Clean room and method

Abstract
A clean room which uses a perforated floor upon which equipment can be directly placed is presented. The perforated floor includes a regular array of openings through which air can pass to an underlying facility room. The openings are covered by a grate through which the air can pass. In combination the perforated floor and the grates are able to support equipment in any location thereon.
Description




BACKGROUND OF THE INVENTION




This invention relates generally to a clean room, and more specifically to a floor for a clean room and to a method for establishing a clean room.




Clean rooms are used extensively in the electronics industry and in other industries in which a clean, particle free environment is necessary during the fabrication or testing of a product. Clean rooms are rated by the number of particles of a given standard size that are detected in a standard volume of air within the clean room. According to this rating system a “Class 10” clean room has only one-tenth the particle count of a “Class 100” clean room. Similarly, a “Class 1” clean room has only one-tenth the particle count of a “Class 10” clean room. The low particle count in a clean room is achieved by a large number of distributed air changes in the room. Air flows through the room, usually in a laminar fashion and usually downwardly from the ceiling to the floor or to vents located near the floor. The air changes wash the particulate matter from the room. Other things being equal, the greater the number of air changes, the lower the particle count in the room. For example, a “Class 1” clean room usually requires more than 450 air changes per hour.




Typically the air in a clean room enters the room through filters located in the ceiling, passes through the room, washing over the contents of the room, and exits the room through openings or vents in a raised clean room floor to a plenum formed between the raised floor and the structural floor of the building. The air is then recirculated and again passes through the ceiling filters and into the room.




Prior art clean rooms have all used a raised clean room floor. The raised and usually perforated clean room floor is supported on a pedestal or plurality of pedestals. The pedestals are usually specially constructed structures designed specifically for the equipment that is to be placed on the raised floor. The raised floor itself is inadequate to support the weight of the equipment. The necessary pedestal is often very expensive, sometimes having a cost equaling a large percentage of the total equipment cost. The raised floor is necessary to form the return air plenum and to provide a way to facilitate the equipment. Power lines, chemical lines, exhausts, drains, and the like pass through the raised floor and run under the raised floor to a facilities area. In addition, another reason for the widespread use of raised clean room floors, it is the desire, and often necessity, of suppressing vibrations caused by the equipment located in the clean room. Much of the processing that is done in the clean room requires a vibration free environment as well as a particle free environment. The raised floor and the platform upon which the raised floor is supported dampen vibrations that otherwise might be propagated by the underlying structural floor. A concrete slab floor has not been found satisfactory for a clean room environment because the slab tends to be a conduit for vibration.




In addition to the expense of the customized pedestal that must be used to support a raised clean room floor, there are a number of other significant drawbacks to such a floor. Because the raised floor, by itself, is unable to support the weight of equipment that might be placed in the clean room, the raised floor also cannot support the weight of that equipment as it is moved into a clean room. This results in the necessity for disassembling the raised floor when equipment is moved into a clean room or is moved about the clean room. The floor is disassembled, equipment is moved into the clean room, placed on the portion of the raised floor in substantially its final location, and then the remaining portion of the raised floor is reassembled. This activity compromises the cleanliness of the clean room every time a piece of equipment is moved into or is moved about the clean room. In addition, any facilities lines that would be located under the portion of the raised floor that has to be removed will also be disturbed by the moving of equipment. Because of these difficulties, it is commonplace to build relatively small or compartmentalized clean rooms so that only a small area is contaminated by any moving process. This, of course, leads to disadvantages in terms of material flow because materials being processed must be moved into and out of these individual compartmentalized clean rooms.




In view of these and other problems with conventional clean room designs, it has been recognized that a need exists for a clean room that is less expensive than a raised floor clean room. There is also a need for a clean room that allows for non-intrusive clean room practices for facilitizing equipment located in the clean room. The need also exists for a clean room that does not require an expensive and customized pedestal for equipment, but rather allows the placement of equipment anywhere within a clean room. There is also a need for a clean room into which equipment can be moved and relocated without compromising the integrity of the clean room. A need also exists for a clean room that can be large in area and arbitrarily expandable in area.




BRIEF SUMMARY OF THE INVENTION




In accordance with one embodiment of the invention, a clean room is provided having a bearing floor capable of supporting equipment in any location thereon. The bearing floor is positioned over a facilities room which, in effect, is an extension of the clean room. The bearing floor has a regular array of openings through the floor which permit air to flow from the clean room into the underlying facilities room. A wall structure is positioned on the bearing floor to surround a selected area of the bearing floor. A ceiling having a plurality of filtered air inlets is provided above the bearing floor and in contact with the top of the wall structure. A plurality of grates are positioned in those floor openings of the regular array that are located within the selected area bounded by the walls and solid, air impervious members are positioned in those floor openings of the regular array that are located outside the selected area. By changing air impervious members for grates, or vice versa, the area of the clean room can be expanded or reduced. Preferably the location and number of filtered air inlets is also adjusted to correspond to the number of grated openings in the clean room floor.




BRIEF DESCRIPTION OF THE DRAWINGS





FIG. 1

illustrates, in plan view, a perforated clean room floor in accordance with one embodiment of the invention;





FIG. 2

illustrates, in cross-section, a clean room floor in accordance with the invention;





FIG. 3

illustrates, in cross-section, a portion of a clean room facility;





FIGS. 4 and 5

illustrate a grate and its method for installation in a perforated floor in accordance with one embodiment of the invention;





FIG. 6

illustrates schematically, in cross-section, a clean room facility in accordance with the invention;





FIG. 7

illustrates a facilities line extending between clean room equipment and facilities equipment.











DETAILED DESCRIPTION OF PREFERRED EMBODIMENTS





FIG. 1

illustrates, in plan view a floor


20


for a clean room in accordance with the invention.

FIG. 2

illustrates a cross-section taken through the floor


20


, as indicated, and

FIG. 3

illustrates a further cross-section through floor


20


and the substructure, as indicated.




In accordance with one embodiment of the invention, as illustrated in

FIGS. 1-3

, the floor


20


is a poured in place concrete floor having a plurality of openings


22


extending through the thickness of the floor. Preferably the plurality of openings


22


are arranged in a regular array. The openings can be, for example, square openings having a side dimension of two feet with a spacing of two feet between openings. As will be explained below, each of the openings has a cover


24


inserted therein with the top of the cover co-planar with the top of the solid floor. The cover consists of either a grate or an air impermeable cover, depending upon the location within the clean room floor. Floor


20


is constructed overlying a room


30


. Preferably room


30


is a below grade basement. Room


30


can be used advantageously to house facilities to be used by the equipment employed in the clean room. Accordingly, room


30


will be referred to herein as a facility room. Room


30


includes, as illustrated in

FIG. 3

, bearing side walls


32


and a supporting concrete floor


34


. A plurality of support pillars


36


extend upwardly from the concrete slab floor


34


. A plurality of beams


38


span the facility room


30


and are supported by the plurality of columns


36


. The support beams


38


, in turn, support the perforated clean room floor


20


. The facility room floor


34


, walls


32


, support pillars


36


, beams


38


, and floor


20


are preferably constructed of reinforced concrete. The composition of the concrete and the size and amount of rebar used for reinforcing are determined in accordance with standard structural calculations to support the weight of the equipment intended to be used in the clean room. Sound engineering practice, of course, dictates that the structure be overdesigned to support a weight much greater than that actually intended to be used in the clean room.




A preferred grate structure


50


to be used as one of the covers


24


inserted in an opening


22


in a clean room floor is illustrated in FIG.


4


.

FIG. 5

illustrates how that grate is held in place within the floor


20


. Grate


50


includes a mesh top


52


and an apron


54


extending downwardly from at least two of the sides of the mesh top. Slots


56


are provided in the apron to allow adjustable attachment of the grate within opening


22


as will be explained below. The grates can be made of any suitable, structurally sound material. Preferably the grates are made of a metal such as stainless steel. The mesh top is designed to provide the free flow of air therethrough and simultaneously to provide structural strength. In accordance with one embodiment of the invention, the mesh top is fabricated from stainless steel and has openings of about 1 inch by 4 inches. The mesh top can be about 1½-2 inches in height and the apron is preferably about 4-5 inches in height.





FIG. 5

, which illustrates a portion of floor


20


in cross-section, depicts a preferred method for attaching the grates within the openings


22


. During the pouring of concrete floor


20


, ferrule loops


60


are embedded in the solid portion


21


of floor


20


. Preferably four ferrule loops are embedded in the walls of each of the openings


22


, two each on opposing sides of the opening. The ferrule loops are positioned to align with slots


56


in the grates. A ferrule loop is used because the loop portion provides a good anchoring mechanism within the concrete material. The end of the ferrule loop extending out from the concrete is threaded to receive a bolt


62


. The grate is placed in the opening so that the slots


56


in apron


54


are positioned over the threaded ends of ferrule loops


60


. Bolts


62


are threaded onto the ferrule loops, the height of the grate is adjusted to be substantially co-planar with the surface of the concrete


21


, and the bolts are tightened to hold the aprons and therefore, the grates securely in this aligned position.




The clean room facility, in accordance with the invention, is further illustrated schematically in FIG.


6


. In this illustration the clean room facility is illustrated along a vertical cross-section. The clean room facility includes facility room


30


as previously described. Overlying the facility room is a perforated floor


20


. Vertical walls


70


surround an area of the perforated floor


20


. The area of the perforated floor surrounded by walls


70


may encompass all of the perforated floor or, alternatively, a portion of the floor, leaving a second portion of the floor external to the walls


70


. A ceiling


80


overlies perforated floor


20


including the portion of the perforated floor that is enclosed by walls


70


. An airtight seal is made between the walls


70


and the ceiling


80


and also between the walls


70


and the perforated floor


20


. Walls


70


, a portion of ceiling


80


, and a portion of perforated floor


20


thus enclose a volume constituting the clean room


90


. Ceiling


80


includes a plurality of filtered air inlets


82


. The filtered air inlets


82


have a greater density over the clean room


90


than they do over the area outside walls


70


. In addition, the openings


22


which extend through floor


20


and which are located within the area bounded by walls


70


are covered by grates


50


. The majority of the openings


22


through the floor


20


which are located outside the clean room


90


are covered by an air impervious cover


53


.




Air circulation through the clean room facility is also illustrated in FIG.


6


. Air enters clean room


90


through the filtered air inlets


82


as illustrated by arrows


84


. The filtered air passes through clean room


90


and is exhausted into facility room


30


through the openings


22


in perforated floor


20


as illustrated by the arrows


86


. Air is then exhausted from facility room


30


through an air plenum


88


. A blower


92


conveys the air to a further plenum


94


which overlies ceiling


80


. The air is then again filtered and forced through filtered air inlets


82


. In this manner repeated air changes within clean room


90


“wash” particulate matter from the clean room. The number of air changes in clean room


90


is a function of the speed with which the air is circulated by blower


92


, by the number of air inlets


82


, and by the number of openings


22


through which the air can be exhausted into facility room


30


. Because of the lower density of filtered air inlets in the region outside of walls


70


and because of the smaller number of openings


22


through which air can be exhausted, the particle count outside of clean room


90


will be greater than the particle count within the clean room.




The concept illustrated in

FIG. 6

has a very important advantage over prior art clean rooms. A relatively large perforated floor


20


can be initially constructed over a relatively large facility room


30


. Thereafter temporary walls


70


can be constructed on floor


20


to construct a clean room of any desired size up to and including a clean room encompassing all of floor


20


. To change the size of clean room


90


requires only that the walls


70


be moved, the coverings on openings


22


be changed from air impervious to grates or vice versa, and the ceiling tiles be changed to increase or decrease the area of high density filtered air inlets.




Floor


20


is designed and constructed to be a load bearing floor. The floor is designed so that equipment can be placed directly on the perforated floor at any location within the clean room


90


regardless of the size of the clean room. Because equipment can be placed and supported anywhere on the perforated floor, equipment can be moved into and out of the clean room at will, and can be placed in any location within the clean room. Moving equipment into or about clean room


90


does not require the dismantling of a raised floor nor the assembly or moving of a costly support platform upon which the equipment must rest. Equipment can easily be moved into or out of clean room


90


on an air palette without compromising the cleanliness of the clean room. An air palette can easily move across the perforated floor by placing thin sheets of air impervious material such as thin sheets of plastic or metal over the floor grates as a temporary measure while the air palette passes over the grates.




In addition, all facilities lines such as gas lines, chemical lines, power lines, and, the like can be routed from the equipment through the nearest opening


22


to the facilities room below. For example, and with momentary reference to

FIG. 7

, a facilities line


104


extends from clean room


90


through an opening


22


, and into facilities room


30


. Facilities line


104


may thus conveniently extend between a piece of facilities equipment


106


, located in facilities room


30


, and a piece of clean room equipment


102


, supported on bearing floor


20


within clean room


90


. As stated above, one or more pieces of facilities equipment


106


may be housed in facilities room


30


to facilitate clean room equipment


102


with gas, chemicals, power, drainage, as appropriate. This is in contrast to the conventional raised floor clean room in which facilities lines are routed underneath the raised floor. Thus, in accordance with the invention, facilities lines need not be routed across the floor and thus need not impede the movement of equipment across the floor.




In a preferred method the clean room in accordance with the invention is constructed as follows. The facilities room


30


is first constructed in accordance with normal construction practices utilized in the building of fabrication facilities for the electronics and other similar industries. Preferably, facilities room


30


is constructed below grade and the floor and walls of the facility room are poured concrete constructed on substantial footings to minimize terrestrial vibration. Support pillars


36


and beams


38


are then erected in accordance with calculations done, as described earlier, on the size and reinforcing necessary to support the intended load. When properly designed in this manner, the perforated floor to be constructed overlying the beams can be extended to virtually any size by repeating the pattern of support pillars and beams. A clean room of any desired size can thus be constructed in this manner.




After the support pillars and beams are in place, temporary forms are erected over the beams. In accordance with a preferred embodiment the concrete forms for the perforated floor include a regular array of wooden boxes having the size desired for the openings in the floor. These wooden boxes can be made, for example, from plywood and are supported on or integral with the concrete forms. Ferrule loops


60


are attached to the wooden boxes for the ultimate attachment of the floor grates


50


. With the forms including the wooden boxes in place, and with the appropriate amount of reinforcing rods in place, the perforated concrete floor is poured to a depth substantially co-planar with the tops of the array of wooden boxes. After the concrete has set, the wooden boxes can be broken apart and removed leaving the ferrule loops in place in the edges of the openings through the concrete floor. In those areas which are not intended for immediate use as a clean room area, a temporary, air impervious cap can be placed in the openings


22


. One way to form the air impervious caps, for example, is to pour about 4 inches of concrete in each of the openings that are not intended to receive a grate. Upon later expansion of the clean room, the 4 inches of concrete can easily be removed. Until so removed, however, the 4 inches of concrete is adequate to provide a safe floor upon which foot traffic and some equipment can be moved. Alternatively, temporary air impervious caps can be placed in those openings which are not initially intended to receive a grate. Temporary caps can be made from concrete, solid pieces of metal, or the like. Such caps can also be affixed to the ferrule loops.




One difficulty with solid concrete floors in a fabrication area is that vibrations tend to propagate along a concrete slab. Thus vibration generated by one piece of equipment may adversely affect the performance of an adjacent piece of equipment. It has been discovered, however, that the perforated floor in accordance with the invention does not have this problem of easy propagation of vibrations. Instead, it has been discovered that the perforated floor in accordance with the invention serves to dampen vibrations.




Although not illustrated in any of the figures, one further embodiment of the invention includes the incorporation of adjustable louvers in the metal grates


50


. Such adjustable louvers allow for adjusting the air flow through the clean room facility.




Thus it is apparent that there has been provided, in accordance with the invention, a clean room facility and a method for its fabrication that overcomes the disadvantages of prior art clean rooms. Although the invention has been described and illustrated with respect to specific illustrative embodiments thereof, it is not intended that the invention be limited to these illustrative embodiments. For example, those of skill in the art will recognize that other building materials and dimensions can be substituted for those set forth in the specific examples given above. For example, the size and spacing of the openings through the floor can be changed to accommodate particular clean room layouts or particular equipment. Likewise, different forms or shapes of the grates can be utilized as would be obvious to those of skill in the art. Accordingly, it is intended to encompass within the invention all variations and modifications as fall within the scope of the appended claims.



Claims
  • 1. A clean room facility comprising:a facilities room; a bearing floor positioned over said facilities room and capable of supporting equipment at any location thereon; a regular array or openings in said bearing floor through which a flow of air can pass to said facilities room; a movable wall structure positioned on said bearing floor to surround a selected area on said bearing floor; a ceiling above said wall structure having a plurality of filtered air inlets therein; a plurality of grates positioned in a portion of said regular array of openings located within said selected area; and a plurality of solid, air impervious members positioned in a second portion of said regular array of openings located outside said selected area.
  • 2. The clean room facility of claim 1 wherein said solid, air impervious members comprise poured concrete.
  • 3. The clean room facility of claim 1 wherein said solid, air impervious members have a top surface substantially coplanar with the upper surface of said bearing floor.
  • 4. The clean room facility of claim 1 wherein said ceiling comprises a first density of filtered air inlets in the portion of said ceiling above said selected area and a density of filtered air inlets lower than said first density in the portion of said ceiling above an area outside said selected area.
  • 5. The clean room facility of claim 1 wherein selected ones of said openings can be selected for the routing of facilities lines between clean room equipment positioned on said bearing floor and facilities equipment in said facilities room.
  • 6. The clean room facility of claim 1 further comprising air circulating equipment capable of causing the flow of air through said filtered air inlets, through said plurality of grates, and into said facilities room.
  • 7. The clean room facility of claim 6 wherein said facilities room is a plenum for the recirculation of said air circulating equipment.
  • 8. The clean room facility of claim 1 wherein said plurality of grates comprise metal grates comprising a louver adjustable for the control of air therethrough.
  • 9. The clean room facility of claim 8 wherein said plurality of grates further comprises an adjustment mechanism for adjusting the height of said grate relative to the top surface of said bearing floor.
  • 10. A clean room comprising:a facilities room having facilitics equipment housed therein for supplying facilities through facility lines to processing equipment located above the facilities room and defined by a floor and a first wall structure surrounding said floor; a second room, housing the processing equipment, positioned over said facilities room, said second room being defined by a floor having a plurality of openings therethrough through which the facility lines can pass and a wall structure surrounding said floor; a ceiling having a plurality of filtered air inlets positioned over said second room; and at least one air plenum located near an outer perimeter of said facilities room for returning air to said filtered air inlets.
  • 11. The clean room of claim 10 wherein the floor of said second room comprises a load bearing, concrete floor.
  • 12. The clean room of claim 10 wherein the floor of said second room comprises a solid, poured in place, bearing floor capable of supporting equipment at any location thereon and said plurality of openings comprise a regular array of openings having at least one of a grate or a solid, air impervious member positioned therein.
  • 13. The clean room of claim 12 wherein said grates and said solid, air impervious members are removable.
  • 14. The clean room of claim 12 wherein said solid, air impervious members are comprised of concrete.
  • 15. The clean room of claim 12 wherein a top surface of each of said solid, air impervious members lies substantially co-planar with an upper surface of the floor of said second room.
  • 16. The clean room of claim 12 wherein each of said grates includes a louver for adjusting air flow through each of said grates.
  • 17. The clean room of claim 10 wherein facilities lines for connecting the facilities equipment to the clean room equipment are routed through the plurality of openings in the floor of said second room.
  • 18. The clean room of claim 10 further comprising a plurality of support pillars extending from the floor of said facilities room to the floor of said second room.
  • 19. The clean room of claim 18 further comprising a plurality of beams located beneath the floor of said second room, said plurality of beams being supported by said plurality of support pillars.
  • 20. The clean room of claim 10 further comprising a wall structure located within said second room to create an additional room having a same floor and ceiling as said second room.
  • 21. The clean room of claim 10 wherein said plurality of filtered air inlets comprise various densities of filtered air inlets located within a surface area of said ceiling.
  • 22. The clean room of claim 10 further comprising at least one blower to direct a flow of air through said filtered air inlets in said ceiling, through the plurality of openings in the floor of said second room and into said at least one air plenum for return to said filtered air inlets.
  • 23. The clean room of claim 10 further comprising an air plenum located above said ceiling.
  • 24. The clean room of claim 10 wherein said first room functions as an air plenum positioned beneath the floor of said second room.
  • 25. A cleaning room floor structure comprising:a facilities room having facilities equipment housed therein for supplying facilities through facility lines wherein said facilities room has a solid, air impervious floor; a solid, load bearing floor positioned above and acting as a ceiling for said facilities room, said load bearing floor having a plurality of openings therethrough to allow air flow from a clean room above said load bearing floor to the facilities room below the load bearing floor and passage of the facility lines from process equipment positioned on said load bearing floor to the facilities equipment located in the facilities room; and at least one of a grate or a solid, air impervious element positioned in each of said plurality of openings.
  • 26. A clean room system including a clean room housing processing equipment, a facilities room housing facilities equipment for supplying facilities through facility lines to the processing equipment, and an air circulation system configured to maintain a desired level of particulates in said clean room, improved wherein:said clean room comprises a bearing floor having a plurality of openings extending therethrough; and said clean room is disposed above said facilities room such that said air circulation system urges air through said clean room, and thereafter through said plurality of openings and into said facilities room housing said facilities equipment.
  • 27. The clean room system of claim 26, wherein said facilities includes at least one of water, power, drainage, chemicals, and gas.
  • 28. The clean room system of claim 26 wherein said facilities lines pass through selected ones of said plurality of openings.
  • 29. The clean room system of claim 26, wherein said bearing floor is configured for placement of said processing equipment directly thereon.
  • 30. The clean room system of claim 26, wherein the underside of said bearing floor comprises the ceiling of said facilities room.
  • 31. A clean room system, comprising:a clean room including a bearing floor having a plurality of openings extending therethrough and a clean room ceiling having an air inlet configured to urge air downwardly through said clean room and thereafter through said openings; and a facilities room disposed below said clean room such that the underside of said bearing floor forms the facilities room ceiling, said facilities room having facilities equipment housed therein for supplying facilities to said clean room through facility lines.
  • 32. The clean room system of claim 31, further comprising:processing equipment disposed on said bearing floor; and a facilities line extending between said processing equipment and said facilities equipment and passing through one of said openings.
  • 33. A clean room system comprising:a facilities room having at least one piece of facility equipment housed therein which provides at least one of a gas, a chemical, and a power source for transport through facility lines; a second room positioned over said facilities room for housing processing equipment connected to the facility lines, said second room being defined by a floor having a plurality of openings therethrough and a wall structure surrounding the floor; a ceiling having a plurality of filtered air inlets positioned over said second room; and at least one air plenum located near an outer perimeter of said facilities room for returning air to said filtered air inlets.
  • 34. The clean room of claim 33 wherein the floor of said second room comprises a load bearing, concrete floor.
  • 35. The clean room of claim 33 wherein the floor of said second room comprises a solid, poured in place, bearing floor capable of supporting equipment at any location thereon and said plurality of openings comprise a regular array of openings having at least one of a grate or a solid, air impervious member positioned therein.
  • 36. The clean room of claim 35 wherein said grates and said solid, air impervious members are removable.
  • 37. The clean room of claim 35 wherein said solid, air impervious members are comprised of concrete.
  • 38. The clean room of claim 35 wherein a top surface of each of said solid, air impervious members lies substantially co-planar with an upper surface of the floor of said second room.
  • 39. The clean room of claim 35 wherein each of said grates includes a louver for adjusting airflow through each of said grates.
  • 40. The clean room of claim 33 wherein facilities lines for connecting the facilities equipment to the clean room equipment are routed through the plurality of openings in the floor of said second room.
  • 41. The clean room of claim 33 further comprising a plurality of support pillars extending from the floor of said facilities room to the floor of said second room.
  • 42. The clean room of claim 41 further comprising a plurality of beams located beneath the floor of said second room, said plurality of beams being supported by said plurality of support pillars.
  • 43. The clean room of claim 33 further comprising a wall structure located within said second room to create an additional room having a same floor and ceiling as said second room.
  • 44. The clean room of claim 33 wherein said plurality of filtered air inlets comprise various densities of filtered air inlets located within a surface area of said ceiling.
  • 45. The clean room of claim 33 further comprising at least one blower to direct a flow of air through said filtered air inlets in said ceiling, through the plurality of openings in the floor of said second room and into said at least one air plenum for return to said filtered air inlets.
  • 46. The clean room of claim 33 further comprising an air plenum located above said ceiling.
  • 47. The clean room of claim 33 wherein said facilities room functions as an air plenum positioned beneath the floor of said second room.
US Referenced Citations (32)
Number Name Date Kind
844296 Winslow Feb 1907 A
1562865 Brown Nov 1925 A
3023689 Kurek Mar 1962 A
3158457 Whitfield Nov 1964 A
3367257 Raider et al. Feb 1968 A
3850193 Guzzo Nov 1974 A
3918518 James Nov 1975 A
4043354 Brown Aug 1977 A
4267769 Davis et al. May 1981 A
4409889 Burleson Oct 1983 A
4671811 Cadwell, Jr. et al. Jun 1987 A
4699640 Suzuki et al. Oct 1987 A
4733509 Takahashi Mar 1988 A
4747341 Hedrick May 1988 A
4832562 Johnson May 1989 A
4883511 Gustin et al. Nov 1989 A
4883590 Papp Nov 1989 A
RE33220 Collier May 1990 E
5029518 Austin Jul 1991 A
5067289 Ouderkirk et al. Nov 1991 A
5096477 Shinoda et al. Mar 1992 A
5412914 Daw et al. May 1995 A
5444947 Miller Aug 1995 A
5477649 Bessert Dec 1995 A
5518451 Renz et al. May 1996 A
5542223 Inda et al. Aug 1996 A
5564235 Butler Oct 1996 A
5692954 Lee et al. Dec 1997 A
5791096 Chen Aug 1998 A
5871556 Jeanseau et al. Feb 1999 A
6155013 Kim Dec 2000 A
6202374 Cooper et al. Mar 2001 B1
Foreign Referenced Citations (2)
Number Date Country
38 32 915 Mar 1990 DE
0 079 066 May 1983 EP