The present invention relates to an electronic transformer for interfacing with DC transmission.
Historically, there has not been much use of DC-DC converters in the power range of tens and hundreds of MW, because of insufficient market need and the lack of suitable technology. However, the market demand for DC-DC connection has significantly increased in recent years as increasing numbers of power sources which generate DC are developed. DC power sources which approach power levels in the multiple MW range include: —fuel cells, photovoltaics, batteries and redox flow [1,2]. Additionally, variable speed machines such as permanent magnet wind generators or small hydro generators may be viewed as DC sources if the last converter stage is removed [3]. Furthermore, most electrical storage and load levelling devices use some form of DC storage media, such as, batteries, supercapacitors, capacitors, superconducting magnetic energy storage, etc). Many of these DC sources utilise very low voltage basic cell, or require wide variation of DC voltage. Consequently, their integration into the power grid has traditionally been difficult.
The rapid development of High Voltage DC (HVDC) transmission technologies is also driving demand for DC-DC converters. The recently developed HVDC light, ie HVDC with Voltage Source Converters (VSC HVDC), [4] has been implemented in many interconnections and shows many benefits compared with the traditional thyristor based HVDC. Virtually all existing HVDC schemes, both line commutated and VSC HVDC, operate as two-terminal systems. However, there is significant incentive to develop the technology to provide additional access points to the existing HVDC lines. A suitable MW size DC-DC converter would enable tapping on HVDC lines and aid development of multi-terminal HVDC. In particular, the recent development of offshore renewable sources creates the scenario of distributed DC sources with the requirement for submarine DC transmission and DC/DC voltage stepping at MW power levels.
A high-power DC transformer is needed to connect a DC transmission network with another DC network at a different DC voltage level, or to connect DC sources and loads.
DC-DC converters have been extensively utilized at low power levels, and many topologies exist. However, most low power converter technology is unsuitable for scaling up to MW power levels.
Conventional, unidirectional boost converters [5] can not achieve gains larger than 2-4, or higher powers, due to difficulties with the output diode and poor efficiency.
There have been attempts to develop converters with an internal AC transformer, for example flyback and forward converters [5-7], at higher power levels. However, some serious inherent limitations in terms of stepping ratios and power levels have been demonstrated. Reference [1] studies scaling up to 5 kW with a stepping ratio of 5, and [2] describes a 100 kW, 14 kV forward converter. However, these converters utilise MOSFETs (Metal-Oxide-Semiconductor Field-Effect Transistor) as switches with around 10 kHz frequency, which gives little prospect for further increasing to MW power levels, where IGBT (Insulated-Gate Bipolar Transistor) switches are required and lower frequency.
Parallel resonant converters can achieve high step-up gain [5]. The main limitations of these topologies are caused by increased switching losses, poor power quality, poor power factor and switch utilization, difficulties with power direction reversal and control difficulties.
Switched capacitor converters have been proposed as a method of achieving high DC boost without transformers or inductors [8]. However, each module only increases the output voltage by the value of the input voltage. Thus, to achieve a stepping ration of 10, for example, 9 modules are needed and over 18 switches. This results in significant losses and complexity.
A resonant LCLC circuit has been proposed for applications with high-frequency ballast lighting, which shows the capability of transformerless step-down operation [9]. However, such a converter is only suitable for driving a passive capacitive load (two LC circuits), and uses frequency control.
LCL-T resonant converters give improved performance at high power. However, an internal AC transformer is required to achieve voltage stepping [10]. The internal transformer increases weight and losses, and creates difficulties in the case of faults. Moreover, these converter topologies are normally used with one active bridge and one diode bridge, which precludes power reversal.
An LCL resonant converter which does not require a transformer has been proposed for an induction heating application [11]. However, this converter operates as an LCLR circuit and is only suitable for supplying a passive resistive load.
The topologies of [9,10,11] use a single active bridge and must employ a transformer for voltage stepping.
Most of the above topologies have destructive currents under DC fault conditions. DC faults are very important with high power systems because of difficulties in interrupting high fault currents.
A step-up DC-DC converter without internal voltage transformers has been proposed recently [12-15]. This converter can achieve very high step-up gains with a MW range test system, and bidirectional operation is possible. The switches on the low voltage side of this converter should be rated for P12*n12, where P12 is the power transfer and n12 is the stepping ratio (n12=V1/V2). This represents a low switch utilisation factor with consequent disadvantages in terms of cost and increased losses. A further limiting factor of this converter is the low switching frequency caused by the use of thyristor switches, which have a long turn off time and introduce reverse recovery issues.
According to one aspect of the present invention there is provided a converter for transferring power between a first DC system of DC voltage V1 and a second DC system of DC voltage V2, the converter comprising: —
a first AC/DC converter for transforming DC voltage V1 into a first single phase AC voltage V1ac, of frequency ω, RMS line-neutral magnitude V1acm and angle α1;
a second AC/DC converter for transforming DC voltage V2 into a second single phase AC voltage V2ac, of frequency ω, RMS line-neutral magnitude V2acm and angle α2; and
two inductors L1,L2 and a capacitor C, wherein the first terminals of the inductors and capacitor are connected together, the second terminal of inductor L1 and the second terminal of the capacitor C are connected to the first AC voltage V1ac, and the second terminal of inductor L2 and the second terminal of the capacitor C are connected to the second AC voltage V2ac;
wherein the value of the capacitor C, inductor L1 and inductor L2 are selected to enable required power transfer and to
minimise current in inductor L1,
and/or minimise current in inductor L2,
Preferably, for maximum power transfer in one direction, the converter is operated such that the difference between the AC voltage angles α1,α2 is substantially
and, for maximum power transfer in the opposite direction, the converter is operated such that the difference between the AC voltage angles α1,α2 is substantially
Thus, with the present invention, power can be transferred between DC systems without the need for an internal transformer. Moreover, any stepping ratio at low losses can be achieved, unlike other LCL converters such as those disclosed in [11]. Moreover, the converter of the invention can use faster switches such as IGBT, with turn-off capability and no reverse blocking, which represents an improvement over thyristor switches as used in previous DC/DC transformerless converters such as those disclosed in [12, 13]. Furthermore, the converter of the invention is based on a voltage-source approach, whereas previous DC/DC transformerless converters such as those disclosed in [12, 13] are based on a current source approach. Additionally, the converter of the invention achieves excellent DC fault response, which is important for high-power applications. These advantages apply equally to the other aspects of the invention defined below.
According to a second aspect of the present invention there is provided a converter for transferring power between a first DC system of DC voltage V1 and a second DC system of DC voltage V2, the converter comprising: —
a first AC/DC converter for transforming DC voltage V1 into a first p phase AC voltage V1ac of frequency ω, RMS line-neutral magnitude V1acm and angle α1;
a second AC/DC converter for transforming DC voltage V2 into a second p phase AC voltage V2ac, of frequency ω, RMS line-neutral magnitude V2acm and angle α2; and
a resonant circuit for each phase p, wherein each resonant circuit comprises two inductors L1,L2 and a capacitor C connected together at their first terminals, the second terminal of inductor L1 being connected to the respective phase of the first AC voltage V1ac, and the second terminal of inductor L2 being connected to the respective phase of the second AC voltage V2ac;
wherein the value of the capacitor C, inductor L1 and inductor L2 are selected to satisfy:
k
1=1−ω2L2C
k
2=1−ω2L1C
k
3
=L
1
+L
2−ω2L1L2C
and where k1 is selected in the region:
and where
and where P12 represents maximum power transfer by the converter.
Preferably, for maximum power transfer in one direction, the converter is operated such that the difference between the AC voltage angles α1,α2 is substantially
and, for maximum power transfer in the opposite direction, the converter is operated such that the difference between the AC voltage angles α1,α2 is substantially
With the second aspect of the invention, the principles of the invention are applied to a p phase converter. The number of phases p may be any positive integer, preferably 1, 2 or 3. It will be appreciated that the case where p=1 corresponds to a single phase converter, and is equivalent to the first aspect of the invention.
According to a third aspect of the present invention there is provided a converter for transferring power between n first DC systems respectively of DC voltage V1i (i=1, 2, . . . n) and m second DC systems respectively of DC voltage V2j (j=1, 2, . . . m), where n and m are each any positive integer, the converter comprising: —
n AC/DC converters for respectively transforming DC voltages V1i into respective p phase AC voltages V1iac of frequency ω, RMS line-neutral magnitude V1iaCm and angle α1i;
a LCL circuit for each phase p, wherein each LCL circuit comprises n inductors L1i, m inductors L2j and a capacitor C connected together at their first terminals, the second terminal of each inductor L1i being connected to the respective phase of the respective AC voltage V1iac, and the second terminal of each inductor L2j being connected to the respective phase of the respective AC voltage V2jac;
wherein
wherein the value of the capacitor C, each inductor L1i and each inductor L2j are selected to enable required power transfer and to
minimise current in inductors L1i,
and/or minimise currents in inductors L2j,
Preferably, for maximum power transfer in one direction, the converter is operated such that the difference between the AC voltage angles α1i,α2j is substantially
and, for maximum power transfer in the opposite direction, the converter is operated such that the difference between the AC voltage angles α1i,α2j is substantially
Preferably, the converter is operated such that, for power transfer, the AC voltage angle (s) α1i is/are substantially 0 degrees; and the AC voltage angle (s) α2j is/are substantially
for maximum power transfer in one direction, and substantially
for maximum power transfer in the opposite direction.
With the third aspect of the invention, the principles of the invention are extended to a converter with n terminals on one side and m terminals on the other side. n and m may each be any positive integer and are not necessarily equal. It will be appreciated that if n=m=1, the third aspect of the invention is equivalent to the second aspect of the invention, and that if n=m=1 and p=1, the third aspect of the invention is equivalent to the first aspect of the invention. As with the second aspect of the invention, the number of phases p may be any positive integer, preferably 1, 2 or 3.
According to a fourth aspect of the invention, there is provided a converter for transferring power between a p phase AC system of AC voltage V1ac of frequency ω, RMS line-neutral magnitude V1acm and angle α1 and a DC system of DC voltage V2, the converter comprising: —
an AC/DC converter for transforming DC voltage V2 into a p phase AC voltage V2ac, of frequency ω, RMS line-neutral magnitude V2acm and angle α2; and
a LCL circuit for each phase p, wherein each LCL circuit comprises two inductors L1,L2 and a capacitor C connected together at their first terminals, the second terminal of inductor L1 being connected to the respective phase of AC voltage V1ac, and the second terminal of inductor L2 being connected to the respective phase of AC voltage V2ac;
wherein the value of the capacitor C, inductor L1 and each inductor L2j are selected to enable required power transfer and to
minimise current in inductor L1,
and/or minimise currents in inductors L2j,
Preferably, for maximum power transfer in one direction, the converter is operated such that the difference between the AC voltage angles α1,α2 is substantially 270 degrees and, for maximum power transfer in the opposite direction, the converter is operated such that the difference between the AC voltage angles α1,α2 is substantially 90 degrees.
With the fourth aspect of the invention, the principles of the invention are extended to a converter for transferring power between an AC system and a DC system. As compared with the first and second aspects of the invention, the first AC/DC converter is omitted, and the resonant circuit associated with each phase is connected directly to the respective phase of the AC voltage source.
According to a fifth aspect of the invention, there is provided a converter for transferring power between a p phase AC system of AC voltage V1ac of frequency ω, RMS line-neutral magnitude V1acm and angle α1, and m DC systems respectively of DC voltage V2j (j=1, 2, . . . m), where m is any positive integer, the converter comprising: —
a resonant circuit for each phase p, wherein each resonant circuit comprises an inductor L1, m inductors L2j and a capacitor C connected together at their first terminals, the second terminal of each inductor L1 being connected to the respective phase of the respective AC voltage V1ac, and the second terminal of each inductor L2j being connected to the respective phase of the respective AC voltage V2jac;
wherein the value of the capacitor C, inductor L1 and inductor L2 are selected to enable required power transfer and to
minimise currents in each inductor L1i,
and/or minimise current in inductors L2
Preferably, for maximum power transfer in one direction, the converter is operated such that the difference between the AC voltage angles α1,α2j is substantially 270 degrees and, for maximum power transfer in the opposite direction, the converter is operated such that the difference between the AC voltage angles α1,α2j is substantially 90 degrees. [j1]
With the fifth aspect of the invention, the principles of the invention are extended to a converter for transferring power between an AC system and m DC systems, where m may be any positive integer.
In all aspects of the invention, we aim minimizing current through inductors and therefore minimizing losses and stress in the switches and inductors. This is equivalent to minimizing reactive power circulation within each side of the converter.
According to the second aspect of the invention all values of k1 in the range
will give zero reactive current at low voltage (angle of I1ac is equal to angle of V1ac) and at high voltage side (angle of I2ac is equal to angle of V2ac), if other conditions are satisfied. All values for k1 in the above range imply minimal magnitude of I1ac and I2ac.
The actual value for k1 will depend on the other design goals. Large positive values will give small values for inductors but the switching losses will be high. The value k1=k2=0 will give best responses under DC faults but will still give large currents switching instants and switching losses. A very large negative k1 implies minimal switching losses but the dynamic stability will be poor since natural resonance mode will be close to the switching frequency.
In all aspects of the invention, the converter preferably comprises control means for controlling power flow though the converter, wherein said control means comprises: —
means for varying AC voltage magnitude by changing the width of the AC pulses;
varying the angle difference between the AC sources; and/or
varying the operating frequency of the converter.
Preferably, the first DC system is a low voltage system and the second DC system is a high voltage system. That is to say, V1 is preferably lower than V2.
The AC voltages V1ac,V2ac of the two AC/DC converters are described as p phase AC voltages. That is, the AC/DC converters are configured to transform the respective DC voltage into an AC voltage with p phases, where p may be any positive integer value. Thus, for example, the AC voltages V1ac,V2ac may be single phase, 2 phase, 3 phase etc.
It will be appreciated that, in the case of converters with a single terminal on each side, the inner resonant circuit of a single phase converter will comprise one L1 inductor, one L2 inductor and one capacitor, whilst the inner resonant circuit of a 2 phase converter will comprise two L1 inductors, two L2 inductors and two capacitors C, and so on. More generally, the number of inductors L1i,L2j depends on the number of terminals on the respective side of the converter, as well as the number of phases, whereas the number of capacitors C only depends on the number of phases.
The DC/AC converters may each comprise 2p switches arranged as a bridge (or a half bridge), for transforming a DC voltage into a p phase AC voltage in known manner. Each bridge/half bridge may comprise p legs, where each leg comprises two switches, and corresponds to a different phase of the converter.
In cases where the converter has more than one phase, the second terminals of the capacitors are preferably connected to a common point, ie, in a star configuration. However, as with any other AC system, the capacitors may be connected in other configurations. For example, in delta configuration in the case of a 3 phase converter.
Where sides of the converter are referred to, this is with reference to the inner resonant circuits. In general there will be a low voltage side and a high voltage side, wherein the low voltage side is connected to a relatively low DC voltage and the high voltage side is connected to a relatively high DC voltage. The first DC system(s) of the first to third embodiments may be low voltage system(s) and the second DC system(s) may be high voltage system(s), ie V1 (or V1i) may be a relatively low and V2 (or V2j) may be relatively high. However, it will be appreciated that the DC voltages on each side of the converter may be equal.
It will be appreciated that in all aspects of the invention, the converter may be operated at less than maximum power by varying the (difference between) the AC voltage angles α1,α2 (or α1i,α2j) or varying the voltage magnitudes V1ac, or V2acm. Thus, whilst the converter may be operated for maximum power transfer by setting the difference between the AC voltage angles to be, for each k1,
and for case
substantially 270 or 90 degrees, operation at lower k1=0 it is powers may be achieved by varying the difference between these angles. In general, a difference in the range 180-360 degrees will give power transfer in one direction, and a difference in the range 0-180 degrees will give power transfer in the opposite direction.
It will be appreciated that a p phase AC system has p connecting nodes (wires).
In general, features described herein in relation to one aspect or embodiment of the invention may also be applied to any other aspect or embodiment of the invention described herein, either alone or in combination with other features.
According to an aspect of the invention there is provided a converter for transferring power up to maximum level P12 between a DC system of low voltage V1 and a DC system of high voltage V2, comprising of:
an AC/DC converter transforming DC voltage V1 into a single phase AC voltage Vac1, of frequency ω, root mean square magnitude Vac1m and angle α1,
an AC/DC converter transforming DC voltage V2 into a single phase AC voltage VaC2, of same frequency ω, root mean square magnitude VaC2m and angle α2,
two inductors and a capacitor connected in a star L1CL2 circuit at their first terminals; the second terminal of capacitor C and second terminal of first inductor L1 connecting to the first AC voltage Vac1, the second terminal of the capacitor C and the second terminal of the second inductor L2 connecting to the second AC voltage Vac2,
where the components L1, C and L2 are selected for maximum power transfer at minimal losses as:
k
1=1−ω2L2C
k
2=1−ω2L1C
k
3
=L
1
+L
2+ω2L1L2C
and where k1 is selected in the region:
and where
and operated in such way that for maximum power transfer the difference between AC voltage angles is
for one power direction, or
for the opposite power direction.
According to an aspect of the invention there is provided a converter for transferring power up to maximum level P12 between a DC system of low voltage V1 and a DC system of high voltage V2, comprising of:
an AC/DC converter transforming DC voltage V1 into a p phase AC voltage Vac1, of frequency ω, root mean square magnitude Vac1m and angle α1,
an AC/DC converter transforming DC voltage V2 into a p phase AC voltage Vac2, of same frequency ω, root means square magnitude Vac2m and angle α2,
two inductors and a capacitor per each phase connected in a star L1CL2 circuit at their first terminals; the second terminal of first inductor L1 connecting to one phase of first AC voltage Vac1, the second terminal of the second inductor L2 connecting to corresponding phase of the second AC voltage Vac2, and the second terminals of all capacitors C connected to a common point
where the components L1, C and L2 are selected for maximum power transfer at minimal losses as:
k
1=1−ω2L2C
k
2=1−ω2L1C
k
3
=L
1
+L
2−ω2L1L2C
and where k1 is selected in the region:
and where
and operated in such way that for maximum power transfer the difference between AC voltage angles is
for one power direction, or
for the opposite power direction.
According to an aspect of the invention there is provided a converter having n DC terminals on low voltage side and m DC terminals on high voltage side, transferring up to maximum power Pnm between low voltage and high voltage side, and comprising of:
n, AC/DC converters transforming DC voltages V1i (i=1, 2, . . . n), into p phase AC voltages Vac1i, of frequency ω, root mean square magnitude Vac1im and angle α1,
m, AC/DC converter transforming DC voltages V2j (j=1, 2, . . . m), into a p phase AC voltage Vac2j, of same frequency ω, magnitude Vac2jm and angle α2,
n L1 inductors, m L2 inductors and a capacitor C per each phase connected in a star L1CL2 connection at their first terminals, the second terminals of inductors L1i connecting to one phase of AC voltages Vac1i, the second terminals of inductors L2j connecting to respective phases of AC voltages Vac2j, and the second terminals of all capacitors C connected in a common point
where the components L1, C and L2 are selected for maximum power transfer and minimal currents. One feasible solution is:
the capacitor:
the inductors L1=n/(ω2C), L2=m/(ω2C)
operated in such way that for maximum power transfer the AC voltage angles at low voltage side are α1i=0 and the AC voltage angles at high voltage side are α2j=270 for one power direction, but the AC voltage angles at high voltage side are α2j=90 for the opposite power direction.
According to an aspect of the present invention there is provided a converter for transferring power up to maximum level P12 between a p phase AC system of voltage Vac1 with frequency ω, root mean square magnitude Vac1m, angle α1, and a DC system of voltage V2, comprising of:
an AC/DC converter transforming DC voltage V2 into a p phase AC voltage Vac2, of frequency ω, root means square magnitude VaC2m and angle α2,
two inductors and a capacitor per each phase connected in a star L1CL2 circuit at their first terminals; the second terminal of first inductor L1 connecting to one phase of AC voltage Vac1, the second terminal of the second inductor L2 connecting to corresponding phase of the voltage Vac2, and the second terminals of all capacitors C connected to a common point
where the components L1, C and L2 are selected for maximum power transfer at minimal losses as:
k
1=1−ω2L2C
k
2=1−ω2L1C
k
3
=L
1
+L
2−ω2L1L2C
and where k1 is selected in the region:
and where
and operated in such way that for maximum power transfer the difference between AC voltage angles is for
one power direction, or
for the opposite power direction.
Preferably, power flow is controlled using one of the following methods:
a) varying AC voltage magnitude by changing width of the AC pulses,
b) varying the angle difference between the AC sources,
c) varying the operating frequency.
Embodiments of the present invention will now be described with reference to the accompanying drawings in which: —
a shows a 2 terminal, single phase DC/DC converter with half-bridge which embodies the invention;
b shows a 2 terminal, 2 phase, DC/DC converter which embodies the invention;
c shows a 2 terminal, 3 phase, DC/DC converter which embodies the invention;
a-4b illustrate the results of a PSCAD/EMTDC simulation of normal operation of a 2 terminal 2 phase converter;
a-5b illustrate the response of the PSCAD/EMTDC simulation to a change in control angle γ1, for a 2 terminal 2 phase converter;
a-6b illustrate a PSCAD/EMTDC simulation of a reversal in power transfer direction, for a 2 terminal 2 phase converter;
a-7b illustrate the response of the PSCAD PSCAD/EMTDC simulation after a zero impedance fault on V2;
a-10e illustrate the results of a PSCAD/EMTDC simulation of the 3 terminal 2 phase converter shown in
a-13c illustrates the response of a PSCAD PSCAD/EMTDC simulation of a 2 terminal 2 phase DC/AC converter for a low impedance fault on 80 kV DC bus; and
a to 1b illustrate three DC/DC converters which embody the invention. The converters of
It will be appreciated that power may be transferred from the low voltage system to the high voltage system or from the high voltage system to the low voltage system. Thus, each voltage system may be either a source or sink, depending on the direction of power transfer.
a shows the single phase topology of the converter. The converter comprises a low voltage DC/AC converter 10, an inner resonant circuit 12 and a high voltage DC/AC converter 14.
The two DC/AC converters 10, 14 each comprise two switches, (respectively S1,S2 and S5,S6) arranged as a half bridge. The low voltage DC/AC converter is connected to convert the low DC voltage V1 into a first single phase AC voltage V1ac. Similarly, the high voltage DC/AC converter is connected to convert the high DC voltage V2 into a second single phase AC voltage V2ac.
The inner resonant circuit 12 comprises two inductors L1,L2 and a capacitor C connected as a star L1CL2 circuit at their first terminals. The second terminal of inductor L1 and the second terminal of the capacitor C are connected to the first AC voltage V1ac. The second terminal of inductor L2 and the second terminal of the capacitor C are connected to the second AC voltage V2ac.
In
b shows the 2 phase topology of the converter. The circuit of
The low voltage DC/AC converter is connected to convert the low DC voltage V1 into a first 2 phase AC voltage V1ac. Similarly, the high voltage DC/AC converter is connected to convert the high DC voltage V2 into a second 2 phase AC voltage V2ac.
The inner resonant circuit 12′ comprises two inductors L1, L2 and a capacitor C, for each phase of the converter. The components associated with each phase are connected as a star L1CL2 circuit at their first terminals, and the second terminals of the inductors L1,L2 are respectively connected to the corresponding phases of the AC voltages V1ac and V2ac. The second terminals of the capacitors for both phases are connected to a common point.
c shows the 3 phase topology of the converter. The circuit is similar to that of
In what follows, reference is made to the 2 phase converter illustrated in
A design goal is controllable power transfer between a low voltage DC system V1 and a high voltage system V2. It is assumed that V1 and V2 do not change polarity, but that they can deliver or sink power. Thus, bi-directional power flow is achieved by means of current direction change.
Each of the DC/AC bridges 10′,14′ may be operated in a square-wave fashion or using other methods for generating AC from DC.
Square-wave operation of the DC/AC bridges is achieved by sequentially firing gates g1 and g2 on the low voltage side, and gates g5 and g6 on the high voltage side. The converter AC voltages V1ac and V2ac can be expressed as:
V
1ac
=V
1acm∠α1=V1acx+jV1acy (1)
V
2ac
=V
2acm∠α2=V2acx+jV2acy (2)
where V1acm is the magnitude of V1ac, V2acm is the magnitude of V2ac, α1 is the phase angle of V1ac and α2 is the phase angle of V2ac.
The firing angles α1,α2 and the conduction angles γ1,γ2 can be externally manipulated from the converter controller
(not shown). Using Fourier series expansion, the root mean square (RMS) of the fundamental component of the AC voltage magnitude is (line neutral):
V
1acm=4V1/(√2π)·sin(γ1/2),V2acm=4V2/(√2π)·sin(γ2/2) (3)
In equation (3), the conduction angles γ1,γ2 can be used to control the magnitude of the AC voltage, considering that the DC voltages V1 and V2 are constant. The maximum power is obtained for full conduction, ie γ1=γ2=180 degrees.
Further the xy components of control signal M1acx and M1acy can be represented as
The basic equations for the inner resonant circuit are:
I
1ac
=I
1acm∠β1=(V1ac−Vc)/(jωL1), (4)
I
2ac
=I
2acm∠β2=(V2ac−Vc)/(jωL2) (5)
jωCV
c
=I
1ac
+I
2ac (5)
where =2πfs and fs is the converter switching frequency. The coordinate frame can be positioned arbitrarily. Thus, without loss of generality, V1ac can be positioned on the x-axis (α1=0). Thus:
V
1ac
=V
1acx
=V
1acm
,V
1acy=0 (6)
We will conveniently rewrite equations (4)-(5) as:
where the coefficients k1, k2 and k3 are:
k
1=1−ω2L2C (19)
k
2=1−ω2L1C (20)
k
3
=L
1
+L
2−ω2L1L2C (21)
The above variables k1, k2 and k3 are conveniently introduced to study converter behavior. Ultimately, we need to determine the three parameters: L1, L2 and C, which can be obtained from the three equations (19)-(21). The coefficient k3 is a positive non-zero constant that is fully determined by the power transfer level. Coefficients k1 and k2 are manipulated in the design stage, as it is discussed in section C below. Since ω>0, L1>0, L2>0, C>0, from (19)-(21) we have upper limits:
k
1<1,k2<1,k3<L1+L2 (22)
It is essential to minimize reactive power flow in LCL circuit in order to operate with minimum current magnitudes and to reduce switching losses.
The converter has 3 control signals that can be manipulated M1d, M2d and M2q. to minimise reactive power. Using (17) the low voltage side AC current
The condition for zero reactive power at terminal 1, I1acq=0, is obtained from (23):
0=V1M1dk1−V2M2d (24)
Therefore the control law for I1acq=0 is from (24):
Using (25) and (23) we derive power expression:
where p is the number of phases (p=2 for the converter in
On the high voltage side, AC current is from (18):
Using (27), zero reactive power condition at terminal 2 is:
After rearranging (28) and using (25):
Therefore replacing (24) in (29), to provide zero reactive power on high voltage side we operate the converter as:
The above equation implies that the phase angle of AC voltage V2ac is constant and for a given k1 and k2:
B. Calculation of k1, k2 and k3
The influence of k1, k2 and k3 will be discussed in this section, considering full power transfer. We assume that maximum control signals are provided at maximum power transfer (in order to get minimal currents).
M
1mmax
=M
2mmax=1 (32)
Replacing (32) in (25):
Since |M2d|≦1, |M1d|≦1, we get the boundaries for k1:
where s is the stepping ratio V1/V2. Using (33), we can also calculate the maximum q component control signal M2qmax:
M
2qmax=√{square root over (1−M2dmax2)}=√{square root over (1−s2k12)} (35)
Replacing (33) in (29) at maximum power (32):
M
2q
2
V
2
2
k
2
=V
1
2
k
1
−M
2d
2
V
2
2
k
2 (36)
Re-writing (36), we obtain formula for calculating k2:
k
2
=k
1
s
2 (37)
The coefficient k3 is calculated from active power condition (26), and replacing (33):
The converter design procedure is as follows: —
A good initial guess for k1 is middle of the range.
A test system module has been developed using a PSCAD/EMTDC simulator. The test system data for a 3 MW, 2 kV/40 kV converter are given in tables 1a and 1b.
a to 4d show the converter PSCAD model simulation in steady-state in step-up mode. It can be seen that the internal AC circuit correctly achieves the voltage and current stepping, ie, low V1ac and I2ac, high V2ac and I1ac. It can also be seen that voltages and currents at the respective terminals are in phase, which implies low conduction losses due to the minimal current magnitude, and low switching losses due to zero current switching.
Controllability of the converters is illustrated in
Replacing (2) and (3) in equation (24) gives the power equation:
P
1ac
=pωC4V1/(√2π)·sin(γ1/2)·4V2/(√2π)·sin(γ2/2)·sin(α2) (28)
Considering (28) and (9), the power can be controlled in four ways:
The use of γ1 for converter control has been tested using the non-linear PSCAD simulator. The test results are illustrated in
Since the conduction angle can not be negative, it is not possible to reverse the direction of power transfer by varying the conduction angle. Instead power reversal is achieved by changing α2 from 270 to 90 degrees, noting that α2 should stay on the y-axis to enable zero reactive power flow. This power reversal method can be deduced from the phasor diagram in
Operation of the converters illustrated in
An aim of the present invention is to develop a converter which is fully tolerant to external faults on either of the DC voltages V1, V2.
Assuming a fault on V1, we put V1=0 in the above equations and the fault current I1acf1m relative to rated current I1acm is:
In the above formula the fault current magnitude is very close to rated value for all reasonable k1.
Similarly for faults on V2, we put V2=0 to obtain:
IN the above formula the fault current is lower than rated current form most k1.
Assuming a special case k1=0, the fault Equations (16) and (17) can be rearranged as follows,
ωL1=−V2acm/I1ac (29)
ωL2=−V1acm/I2ac (30)
It is evident from equations (29) and (30) that the converter has constant V/I ratio, which implies favourable fault responses. A voltage depression on one side will cause current reduction on the opposite side, given that ωL is constant. An extreme fault on one side of the converter, eg V1=0, will cause open circuit on the opposite side, eg I2=0. Accordingly, such faults are not transferred through the converter. Thus, the converter can be used as a DC circuit breaker, which prevents DC fault propagation.
In contrast, a common 2-coil AC transformer has the following characteristic: V2/V1=N2/N1, where N1 and N2 are the number of turns of the transformer coils. Such a transformer will directly transfer voltage depressions from one side to another. Accordingly, external protection circuits are required to interrupt fault currents (AC circuit breaker).
The converter of
Both low voltage terminals are connected to a respective DC/AC bridge which respectively converts the DC voltages V11,V12 into 2 phase AC voltages V11ac, V12ac. The high voltage terminal is connected to a DC/AC bridge which converts the DC voltages V2 into 2 phase AC voltage V2ac.
For each phase of the converter, the inner resonant circuit comprises two inductors L11 and L12 respectively associated with the two low voltage terminals, a third inductor L2 associated with the high voltage terminal, and a capacitor C. The components L11,L12,L2,C associated with each phase are connected together at their first terminals. The second terminals of inductors L11,L12,L2 associated with each phase are connected to the corresponding phase of the respective AC voltages V11ac, V12ac, V2ac. The capacitors
associated with both phases are connected together at a common point.
The basic converter equations are:
I
11ac=(V11ac−Vc)/(jωL11),I12ac=(V12ac−Vc)/(jωL12),I2ac=(V2ac−Vc)/(jωL12) (31)
jωCV
c
=I
11ac
+I
12ac
+I
2ac (32)
Replacing (31) in equation (32) gives:
-ω2L11L12L2CVc=(V11ac−Vc)L12L2+(V12ac−Vc)L11L2+(V2ac−Vc)L11L12 (33)
Equation (33) can be rearranged as:
V
cx
+jV
cy=(V11acL12L2+V12acL11L2+jV2acL11L12)/(L11L2+L12L2+L11L12−ω2L11L12L2C) (34)
Assuming the low voltages V11,V12 are aligned with the x-axis and the high voltage V2 is aligned with the y-axis:
V
11ac
=V
11acx
,V
12ac
=V
12acx
,V
2ac
=jV
2acy (35)
In order to reduce reactive power circulation on the high voltage side, the y-component of the capacitor voltage should be equal to the voltage on the y-axis:
V
cy
=V
2ac (36)
Replacing (31) and (36) in equation (34) gives:
V
2ac(L11L2+L12L2+L11L12−ω2L11L12L2C)=V2acL11L12 (37)
Assuming L11=L12, (37) gives:
C=2/(ω2L11) (38)
Thus, the capacitor size is twice the value calculated for the two-terminal converters of
V
cx=(V11ac+V12ac)/2 (39)
In the case where V11ac=V12ac, the x-component of the capacitor voltage will be equal to both V11ac and V12ac, and there will be no reactive power circulation.
Combining equations (40) and (37):
L2=L11/2 (41)
The power for the high voltage terminal is:
P
2ac=2V2acI2ac=2V2ac(V11ac+V12ac)/(2ωL2)=2V2acωC(V11ac+V12ac)/2 (42)
If the voltages on the low voltage side are equal, equation (42) becomes:
P
2ac=2V2acV11acωC (43)
If the voltages on the x-axis are equal, the power is:
P
11ac
=P
12ac=2V11acI11ac=2V11acV2ac/ωL11=V11acV2acωC (44)
From equations (43) and (44) it can be deduced that the high-voltage converter should be rated for the sum of powers on the low voltage converters.
The converter design procedure is as follows: —
C=P
2
/{pωV
2ac(V11ac+V12ac)} (45)
L2=1/(ω2C),L11=L12=2/(ω2C) (46)
The value for L2 may be tuned in the final tests.
A test system has been developed using a PSCAD/EMTDC simulator. The test system data are given in tables 2a and 2b.
a-10e show the 3-terminal converter PSCAD model simulation in steady state. A negative step on the V12 terminal conduction angle γ12 is applied to illustrate controllability of the converter.
It can be seen that the converter steady-state variables are as predicted by the above equations. All terminals operate at zero reactive power flow. The reduction in γ12 reduces power on the V12 terminal, and also reduces the exit power P2, which is the sum of P11 and P12. It can also be seen that P11 is unchanged, which demonstrates that power on each terminal can be individually controlled.
The converter of
The n low voltage terminals are connected to respective DC/AC bridges which respectively convert the DC voltages V1i into 2 phase AC voltages V1iac. The m high voltage terminals are connected to respective DC/AC bridges which respectively convert the DC voltages V2i into 2 phase AC voltage V2iac.
For each phase of the converter, the inner resonant circuit comprises n inductors L11 respectively associated with the n low voltage terminals, m inductors L2j respectively associated with the m high voltage terminals, and a capacitor C. The components L1i,L2j,C associated with each phase are connected together at their first terminals. The second terminals of inductors L1i,L2j associated with each phase are connected to the corresponding phase of the respective AC voltages V1iac, V2jac. The capacitors associated with both phases are connected together at a common point.
In order to minimize reactive power circulation, the capacitor voltages on one axis should be close to the average value. Thus, all low voltages should be aligned with the x-axis, and all high voltages with the y-axis.
The basic circuit equations are:
Assuming that L11=L1i=L1n=L1 and L2i=L2i=L2n=L2, and replacing (47) and (48) in equation (49) gives:
Given the assumption that all n-voltages are located on the x-axis and all m-voltages on the y-axis, (50) becomes:
The goal is for the y-component of the capacitor voltage to be equal to the average voltage on the y-axis:
Replacing (52) in equation (50) gives:
Solving equation (52) gives the capacitance:
C=n/(ω2L1) (54)
Minimising current magnitudes on the low voltage side, the goal is for the x-component of the capacitor voltage to equal the average voltage on the y-axis:
Replacing (55) in equation (51) gives:
Solving (56) gives the capacitance:
C=m/( 2L2) (57)
From equations (57) and (54):
L2=mL1/n (58)
The power expressions can be derived as:
If all voltages on corresponding axes are equal, V11=V1i=V1n, V2i=V2j=V2n, then:
P
1iac=2V1iacI1iac=2V1iacV2jac/(ωL1)=2V1iacV2jacωC/n (61)
P
2iac=2V2jacI2jac=2V2jacV1iac/(ωL2)=2V2jacV1iacωC/m (62)
The converter design procedure is as follows: —
L
1
=n/(ω2C),L2=m/((ω2C) (64)
Although
The converter concept described above can also be extended to exchange power on the inner AC circuit. One application is to interconnect a DC source/sink with an AC source/sink. This can be achieved if a converter bridge is replaced with an AC source.
a-13c show simulation responses for a converter which connects an AC system with a DC system. The test system is similar to that used to obtain the results of
However, in the general case, the converter may comprise m DC terminals, where m may be any positive integer. Moreover, the circuit may have p phases, where p is any positive integer.
For clarity of explanation, the converters have been described as having a low voltage side and a high voltage side. However, it will be appreciated that, in certain circumstances, the voltage on both sides of the converter may be equal, such that the converter does not have a low voltage side and a high voltage side. However, it will be appreciated that the above descriptions above still apply in such circumstances, if the terms “low voltage” and “high voltage” are simply regarded as labels for the two sides of the converter.
The converter of the invention comprises control means for controlling AC voltage magnitude, frequency and phase. For example, one way of controlling these parameters is to generate a single square wave as illustrated in
A suitable control circuit for the converter of the invention will be straightforward for a person skilled in the art to implement in view of what is disclosed herein.
Number | Date | Country | Kind |
---|---|---|---|
1110644.0 | Jun 2011 | GB | national |
Filing Document | Filing Date | Country | Kind | 371c Date |
---|---|---|---|---|
PCT/GB2012/051486 | 6/25/2012 | WO | 00 | 3/3/2014 |