Currently available Heating, Ventilation, and Air Conditioning (HVAC) systems broadly fall into two categories. Smaller residential systems consist of a single “zone,” which has a heating system, an air conditioning system, and a thermostat. The thermostat measures the temperature at a single point in the residence, sometimes near the air intake for any recirculating ventilation system, and compares that temperature to a threshold or set of thresholds. If the temperature falls below a minimum threshold, the HVAC system will turn on the heater to warm the residence. If the temperature rises above a maximum threshold, the HVAC system will turn on the air conditioner to cool it.
A second category combines multiple such systems within a larger residential or commercial structure, partitioning the structure into “zones.” For example, an office building might be divided into four zones, each with its own thermostat, heater, and air conditioner. In this example, each zone will act like its own, closed, thermostatically-controlled system, with three settings (heat, cool, or do nothing) and one measurement point (the thermostat). Zones can vary widely in size, from fifty square feet to thousands of square feet.
These existing systems have numerous disadvantages. First, they are inefficient because they don't accurately read the temperature in different spaces within a zone. An office space might have a single thermostat positioned in a hallway, but not in any individual office. This can lead to a situation where an HVAC system continues to cool an already cool room because the thermostat happens to be located in a warmer part of the office. In another example, an office without windows on the north side of a building can have a significantly different temperature than a conference room with windows facing the south side of a building. In residential applications, rooms on the top floor of a house will often be significantly warmer than the basement, due to hot air's natural tendency to rise.
Zones in multi-zone HVAC systems are also inflexible, meaning that it is difficult to re-route air, and impossible to adjust ventilation pathways dynamically during the course of a day. Ducts and air handlers are placed during building construction, and so the only way to change their shape or to add more is to redesign and replace the existing ducts and controllers, an expensive and cumbersome process. Though ducts including motorized dampers exist, the existing ducts are not wirelessly connected or controllable, and any adjustments require the intervention of a building engineer, either manually adjusting one or more dampers or controlling them through a separate, wired control system.
Most ducts used by existing HVAC systems in homes and commercial buildings are “dumb,” i.e. they lack any sensors or actuators for providing measurements, controls, or interoperability with other ducts in the HVAC system. Dumb ducts are open tubes that move air around a system without any intelligence. As a result, they create an inefficient, imbalanced distribution of hot and cold air, making some areas colder when they are cool already and some areas hotter when they are already hot.
Thus, there is a need in the art for a more granular system of air circulation and climate control, with intelligent sensors and actuators to increase efficiency and overall comfort. The present invention satisfies that need.
In one aspect, a smart duct comprises an inlet, an outlet, a damper positioned between the inlet and the outlet, an electromechanical actuator configured to open and close the damper, and a controller configured to operate the electromechanical actuator and retrieve measurements from the sensor and to receive instructions from a central HVAC controller via a communication channel. In one embodiment, the communication channel is a wireless communication channel. In one embodiment, the smart duct further comprises a sensor configured to monitor at least one air parameter within the smart duct. In one embodiment, the sensor is a smoke sensor. In one embodiment, the sensor is a temperature sensor. In one embodiment, the sensor is a humidity sensor. In one embodiment, the sensor is an air quality sensor. In one embodiment, the smart duct further comprises a power connection, wherein the smart duct is configured to close automatically when power is interrupted. In one embodiment, the damper is substantially round and the actuator is configured to rotate the damper to open and close it. In one embodiment, the actuator is an electric motor. In one embodiment, the actuator is a solenoid.
In one embodiment, the smart duct further comprises a spring connected to the damper and a stop positioned between the inlet and the outlet, wherein the spring is configured to drive the damper against the stop to fix the damper in a default position. In one embodiment, the default position is substantially open. In one embodiment, the default position is substantially closed. In one embodiment, the damper is substantially rectangular.
The foregoing purposes and features, as well as other purposes and features, will become apparent with reference to the description and accompanying figures below, which are included to provide an understanding of the invention and constitute a part of the specification, and in which:
It is to be understood that the figures and descriptions of the present invention have been simplified to illustrate elements that are relevant for a clear understanding of the present invention, while eliminating, for the purpose of clarity, many other elements found in related systems and methods. Those of ordinary skill in the art may recognize that other elements and/or steps are desirable and/or required in implementing the present invention. However, because such elements and steps are well known in the art, and because they do not facilitate a better understanding of the present invention, a discussion of such elements and steps is not provided herein. The disclosure herein is directed to all such variations and modifications to such elements and methods known to those skilled in the art.
Unless defined otherwise, all technical and scientific terms used herein have the same meaning as commonly understood by one of ordinary skill in the art to which this invention belongs. Although any methods and materials similar or equivalent to those described herein can be used in the practice or testing of the present invention, exemplary methods and materials are described.
As used herein, each of the following terms has the meaning associated with it in this section.
The articles “a” and “an” are used herein to refer to one or to more than one (i.e., to at least one) of the grammatical object of the article. By way of example, “an element” means one element or more than one element.
“About” as used herein when referring to a measurable value such as an amount, a temporal duration, and the like, is meant to encompass variations of ±20%, ±10%, ±5%, ±1%, and ±0.1% from the specified value, as such variations are appropriate.
Throughout this disclosure, various aspects of the invention can be presented in a range format. It should be understood that the description in range format is merely for convenience and brevity and should not be construed as an inflexible limitation on the scope of the invention. Accordingly, the description of a range should be considered to have specifically disclosed all the possible subranges as well as individual numerical values within that range. For example, description of a range such as from 1 to 6 should be considered to have specifically disclosed subranges such as from 1 to 3, from 1 to 4, from 1 to 5, from 2 to 4, from 2 to 6, from 3 to 6 etc., as well as individual numbers within that range, for example, 1, 2, 2.7, 3, 4, 5, 5.3, 6 and any whole and partial increments therebetween. This applies regardless of the breadth of the range.
In some aspects of the present invention, software executing the instructions provided herein may be stored on a non-transitory computer-readable medium, wherein the software performs some or all of the steps of the present invention when executed on a processor.
Aspects of the invention relate to algorithms executed in computer software. Though certain embodiments may be described as written in particular programming languages, or executed on particular operating systems or computing platforms, it is understood that the system and method of the present invention is not limited to any particular computing language, platform, or combination thereof. Software executing the algorithms described herein may be written in any programming language known in the art, compiled or interpreted, including but not limited to C, C++, C#, Objective-C, Java, JavaScript, Python, PHP, Perl, Ruby, or Visual Basic. It is further understood that elements of the present invention may be executed on any acceptable computing platform, including but not limited to a server, a cloud instance, a workstation, a thin client, a mobile device, an embedded microcontroller, a television, or any other suitable computing device known in the art.
Parts of this invention are described as software running on a computing device. Though software described herein may be disclosed as operating on one particular computing device (e.g. a dedicated server or a workstation), it is understood in the art that software is intrinsically portable and that most software running on a dedicated server may also be run, for the purposes of the present invention, on any of a wide range of devices including desktop or mobile devices, laptops, tablets, smartphones, watches, wearable electronics or other wireless digital/cellular phones, televisions, cloud instances, embedded microcontrollers, thin client devices, or any other suitable computing device known in the art.
Similarly, parts of this invention are described as communicating over a variety of wireless or wired computer networks. For the purposes of this invention, the words “network”, “networked”, and “networking” are understood to encompass wired Ethernet, fiber optic connections, wireless connections including any of the various 802.11 standards, cellular WAN infrastructures such as 3G or 4G/LTE networks, Bluetooth®, Bluetooth® Low Energy (BLE), Bluetooth Mesh, Bluetooth Low Energy Mesh, Zigbee®, or Z-wave communication links, or any other method by which one electronic device is capable of communicating with another. In some embodiments, elements of the networked portion of the invention may be implemented over a Virtual Private Network (VPN).
As used herein, a “MicroZone System” or “MicroZone” is a system where airflow into each space in a HVAC zone can be independently controlled without the need for additional HVAC controllers. For example, a “space” in an HVAC zone can be a living or working space room, a hallway, conference room, or other space usually defined by partitions such as walls and doors. In some instances, a MicroZone may be a subsection of a larger room, for example one half of a gymnasium. The MicroZone allows precise control of airflow to areas smaller than a typical HVAC zone, heating or cooling each MicroZone independently of the other spaces in the HVAC zone. In this way, a MicroZone system may allow for more efficient and more effective equalization of temperature throughout one or more HVAC zones. It is also possible to independently affect the temperature in a single MicroZone by controlling airflow to the MicroZone and periodically reading temperature measurements from one or more MicroZone sensors.
As used herein, a “smart duct” is a duct or portion of a duct that includes an attached actuator and one or more dampers that are moved by the actuator to control airflow. In some embodiments, the smart duct further includes one or more printed circuit boards (PCBs) including for example a microprocessor or microcontroller and a wireless connection. Some smart ducts may also further comprise zero or more sensors for measuring parameters of the air flowing through the duct or the surrounding environment.
MicroZones typically include at least one smart duct that supplies or returns air to the HVAC system. A MicroZone may include one or more smart supply ducts, smart return ducts, bypass smart ducts, or a combination of two or more of these. Each MicroZone also typically includes at least one temperature sensor, the measurements of which are used by one or more controllers to drive air into or out of the MicroZone. Systems of the present invention may also include additional sensors of various types, connected via wired or wireless connections to the one or more controllers. Although smart ducts allow for enhanced control of airflow, a MicroZone system can be constructed with any combination of smart and dumb ducts. For example, it is possible to construct a MicroZone system using only one or more smart supply ducts, only one or more smart return ducts, or only one or more smart bypass ducts, with the remaining ducts in the system being dumb.
A controller of the present invention is configured to intelligently distribute hot or cold air to MicroZones, and to control the temperature in each MicroZone independently of other MicroZones and the existing HVAC zone. In some embodiments, a conventional thermostat may act as the controller, but in other embodiments the controller may also include additional sensors and processing elements. For example, a controller may include a microprocessor or microcontroller, communicatively connected to one or more communication transceivers. These communication transceivers may support one or more wired or wireless communication protocols, including but not limited to Bluetooth, Bluetooth Mesh, Bluetooth Low Energy, Zwave, Zigbee, wi-fi, Ethernet, USB, IR, or any other suitable communication protocol known in the art. In one embodiment, the controller uses the various communication interfaces to gather data from a set of at least one sensor, process the data received from the at least one sensor, and based on the processed data, send control signals to one or more air conditioning units, heaters, air handlers, or smart ducts in order to control air flow for each MicroZone.
Each MicroZone may contain one or more sensors configured to gather relevant parameters about the MicroZone for use by the controller to control temperature and airflow. Examples of such sensors include, but are not limited to, temperature sensors, air quality sensors, air flow sensors, humidity sensors, motion sensors, CO2 detectors, CO detectors, light sensors, smoke sensors, cameras, proximity sensors, microphones, near-field communication (NFC) sensors, load cells, or any other type of sensor that could be useful for controlling HVAC parameters. Sensors of the present invention may be positioned by themselves, or may alternatively be integrated into custom housings or the housings of existing elements of the system or the room. Exemplary sensors may be integrated into a thermostat or other control mechanism for the HVAC system, or may alternatively be positioned within a light switch, a light switch cover, a wall power outlet, a wall power outlet cover, a motion detector, a smoke detector, a CO2 detector, a CO detector, a window frame, a door frame, a hinge, crown molding, a baseboard, a doorknob, a door, a television, a chair, a bed, a sprinkler head, or any other position within a room advantageous for taking the appropriate measurement.
In some embodiments, one or more of the MicroZone sensor measurements may be used by the controller to determine whether or not a person is present in the MicroZone. For example, a motion sensor may monitor movement within the MicroZone, or a sound sensor may measure sounds made by people within the MicroZone. When the controller determines that a person is detected within the MicroZone, the controller may adjust the air temperature or air distribution to compensate. For example, the controller may open one or more smart ducts leading into a MicroZone where a person has been detected, and close one or more smart ducts leading into a MicroZone where no person is detected. By doing so, the MicroZone system will prevent the system from cooling or heating an area of the HVAC zone that is not currently in use by the occupants.
Each MicroZone may have at least one sensor positioned within it, or alternatively multiple MicroZones may share one or more sensors. The sensor or sensors transmits measurements to the controller, either autonomously or on demand when a query signal or message is received from the controller. The controller then processes the measurements and compares them with user settings, to determine which actions to take, for example turning an air conditioner on or off, or opening or closing one or more smart ducts.
In one example, the top floor of a home is hotter than the bottom floor, as detected by temperature sensors placed on the top and bottom floors. If the controller is set to cooling, i.e. to maintain a temperature below a given threshold, the MicroZone system may close one or more smart ducts leading to the bottom floor and open one or more smart ducts leading to the top floor, while activating the air conditioner. In this way, the cool air from the air conditioner will be routed only to the top floor, where it is needed most. The system may additionally or alternatively open a smart bypass or smart recirculation duct, designed to recirculate air from the output of the air handler, or air conditioning unit back into the intake. In this way, the exhaust air that ultimately reaches the vents in the one or more micro zones will be cooler than it otherwise would have been, because longer exposure to the cooling elements leads to more heat being withdrawn. The system may additionally or alternatively open one or more smart return ducts on the bottom floor, drawing cooler intake air from the lower floors. The system may activate the air conditioning unit to further cool the air, or may alternatively simply vent the cooler air from the lower floor to the hotter upper floors without additional cooling. In this way, the system saves significant energy by running the air conditioner less when there is a ready supply of cold air accessible. It is understood that although the foregoing example describes cooling, the same system could work with heating if desired. The system may for example draw hot air from a higher floor for circulation to a lower floor if heating is needed.
In some embodiments, each zone has a return vent and a supply vent, but in other embodiments the vents may be shared by the supply and return ducts. For example, one vent in a MicroZone may have two air flow paths connecting it to the air handler, one at the exhaust and the other at the supply. One or more smart ducts then opens or closes to allow air flow via one path, but not the other.
In another example, an office space on the north side of a building may be naturally cooler in the afternoon than a conference room with south facing windows. The MicroZone system, with the HVAC set to cooling, can open one or more smart ducts that lead to the conference room while closing one or more smart ducts that lead to the office space on the north side of the building. This in effect creates MicroZones in the office space that work with a single controller but whose temperatures can be controlled independently of other MicroZones. The MicroZone system may alternatively draw cool air from the office space on the north side of the building, either to be cooled further or to be vented into the conference room to cool it down.
Smart ducts of the present invention may be manufactured similarly to currently available HVAC air ducts, and may thus easily be made compatible with existing HVAC systems. In some embodiments, the smart ducts may be made from steel or aluminum, though other materials, such as plastic, may also be used. Smart ducts may be made in any size or shape, and may be made to interlock with existing ducts in currently-available HVAC systems. Duct sizes include but are not limited to 4″ round, 20″ round, 10×14″ rectangular, 12×12″ rectangular, 10×22″ rectangular, etc. Smart ducts may include one or more dampers, controlled by one or more actuators and configured to constrict or increase airflow. The damper will in some embodiments be made of the same material as the surrounding duct, or may alternatively be made from a different material. The damper may be substantially round, substantially rectangular, or any other shape as appropriate to allow and constrict airflow through the smart duct. In some embodiments, the smart duct may comprise a spring connected the damper and configured to drive the damper into a default position, for example configured to drive the damper substantially open or substantially closed in the absence of force applied by a motor. In some embodiments, the smart duct further comprises a stop, for example a mechanical stop positioned on an inner surface of the duct, configured to stop the damper from rotating further in a given direction. In some embodiments, a spring is configured to drive the damper against the stop. In other embodiments, the damper may be controlled for example by a stepper motor, or some other motor or mechanical arrangement that preserves the position of the damper when power is not applied.
Smart ducts of the present invention may be modeled after any currently-available duct component, including but not limited to a connector duct that connects two separate ducts, a starting collar duct configured to facilitate transition from a plenum box or HVAC box to a round air duct, a saddle take off, a side take off, a top take off, or any other duct component.
The actuator may be any actuator suitable for moving a damper into position, including but not limited to a motor or a solenoid. The actuator may be any size, shape, speed, or power rating. In some embodiments, the actuator may include a gearing system for multiplying torque. In some embodiments, the actuator is configured to drive the damper to either a substantially closed position (constricting air flow through the duct) or a substantially open position (allowing air to flow freely through the duct). In other embodiments, the actuator may be configured to additionally hold the damper in one or more partially-closed positions, to allow for varying degrees of limited air flow through the duct. In some embodiments, the actuated damper may be configured to close automatically when power is disconnected.
Smart ducts of the present invention may further include one or more microcontrollers, microprocessors, or other processing means. The microcontroller may control the actuator for the damper in response to instructions received from a controller, and may additionally collect data from one or more sensors positioned on or around the smart duct. Sensors that may be used with a smart duct include, but are not limited to an airflow sensor, an air quality sensor, a temperature sensor, a humidity sensor, and a smoke detection sensor. An airflow sensor could be configured, for example, to monitor air flow through the duct to detect that the expected amount of air is flowing. The airflow sensor may also be used as a feedback when adjusting the air flow to meet manufacturer specifications for the duct or system.
An air quality sensor may be used for example to detect and report the quality of the air flowing through the duct. The air quality sensor may be used to notify users of good or bad air quality, and may further be used for example to indicate when an air filter in the HVAC system's intake should be replaced. A temperature sensor may be used to detect the temperature of the air flowing through the duct. This can be helpful for example in determining whether the heating or cooling element is providing exhaust air of an appropriate temperature, and may also be used to determine whether there is a fire or other heat event. In one embodiment, if a smart duct detects a very high temperature, indicating that there is a fire nearby, the smart duct will close so as to slow the spread of the fire. Similarly, a smoke sensor may be positioned in the duct to detect the presence of smoke, and a smart duct may be configured to close automatically when smoke is detected, so as not to circulate smoke to other areas in the HVAC zone. Finally, a humidity sensor of the present invention may be configured to detect the humidity of the air flowing through the duct. Humidity information can then be used to notify users of the humidity or to interact with other systems to adjust humidity of the recirculated air.
A smart duct of the present invention may further include one or more wireless radios or wired connections, configured to communicate with the controller, a hub, a thermostat, a smartphone, the Internet, a remote controlling computer system, or other smart ducts. In some embodiments, each smart duct acts as a repeater for the wireless signals of other smart ducts, allowing for the formation of a mesh network and extending the range at which smart ducts may be placed from the controller, hub, thermostat, or Internet gateway. Exemplary communication messages sent to and from smart ducts include, but are not limited to sensor readings and control signals to direct the dampers open or closed.
Examples of smart ducts for use with a system of the present invention include smart supply ducts, smart return ducts, smart bypass ducts, smart smoke ducts, and smart fire ducts. A smart supply duct can be used for example to intelligently distribute air to spaces that require warm or cool air from the HVAC system. Working with other smart ducts, each supply duct can dynamically control the flow of air that goes to each MicroZone, cooling or heating MicroZones that need it and inhibiting wasteful airflow into any MicroZone that doesn't. For example, if a home has two floors and the top floor is warmer than the bottom floor when the HVAC is in cooling mode, a smart supply duct can restrict cold airflow into the bottom floor and open airflow into the top floor. This will more efficiently cool the home and better equalize the temperature throughout the home.
A smart return duct intelligently controls the airflow into the HVAC system. In one example, the air in the top floor of a home is hotter than the air in the bottom floor, and the HVAC is set to cooling. In this example, a smart return duct can intelligently choose to draw air from the bottom floor and, working with a smart supply duct, expel it to the top floor helping to save energy and equalize the temperature throughout the home more efficiently.
A smart bypass duct allows supply air to be directed to the return of the HVAC system. HVAC manufacturers require proper airflow in cfm (cubic feet per minute) to ensure proper operation of the HVAC system. Smart bypass ducts can be used to help control this airflow and allow for more efficient cooling or heating of the air, as already-heated or cooled air is returned directly into the HVAC system for further heating or cooling. Smart bypass ducts can also be intelligently controlled by measuring the airflow in the smart supply ducts. For example, if the smart supply ducts do not detect enough airflow per the manufacturers specifications, one or more smart bypass ducts can be opened or adjusted to facilitate proper airflow through the HVAC system.
A smart smoke duct has a smoke detection sensor that detects the presence of smoke in the air that is passing through the duct. Upon detection of a large amount of smoke, the smart smoke duct closes, preventing the return or supply of the smoke into and out of the HVAC system. Similarly, a smart fire duct has a temperature sensor that reads the temperature of the air flowing through the duct. When the smart fire duct detects an extremely high temperature, the smart fire duct closes, preventing the return or supply of fire or extremely hot air through the HVAC system or to the HVAC zone.
With reference now to
With reference now to
With reference to
The behavior of a MicroZone system in two exemplary situations may be illustrated with reference to
In a second situation, the second floor of a home is warmer than the first floor of a home, but the system is set to heating (i.e. maintain the temperature in the entire home above a set threshold). In this second example, the MicroZone system pulls air from the second floor and/or the first floor of the home using the second floor return vent 16 (by opening second floor smart return duct 5) and first floor return vent 19 (by opening first floor smart return duct 4). The air is then heated by HVAC unit 1 and supplied to rooms 12 and 14 on the first floor using supply air vents 18 and 20 (by opening first floor smart supply duct 8). Smart supply duct 7 is closed, so that none of the supply air from the supply plenum box 3 gets distributed to the top floor rooms 9 and 11, because those rooms are already warm. Smart bypass duct 6 may also be opened to increase the efficiency of the HVAC system. In this way, the MicroZone system more efficiently heats the whole home to a uniform temperature.
Two further examples may be illustrated with reference to
In a second example, rooms 11 and 14 on the east side of a house are warmer than rooms 9 and 12 on the west side of the house, and the system is set to heat. In this example, the system pulls air from the first and second floors of the home using first and second floor return vents 16 and 19. The air is heated in HVAC system 1 and suppled to rooms 9 and 12 through supply vents 15 and 18, by opening smart supply ducts 7 and 26. Smart supply ducts 8 and 27 are closed, meaning that none of the heated air will flow to rooms 11 and 14, which are already sufficiently warm.
Two further examples of commercial applications may be illustrated with reference to
In the first example, the north facing rooms 14, 15, and 16 are warmer than the south facing rooms 17 and 19, and room 20 has a temperature near the thermostat set temperature. In a typical office environment, there are no return vents or return ducts within the office. By closing supply ducts where the temperature is at or below the set temperature, higher levels of efficiency can be achieved. Because the north facing rooms are warmer than the desired temperature, as measured by sensors 2, 6, and 8, the smart supply ducts 3, 7, and 9 that lead to those rooms are opened to allow cooled air into the rooms. Because rooms 17 and 19 are already sufficiently cool, as detected by sensors 4 and 12, the MicroZone system closes smart supply ducts 5 and 13 to prevent cooled air from the central duct or VAV 21 from further cooling rooms 17 and 19. The smart supply duct 14 leading to room 20 is also closed, because the temperature in room 20 is near the desired temperature. If the temperature in any of these rooms increases above the desired temperature, the corresponding smart supply ducts leading to those rooms is opened, in order to cool the rooms until the desired temperature is reached. In this way, the MicroZone system is capable of dynamically controlling the temperature in each MicroZone.
In a second example, where the system is set to heating, the MicroZone system will supply air to rooms where the temperature is cooler than the thermostat set temperature. Ducts that lead to rooms that are above or near the thermostat set temperature will be closed to maintain the temperature above or near the thermostat set temperature. The north facing rooms 14, 15, and 16 in the second example are cooler than the south facing rooms 17 and 19 and room 20 has a temperature near the thermostat set temperature. The smart supply ducts 3, 7, and 9 that lead to rooms 14, 15, and 16 are opened to allow warmer air into the room. Smart supply ducts 5 and 13, leading to rooms 17 and 19, and closed to prevent warmer air from further warming the rooms. Smart supply duct 14, leading to room 20, is also closed because the temperature is near the desired temperature. If the temperature in any of these rooms falls below the desired temperature, the smart supply ducts leading to those rooms are opened in order to warm the room until the desired temperature is reached.
A MicroZone system of the present invention may further comprise a Variable Air Volume (VAV) air handler or VAV box. In some HVAC systems, particularly multi-unit HVAC systems, a single large HVAC unit is used to provide conditioned air to multiple zones in a building. Some embodiments of the present invention include a VAV box in addition to an HVAC unit, while in other embodiments, some or all of the functions otherwise performed by the HVAC unit for the purposes of the invention (for example, providing conditioned air, consuming unconditioned air) are instead effectively performed by the VAV box. In some embodiments, the VAV box is controlled by the controller, while in other embodiments the VAV box is controlled independently from the system of the present invention.
Referring now to
Referring now to
A detail view of smart duct placement is shown in
With reference to
Referring now to
Referring now to
Referring now to
The disclosures of each and every patent, patent application, and publication cited herein are hereby incorporated herein by reference in their entirety. While this invention has been disclosed with reference to specific embodiments, it is apparent that other embodiments and variations of this invention may be devised by others skilled in the art without departing from the true spirit and scope of the invention. The appended claims are intended to be construed to include all such embodiments and equivalent variations.
This application claims priority to U.S. Provisional patent application No. 62/632,480, filed on Feb. 20, 2018, incorporated herein by reference in its entirety.
Number | Date | Country | |
---|---|---|---|
62632480 | Feb 2018 | US |