This invention relates to cables for downhole use, particularly the disposition of cables for powering tools.
Coiled tubing is often used to suspend downhole tools in a well bore. The coiled tubing is stiff enough to apply a generally downward force to the tool if necessary, to push the tool vertically or horizontally along the well, and has sufficient strength to pull the tool from the well. Coiled tubing also allows the tools to be conveniently deployed in the well without having to kill the well, and provides a protected environment for power cables with which to power the tool.
To support the electrical cable in the coiled tubing, coiled tubing may be supplied with anchor devices to frictionally support the cable at intervals. Further methods include providing dimples on the inner surface of the coiled tubing to support the electric cable, and filling the coiled tubing with a dense liquid so that the electric cable supported by some degree of buoyancy.
Further, many wells have high temperatures, for example a Steam-assisted gravity driven (SAGD) well may approach 250° C. Any solution should be able to withstand such high temperatures for extended periods.
The object of the present invention is provide an alternative method of deploying cable in coiled tubing that is more convenient and economic to install.
According to the present invention, there is provided cable and coiled tubing for suspending an electrically powered tool in a borehole and providing the tool with electrical power by the cable, the cable being disposed in the coiled tubing, the cable incorporating a conducting member which carries the majority of the tensile stress on the cable, and without the cable being secured along its length to the inside of the coiled tubing.
According to another aspect of the present invention, there is provided cable for use in a borehole or the like for supplying high voltage electrical power, wherein the cable comprising:
a conducting member having a steel core, an outer cladding of copper, and at least one insulating layer surrounding the outer cladding of copper,
the copper making up between 20% and 40% of the total copper and steel content of the cable, the cable being able to support at least its own weight.
The coiled tubing and power cable have very similar coefficients of thermal expansion, so when exposed to high temperatures limited differential stress is applied to the electrical insulation.
According to a further aspect of the present invention there is provided a cable termination member adapted for a cable as herein defined, including a gripping element for attaching to the steel core of the cable, and a conductive element for conductively abutting to the outer cladding of copper.
The invention will now be described, by way of example, with reference to the following drawing, of which
Referring to
Steel conductors are less conductive than copper, but have a much higher tensile strength. The recommended cable size for 104 Amps in pure copper is AWG #3 gauge or 5.827 mm OD. To achieve the same heat flux with Copper Clad wire of 40% conductivity, an AWG #0 or 8.252 mm OD is required. To accommodate the deployment of the cable, a standard coil tubing size was selected. A 1.75 foot (0.53 m) OD coiled tube with a 0.109 foot (0.03 m) thickness was selected.
Such a cable made of steel conductors is sufficiently strong to support itself over a borehole depth of many 1,000s of feet. The cable therefore does not need to be anchored or secured to the inner surface of the coiled tubing. In addition, since coiled tubing is typically manufactured from steel, the conductors of the cable and the coiled tubing will expand at the same rate as the temperature of the well increases. The insulating material described all performs well under increased temperature.
Referring to
Referring to the
The steel core provides the cable with sufficient strength to support the cables own weight at the type of lengths necessary (600 metres and more) to provide power to tools in a downhole environment. The steel core also conducts electricity, but is not as conductive as the copper cladding, which carries most of the current. It has been found that when the copper cladding makes up over 20% of the total metal content by weight of the cable, the cable is able to carry a high voltage over the necessary lengths. However, when the weight of the copper cladding makes up over 40% of the total metal content by weight of the cable, although the conductivity of the cable is improved, the cable is not sufficiently strong to support its own weight. Therefore, the optimum copper content of the total metal content by weight of the cable is between 20% and 40%. Particularly at the lower percentages of copper, the cable may be sufficiently strong to also support a load, such as a motor and/or pump suspended from the cable.
Referring now to
An upwardly-pointing male pin 18 has a copper spacer skirt 57, which slides over both the gripping segments 4 and bowl 5, and the copper spacer 6, to fight tightly against the copper spacer 6. The upper end of the male pin 18 has an insulation member 9 with seal 19 fitted over it.
Referring to
A seal 39 around each of the cables has a series of ridges facing the direction of pressure, to distribute the compression force on the cable insulation 3.
At the upper termination, individual female connectors 58 plug onto the male pins 18. The female connectors 58 consist of a copper attachment 54 which terminates the cable and allows a tight electrical contact to the male pin 18. An insulation bushing 55 fits over the connector 54 and a rubber boot 41 fits tightly over the bushing 55. When fitted over the male pin 18, matching profiles 24 on the inner surface of the boot 41 and the insulated member 9 seals the boot 41 and the insulated member 9.
Number | Date | Country | Kind |
---|---|---|---|
0823225.8 | Dec 2008 | GB | national |
Filing Document | Filing Date | Country | Kind | 371c Date |
---|---|---|---|---|
PCT/GB09/51535 | 11/13/2009 | WO | 00 | 7/13/2011 |