Not applicable.
Not applicable.
This invention relates generally to a method and apparatus for automatic control of multiple pumps operated either in parallel (to increase flow rate to and/or from the process) or in series (to increase the overall head). More specifically, the invention relates to a method for manipulating the operation of pumps, thereby preventing them from reaching their minimum flow limit until process requirements are such that all pumps must reach their respective limits. This course of action drastically reduces the chances of damage due to operation beyond the above-mentioned limit, as well as reducing the likelihood of inefficient recycling (to avoid running below the pumps' minimum flow limits).
Multiple centrifugal or axial pumps are frequently installed in piping systems to increase the overall flow rate to a process (in this case, pumps are operated in parallel), or to increase the overall head produced by the pump combination (pumps are operated in series).
Typically, there is a minimum flow limit to the acceptable flow through a pump. When flow rates are “low,” some pumps experience higher levels of vibration and noise, as well as elevated temperatures (due to low efficiencies). This minimum flow limit is referred to as the Minimum Continuous Stable Flow (MCSF) limit. The level at which vibration or noise becomes unacceptable is specified by the customer, often referring to an industry standard.
Additionally, when pumps are piped in parallel, there may be a range of operation where two flow rates exist for each head value; this occurs when pump performance curves exhibit a point at which the slope is zero when the flow is greater than zero. When two or more pumps are operated in parallel, it is possible for the operating point in a set of pumps to oscillate rapidly between these two flow rates while always maintaining the required head. This rapid change in flow rate can damage or destroy a pump and should be avoided. Many pumps are fitted with recycle or bypass valves for maintaining an adequate flow rate to avoid operating in this hazardous region.
Many pumps are driven with variable-speed drivers such as steam turbines. Varying a pump's speed can be used to control its performance. An alternative is to throttle the discharge valve to maintain performance. When multiple pumps are operated in a network, either parallel or in series, the control objective (usually a flow rate or pressure) can be divided between the pumps in an infinite number of ways.
Present-day speed control systems (for multiple pumps) do not consider the low flow limit. For example, one pump may be running at a high flow rate, while another pump requires an open recycle valve to maintain operation above its MCSF limit. This approach not only increases the risk of a pump operating beyond of its MCSF limit, but it is also inefficient. For these reasons, there is need of a more extensive approach for controlling multiple pumps operating in a network of pumps.
A purpose of this invention is to provide a method for controlling a set of pumps (centrifugal or axial) in a manner that reduces the chance of any pump operating in a zone in which damage or destruction, such as the Minimum Continuous Stable Flow (MCSF) limit, is likely to occur. Another purpose is to control a plurality of pumps, such that inefficient recycling or throttling is kept to a minimum.
To accomplish these objectives, pump performance curves are converted through a coordinate transformation known as affinity laws or pump laws that reduces three-dimensional maps to two-dimensional maps. An additional transformation maps the stable operating regions into a given range, e.g., S≦1. All pumps are operated so as to equalize their values of S; in this way, no pump arrives at its MCSF limit until all pumps arrive at their respective limits. Therefore, inefficient recycling is avoided until absolutely necessary.
When operating two or more centrifugal or axial pumps 103, 104 (
Pump performance can be controlled through changes in rotational speed (see
Acceptable flows for most pumps 103, 104 lie to the right of a limit, as shown in
The control system is not concerned with the actual MCSF limit 401, but rather with an artificial limit situated a safe distance from the actual pump MCSF limit 401. The distance between the actual MCSF limit 401 and the control-system limit (referred to here as the “control limit”) is the safety margin. The pump map (
By performing dimensional analysis on the important pump-variables, it is found that only two variables are required to describe a pump's characteristics: the flow coefficient [Q/(D3N)] and the head coefficient [Hg/(DN)2], where g is the acceleration of gravity and D is a characteristic length of the pump. These coefficients are part of the well-known pump laws or affinity laws. The four pump-characteristic curves of
A simple scaling of the pump map (
where K=Q2/H on the actual MCSF limit 401, not the control limit [or K=(Q2/H)MCSF] and b is the safety margin. Curves 601–605 each having a constant S values are shown in
In
where Δpp is the pump differential pressure signal from the pump differential pressure transmitter, ΔPT 800, and Δpo is the differential pressure signal from the flow meter differential pressure transmitter, FT 810. A division block 820 produces the quotient, Δpp/Δpo. Multiplying this quotient by a constant, K 830, in a multiplier block 840 and summing this product with b 850 in the summation block 860 produces the value of S 870.
Many (in fact, an infinite number) other ways to scale the pump performance curve are available. Any scaling making the MCSF control limit a constant (and known) value may be valid and would be considered equivalent in the context of this invention. Other obvious choices include:
where, for Eq. 2, K=(N/Q)MCSF and for Eq. 3, K=(N/Q)2MCSF and, again, b represents the safety margin in each case. Each of the definitions of S (Eqs. 1–3) are equivalent, and many others are also valid. This invention is not limited to these definitions of the scaling, S.
Once S 870 is calculated using any of Eqs. 1–3 (or an equivalent form), the control system's job is to equalize the value of S 870 for all pumps 103, 104 during their operation while, simultaneously, process demands are met. A master PID controller 1201 (
A pair of load-sharing PID controllers 1202, 1203 (one for each pump 103, 104) are dedicated to equalizing (balancing) the values of S 870, which takes place somewhat slower than the master PID controller's 1201 action, to maintain the process variable on set point; as a result, balancing will not disturb the process.
There is also an advantage to scaling the pump performance maps in a given network: all S's 870 may be scaled to have the same value at the maximum-efficiency point for each pump; then, as the control system manipulates pump performance, such that the values of S 870 are equal, each pump 103, 104 will be the “same distance” from its highest efficiency.
An additional embodiment of this invention is shown in
where B is the parameter to be equalized for all pumps, and f(M) represents the balancing criterion used to the right of the region 1302 of
Details of the
The master controller 1201 inputs to two summation blocks 1207, 1208; each summation block 1207, 1208 receives a signal from its corresponding load-sharing controller 1202, 1203. Once these signals are summed, the summation blocks' outputs set the positions of the steam valves 1110, 1111 (or throttling valves 101, 102 for constant rotational speed operation). These control actions may also be carried out in a split range approach, where the steam valves 1110, 1111 are manipulated until the rotational speed of the pumps reaches a lower limit, then the throttling valves 101, 102 are manipulated to further reduce the process flow rate.
Not shown are checks to determine if any pump has reached a speed limit (maximum or minimum). In case of a speed-limited pump, controllers would be prohibited from sending a signal that would cause the speed to move further into its limit; and the integral portion of the controllers would be turned off to eliminate integral windup.
Two minimum-flow PID controllers 1211, 1212 are dedicated to keeping pumps from crossing the MCSF control limit. As shown in
When all pumps 103, 104 reach their respective MCSF limits 600, varying the speed alone cannot keep them from crossing their limits while maintaining the process variable on its set point. If the MCSF limit is reached by all pumps, the overall recycle valve 105 is then opened by the minimum-flow PID controllers 1211, 1212 which permits sufficient flow to maintain stable and safe operation of all pumps 103, 104. Rotational speeds must also be manipulated simultaneously to keep all pumps on their respective control lines.
Referring back to
This open-loop control action is intended to prevent pump damage due to large, fast transients. The predetermined amount of opening of the recycle valve, can be made variable during pump operation as shown in
If the instantaneous value of S 870 is not greater than the open-loop limit, SOL 620, no additional change is made to the control system's valve-position set points.
Note that, if S 870 is calculated by Eq. 2 or Eq. 3, the comparison block 1405 would check if S<SOL. The rest of the flow diagram in
Often, an open-loop response will be applied only once; after that, the pump 103, 104 returns to safe operation. If this is not the case, a process illustrated in
When a pump reaches its minimum-flow, open-loop limit (after opening the valve by the open-loop response), the recycle valve 105 is ramped closed at a predetermined rate, yet sufficiently slow to avoid returning the pump into the MCSF region 403. As the valve ramps closed, the closed-loop control system will take control of the valve when the operating point once again reaches the MCSF control limit.
As mentioned, some process functions are not unique; for example, normalizing of the flow coordinates, configuration of the pump network, and destination of the control system's outputs. The present invention is not limited to those examples described above, but may be realized in a variety of ways.
Obviously many modifications and variations of the present invention are possible in light of the above teachings. It is, therefore, to be understood that within the scope of the appended claims, the invention may be practiced otherwise than as specifically described.
This application contains disclosure from and claims the benefit under Title 35, United States Code, §119(e) of the following U.S. Provisional Application: U.S. Provisional Application Ser. No. 60/390,072 filed Jun. 20, 2002, entitled METHOD AND APPARATUS FOR CONTROLLING MINIMUM CONTINUOUS STABLE FLOW OF A PUMP STATION WITH MULTIPLE DYNAMIC PUMPS.
Number | Name | Date | Kind |
---|---|---|---|
5347467 | Staroselsky et al. | Sep 1994 | A |
6045332 | Lee et al. | Apr 2000 | A |
6217288 | Mirsky et al. | Apr 2001 | B1 |
6602057 | Saxena et al. | Aug 2003 | B1 |
Number | Date | Country | |
---|---|---|---|
20030235492 A1 | Dec 2003 | US |
Number | Date | Country | |
---|---|---|---|
60390072 | Jun 2002 | US |