This invention relates to air filtration systems in general, and more particularly to ductless fumehoods for purging hazardous substances from the air.
Air filtration systems are used in many situations to purge unwanted substances from the air. Such air filtration systems generally exist in a variety of forms, depending upon their use and function.
One type of air filtration system is the ductless fumehood. Ductless fumehoods provide a protected enclosure for isolating a workspace from an ambient atmosphere, in order that dangerous substances may be handled safely in the workspace without endangering nearby personnel and the surrounding environment.
More particularly, and looking now at
Ductless fumehoods have become popular due to their technical effectiveness, low acquisition and implementation costs, rapid installation, and substantial energy savings. More particularly, with proper filter selection, ductless fumehoods can be extremely effective in removing hazardous materials from the air. Furthermore, due to their simple design and their ductless nature, ductless fumehoods are relatively inexpensive to buy and relatively inexpensive to implement, since they do not require the extensive engineering and installation efforts normally associated with ducted fumehoods. Furthermore, installation is very fast, since ductless fumehoods require little more than uncrating and initial setup and testing before use. Ductless fumehoods are also quite energy efficient, since they return the filtered air to the room rather than venting it to the outside atmosphere. As a result, already-heated air is retained in the room during winter and already-cooled air is retained in the room during summer.
Despite the significant advantages associated with ductless fumehoods, current ductless fumehoods have nonetheless encountered certain resistance in the marketplace. This is generally due to concerns about the risk of failure in the filtration system. More particularly, while conventional ductless fumehoods generally have their outlet fan 40 and sensor 45 connected to an alarm 50 which can alert the operator if outlet fan 40 and/or sensor 45 should fail, they still require that the operator be in the general vicinity of the ductless fumehood and that the operator be somewhat attentive. This can be of concern when the ductless fumehood is located in a loud and/or otherwise distracting environment, and/or when placed in the hands of poorly trained and/or unreliable personnel. Furthermore, this can present an administrative problem when the ductless fumehoods are deployed in large numbers and dispersed throughout several laboratories. Due to these concerns and inconveniences, some safety organizations have advised against the use of ductless fumehoods even though ductless fumehoods can offer significant advantages in the areas of technical effectiveness, low acquisition and implementation costs, rapid installation, and substantial energy savings.
In addition to the foregoing, current ductless fumehoods are not modular. As a result, when a new fumehood model with a different filter capacity must be produced, manufacturers must fabricate a new filtration system and all of its command and control elements. Thus, manufacturers must provide filtration systems in a variety of capacities and dimensions, which multiplies both the number of different fumehood models which must be manufactured as well as their associated manufacturing costs. Furthermore, the administrative burden associated with managing a large number of these ductless fumehoods can be enormous. As an illustration of this problem, consider the example of trains without cars, made up only of locomotives, with each locomotive having a different seating capacity. The cost of manufacturing large numbers of different models, and the administrative burdens associated with managing a fleet of such trains, made up of countless different models, can be prohibitive. The situation is currently somewhat analogous for the manufacturers and users of conventional ductless fumehoods.
These and other problems associated with conventional ductless fumehoods are addressed by the present invention, which comprises a unique ductless fumehood system comprising at least one ductless fumehood and a remote monitor unit, wherein the at least one ductless fumehood is connected to the remote monitor unit through a communication link, such that the remote monitor unit can monitor one or more ductless fumehoods from a central location and provide alerts to an operator located at the ductless fumehood, or to others located at another location, when a failure is detected at a ductless fumehood.
In one form of the present invention, there is provided a ductless fumehood system, the system comprising:
at least one ductless fumehood, the ductless fumehood comprising:
In another form of the present invention, there is provided a ductless fumehood system comprising:
at least one ductless fumehood for purging hazardous substances from a workspace located within the ductless fumehood; and
a remote monitor unit for receiving information from the at least one ductless fumehood and issuing an alert upon the occurrence of a pre-determined condition at the at least one ductless fumehood.
In another form of the present invention, there is provided a ductless fumehood system comprising a ductless fumehood comprising:
a housing;
a workspace formed within the housing;
a door for selectively closing off the workspace;
an air inlet for introducing air into the workspace;
an air outlet for removing air from the workspace;
a filter system for receiving air from the air outlet, purging unwanted substances from that air, and then exhausting that filtered air to the ambient room air;
an alarm;
a sensor for monitoring operation of the filter system;
a sensor for monitoring function of the air outlet;
a sensor for monitoring door closure;
a sensor monitoring ambient room air; and
a central processing unit for receiving data from the filter sensor, the air outlet sensor, the door closure sensor and the ambient room air sensor.
In another form of the present invention, there is provided a ductless fumehood comprising:
a housing;
a workspace formed within the housing;
a door for selectively closing off the workspace;
an air inlet for introducing air into the workspace;
a master module for receiving air from the workspace, purging unwanted substances from that air, and then exhausting that filtered air to the ambient room atmosphere;
at least one slave module for receiving air from the workspace, purging unwanted substances from that air, and then exhausting that filtered air to the ambient room atmosphere;
wherein each of the at least one slave modules communicates with the master module so that the master module can control operation of, and detect failures within, each of the slave modules.
In another form of the present invention, there is provided a ductless fumehood system, the system comprising:
at least one ductless fumehood, the ductless fumehood comprising:
In another form of the present invention, there is provided a ductless fumehood system, the system comprising:
at least one ductless fumehood for isolating a workspace located within the ductless fumehood from hazardous substances in the ambient room atmosphere; and
a remote monitor unit for receiving information from the at least one ductless fumehood and issuing an alert upon the occurrence of a pre-determined condition at the at least one ductless fumehood.
In another form of the present invention, there is provided a ductless fumehood comprising:
a housing;
a workspace formed within the housing;
a door for selectively closing off the workspace;
an air inlet for introducing air into the ductless fumehood;
an air outlet for removing air from the ductless fumehood;
a filter system for receiving air from the air inlet, purging unwanted substances from that air, and then exhausting that filtered air to the workspace;
an alarm;
a sensor for monitoring operation of the filter system;
a sensor for monitoring function of the air outlet;
a sensor for monitoring door closure;
a sensor monitoring ambient room air; and
a central processing unit for receiving data from the filter sensor, the air outlet sensor, the door closure sensor and the ambient room air sensor.
In another form of the present invention, there is provided a ductless fumehood comprising:
a housing;
a workspace formed within the housing;
a door for selectively closing off the workspace;
an air inlet for introducing air into the ductless fumehood;
a master module for receiving air from the ambient room atmosphere, purging unwanted substances from that air, and then passing that filtered air to the workspace;
at least one slave module for receiving air from the ambient room atmosphere, purging unwanted substances from that air, and then passing that filtered air to the workspace;
wherein each of the at least one slave modules communicates with the master module so that the master module can control operation of, and detect failures within, each of the slave modules.
These and other objects and features of the present invention will be more fully disclosed or rendered obvious by the following detailed description of the preferred embodiments of the present invention, which are to be considered together with the accompanying drawings wherein like numbers refer to like parts and further wherein:
Looking next at
Additionally, remote monitor unit 106 may also be connected to a customer safety center 108 and/or other entity 109 (e.g., a local fire department) via a communication link 111, in order to provide alerts to those parties when a failure is detected at that ductless fumehood. Communication link 111 may be a “hard-wired” connection (e.g., electrical wire or optical fiber) or a “wireless” connection (e.g., an RF link or a cellular telephone link). Furthermore, communication link 111 may utilize a conventional or proprietary protocol. By way of example but not limitation, communication link 111 may comprise an Ethernet connection.
Furthermore, remote monitor unit 106 may also be connected to the system's manufacturer 112 and/or to an other monitoring service 113 via a communication link 114, in order to provide alerts to those parties when a failure is detected at that ductless fumehood. Communication link 114 may be a “hard-wired” connection (e.g., electrical wire or optical fiber) or a “wireless” connection (e.g., an RF link or a cellular telephone link). Furthermore, communication link 114 may utilize a conventional or proprietary protocol. By way of example but not limitation, communication link 114 may comprise a conventional telephone connection.
More particularly, and looking now at
Each ductless fumehood 105 also comprises a master module M and, optionally, one or more slave modules S for providing air filtration functions. Master module M also provides control and monitoring functions as will hereinafter be discussed in detail. By way of example but not limitation, the ductless fumehood shown in
As noted above, master module M provides air filtration functions. To this end, master module M draws air out of workspace 110 and passes that air through a filter before the air is released to the ambient air (e.g., the room air within a laboratory). More particularly, master module M includes, among other things, a filter 135 for removing hazardous substances from the air as the air is drawn through master module M, thereby rendering the air safe before it is vented to the ambient air. In this respect it will be appreciated that the filter media used in filter 135 may vary in accordance with the specific substance which is to removed from the air, e.g., for many applications, filter 135 may comprise activated carbon granules captivated between a pair of screens. An outlet fan 140 is provided so as to draw air from the enclosed workspace 110 through filter 135 before being vented to the atmosphere. A filter sensor 145 is provided at the outlet of filter 135 so as to ensure that the filter purges any hazardous substances from the workspace air before that air is vented to the ambient air. An ambient air sensor 146 is mounted to the exterior of master module M to monitor the ambient air in the vicinity of ductless fumehood 105. Master module M also comprises a sash monitor 121 to confirm when front door 115 is in its closed (i.e., sealed) position against sash 120.
In accordance with the present invention, master module M also comprises a central processing unit 147. It will be appreciated that central processing unit 147 comprises appropriate electronics and software in order that central processing unit 147 may control operation of the active elements of master module M, detect any failures of the components of master module M, and also function in the manner hereinafter described. Central processing unit 147 is connected to the aforementioned sash monitor 121, outlet fan 140, filter sensor 145 and ambient air sensor 146.
Central processing unit 147 is also connected to an alarm 150 which can alert the operator in the event that there is a system failure, and central processing unit 147 is connected to a display monitor 155 (e.g., a touchscreen display, or other user interface such as a computer monitor and keyboard, etc.) in order that the operator may interface with central processing unit 147. Central processing unit 147 is also connected to a communication interface 160 which is connected to the aforementioned communication link 107, whereby central processing unit 147 may communicate with remote monitor unit 106.
By virtue of the foregoing construction, central processing unit 147 is able to detect when there is a system failure. More particularly, central processing unit 147 is capable of detecting when front door 115 is open (by virtue of sash monitor 121), and/or if outlet fan 140 has failed and/or if filter 135 is not operating properly (by virtue of filter sensor 145). When such a system failure is detected, central processing unit 147 activates alarm 150 (and may flash an alert on display monitor 155) so as to alert the operator. At the same time, central processing unit 147 also alerts remote monitor unit 106 via communication link 107. Remote monitor unit 106 can then alert customer safety center 108 and/or some other entity 109 via communication link 111, as well as alert manufacturer 112 or some other monitoring service 113 via communication link 114. Thus, failures in any of the ductless fumehoods 105 can be monitored remotely via remote monitor unit 106, thereby making it practical and convenient to operate large numbers of ductless fumehoods 105 in a safe and reliable manner.
Furthermore, inasmuch as central processing unit 147 is connected to ambient air sensor 146, the system is also capable of monitoring ambient air conditions in the vicinity of each ductless fumehood 105. Thus, the system also provides a means for detecting the presence of hazardous substances in the air around each ductless fumehood 105. Significantly, the system is capable of detecting the presence of hazardous substances which may emanate from sources other than the ductless fumehood itself, e.g., the hazardous substances may emanate from a chemical spill elsewhere in the laboratory.
Furthermore, inasmuch as each master module M includes both a filter sensor 145 and an ambient sensor 146, the system is capable of differentiating a global hazard from a local hazard. More particularly, when filter sensor 145 is detecting the presence of a hazardous substance and ambient sensor 146 is not, the hazard is likely to be associated with a local filter failure. However, when filter sensor 145 is not detecting the presence of a hazardous substance and ambient sensor 146 is, the hazard is likely to be associated with a global hazard event.
In addition to the foregoing, central processing units 147, remote monitor unit 106, and/or any of the other entities (e.g., customer safety center 108, other entity 109, manufacturer 112, and/or other monitoring service 113) may keep a log of system operation. Logged events may include system failures, filter replacements, door openings, responsiveness of operators to alerts, etc.
As noted above, each ductless fumehood 105 may also comprise one or more slave modules S. Slave modules S also provide air filtration functions. To this end, each slave module S comprises a filter 135, a filter sensor 145 and an outlet fan 140. Outlet fan 140 draws air from workspace 110 up through filter 135 before venting the filtered air into the ambient room atmosphere. Filter sensor 145 monitors the function of filter 135. Thus, each slave module S is capable of purging unwanted substances from the air within workspace 110 before venting that air into the ambient room atmosphere. Significantly, each slave module S in ductless fumehood 105 is electrically connected to the master module M provided for that ductless fumehood, in order that central processing unit 147 can control operation of the active elements of each slave module S and detect any failures in any of the components (e.g., filter sensor 145 or outlet fan 140) of any of the slave modules S.
Thus it will be seen that each ductless fumehood 105 includes an enclosed workspace 110 and a master module M, and may include one or more slave modules S. In fact, each ductless fumehood 105 includes as many slave modules S as are necessary to provide, in conjunction with the air filtering capacity already provided by that fumehood's master module M, the appropriate filter capacity for workspace 110. Thus, for a ductless fumehood 105 having a length X, one master module M and no slave modules S might be provided; for a ductless fumehood 105 having a length (X+Y), one master module M and one slave module S might be provided (
Thus it will be seen that manufacturing, inventory and service requirements will be dramatically reduced through use of the present invention, since only two types of air filtering modules (i.e., master modules M and slave modules S) need be manufactured, inventoried and serviced, regardless of the size ductless fumehoods which are to be produced. In fact, in this respect it should be appreciated that slave modules S are in essence a simplified form of master module M, since they include the air filtering components (e.g., filter 135, filter sensor 145 and outlet fan 140) but omit the control and communication components (e.g., central processing unit 147, communications interface 160, etc.). Or viewed another way, the master module M is essentially an enhanced form of slave module S, since the master module includes components in addition to those provided in a slave module S (e.g., the control and communication components). As a result, slave modules S and master modules M can share many common elements, thereby further simplifying manufacturing, inventory and service requirements, and hence further reducing cost. In fact, before receiving the components that differentiate the master modules M from the slave modules S, the modules are identical to one another, and therefore can be manufactured in high volumes, which provides a substantial economic advantage.
Central processing unit 147 may also, in conjunction with other appropriate hardware, provide additional functionality to the ductless fumehood 105. This functionality may include, but is not limited to:
(i) the provision of an audio-visual video program displayed on an appropriately-sized display monitor 155—the program could be a live or pre-recorded audio-visual feed designed to provide a user with relevant information—by way of example but not limitation, the program could be intended to provide students with remote access to experiments performed within another ductless fumehood by a professor, or the program might intended to provide students with a step-by-step procedure for conducting an experiment; and/or
(ii) the provision of a database identifying those chemicals for which operation of the ductless fumehood is approved; and/or
(iii) a sensor detecting the presence or absence of filters in the ductless fumehood; and/or
(iv) a bar code reader allowing the fast and accurate identification of chemicals which will be used within the fumehood—the bar code reader allows universal product codes (UPC) to be read from the labels on the chemical containers, etc.
Central processing unit 147 is preferably also programmed to manage, in an interactive manner, each of the functions of each of the modules, in order to ensure that each of the modules remains within its operational limits as determined by the manufacturer.
The central processing unit is preferably configured in such a way that it transfers all of the data gathered for its associated ductless fumehood to the communications interface 160, for subsequent transfer to remote monitor unit 106.
The information emitted by each or all of the ductless fumehoods 105 is then preferably gathered by an appropriate wireless transmitter/receiver placed within a computer separate from each or all of the ductless filtering fume hoods (i.e., remote monitor unit 106). This computer is programmed to interactively manage the information coming from each or all of the ductless fumehoods. This information can be placed at the disposal of the person or persons in charge of safety so as to permit them to remotely manage one or all of the ductless fumehoods in order to ensure proper functioning or maintenance. In other words, remote monitor unit 106 can report to customer safety center 108, and/or an other entity 109, and/or manufacturer 112 and/or other monitoring service 113.
With this arrangement it is possible to send the information gathered by the system at one or all of the ductless fumehoods, via the Internet or other communication link, to another location, in order to be managed by another entity, for example, a service and control department of the manufacturer.
In one preferred form of the present invention, prior to purchasing the ductless fumehoods, a questionnaire (see
Preferably, upon receipt of a purchase order from the user, the manufacturer provides an access card (preferably similar to a credit card) on which is recorded various pertinent information, including the chemicals previously validated for use in the fumehood. See
Thus it will be seen that, with the present invention, a number of sensors and interactive detectors placed within the ductless filtering fume hood modules are linked to a processor (e.g., a central processing unit) placed within one of the modules (e.g., the master module M) that controls the active elements of all the other modules (e.g., the slave or “dummy” modules S); for example, sensors and detectors are placed within elements such as, but not limited to, fans or blowers, face velocity meters, gas detectors and lighting. This processor also controls the activation of the working modules that constitute the ductless filtering fumehood. In other words, these sensors and detectors are linked to the management processor and to all of the functions (provided or to be provided) of all of the modules that make up the ductless filtering fumehood such as, for example: an audio-visual video system designed to provide students with remote access to experiments performed within the hood by a professor in cases when the ductless filtering fumehood is used in the educational sector, or a database allowing the operation of a chemical listing, or a sensor detecting the presence of filters, or also a bar code reader allowing the identification of chemical molecules from the bottles that contain them, etc. The electronic processor is programmed to manage in an interactive manner each of the functions of the modules so that they react and act upon the elements of the modules of the ductless filtering fumehood in order to maintain within their limits the settings determined by the manufacturer.
This central processing unit is configured in such a way that it transfers all of the gathered information towards an electronic board placed within the main or master module M that reads the information and also transfers this information towards a remote transmitting and receiving wireless system also placed within the master module M.
The information emitted by each or all of the ductless filtering fumehoods is then gathered by an appropriate wireless transmitter receiver placed within a computer separate from each or all of the ductless filtering fumehoods. This computer is equipped with a program specially designed by the manufacturer of the ductless filtering fumehood to interactively manage each or all of the information coming from each or all of the ductless filtering fumehoods. This construction can be placed at the disposal of the person or people in charge of safety so as to permit them to remotely manage one or all ductless filtering fumehoods in order to insure proper functioning or maintenance.
With this arrangement it will also be possible to send the information gathered by the system of one or all of the ductless filtering fumehoods, via the Internet, in order to be managed by a service and control department of the manufacturer.
The filtration portion of the ductless filtering fumehood is comprised of one or more filtration modules that make up, by multiplication, the length of the hood. For example the modules will preferentially have a length of 40 centimeters or 16 inches. The command or main module M will be linked to the other slave or “dummy” modules S by electrical connectors so that the interactivity of commands or information coming from the central processing unit (found on the command or main module M) can be transferred to the active elements of all the modules. The inconveniences coming from the use of non-modular systems to constitute a multitude of fumehood sizes have been described above. The advantages of using modular systems are therefore clear, specifically in the case of putting together an intercommunication system such as the one described above.
In the preceding discussion, ductless fumehood 105 is discussed in the context of a fumehood designed to protect personnel and the environment from the contents of workspace 110, i.e., filter 135 filters air as that air passes from workspace 110 to the ambient room atmosphere. However, it should also be appreciated that the present invention can be applied to situations where ductless fumehood 105 is designed to protect the contents of workspace 110 from substances in the ambient room air. In this case, outlet fan 140 is reconfigured so that it operates as an inlet fan, i.e., it moves ambient room air into the fumehood through filter 135, so that the ambient room air is filtered before it is moved into workspace 110. Openings in ductless fumehood 105 then permit the air in workspace 110 to pass back into the ambient room atmosphere.
It should be understood that many additional changes in the details, operation, steps and arrangements of elements, which have been herein described and illustrated in order to explain the nature of the present invention, may be made by those skilled in the art while still remaining within the principles and scope of the invention.
This patent application claims benefit of prior U.S. Provisional Patent Application Ser. No. 60/816,211, filed Jun. 23, 2006 by Francois P. Hauville for MODULAR FILTRATION SYSTEM WITHOUT DUCTING, AND EQUIPPED WITH A MANAGEMENT SYSTEM COMPRISING A REMOTE INTERCOMMUNICATION SYSTEM DESIGNED TO ENSURE THE SAFE USE OF DUCTLESS FILTERING FUME HOODS, PRIMARILY IN A LABORATORY SETTING (Attorney's Docket No. FIPAK-6 PROV), which patent application is hereby incorporated herein by reference.
Number | Date | Country | |
---|---|---|---|
60816211 | Jun 2006 | US |
Number | Date | Country | |
---|---|---|---|
Parent | 12806001 | Aug 2010 | US |
Child | 14270574 | US | |
Parent | 11821634 | Jun 2007 | US |
Child | 12806001 | US |