The present invention generally relates to power transmission systems and, more particularly to equipment used to address phase imbalances associated with power transmission systems.
High capacity electric power transmission systems using alternating current typically operate with three phases, using a three-wire system for transmission. (This discussion will focus on three phases even though more than three may be used in unusual circumstances.) Nominally, each of the three wires has a voltage and current waveform that is 120° leading or lagging relative to its two companions, and each wire is carrying the same RMS current. In the real world, the desired balance of the currents in the three wires does not come easily, usually because of imbalances in load conditions, but imbalance may also occur because of reactive differences among the three wires supporting the transmission system or from imbalances among distributed power sources. A very practical consequence of poor balance among the three phases is a loss of system capacity because the high current line reaches its limit while its companions are underloaded. In contemporary power networks, the balance among phases can be monitored, simulated and corrected by inserting either inductive or capacitive reactance into selected phases.
In many cases, there are transmission paths that are essentially parallel, but because of local conditions, one of two or more parallel paths may tend to operate at or beyond its capacity while the alternative paths are underloaded. Again, the overall system capacity is increased when inductive or capacitive reactance is introduced into the transmission paths.
In all the cases above, inserting reactance can be accomplished without switches. Two examples are U.S. Pat. No. 7,105,952, “Distributed floating series active impendences for power transmission systems,” by Divan et al. and U.S. Pat. No. 9,172,246, “Phase balancing of power transmission system,” by Ramsay, et al. Both of these schemes utilize the transmission line itself as a “single-turn” primary of a transformer that is completed by hollow, cylindrical ferromagnetic core and a secondary wrapped around the core. The core and secondary are split so they can be clamped on the transmission line, the primary, using a clam shell arrangement. The injected reactance is managed by controlling the current flow in the secondary of the transformer.
In practice, equipment of this type is exposed to the elements, and a typical ambient temperature rating is 50° C. Under operating conditions, resistive losses in the windings and hysteresis and eddy current losses in the ferromagnetic core of the transformer give rise to heating. This heating is exacerbated in overload and fault conditions, and hot spot heat rises may reach 150° C.
This invention addresses an alternative design for the transformer to be used for coupling to the transmission line.
The subject matter that is regarded as the invention is particularly pointed out and distinctly claimed in the claims at the conclusion of the specification. The foregoing and other objects, features, and advantages of the invention will be apparent from the following detailed description taken in conjunction with the accompanying drawings.
The use of transformers to actively inject series reactance into a transmission line is well established.
Similarly, the application of Munguia et al. US 2017/0163036 (Transformers with multi-turn primary windings for dynamic power flow control) addresses the case where an impedance injection module is more favorably realized using a principal transformer with a multi-turn primary, element 305 in
In the work described above, transformers are based on cylindrical ferromagnetic cores, which makes the transformers difficult to manufacture. The paragraphs that follow will describe a transformer structure for power line reactance injection that is readily adapted to a wide range of operating currents, offers superior cooling under operating conditions, tolerates high fault currents, and offers manufacturing advantages when a range of products must be produced.
The basic structure for a current adaptive reactor transformer is shown in
The center post 515 of the rectangular core 510 has multiple gaps 530 and 535 in the magnetic circuit to avoid saturation in the operating current range and to manage the total inductance seen by the primary. Traditionally, these gaps are regarded as “air gaps,” but here the gaps are filled with materials chosen for their dielectric and mechanical strength, high temperature tolerance, and especially for high thermal conductivity. Specific examples of materials that may be used to fill the gaps 530 and 535 are ceramics (high-purity alumina or beryllium oxide), thin borosilicate glass (e.g. Borofloat), papers made of aramid with inorganic fillers (e.g. ThermaVolt AR, which is useable to 220° C.), and high temperature glass composites. These materials assist in cooling the transformer under operating conditions and increase the tolerance to high fault currents. If the gaps were filled with air, absent convection, the thermal conductivity κ in the gaps would be low, approximately 0.03 watt/mK°. An air gap of 750 μm having an area of 1000 square centimeters would sustain a temperature difference of 250° K if it were passing 1000 watts of heat. Filling that gap with an aramid (e.g. Nomex) with κ near 0.1 watt/mK° would reduce the temperature difference to about 75° K. Filled aramid would bring the temperature difference to about 20° K, borosilicate glass to less than 7° K, and alumina (κ˜35 watt/mK°) would bring the temperature difference to about 0.21° K. Table 1 below provides thermal conductivities and temperature differences for air and a number of possible fillers for the gaps. Preferably the thermal conductivity of any material used for filing the gaps is at least 0.2 watt/(mK°), and more preferably at least in excess of 20 W/(mK°).
1ThermaVolt AR thermal conductivity reported for a thickness of 0.29 mm.
2ThermaVolt AR thermal conductivity extrapolated to a thickness of 0.75 mm.
Thermal and magnetic design considerations may require different materials at the ends 530 of the center post than are used in the intermediate gaps 535. In every case, the employment of structurally rigid materials in the gaps 530 and 535 enhance the transformer's ability to withstand high fault currents.
Looking at the completed structure in cross section in
As illustrated by
The primary 705 is configured in
While one and two laminar turns are illustrative, preferred embodiments utilize at least three laminar turns. A three-laminar turn primary 705 as illustrated in
Logically, this configuration can be extended beyond three or four laminar turns to N laminar turns, and each of the laminar turns would be confined to have a thickness of 1/N times the total thickness of the primary. With a common height, the current carrying capacity would scale downward by the factor 1/N. In other words, the interchangeability of primaries having different current ratings is assured by having constant total cross sections, for example thickness 540 and height 550 shown in
The interchangeable primaries 705 as illustrated in
The current density of 96 A/cm2 used above is illustrative, and nominal current densities larger or smaller may be employed. Minor deviations from precise duplication of the cross-sections may be tolerated as long as interchangeability is maintained across the family of transformers.
Table 2 above shows representative characteristics for a family of transformer configurations illustrated by
In every high current application, heating is a consideration. The thermal characteristics of the described transformer are dominated by the rectangular core 510 in
Even though the invention disclosed is described using specific implementation, it is intended only to be exemplary and non-limiting. The practitioners of the art will be able to understand and modify the same based on new innovations and concepts, as they are made available. The invention is intended to encompass these modifications.
This application claims the benefit of U.S. Provisional Patent Application No. 62/713,290 filed Aug. 1, 2018, the entirety of which is incorporated herein by reference.
Number | Name | Date | Kind |
---|---|---|---|
3671847 | Shibano | Jun 1972 | A |
3747205 | Moore | Jul 1973 | A |
6919788 | Holdahl et al. | Jul 2005 | B2 |
7105952 | Divan et al. | Sep 2006 | B2 |
9172246 | Ramsay et al. | Oct 2015 | B2 |
20030197583 | Choi | Oct 2003 | A1 |
20040061584 | Darmann | Apr 2004 | A1 |
20120299680 | Zajc | Nov 2012 | A1 |
20120299686 | Matsuda | Nov 2012 | A1 |
20130241686 | Nakatsu | Sep 2013 | A1 |
20140132380 | Jacobson | May 2014 | A1 |
20170163036 | Munguia et al. | Jun 2017 | A1 |
Entry |
---|
English translation of GB2037089 (Year: 1980). |
Minhaz, Ronnie, “Transformer Design & Design Parameters”, IEEE Green Mountain Chapter of the IEEE Power Engineering Society, Dec. 1, 2014, 56 pp. total. |
Smart Wires Inc., “Power Guardian 700 Data Sheet”, Feb. 8, 2018, 2 pp. total. |
Number | Date | Country | |
---|---|---|---|
62713290 | Aug 2018 | US |