 via a built in plug 304. Since the generator will have built-in receptacles for connections, this plug will need to match the main generator receptacle that is capable of the full generator output. A first glance evaluation would seem to indicate that a receptacle, similar to that on the generator, would be the best choice for this application. Then a cord could be used that had plugs that would match both the generator and the Auxiliary Distribution Box. However, safety indicates that this scenario would allow the blades of the plug to be electrically “hot” if one end were plugged into the generator, and the other not plugged into the box. This would be unacceptable so conditions must be in place to insure that the plug is never “hot” when the blades are exposed. The Auxiliary Distribution Box can be set up and interlocked to maintain an open circuit until it is plugged in to a proper location. The sequence may require that the generator be up and running and the plug inserted into the generator, before the control would allow the relay contacts in the Auxiliary Distribution box to be closed.
The programmable controls permit the safety issues to be addressed. Voltage sensors 305 are installed in the Auxiliary Distribution Box to keep the relay contacts 303 open if voltage is not sensed on the Input Plug 304. Also, if the existing Distribution box is feeding electricity to the Auxiliary box, the voltage sensor 305 will detect this and the relay contacts 303 will open.
The relay contacts 303 maintain the required control of the system so that if any improper condition occurs, the contacts will open, preventing the systems from conflict. This control comes from the sensors 301, 305 and system programming controls 307. These controls may energize and de-energize one or more, or the entire relay coils 306 as conditions dictate. This in turn opens and closes one or more, or the entire relay contacts 303.
If an over-current is detected by the Current Sensors 302 on one of the circuits, the relay contacts 303 are designed to open. If improper voltage is sensed, the relay contacts 303 are designed to open. If any kind of fault is sensed by any of the sensors, the appropriate contact or all of the relay contacts 303 are designed to open.
The Auxiliary Distribution Box connects to the downstream side of individual circuits in the existing distribution box 402. The panel circuit breakers in the Existing Distribution Panel 402 that have these connections will be opened during the time auxiliary power is used. This prevents the auxiliary power from feeding back into the main circuit and energizing unneeded circuits. In all cases, any auxiliary power must not feed back to the utility input. This is a major safety hazard to utility workers. This means that the main breaker switch 403 must be open for any auxiliary or portable power generation.
The circuit breakers in the Auxiliary Distribution Box may be sized to match the capability of the generator. They will also have to not exceed the size of the existing circuit breakers they will temporarily replace. The connections shown in
The relay contacts in the Auxiliary Distribution Box 401 may be used to cycle the loads. This allows the Auxiliary Box 401 to be configured to match the capabilities of the auxiliary generator. For instance, the generator may not have the capacity to run both the refrigerator and freezer at the same time. So the refrigerator is first run for a period time. Then it is disconnected and the freezer is run for a period of time. This may be accomplished through the programming of the relay circuits to open and close the individual relay contacts. The relay contacts and the current sensing give a greater measure of control to the system. The current sensing detects the amount of current used, and whether it is in the range of the generator capabilities. The relay controls can be programmed to fit the capacity of the auxiliary generator used.
In one possible embodiment, the system is utilizing a 3 KW generator. The maximum current output would be about 25 amps. The generator has the capability of running either the refrigerator or the freezer, both of which use about 15 amps, but not both at the same time. It can also run a few lights or the TV along with the refrigerator or freezer. In
The power input plug from the generator to the Auxiliary Distribution Box is another variable factor. Most generators have built in plugs where inputs can be made.
Number | Date | Country | |
---|---|---|---|
61367060 | Jul 2010 | US |