The present invention relates to a battery energy storage system (BESS) high-level energy management method.
Previous studies have utilized droop control to achieve other objectives. This subsection highlights these studies.
Droop control is a common method for energy management in AC microgrids since data can be communicated by signals that are locally measurable. In a study, Engler notes that, if the inverters set their instantaneous active and reactive power, then droop can be utilized to provide power control [1]. Specifically, Engler relates active and reactive power to inverter output frequency and voltage and compares both pairings (P/f, Q/V & P/V, Q/f). This is visually explained in
Sao utilized the conventional droop discussed previously to conduct load sharing for multiple VSCs [2]. Conceptually, grids have a bus that is common among all connected components, which can be used as a communication signal. By utilizing this potential communication signal, autonomous methods such as load sharing can be provided to a system.
For a system such as
To balance reactive power, Sao proposes altering the reference bus voltage for individual VSCs. This is done through the relationship between reactive power and the difference in magnitude between the VSC and the common bus, which is expressed by (2). By adjusting the reference VSC voltage, the common bus voltage adjusts until the reactive power is balanced.
Turbine generators' power and frequency have a similar relationship to that of the droop characteristic. Specially, they experience a linear frequency change that is related to the system load and its own rating. Given an external power reference demand, the relationship between mechanical power and generator frequency is provided by (3) [3]. Note that R is a constant that is based on the turbine parameters.
If two generators are interconnected to supply a load and their characteristics are different, a power imbalance is introduced. This is due to the interconnection of the two turbines forcing the frequency to match. For this system, Pref is the power reference setting that the user provides based on the load demand. Since the power reference (Pref) is externally defined, it can be altered to change the power provided to the load while maintaining a desired system frequency. This is illustrated in
To maintain the desired frequency, Kundur proposes utilizing an integral control to adjust Pref [4]. This is provided by (4).
Where:
Δw=wref−wmeas (5)
This is also commonly referred to frequency restoration since, over time, it maintains a specific frequency irrespective of load. Since the curve produced by the turbine matches a typical droop characteristic, this concept provides some guidance to DC microgrid power sharing.
Akagi utilized droop control to provide power sharing in a DC microgrid [5]. Akagi's system consisted of a battery energy storage system (BESS) and a grid-tied inverter to reliably provide power to the microgrid. In his paper, Akagi proposes a piecewise linear function to relate the microgrid's bus voltage to the output current of each supply. This is illustrated in
At low current demands, the energy storage unit supplies more power than the inverter to increase microgrid independence. At high current demands, however, the inverter begins to supply more power since the energy storage unit is approaching its rated limit. In conclusion, Akagi defines the droop characteristic with different slopes to alter power demand from individual units.
The present invention proposes an energy management method that utilizes DC voltage signaling to provide indirect communication between local controllers, to provide battery state-of-charge balancing, overcharge protection and undercharge that incorporates variable battery and generation source current limiters. Furthermore, this method is capable of providing offset correction to account for several factors such as, but not limited to, sensor errors, line losses and battery cost optimization.
Figures and embodiments will be described, by way of example, with reference to the accompanying drawings, in which:
The embodiments discussed herein are merely illustrative of specific manners in which to make and use the invention and are not to be interpreted as limiting the scope.
While the invention has been described with a certain degree of particularity, it is to be noted that many modifications may be made in the details of the invention's construction and the arrangement of its components without departing from the scope of this disclosure. It is understood that the invention is not limited to the embodiments set forth herein for purposes of exemplification.
The effects of greenhouse gases (GHG) have generated an interest in DC microgrid research due to its ability to integrate renewable energy sources and provide storage to existing grid infrastructure. Larger systems typically have multiple energy storage mediums and generation sources integrated into the microgrid. Such systems require an energy management method to ensure proper functionality under all conditions.
For microgrid systems, energy management includes:
Past studies have used supervisory-level controllers to detect and correct these scenarios [6]-[7]. This requires direct communication between multiple local controllers and the supervisory control, which introduces time delays and additional communication equipment to provide functionality. These limitations can be overcome with an autonomous energy management method that requires no fast acting communication between local controllers.
One such method is to utilize droop control to modify the microgrid bus voltage. This method allows local controllers to determine the state of the system without direct communication. The general formulation of the curve is:
Vbusref=Cbusnom−Kd
Where:
Vbusref—Bus Voltage Reference for Local Controller
Vbusnom—Nominal Bus Voltage
Kd—Virtual Resistance
iout—Converter Output Current
By adjusting the parameters of the droop curve then defining specific voltage ranges to represent system states, energy management can be conducted. Previous studies have utilized this method [8]-[12]. However, the existing studies are not capable of providing all the energy management functions listed previously. Additionally, altering the virtual resistance (Kd) affects the eigenvalues of the system, which introduces potential stability issues and limit system scalability. Therefore, a method to indirectly handle all energy management requirements while reducing the effect on stability has the potential to be implemented on all DC microgrid systems.
Energy Management Method
This section outlines the energy management method that provides the requirements discussed, which are:
The general control scheme for the energy management method is provided in
Conceptually, the method utilizes the droop characteristic set by the BESS. Specifically, the V-I curve of the droop characteristic's y-intercept becomes a function of SOC. The slope of the droop characteristic will remain unchanged to prevent eigenvalues from changing based on the SOC. This is illustrated in
The main advantage of this design is that there is no direct communication required between converters to implement energy management amongst the batteries. Instead, each converter measures the bus voltage to interpret the state of the system. This allows the local controllers to adjust without the need to wait for information from a system supervisory control. Therefore, this method offers a cost-effective method to implement an indirect-communication energy management that responds quickly and has reduced effect on stability.
Droop Curve Per-Unitization
To discuss the details of the energy management method, it is beneficial to define the droop curve of each converter on a normalized per-unit basis. The droop curve is defined by (7).
Vref=Vnom−KdIout (7)
Both the voltage and current can be defined in per-unit by (8) and (9).
By substituting (8) and (9) into (7), the per-unit equation of the droop curve is described by (10).
VrefpuVbase=VnompuVbase−KdIoutpuIbase (10)
From here, the goal is to define the droop curve's slope in per-unit. This can be done by dividing both sides of (10) by Vbase. In doing so, the droop curve slope (Kdpu) is defined by (11).
Therefore, the new per-unit droop characteristic is defined by (12). Each converter has its own unique base values, Vbase and Ibase, which are determined by the power rating of the associated converter. For the sake of simplicity, assume that each converter has the same base voltage and current.
Vrefpu=Vnompu−KdpuIoutpu (12)
For the example system, the base values for the converter are given in Table II.
Droop Curve Adjustment
This subsection will discuss how the droop curve is adjusted to provide state-of-charge (SOC) balancing of the BESS, overcharge protection (OCP) and load shedding. For ease of understanding, the adjustment curve is provided first, then how it provides each requirement in the energy management system is discussed individually.
The nominal voltage of the droop curve (Vnompu) is a non-linear adjustment based on the SOC of the local BESS. This is illustrated by
The droop characteristic used in the example system is outlined in Table III. Note that the 5% droop slope is based off the NERC BAL-001-TRE-1 standard [13], which is used for AC power systems. Using these values, the droop curve for various SOCs take on the form shown in
As expected, there is a significant rise between SOC=80% and SOC=100%. Suppose that these three curves represented three unique BESS in the system. Assuming no line losses, all BESSs have the same output voltage during steady-state operation. This phenomenon results in SOC balancing. To further illustrate this,
The aggregate curve in
Since there is no load on the system, the output current of BESS 1 is providing rated power to BESS 3, while BESS 2 outputs no current, resulting in no net output current (no load). This continues until SOC1=SOC2=SOC3. At that point, all BESS droop curves are identical and SOC balancing is achieved.
There are two important ramifications to observe at this point:
These introduce a risk, since the system is rated to handle a maximum bus voltage here of 1.1 [pu]. Additionally, since the BESS can still receive rated power at high SOC, the batteries could potentially be overcharged and permanently damaged. At high SOC, many batteries cannot be charged with a constant current. Therefore, an overcharge protection (OCP) method is needed to ensure the safety of the BESS.
This protection can be provided via a generation source limiter. The goal of the OCP scheme is to steadily reduce the maximum output power of the sources until all battery's SOCs are at 100%. Once this is achieved, the generation sources halt power production until a load demand occurs. This is illustrated by
An observation can be made that, if all the BESS are below SOC=80%, then the renewable source's maximum permissible power (or current) will always remain at its rated value. On the other hand, if any of the BESS exceed 80%, then maximum permissible power can potentially decrease depending on the system load. Therefore, the region between 1.05<Vbusref<1.1 can be defined as the OCP region.
Another observation is that, if all the BESS are fully charged and a load is introduced, the maximum power that the renewable generation source can provide is increased. Therefore, if the BESSs are discharging, the renewable generation source attempts to provide a portion of the load demand depending on the loading conditions of the system.
The final requirement is system load shedding. If the loads demand power that exceeds the BESS and renewable generation source's capabilities, the system bus voltage collapses. However, the energy management method is capable of preventing this. The acceptable bus voltage operating range is here assumed to be 0.9<Vbus<1.1. Therefore, if a load occurs beyond the system's capabilities, the bus voltage reduces below 0.9 pu. When this occurs for a time scale that exceeds normal transient times, selected loads are tripped off-line based on a priority basis, consistent with standard practice in AC power systems, until the load is under the system's power rating. Using this method, load shedding can be achieved. Therefore, this energy management method is capable of providing all requirements mentioned at the beginning of the chapter.
Incorporation of BESS Current Limits
The above sections describe energy management under the assumption that the BESS can always supply current up to a fixed maximum and minimum current level (I+max and I−max). In practice, the BESS contains its own battery management system (BMS) which has authority to impose output current limits. This is readily accommodated by allowing the battery EMS to reduce I+max and/or I−max from its nominal values. When the BESS becomes fully depleted at 0% SOC, its EMS will demand a reduction in output current to zero to provide undercharge protection (UCP).
This scenario is graphically depicted in
It is important to note that the large state of charge difference depicted in
Observe that each BESS continues to define its own droop curve based on the local battery SOC and BMS current limit signals. Since this data is available locally, the energy management method continues to maintain autonomy during operation without reliance on communication of remote data.
Supervisory controls for system optimization and economic dispatch of the batteries or other non-critical functions may be readily added. However, full functionality is maintained even in absence of communication-based supervisory controls.
Test Scenario 1
To validate the energy management method, the system was simulated using PSCAD™. The system consists of two BESSs, two solar PV arrays and one VSC, which is depicted in
The system parameters for this system are provided in Table V and use the base values in Table II. The initial conditions for the system are outlined in Table VI. It should be noted that a disproportionately small BESS capacity, Q, is employed for simulations to depict change/discharge behaviour over an accelerated time frame.
The simulation results are provided in
Test Scenario 2
To further demonstrate the energy management method, a scenario was created to demonstrate the current distribution of the BESS with different SOCs. The initial SOCs are outlined in Table VII and the load demand during each time interval is highlighted in Table VIII. These results are highlighted in
In physically implemented systems, offsetting the bus voltage can offer many advantages (i.e. sensor error correction, line loss compensation, BESS cost optimization). For the energy management system, mismatches in the measured and actual bus voltage can reduce the effectiveness. For example, by referring to
Conceptually, the goal of the correction method is to record the bus voltage (Vbus) measurement from all converters to calculate a statistical average. This can be done using a monitoring system with very limited or even intermittent communication bandwidth, as this action only compensates nearly static sensor offsets without closed-loop control. The difference between this average and the voltage measured by each converter is then determined and added onto the measurement as an offset. By utilizing this method, the objective is to ensure all BESSs and generation sources are measuring an identical bus voltage, where the energy management method uses this measurement as a non-critical communication signal. This offset only requires an infrequent update (˜1-24 hrs), meaning that the energy management method still maintains its autonomy, and any loss of communication merely results in somewhat suboptimal SOC balancing.
The calculation for the statistical average is provided by (14).
Where:
VbusBi—The bus voltage measured by the i-th BESS
VbusSi—The bus voltage measured by the i-th generation source
n—The total number of BESSs
m—The bus voltage measured by the i-th BESS
The average bus voltage,
With this correction, all controllers see an identical bus voltage that is, on average, a more accurate measurement. This means that each local controller interprets the state of the system the same, which improves the functionality of the energy management method. This offset calculation can also be expanded to incorporate other calculations, such as line losses or BESS cost optimization, which maximizes the utilization of the offset correction in the local controller.
The energy management method provides SOC balancing, OCP, UCP and load shedding for a DC microgrid system using indirect communication between local controllers, which increases response time and reduces communication infrastructure costs. The combined SOC balancing/OCP/UCP method yields a net microgrid bus voltage that decrease in a piecewise linear manner with DC microgrid loading. Keeping the virtual resistance (Kd) unchanged during operation reduces eigenvalue movement, which implies that the energy management method has minimal influence on system stability. Finally, the offset correction provides a method to overcome practical limitations/optimizations of such systems. Therefore, the energy management method is applicable to all DC microgrid systems, regardless of power capacity, number of BESSs, generation sources or loads.
This application claims the benefit of U.S. Provisional Patent Application Ser. No. 62/519,918, filed Jun. 15, 2017 and entitled AUTONOMOUS ENERGY MANAGEMENT METHOD FOR DC MICROGRID SYSTEMS.
Entry |
---|
Bhavsar, Yogesh S. et al., “Energy Management in DC Microgrid”; 2015 International Conference on Energy Systems and Applications (ICESA-2015); pp. 209-213, (978-1-4673-6817-9/15/$31.00 2015 IEEE). |
Alfred Engler, Nikos Soultanis, “Droop Control in LV-Grids”, pp. 1-3. |
Rui Hu and Wayne W. Weaver, “DC Microgrid Droop Control Based on Battery State of Charge Balancing”, (978-1-5090-0261-0/16/$31.00 2016 IEEE). |
Youichi Ito et al.; “DC Micro-grid Based Distribution Power Generation System”, pp. 1740-1745. |
Hyun-Jun Kim et al., “Operation Analysis of Stand-alone DC Micro-grid with Coordinated Droop Control”, pp. 692-698, (978-1-4799-0482-2/13/$31.00 2013 IEEE). |
Sneha Mane, et al., “Optimal Load Balancing Strategy for Hybrid Energy Management System in DC Microgrid with PV, Fuel Cell and Battery Storage”, 5th International Conference on Renewable Energy Research an Applications, Nov. 20-23, 2016, Birmingham, UK, ICRERA 2016, pp. 851-856. |
Wayne Panboa, et al., “An Autonomous Control Scheme for DC Micro-Grid System”, pp. 1519-1523, (978-1-4799-0224-8/8/13/$31 2013 IEEE). |
Gaurav Pandey, et al., “Protection and Energy Management of Zero Net Electric Energy Clusters of Buildings”, (978-1-4673-8597-8/15/$31.00 2015 IEEE). |
Charles K. Sao, et al., “Autonomous Load Sharing of Voltage Source Converters”, IEEE Transactions on Power Delivery, vol. 20, No. 2, Apr. 2005, pp. 1009-1016 (0885-8977/$20.00 2005 IEEE). |
Bernd Wunder, et al., “Voltage Control and Stabilization of Distributed and Centralized DC Micro Grids”, PCIM Europe 2015, May 19-21, 2015 Nuremberg, Germany, pp. 660-667 (ISBN 978-3-8007-3924-0). |
J. Duncan Glover, et al.; “Power System Analysis and Design”, Fourth Edition, 2008. |
Hydro One Networks Inc.; In the Matter of an Application for Electricity Distribution Rates 2006, Decision with Reasons Apr. 12, 20016, Ontario Energy Board, RP-2005-0020, EB-2005-0378. |
BAL-001-TRE:1—Primary Frequency Response in the ERCOT Region, pp. 1-49. |
Prabha Kundur, “Power System Stability and Control”, Electric Power Research Institute, Power System Engineering Series, 1994. |
Number | Date | Country | |
---|---|---|---|
20180366948 A1 | Dec 2018 | US |
Number | Date | Country | |
---|---|---|---|
62519918 | Jun 2017 | US |