Embodiments of the present disclosure relate generally to dehumidification and air conditioning systems for indoor spaces. Particular embodiments find use in indoor pool rooms and indoor agricultural grow rooms, both of which have extensive dehumidification and air conditioning needs. However, the disclosed technology may be used in connection with any other type of HVAC application. The demands of the needs in these types of rooms can vary significantly, either as a result of the different activities conducted in the room, the number of people and/or the number of plants in the room at any particular time, the time of day, the annual seasonal effect on the building, and/or various combinations thereof. This disclosure seeks to provide an efficient way to manage and scale (either up or down) dehumidification and air conditioning needs for interior spaces.
Designing or specifying equipment for an indoor pool environment or an indoor grow house /grow room environment can present challenges. Specifically, these challenges can include properly adjusting the indoor air environment, which can be exacerbated by the fact that the equipment must be designed to handle a maximum load, which is not always the load experienced in the environment. For example, pool room dehumidification equipment must be able to dehumidify the room when an absolute maximum number of bathers is present. However, there are many instances when fewer than the maximum number of bathers will be enjoying the pool room environment.
Additionally, with indoor pool environments, there is a complex set of factors to balance. These factors include but are not limited to room size, pool activity levels, expected and actual capacity, inside air and water temperatures, air distribution, outside air temperatures and humidity ranges, proper building features, HVAC and humidity control design, operating and maintenance costs, along with a number of other factors, as well as ultimately, the need to meet patron expectations. These factors may all be interrelated on various levels. Similarly, with indoor grow room environments, various factors that can present challenges include but are not limited to a desire for the environment to house a varied number of plants and/or varied types of plants, which may all exhibit various differences in carbon dioxide consumption, oxygen offload, and perspiration; necessary light levels; time of day; desired humidification level; and/or desired temperature level. The above-described pool environment factors may also be present. Getting any one of these factors wrong in the environment can lead to problems, and potentially expensive and/or frustrating results for the indoor environment owners, operators, and patrons.
As discussed above, current equipment for these environments must be designed to manage a maximum capacity, whether a maximum bather capacity, a maximum plant capacity, or other expectations. However, maximum capacity may not always be reached. For example, an indoor pool may be designed with equipment that is required to manage an environment for a capacity of 50-60 people. In the instance when only two or three people are in the pool room, the equipment must still typically operate at the same or similar levels required for maximum capacity. This can result in wasted energy. The same example may be envisioned for an indoor grow room environment. If the indoor grow room environment is designed with equipment that is required to manage plants within a certain square footage, but only half of the environment is filled with plants, the equipment must still typically operate at the same or similar levels required for maximum capacity. This can also result in wasted energy.
Additionally, at nighttime, plants expel large amounts of moisture which increases the level of humidity in the grow room. This excess moisture needs to be kept under control in order to allow the plants to thrive. The disclosed technology is designed to incrementally increase the dehumidification capacity to match the load required at any given point. Furthermore, in the daytime, the grow room may require a significant reduction in dehumidification needs and an increase in cooling needs, due to the daylight lighting load. The disclosed technology can help maintain a steady state with the appropriate capacity matching.
Embodiments of the present disclosure provide a system that fragments unit cooling in dehumidification capacity into incremental sizes. The general goal is that only the appropriate amount of capacity is in use for systems at any given need. This can provide better room control and can reduce the amount of capacity cycling typically required by systems that only incorporate one or two large, many ton compressors.
Specifically, in one example, there is provided an air management system, comprising: a plurality of circuits, each circuit comprising an evaporator, a compressor, and a plate heat exchanger; wherein each circuit in the plurality of circuits is configured to be operated independently of the other circuits, wherein the plurality of circuits are provided in a modular array. Each circuit may be mounted within a module housing. The module housings may be mounted within a master housing. The plurality of circuits may be fluidly connected via a hydronic loop. The circuits may receive airflow and may be configured to cool or warm the received airflow and expel cooled or warmed air into an indoor environment. In one example, the system is mounted with respect to an indoor pool. In an alternate example, the system is mounted with respect to an indoor growing room or greenhouse. In other examples, the system may be used in connection with any other type of HVAC application. These include but are not limited to air-conditioning and dedicated outdoor air systems (DOAS).
It is generally desirable that each circuit within the plurality of circuits is configured to be separately removable from the system, and the system is configured to continue to function with one or more circuits removed from the system.
The system may include one or more fluid pumps, one or more check valves, one or more modulating valves, one or more filters, or any combination thereof. These may be shared features, that function to flow the fluid through the hydronic loop. It is possible for each circuit in the plurality of circuits to range in size anywhere from about 2 to about 40 tons.
Another example provides a method for maintaining an indoor environment, comprising: providing an air management system as described herein; removing at least one of the circuits from the plurality of circuits from the system for repair or replacement; and continuing to run the air management system without the removed circuit.
A further example provides a method for maintaining an indoor environment, comprising: providing an air management system of claim 1, wherein the air management system is configured to receive and react to information about load capacity; and activating only a number of circuits within the plurality of circuits necessary to maintain the load capacity.
Matching the unit capacity to the load in the desired space is often not well executed due to current limitations of equipment. For example, it is often the case that one or more 20 or 30 ton circuits are installed for indoor environment management. However, if a load only requires 2 tons, a 20 or a 30 ton circuit must still be run.
Embodiments of the present disclosure thus provide a compressor wall system 10 that incorporates a plurality or series of smaller circuits 12 to achieve the required capacity modulation. Generally, providing a series of smaller circuits 12 can better match a given load in real time as opposed to a single larger circuit or multiple larger circuits. This allows the system to achieve a required capacity modulation by only activating the number of circuits required to reach the amount of capacity for the current need.
In a specific example, four to sixteen smaller circuits 12 may comprise the system 10. These smaller circuit 12 may be from about 3-12 tons. In specific examples, the compressors may be 6-8 ton compressors. Specific tests have been run with 6.33 ton and 7.8 ton compressors with good results. It should be understood that each circuit is capable of operating independently from every other circuit. The circuits operate on their own, but may be mounted in a module such that they provide an array of independently operating circuits. If a single circuit is removed, it does not affect the operation of the remaining circuits.
As shown by the hydronic loop 22 of
Airflow and coolant flow through the system as follows. Coolant fluid from a fluid cooler enters the system at inlet 42, flowing through a conduit and moved via one or more fluid pumps 24. The fluid is directed past and through a heat exchanger 18. Airflow 20 also enters the system across evaporators 14. Heat from airflow is transferred to the refrigerant or coolant fluid, which cools the air and warms the coolant fluid. The warmed coolant fluid is then delivered to a fluid cooler via an outlet 44. The cooled air passes over one or more hydronic reheat coils 40 and is delivered to the environment. If warmed air is needed in the environment, rather than exhausting warmed air external to the system, it may be routed across the hydronic reheat coils 40 and delivered to the environment.
One of the benefits of the disclosed system 10 is that by providing an array of circuits 12 contained in individual module housings 30 within a single system 10, it is easy to interchange or otherwise replace one of the circuits 12 when needed. For example, in a 4×4 array that has sixteen circuits 12, if a single circuit 12 malfunctions, it may be replaced or repaired without affecting the remainder of the circuits or their functioning. Additionally, until that single circuit can be replaced or repaired, the entire system 10 can continue to run at almost capacity. In this example, fifteen circuits are still available.
An additional benefit of the disclosed system 10 is that it is possible to maintain a load at any given point by turning on or off any of the circuits 12 in the system 10. As an example, a traditional system may have two 30-ton circuits managing a particular environment. It may be the case that a particular load only requires 15 tons at a particular level of capacity. However, even if only one circuit is turned on in this example, 30 tons are in use, meaning that extra energy is expended/wasted. By contrast, if a system incorporates twelve 6-ton circuits managing a particular environment and only 15 tons is required, it is possible to only activate three circuits to deliver 18 tons, resulting in a great energy saving. In the example provided, it is possible to manage a load as low as 6 tons with only a single circuit. This allows the system to easily match the load in real time by managing activation of only the number of circuits required although a complete load is always available when/if needed. A greater number of circuits and smaller circuits may also be used.
As shown by
In a specific example, the circuits 12 may be individual water-cooled air conditioning modules that can easily be replaced if one module experiences difficulty. The individual modules may all be connected to a single fluid cooled loop (hydronic loop 22) that is cooled by fluid coils. The fluid coils may either be located in the air handling unit for reheat purposes or may be located outdoors for rejection of heat to the outdoors. This may be configured to be switched in use as well. For example, if heat is needed inside the environment, heat may be routed inside. If the inside environment needs to be cooled, the heat may be routed outside the environment. A valve, dial, or other modulator may be provided in order to actuate this movement of warmed air.
It is possible to vary or alter the number of modules or the size of each of the module components. It is also possible to vary the location of the components. In summary, there is provided an array of modularized circuits that work collectively to provide a system that can manage an indoor environment. The system is designed in order to match the delivered load more closely to the required load then has been done in the past. The system is also designed in order to enhance and ease of serviceability of the individual circuits when needed.
Advantages of the disclosed system include but are not limited to enhanced capacity control; ease of serviceability; a more compact air handling unit; redundancy in compressor capacity at partial loads; improved energy efficiency at partial loads; decrease in manufacturing labor.
The traditional and prevailing thought had been that it is more costly to build a system using a greater number of smaller circuits than it is to provide the traditional larger circuit configuration with fewer circuits. The present inventors have broken that paradigm by designing the disclosed system.
The subject matter of certain embodiments of this disclosure is described with specificity to meet statutory requirements, but this description is not necessarily intended to limit the scope of the claims. The claimed subject matter may be embodied in other ways, may include different elements or steps, and may be used in conjunction with other existing or future technologies. This description should not be interpreted as implying any particular order or arrangement among or between various steps or elements except when the order of individual steps or arrangement of elements is explicitly described.
It should be understood that different arrangements of the components depicted in the drawings or described above, as well as components and steps not shown or described are possible. Similarly, some features and sub-combinations are useful and may be employed without reference to other features and sub-combinations. Embodiments of the invention have been described for illustrative and not restrictive purposes, and alternative embodiments will become apparent to readers of this patent. Changes and modifications, additions and deletions may be made to the structures and methods recited above and shown in the drawings without departing from the scope or spirit of the invention disclosure and the following claims.
Filing Document | Filing Date | Country | Kind |
---|---|---|---|
PCT/IB2019/060635 | 12/10/2019 | WO |