This invention relates to a dual pressure damper having two damper blades with different opening pressure thresholds, and more particularly, but not by way of limitation, to a dual pressure damper used with an air intake fan for venting toxic gases in an oil extraction room or oil extraction booth and maintaining a negative air pressure “N” in the room. Also, the subject invention can be used for maintaining a positive air pressure “P” in a room.
Heretofore, in a laboratory having an inside oil extraction room, air flow is run in a negative ambient pressure “N”. The negative pressure “N” can be accomplished by running a ceiling exhaust fan, for example, at 1000 rpm and a ceiling intake fan at 800 rpm. A gas sensor is used to detect hazardous gasses from the oil extraction process. If a hazardous gas does leak during the operation, then the gas escapes out an exhaust duct and not from the oil extraction room into the surrounding area in a laboratory.
Similarly, a positive air pressure “P” in a room can be represented by a computer chip assembly room where HEPA filtered air is introduced into the room under a higher pressure than the ambient pressure in a surrounding facility. This feature ensures that the air in a positive pressure enclosure remains pure, filtered, and dust free. For the purposes of this patent application, reference to negative pressure “N” can also be attributed to positive pressure applications.
During a shutdown of the laboratory and oil extraction room, an air exhaust fan and an air intake fan are not operational. Therefore, there is no airflow through the room. But, a control system continues to monitor hazardous gas levels by reading values on a gas detector. If the control system senses a hazardous or toxic leak during the shut down, the intake fan and the exhaust fan instantaneously increase airflow from stop to full speed. During the increase in airflow, an exhaust air damper in an exhaust duct is pushed open from a positive pressure generated by the exhaust fan. Also at this time, a negative pressure is created by the intake fan, which forces an intake damper open in an intake duct. The intake fan and the exhaust fan are connected to the same building power supply and ramp up to full speed at the same rate. Another instance of instantaneous airflow is when an operator of the oil extraction room hits an emergency button during a shutdown.
Therefore during startup of the fans, the interior of the room may cause a risk to an operator, when instantaneous airflow creates a positive pressure “P” when the intake fan temporarily overpowers the exhaust fan, thus allowing hazardous or toxic gases to escape through openings in the room, such as doors, windows, utility holes, and gaps in wall panels and into the laboratory.
The subject invention includes a dual pressure damper, with an air intake fan, connected to a control system in the oil extraction room. The dual pressure damper is designed to prevent the positive pressure “P” in the room during startup of the intake fan and the exhaust fan.
In view of the foregoing, it is a primary object of the subject invention to provide a dual pressure damper, used with an air intake fan. The damper having a low pressure damper blade that opens at a lower air pressure, when compared to a high pressure damper blade to help maintain a negative air pressure “N” in the oil extraction room.
Another object of the invention is to provide the dual pressure damper with field changeable torsion coil springs to vary an opening pressure of a low pressure damper blade and a high pressure damper blade.
Yet another object of the invention is to reduce a risk to an operator in the oil extraction room or the laboratory from being exposed to toxic gas when instantaneous airflow, during a startup, creates a positive pressure “P”, when the intake fan temporarily overpowers the exhaust fan, thus allowing the toxic gas to escape from the oil extraction room through room openings and into the surrounding laboratory.
These and other objects of the present invention will become apparent to those familiar with plant oil extraction rooms when reviewing the following detailed description, showing novel construction, combination, and elements as herein described, and more particularly defined by the claims, it being understood that changes in the embodiments to the herein disclosed invention are meant to be included as coming within the scope of the claims, except insofar as they may be precluded by the prior art.
The accompanying drawings illustrate complete preferred embodiments in the present invention according to the best modes devised for a practical application of the subject dual pressure damper, and in which:
In
The plant oil extraction room 14 consists of room lights 16 and a control system 18 that communicates with a gas detector 20. The gas detector 20 is used to sense hazardous or toxic vapor concentrations exceeding levels safe to humans. If the gas detector 20 senses hazardous gas levels considered to be unsafe, a visual alarm 22 and an audible alarm 24 are activated. The alarms notify an operator the room is unsafe. Also, the alarms 22 and 24 can be manually activated by the operator using an emergency button 26. In both cases, the controls system 18 sends power to an intake fan 28 and an exhaust fan 30 to increase the airflow through the room 14 to purge contaminated air with hazardous toxic gases. The subject dual pressure damper is used with the intake fan 28.
The airflow system's intake system consists of an intake duct 32, a spring-loaded, back draft, intake damper 34, the intake fan 28, and an intake plenum 36. The intake plenum is designed to disperse intake air evenly through a cross section of the room 14.
The airflow system's exhaust system consists of an exhaust duct 38, an exhaust damper 40, the exhaust fan 30, and an exhaust plenum 42. The exhaust plenum 42 is designed to concentrate a pull of airflow to specific regions of the plenum so there is laminar flow through the room 14. The intake damper 34 and the exhaust damper 40 are fully closed during a shutdown to prevent outside air from the entering the oil extraction room 14. This feature saves heating and air conditioning expense, when the room's control system 18 is not in operation.
It should be noted in this drawing, incoming fresh air, as indicate by arrows 44, is drawn, using the intake fan 28, from outside the facility 10, into the intake plenum 36. The fresh air 44 is then introduced into the oil extraction room 14. At this time, the air, as indicated by arrows 46, can be contaminated from toxic gases from the oil extraction process in the room and before the contaminated air 46 is drawn into the exhaust plenum 42, using the exhaust fan 30. Exhaust air, as indicated by arrows 48, then exits the facility 10.
In
In
In
In
In
In
In
In
In
In
In
Hazardous solvents used in the plant oil extraction process can still be present in vessels contained within the extraction room 14. Also during a shutdown, the gas detector 20 continues to monitor the extraction room 14 for leaks of the hazardous gas. If the gas detector 20 senses hazardous gas, the controls system 18 instantaneously turns on both air intake fan 28 and the exhaust air fan 30 to purge the extraction room of the hazardous gas.
When the two fans are turned on to purge the extraction room 14, there is a 2 to 5 second delay until both fans are at full speed. To ensure the hazardous gas will not escape from the extraction room 14 and into the laboratory 12, while the fans are ramping to full speed, the exhaust damper 40 has little resistance and will open instantaneously to an open position. The dual pressure damper 50, has variable torsion coil springs 62 that require more force to open a high pressure damper blade 60 resulting in a half open damper blade configuration. The difference in the fully exhaust damper 40 and half open dual pressure damper 50 ensures that a negative pressure “N” is achieved in the extraction room 14, while the fans ramp up to full speed.
When the gas detector 20 no longer senses hazardous gases, the power to the fans is turned off. The air continues to move through the air exhaust duct 38, and a net negative pressure “N” is maintained. As the fans decelerate, the exhaust damper 50 is fully open. At this time, the variable torsion coil springs 62 on the dual pressure damper 50 result in a closing of the high pressure damper blade 60 to decelerate the intake fan 28 quicker than the exhaust fan 30 to maintain the net negative pressure “N” in the extraction room 14.
While the invention has been particularly shown, described and illustrated in detail with reference to the preferred embodiments and modifications thereof, it should be understood by those skilled in the art that equivalent changes in form and detail may be made therein without departing from the true spirit and scope of the invention as claimed except as precluded by the prior art.
Number | Name | Date | Kind |
---|---|---|---|
6038737 | Boright | Mar 2000 | A |
10232286 | Havelick | Mar 2019 | B1 |
20060105696 | Wenger | May 2006 | A1 |
20130072741 | Tsia | Mar 2013 | A1 |
20180038605 | Lieberman | Feb 2018 | A1 |
Number | Date | Country |
---|---|---|
102012205984 | Oct 2013 | DE |
Entry |
---|
English translation of DE-102012205984-A1, dated Jan. 17, 2023 (Year: 2023). |
Number | Date | Country | |
---|---|---|---|
62978955 | Feb 2020 | US |