The invention pertains generally to the field of heat exchanger control. More particularly, the invention relates to a system and method for control of a vaporizer, such as a submerged combustion vaporizer for LNG vaporization, in combination with an atmospheric heating tower.
Heat exchangers are in wide use in industry. One application for heat exchangers is the vaporization of liquefied natural gas (LNG). Systems are known for adding heat to liquefied natural gas to convert it to a gas state. One type of LNG evaporator is a so-called submerged combustion vaporizer (SCV). An SCV generally has a water bath tank in which is submerged a vaporization coil. Liquefied LNG is supplied to the vaporization coil from outside the SCV, runs through the coil and is evaporated inside the coil, and exits the SCV as a gas. To accomplish this, heat needs to be continually added to the water bath.
One way the heat can be added is that the SCV contains a partially submerged fan-driven combustion device having a specially designed burner which will produce hot flue gases that are conveyed via distributor ductwork and sparger assemblies into the water bath below the LNG vaporization coil. The sparger assemblies direct heat into the water bath both by surface convection on the outside metal walls and conductive heat transfer via direct contact of hot flue gases with surrounding water. Thus, heat transferred to the water bath is subsequently transferred to the outside metal wall surface of the LNG vaporization coil submerged with the water bath.
Some SCVs have an adjustable operating range of heat addition. That is, there will be a 100% design operating condition, whereby the fan and/or fuel gas burn rate can be reduced continuously to a lower level as necessary to match the heat input requirements to produce/maintain the desired LNG vaporization rate. However, there is a lower limit to which the SCV output may be reduced without reaching mechanical/process constraints with the equipment. That is, it is difficult to operate a SCV below a certain minimum level because turndown capability is fixed by factors such as fan performance characteristics and flame stability under various air/fuel ratios. This turndown capability characteristic of SCVs is discussed in more detail below.
Another method for adding heat to a water bath is the use of an atmospheric heating tower. Atmospheric cooling towers are well known, and it has been found that where it is desired to heat a fluid, rather than cool it, so long as the atmospheric temperature is greater than the supply temperature to the tower, it is possible to use atmospheric towers that are configured generally like cooling towers but operated in a fashion so that they will actually heat the water supplied to the tower and provide an output warmer than the input.
Operation of SCV, and operation of heating towers, often occur in areas where the ambient temperature will change both during the course of the day and evening, and also seasonally. It would be desirable to have a system and method that could control an SCV and/or heating tower in such a way as to provide the efficient and effective vaporization of LNG.
One embodiment of the invention provides a method of vaporizing liquefied natural gas consists of passing liquefied natural gas through a submerged combustion vaporizer having a water bath at a bath temperature and a burner to provide a vaporized gas output at a send-out temperature, drawing water from the bath of the submerged combustion vaporizer and supplying it to an atmospheric heating tower having an ambient air temperature, returning water from the atmospheric heating tower to the bath of the submerged combustion vaporizer, modulating the operating rate of the burner of the submerged combustion vaporizer, and modulating the operating rate of the atmospheric heating tower.
Another embodiment of the present invention comprises means for passing liquefied natural gas through a submerged combustion vaporizer having a water bath at a bath temperature and a burner to provide a vaporized gas output at a send-out temperature, means for drawing water from the bath of the submerged combustion vaporizer and supplying it to an atmospheric heating tower having an ambient air temperature, means for returning water from the atmospheric heating tower to the bath of the submerged combustion vaporizer, means for modulating the operating rate of the burner of the submerged combustion vaporizer, and means for modulating the operating rate of the atmospheric heating tower.
Another embodiment for vaporizing liquefied natural gas includes a submerged combustion vaporizer having a water bath of a bath temperature and a burner, to provide a vaporized gas output at a send-out temperature, an atmospheric heating tower having an ambient air temperature, a circuit that draws water from the bath of the submerged combustion vaporizer and supplies it to the atmospheric heating tower and returns the water from the atmospheric heating tower to the bath of the submerged combustion vaporizer, and a controller that modulates the operating rate of the burner of the submerged combustion vaporizer, and the operating rate of the atmospheric heating tower.
There has thus been outlined, rather broadly, certain embodiments of the invention in order that the detailed description thereof herein may be better understood, and in order that the present contribution to the art may be better appreciated. There are, of course, additional embodiments of the invention that will be described below and which will form the subject matter of the claims appended hereto.
In this respect, before explaining at least one embodiment of the invention in detail, it is to be understood that the invention is not limited in its application to the details of construction and to the arrangements of the components set forth in the following description or illustrated in the drawings. The invention is capable of embodiments in addition to those described and of being practiced and carried out in various ways. Also, it is to be understood that the phraseology and terminology employed herein, as well as the abstract, are for the purpose of description and should not be regarded as limiting.
As such, those skilled in the art will appreciate that the conception upon which this disclosure is based may readily be utilized as a basis for the designing of other structures, methods and systems for carrying out the several purposes of the present invention. It is important, therefore, that the claims be regarded as including such equivalent constructions insofar as they do not depart from the spirit and scope of the present invention.
The SCV has a cold water output line 20 which feeds to a heating tower input line 22. A heating tower 24 is provided as an atmospheric heating tower where the cold water falls through the tower and is heated by interaction with warmer ambient air. The operation of the heating tower 24 can be controlled by a fan speed control 26 which controls a fan 28 to modulate the air flow rate through the tower. The cold water, after being warmed in the heating tower, is collected in a basin of the heating tower and exits the heating tower via a hot water outlet conduit 30 which leads to a hot water inlet conduit 32 which is supplied into the SCV water bath. The flow rate of the heating tower hot water to the SCV is controlled by an on/off valve 34.
It will be appreciated that the system can be operated in several modes. For example, the system can be operated in a mode where only the SCV 10 is turned on, and the SCV 10 provides all of the heat needed for vaporization of the gas, and the tower fans are turned off and water is not recirculated through the tower.
In another mode, the SCV can be turned off (that is, has its burner turned off), and the circulation of water through the heating tower can be used to supply all the heat to the SCV bath water for vaporization of the LNG.
In yet another mode, both the SCV and heating tower can be operated at the same time. Also, both the SCV and the heating tower are typically operable through a continuous range. Thus, it is possible to operate the SCV fully, while operating the heating tower partially, or to operate the heating tower fully while operating the SCV partially, or to operate both devices at a partial rate.
The SCV consumes energy and cost due to the fuel (typically natural gas) used in the SCV combustion as well as a fan that is usually associated with the SCV to force the air through the burner and out the flue gas (sparger pipe) outlet. The heating tower also consumes power by virtue of one or more fans and water pumps to circulate the water to and from the tower. In general, however, the heating tower fan electricity consumption in many conditions will be significantly lower per energy unit added than the fuel cost that is required by the SCV. Of course, this will depend upon the ambient temperature, as well as the relative cost of gas and electricity.
The following discussion will refer to several terms which can be generally explained as follows. The atmospheric temperature at the heating tower will generally be described as a wet bulb temperature, which is a term well known in the art, and is essentially a function of dry bulb temperature and relative humidity. The amount of heat that a heating tower can add to a system is a function of the entering wet bulb temperature to the tower. The temperature varies throughout the day, typically, and also often varies seasonally throughout the year. This causes the immediate heat rate addition capability of a heating tower to vary also.
An SCV is also described herein as having a gas send-out temperature, which is the temperature of the natural gas vapor that exits the vaporizer in the SCV. A supplier of natural gas vapor is typically required to provide the gas at a certain minimum temperature which may typically, for example, be 40° F. Minimum send-out temperatures are generally specified to avoid concern over freezing of ground in which gas pipes may exist or other cold damage to the piping.
SCVs also typically have a maximum turndown ratio. That is, when an SCV burner is dialed down to operate at a fraction of its maximum output, at some point the fuel gas concentration in combustion air will become too dilute to remain within the lower flammability limit. When this limit has been reached, the flame will be extinguished. However, prior to this point the flame will transition into an unstable zone with increased emissions of carbon monoxide and unburned hydrocarbons. A typical turndown ratio limit of 4.5:1 is used in the examples in this application, which means that the SCV burner exhibits a lowest operable setting that is 22% of its maximum setting.
There will also typically be a specified gas send-out rate, which is the amount of vaporized gas exiting the vaporizer. This is generally governed by the pipeline company or gas purchaser itself, which will demand a certain supply rate at any given time.
Referring back to
These controls can be modulated by measuring and performing feedback on the measured gas send-out temperature. However, because the wet bulb temperature does affect the amount of heat that is available from the heating tower source, control can sometimes be performed more efficiently and easily by measuring the ambient wet bulb temperature in conjunction with calculations based on a mathematical model of a given heating tower's heat addition performance of that wet bulb temperature.
When the ambient air wet bulb temperature to the tower is high, all of the heat required by an SCV can sometimes be added by the heating tower alone. The gas send-out temperature can be modulated by modulating the fan speed or the fan on/off of the heating tower, while the SCV is turned off and provides no additional heat. The send-out temperature can be measured and the fan speed simply controlled in the feedback loop.
When the wet bulb temperature drops to a point where the heating tower is not maintaining a high enough gas send-out temperature, then supplemental heat from the SCV is added. If all of the heating tower fans are on and the gas send-out temperature is lower than the requirement, the SCV heater is fired or turned on. At this point, the minimum heat added by the SCV as set by the turn down ratio of the SCV burner will be added. Since this may be slightly more than desired, the heating tower might be turned down slightly, or as discussed more below, this transition phrase can simply be operated through.
If the gas send-out temperature still remains too low with the burner operating at a minimum setting, then more heat is required from the SCV. The SCV heat rate can be increased by turning up the burner to maintain the gas send-out temperature at or above the required level.
As the wet bulb temperature continues to decline, at some point the ability of the heating tower to add heat reduces to a point where it becomes uneconomical to run the tower fan to generate such a small or non-existent heat supply from the heating tower. When the ambient wet bulb temperature is equal to or lower than the desired hot water return temperature, the heating tower fans and pumps are shut off.
In the flow diagrams discussed below, certain terms are used which are explained below. The term “RH” refers to relative humidity of the ambient air. The term “DB” refers to dry bulb temperature of the ambient air. The term “baro” refers to barometric pressure of the ambient air. The term “WB” refers to wet bulb temperature of the ambient air. The term “HW” refers to the return temperature of the hot water that is supplied from the basin of the heating tower. The term “SCV” refers to a submerged combustion vaporizer. The term “SCV turn down rate” refers to the lowest output capacity level permitted for operation of the SCV, and is provided as a ratio of the lowest output compared to the maximum output of the SCV. The term “minimum bath temperature” is a selected minimum temperature that is used in the system.
In applications where the SCV has a superheater, superheat can be used to increase the gas send-out temperature for a certain minimum SCV bath temperature, so that in systems with superheat, a lower minimum bath temperature might be practical than would be the case without superheat.
The reference to heating tower models refers to a mathematical performance model determined by expectation or by computer simulation for a given heating tower. Examples are shown in
In the examples given below, a system having a single SCV and a single heating tower is used for explanatory purposes. However, it will be appreciated that the control systems and methods described herein can also be applied to arrangements having multiple heating towers and/or multiple SCVs. In particular, in the case of multiple SCVs, it is possible to make the minimum turn down rate be lower for the combined multiple SCVs than it typically is for a single SCV, because it would be possible to run only one or some of the SCVs rather than all of them at the minimum rate.
Referring now to
If there is a demand for vaporized gas at step 102, the controller will perform step 104, which is to check if the tower is on. If the tower is not on, the system will measure the relative humidity, dry bulb temperature, and barometric pressure at step 106 and calculate a wet bulb temperature at step 108. Of course, if an appropriate sensor is available that can simply sense the wet bulb temperature, then there is no need to perform the measurements and calculations, but in any event the system continues its operation based on a calculated or measured wet bulb temperature.
Next at step 110, the system refers to the heating tower model for the heating tower that is being used and calculates an estimated hot water return temperature that is available from the heating tower based on the assumption of a certain cold water supply temperature from the SCV, which is a pre-set selected value (also referred to below as minimum defined bath temperature, or simply bath temperature).
If the tower is determined to be on at step 104, then at step 112 the system measures the hot water return temperature from the heating tower. Next, using a measured or calculated estimated hot water output temperature from the heating tower, at step 114 the system compares the hot tower output temperature to the minimum desired bath temperature in the SCV. If the actual calculated hot water temperature from the tower is not greater than the minimum bath temperature, the system checks whether the heating tower is on at step 116, and if it is, turns off the heating tower at step 118.
At step 120 the system will operate the SCV only based on determined SCV heat demand. If the SCV heat demand is not greater than the SCV minimum turn down rate at step 122, then the SCV is operated at step 124 at its minimum turn down. If the SCV demand is greater than the SCV turn down rate at step 122, then at step 126 the SCV is operated at a computed partial or full SCV demand rate.
Returning to step 114, if the calculated or actual hot water output from the tower is greater than the minimum bath temperature for the SCV, then the system uses the heating tower model to calculate a potential supply of heat from the tower at step 130, checks if the heating tower is on at step 132, and turns it on, if necessary, at step 134. Then, it is checked whether the heat demand at the SCV is greater than the heating tower potential supply at step 136. If it is not, then at step 138 it is possible to operate the heating tower only, check if the SCV is on at step 140 and, if it is, turn off the SCV at step 142. If the heat demand is greater than the potential heat that can be supplied from the heating tower, then at step 144 it is checked whether the SCV is on, and if it is not, is turned on a step 146.
The system then determines at step 150 the SCV demand which is required in addition to the heat that is being supplied by the heating tower, and if the SCV demand is greater than the SCV turn down rate at step 152, the tower will be operated at full capacity and the SCV operated at a computed percentage of its maximum power in order to maintain the bath temperature at the desired bath temperature at step 154. If the SCV demand is not greater than the SCV turndown rate, then the SCV is operated at minimum turndown and the tower operating requirement is determined at step 156. If at step 158 the heating tower requirement is zero or less, the heating tower is turned off at step 160.
After step 154, 158 or 160, the system returns to the delay point 103 and then returns to the start 100, unless there is a superheater system. If there is a superheater system, then after step 154, 158 or 160, the system enters the steps in the dotted box. At step 164 it is determined whether the SCV send-out temperature is greater than a minimum required send-out temperature. If not, at step 166 a check is made to determine if the superheater is turned on. If the superheater is off, step 168 turns the superheater on. If at step 164 the SCV send-out temperature is greater than a minimum required send-out temperature, it is checked at step 170 whether the superheater is off, and if not, the superheater is turned off at step 172. After steps 166, 168, 170, or 172 the control returns to the delay point 103 and the start 100.
Turning next to
Between 68° and 66° ambient temperature, the heating tower is no longer able to supply 100% of the required heat, and so the SCV is turned on. In this transition range the SCV is operating at its minimum turndown rate. Thus, it would be desirable in theory to modulate the heating tower so that the SCV does not provide excess heat beyond what is needed. However, if the time period spent in the ambient conditions in the transition range is relatively short, in other examples it may be desirable to simply turn the SCV on at its minimum turndown rate and allow some extra heat to be added by the combination of the SCV at minimum turndown and the tower at its full rate.
Next, at an ambient temperature between 65° and 55°, the heating tower is fully operational but as the ambient temperature decreases, the heating tower is providing gradually less heat. The SCV is modulated to gradually supply more heat to accommodate this decrease, so that the bath is maintained at a 55° supply temperature. When the ambient temperature falls below the desired bath temperature of 55°, the pump to the heating tower is shut off as well as the fans for the heating tower, in order to avoid the heating tower performing undesirable cooling. The SCV can be designed so that it has sufficient heat addition to add all the necessary heat by itself.
In the wet bulb ambient temperature range of 85° to 69°, this chart is the same as
Between an ambient wet bulb temperature of 48° and 39° in this example, the heating tower is operated at 100%, the superheater is operating at full capacity, and the SCV is modulated to maintain a 35° water bath temperature which is also a 35° water supply temperature to the tower. At approximately 38°, the pump to the heating tower is shut off and all heat comes from the superheater combined with the SCV. Although there is still a small difference between the wet bulb temperature of 38° and the water bath heating tower supply temperature of 35°, at these temperatures, the heating tower is not very efficient and the heat added may not be worth the cost of running the heating tower pump and fans.
In this example, moreover, the water bath temperature which is the supply temperature is allowed to fluctuate in a range between 55° and 35° as a minimum, with 35° selected as a cutoff temperature just high enough so icing will not occur. Also in this condition where the heating tower is shut off, it may in some instances be desirable to operate the SCV to raise the bath temperature up to 55° at which the superheater may not be required. This will depend on the balance of efficiency between the superheater and the SCV.
Similarly, during the transition phase between 51° and 49°, as well as during the phases below the wet bulb temperature of 48°, depending on the design and capacity of the SCV, it would be possible to operate the SCV only without the superheater.
The system described above is an example control system which modulates the operation of a heating tower and/or an SCV by controlling parameters of one or both devices in response to the operating condition of the system. This system can provide significant benefits compared to the simple use of either an SCV or a heating tower by itself. For example, depending on the environmental conditions, the system can allow an installation to temperature over a wide range of ambient temperatures, while reducing fuel and/or electricity costs compared to a system lacking these controls.
The control method outlined in
The many features and advantages of the invention are apparent from the detailed specification, and thus, it is intended by the appended claims to cover all such features and advantages of the invention which fall within the true spirit and scope of the invention. Further, since numerous modifications and variations will readily occur to those skilled in the art, it is not desired to limit the invention to the exact construction and operation illustrated and described, and accordingly, all suitable modifications and equivalents may be resorted to, falling within the scope of the invention.
Number | Name | Date | Kind |
---|---|---|---|
3726101 | Arenson | Apr 1973 | A |
4519213 | Brigham et al. | May 1985 | A |
5819542 | Christiansen et al. | Oct 1998 | A |
6076359 | Jurcik et al. | Jun 2000 | A |
6581412 | Pant et al. | Jun 2003 | B2 |
6622492 | Eyermann | Sep 2003 | B1 |
6644041 | Eyermann | Nov 2003 | B1 |
20050081535 | Engdahl | Apr 2005 | A1 |
20060242970 | Yang et al. | Nov 2006 | A1 |
20080120983 | Eyermann | May 2008 | A1 |
20090065181 | Mockry et al. | Mar 2009 | A1 |
Entry |
---|
C.C. Yang and Zupeng Huang, “Lower Emission LNG Vaporization”, LNG Journal Nov./Dec. 2004, pp. 24-25. |
Number | Date | Country | |
---|---|---|---|
20090064688 A1 | Mar 2009 | US |