This application relates to window construction, and in particular to an assembly construction made from fire rated glass and a fire rated surrounding framing system.
Architects and the public at large appreciate the aesthetics of glass and other light transmitting materials used in the built environment, both in interior spaces and for exterior uses. Light transmitting materials that serve both an aesthetic function as well as a structural function are appreciated for their economy and visual effects. A common means prescribed by architects to achieve these goals in building structures is through the use of glass “curtain wall” systems, either for exterior applications or for use in interior spaces.
Although some glass and frame technologies have been developed that are capable of passing applicable fire test and building code requirements, there is always a need to develop systems with improved fire resistance and smaller frame members for improved visual aesthetics.
In the following embodiments, fire-rated curtain wall or store front wall systems are provided. As described herein, the systems have unique and novel construction elements to maintain structural integrity while barring the transfer of heat beyond acceptable limits as per standards, including ASTM E119/UL263.
In one embodiment, a structurally-glazed curtain wall system comprises a first fire-rated glazing unit coupled to a second fire-rated glazing unit by a framing system. The framing system comprising a plurality of uninsulated vertical mullions with a roll-formed steel profile. The roll-formed steel profile can comprise a first wall portion and two projecting wall portions that extend from the first wall portion in a generally perpendicular manner.
In some embodiments, a silicone gasket system can be positioned between the framing system and the respective glazing units. In other embodiments, a vertical moment brace can be provided and the brace can be an all-bolted assembly between mullions, such that the moment brace is not welded to either mullion. A glass setting platform can be provided that is formed as a combination of horizontal and vertical connecting members. In some embodiments, intermediate anchors can be provided between vertical mullions. The plurality of vertical mullions can be spaced apart from one another to form a generally curved surface.
In other embodiments, a store front system can be provided that includes a plurality of uninsulated vertical mullions with a roll-formed steel profile, a plurality of uninsulated horizontal mullions with a roll-formed steel profile, and a plurality of fire-rated glazing units that are positioned between adjacent vertical and horizontal mullions. The roll-formed steel profile can form a first wall portion and two projecting wall portions that extend from the first wall portion in a generally perpendicular manner.
The systems provided herein can have insulated glazing units that meets fire barrier and thermal transfer limitations of ASTM-E-119 for a period duration of at least 45 minutes, 60 minutes, and/or 120 minutes.
The foregoing and other objects, features, and advantages of the disclosed embodiments will become more apparent from the following detailed description, which proceeds with reference to the accompanying figures.
The following description is exemplary in nature and is not intended to limit the scope, applicability, or configuration of the invention in any way. Various changes to the described embodiment may be made in the function and arrangement of the elements described herein without departing from the scope of the invention.
Although the operations of exemplary embodiments of the disclosed method may be described in a particular, sequential order for convenient presentation, it should be understood that disclosed embodiments can encompass an order of operations other than the particular, sequential order disclosed. For example, operations described sequentially may in some cases be rearranged or performed concurrently. Further, descriptions and disclosures provided in association with one particular embodiment are not limited to that embodiment, and may be applied to any embodiment disclosed.
Moreover, for the sake of simplicity, the attached figures may not show the various ways in which the disclosed system, method, and apparatus can be used in combination with other systems, methods, and apparatuses. However, those ways are readily discernable, based on this disclosure, by one of ordinary skill in the art. Additionally, the description sometimes uses terms such as “produce” and “provide” to describe the disclosed method. These terms are high-level abstractions of the actual operations that can be performed. The actual operations that correspond to these terms can vary depending on the particular implementation and are, based on this disclosure, readily discernible by one of ordinary skill in the art.
As used herein, the terms “curtain wall system” or “store front systems” or “framing system” refer to a generally non-structural use of transparent materials for either (1) exterior uses as an outer covering of a building or (2) interior uses as a space divider or for other purposes, such as fire safety.
The use of curtain wall and building design requirements are governed by applicable building codes. In the U.S., this generally means following the International Building Code (IBC) requirements as developed by the International Code Council (ICC). The IBC defines the parameters for building design by addressing items such as “General Building Height and Area Limitations,” “Structural Design,” “Means of Egress,” and “Fire Resistance Rated Construction.”
Chapter 7 of the International Building Code govern the materials and assemblies used for structural fire resistance and fire resistance rated construction to safeguard against the spread of fire within a building, or from one building to another. This chapter specifies the various types of fire rated construction required for different building types, in addition to what design allowances are provided for those fire rated areas. Further, the chapter prescribes what standardized tests materials must pass to be classified as “fire rated,” and therefore allowable for use in such areas as dictated by Code.
For fire resistance rated construction, these test standards commonly require the applicable building material to withstand fire exposure for a specified amount of time. This can include the resistance to passage of flame, smoke, and radiant and conductive heat from twenty minutes to several hours. In addition, these test standards commonly require the assembly be impacted by water sprayed from a two-man fire hose immediately after exposure to the fire. Such exposure is intended to provide a means of testing the materials resistance to the impact, erosion, and cooling effects of the water; and eliminates inadequate materials or constructions. The inability to pass such test standards generally prohibits their use in building areas required by the IBC to utilize fire rated materials.
Traditional curtain wall materials (e.g., those that include conventional glass, framing members, anchoring systems, and other accessories) are unable to pass the fire test standards described above, and therefore may not be considered as fire rated construction. The inability of typical curtain wall construction to meet these standards is due to numerous reasons. For example:
1. Framing members and window glass cannot withstand the high temperatures and pressures created by the fire tests.
2. Framing members and window glass cannot withstand the impact, erosion and cooling (thermal shock) of the mandatory ‘fire hose stream test’ prescribed in standards.
3. Framing members and window glass cannot provide the barrier to radiant and conductive heat transfer prescribed in standards.
The following embodiments illustrate glazed framing systems that meet applicable building code, including requirements for classification as a fire rated assembly.
The framing systems disclosed herein comprise frames with fire-rated glass (e.g., Pilkington Pyrostop® fire-rated glass) that provide a barrier to radiant and conductive heat transfer, allowing for unlimited areas of glazing in fire separations. In some embodiments, the frame comprises high strength steel sub-frame that is only 2 inches wide, yet has sufficient strength for tall spans, while the aluminum cover system provides a durable and flexible system with various anodizing and coating options. Such framing systems provide various features and advantages including:
Sizing guidelines for the system are set out below in Table 1:
In one embodiment, the framing systems can utilize Pilkington Pyrostop® fire-rated glazing options to complement the framing system. Pilkington Pyrostop® fire resistant glass offers up to 2 hour fire rating and up to a Level III bullet resistance rating. It can also be combined with other glazing products to achieve nearly any level of security protection. The framing systems described herein can be provided with 45 minute fire rated windows and 60 or 120 minute transparent glass wall applications. Wall applications are UL rated as per UL263/ASTM E-119 and allow for large expanses of glass and frame. 45 minute window systems are classified as an Opening Protective as per UL 9, ASTM E2010 with a maximum overall frame size of 144″×144.″
Table 2 below illustrates various fire rating designations for the systems disclosed in
The vertical mullions shown in
As shown in
Assembly of the framing systems described herein can be achieved without welding. For example, as shown in
When installing the framing system, parts marked with a “A” are to be installed on the interior side, while parts marked with a “B” are to be installed on the exterior side. Framing parts should be arranged so that vertical mullions with a spacer attached are to be installed at the jambs and the horizontal mullions with the spacer attached are to be installed at the head and sill.
In embodiments where the curtain wall systems is intended for exterior use, a structurally glazed curtain wall system can include an insulated glazing unit (i.e., a fire rated glazing unit) spaced apart and coupled to a glass unit.
In view of the many possible embodiments to which the principles of the disclosed invention may be applied, it should be recognized that the illustrated embodiments are only preferred examples of the invention and should not be taken as limiting the scope of the invention. Rather, the scope of the invention is defined by the following claims. We therefore claim as our invention all that comes within the scope and spirit of these claims.
This application claims the benefit of U.S. Provisional Application No. 61/709,097, which was filed on Oct. 2, 2012 and is incorporated herein by reference in its entirety.
Number | Name | Date | Kind |
---|---|---|---|
3082848 | Keller | Mar 1963 | A |
3321880 | Ferrell et al. | May 1967 | A |
4117640 | Vanderstar | Oct 1978 | A |
4141188 | Sukolics | Feb 1979 | A |
4418506 | Weber et al. | Dec 1983 | A |
4428171 | Harbin | Jan 1984 | A |
4750310 | Holcombe | Jun 1988 | A |
4996809 | Beard | Mar 1991 | A |
5036637 | Biebuyck | Aug 1991 | A |
5067293 | Reynolds | Nov 1991 | A |
5481839 | Lang et al. | Jan 1996 | A |
5592795 | Rinehart et al. | Jan 1997 | A |
5601888 | Fowler | Feb 1997 | A |
6141923 | Habicht et al. | Nov 2000 | A |
6550196 | Braybrook | Apr 2003 | B2 |
6857233 | Farag | Feb 2005 | B2 |
7594364 | Rinehart et al. | Sep 2009 | B2 |
8567142 | Swartz | Oct 2013 | B2 |
20120066991 | Swartz | Mar 2012 | A1 |
Number | Date | Country |
---|---|---|
2011-236628 | Nov 2011 | JP |
Entry |
---|
International Search Report for PCT/US2013/063011, mailed Jan. 21, 2014, by the ISA/KR: Korean Intellectual Property Office. |
Written Opinion for PCT/US2013/063011, mailed Jan. 21, 2014, by the ISA/KR: Korean Intellectual Property Office. |
Number | Date | Country | |
---|---|---|---|
20140090319 A1 | Apr 2014 | US |
Number | Date | Country | |
---|---|---|---|
61709097 | Oct 2012 | US |