A portion of the disclosure of this patent document contains material which is subject to (copyright or mask work) protection. The (copyright or mask work) owner has no objection to the facsimile reproduction by anyone of the patent document or the patent disclosure, as it appears in the Patent and Trademark Office patent file or records, but otherwise reserves all (copyright or mask work) rights whatsoever.
The present disclosure relates generally to the field of energy conservation and in one exemplary aspect to dynamic transformer loading systems as well as methods of operating and using the same.
The impacts of climate change have been increasingly understood to have broad and far-reaching environmental impacts that have affected our oceans, ice accumulation in the polar regions of our planet, as well as weather patterns around the globe. The main causes of climate change have been attributed to the emission of greenhouse gases, mainly carbon dioxide (CO2) and methane. In response, the global community has implemented a wide swathe of government regulations with the intention of reducing fossil fuel consumption. In the state of California, Title 24 of the California Code of Regulations has implemented building code requirements that address, among other things, individual responsibility for businesses as well as individuals for the reduction of their respective carbon footprints. For example, Title 24 has implemented so-called demand response requirements which, in response to signals transmitted by utility companies, reduce the amount of energy consumed by heating, ventilation, and air conditioning (HVAC) systems; indoor lighting systems; as well as electronic message centers (also known as digital signage or digital billboards).
Despite the wide variety of energy conservation measures that have been implemented throughout the world, one overlooked item of wasted energy has been transformer inefficiencies that affect virtually every electric energy distribution system in the world. Historically, transformers are currently built as a single unit that is sized in accordance with the kilo volt-ampere (kVA) requirements for the network that the transformer is intended to service. However, most transformers are typically 15-60% loaded at any given time during their period of operation which results in sub-optimal operating efficiency for these transformers. Additionally, these transformer cores are often energized on a 24-hour per day/seven-day a week basis compounding the amount of wasted energy associated with their usage. Accordingly, there remains a salient need for systems and methodologies that address these inefficiencies present in current electrical distribution systems.
The present disclosure satisfies the foregoing needs by providing, inter alia, dynamic transformer loading systems as well as methods of their operation and use.
In one aspect, a dynamic transformer loading system is disclosed. In one embodiment, the dynamic transformer loading system includes a plurality of transformers arranged in parallel; a plurality of current transducers, respective ones of the plurality of current transducers being in electrical communication with respective ones of the plurality of transformers; a plurality of contactors, respective ones of the plurality of contactors enabling a given transformer or transformers of the plurality of transformers to be operationally removed or operationally enabled from the dynamic transformer loading system; and a transformer load controller which receives as input, measurements from the plurality of current transducers, and in response to the received measurements, output signals to one or more of the plurality of contactors.
In one variant, the measurements received by the transformer load controller enables the transformer load controller to stage each of the plurality of transformers.
In another variant, the measurements received by the transformer load controller includes information associated with a current load that the dynamic transformer loading system is servicing.
In yet another variant, the information associated with the current load enables the plurality of transformers arranged in parallel to be staged in accordance with load requirements of the current load that the dynamic transformer loading system is servicing.
In yet another variant, the information associated with the current load enables the transformer load controller to sequentially enable bringing an additional transformer of the plurality of transformers online once one or more currently active transformers exceed approximately 80% of the one or more currently active transformers load rating.
In yet another variant, the transformer load controller is further configured to receive signals transmitted by a utility, and in response, output signals to one or more of the plurality of contactors.
In yet another variant, the received signals transmitted by the utility comprise demand response and demand control signals in accordance with Title 24 Demand Response Requirements.
In another aspect, a transformer load controller is disclosed. In one embodiment, the transformer load controller includes a non-transitory computer readable medium, the non-transitory computer readable medium including a plurality of computer executable instructions, that when executed by a processor apparatus, enable the transformer load controller to: receive one or more signals from one or more of a plurality of current transducers, respective ones of the plurality of current transducers being indicative of current load requirements of a load that the transformer load controller is servicing; and in response to the received signals from the one or more of the plurality of current transducers, output one or more signals to one or more of a plurality of contactors, the one or more signals output to the one or more of the plurality of contactors enabling one or more of a plurality of transformers that are arranged in parallel to be either brought offline or brought online in order to service the load.
In one variant, the one or more signals received by the transformer load controller enables the transformer load controller to stage each of the plurality of transformers.
In another variant, the one or more signals received by the transformer load controller includes information associated with a current load that the plurality of transformers are servicing.
In yet another variant, the information associated with the current load enables the plurality of transformers arranged in parallel to be staged in accordance with current load requirements.
In yet another variant, the information associated with the current load enables the transformer load controller to sequentially enable bringing an additional transformer of the plurality of transformers online once one or more currently active transformers of the plurality of transformers exceed approximately 80% of the one or more currently active transformers load rating.
In yet another variant, the transformer load controller is further configured to receive signals transmitted by a utility, and in response, output signals to one or more of the plurality of contactors.
In yet another variant, the received signals transmitted by the utility comprise demand response and demand control signals in accordance with Title 24 Demand Response Requirements.
In yet another aspect, a method of staging a plurality of transformers that are arranged in parallel to support load requirements for a changing load are disclosed. In one embodiment, the method includes receiving one or more signals from one or more of a plurality of current transducers, the one or more signals received being indicative of current load requirements of the changing load; and in response to the receiving of the one or more signals from the one or more of the plurality of current transducers, outputting one or more signals to one or more of a plurality of contactors, the outputting of the one or more signals to the one or more of the plurality of contactors enabling one or more of the plurality of transformers that are arranged in parallel to be either brought offline or brought online in order to service the changing load.
In one variant, the receiving of the one or more signals from the one or more of the plurality of current transducers enables staging of the plurality of transformers to support the changing load.
In another variant, the staging of the plurality of transformers includes sequentially enabling an additional transformer of the plurality of transformers to be brought online once one or more currently active transformers of the plurality of transformers are exceeding approximately 80% of the one or more currently active transformers load rating.
In yet another variant, the method further includes receiving signals transmitted by a utility, and in response, outputting signals to one or more of the plurality of contactors.
In yet another variant, the receiving of the signals transmitted by the utility comprises receiving demand response and demand control signals in accordance with Title 24 Demand Response Requirements.
In yet another variant, in response to the receiving of the demand response and demand control signals in accordance with Title 24 Demand Response Requirements, transmitting one or more signals to the plurality of contactors in order to enable the one or more of the plurality of transformers that are arranged in parallel to be either brought offline or brought online in order to service the received demand response and demand control signals in accordance with Title 24 Demand Response Requirements.
In one embodiment, the dynamic transformer loading system includes two or more transformers arranged in parallel; multiple current transducers, respective ones of the current transducers being in signal communication with respective ones of the transformers; multiple contactors, respective ones of the contactors enabling a given transformer or transformers to be operationally removed from the dynamic transformer loading system; and a transformer load controller which receives as input measurements from the current transducers, and in response outputs signals to the contactors.
In another aspect, methods of operating or installing the aforementioned dynamic transformer loading system are disclosed. In one embodiment, the method includes receiving a signal at the dynamic transformer loading system from a utility, and in response, reducing or shutting off the load that the dynamic transformer loading system is servicing.
Other features and advantages of the present disclosure will immediately be recognized by persons of ordinary skill in the art with reference to the attached drawings and detailed description of exemplary implementations as given below.
All Figures disclosed herein are © Copyright 2022-2023
Implementations of the present technology will now be described in detail with reference to the drawings, which are provided as illustrative examples to enable those skilled in the art to practice the technology. Notably, the figures and examples below are not meant to limit the scope of the present disclosure to any single implementation or implementations, but other implementations are possible by way of interchange of, substitution of, or combination with some or all of the described or illustrated elements. Wherever convenient, the same reference numbers will be used throughout the drawings to refer to same or like parts.
In some embodiments, numerical parameters set forth in the written description and attached claims are approximations that can vary depending upon the desired properties sought to be obtained by a particular embodiment. In some embodiments, the numerical parameters should be construed in light of the number of reported significant digits and by applying ordinary rounding techniques. Notwithstanding that the numerical ranges and parameters setting forth the broad scope of some embodiments of the disclosure are approximations, the numerical values set forth in the specific examples are reported as precisely as practicable. The numerical values presented in some embodiments of the disclosure may contain certain errors necessarily resulting from the standard deviation found in their respective testing measurements.
Recitation of ranges of values herein is merely intended to serve as a shorthand method of referring individually to each separate value falling within the range. Unless otherwise indicated herein, each individual value is incorporated into the specification as if it were individually recited herein. All methods described herein can be performed in any suitable order unless otherwise indicated herein or otherwise clearly contradicted by context. The use of any and all examples, or exemplary language (e.g., “such as”) provided with respect to certain embodiments herein is intended merely to better illuminate the disclosure and does not pose a limitation on the scope of the disclosure otherwise claimed. No language in the specification should be construed as indicating any non-claimed element essential to the practice of the disclosure. Unless a contrary meaning is explicitly stated, all ranges are inclusive of their endpoints, and open-ended ranges are to be interpreted as bounded on the open end by commercially feasible embodiments.
Referring now to
Referring again to
Referring now to
Referring now to
Referring now to
In the example illustrated in
In the example illustrated in
Referring now to
The functionality of the controller(s) 204 described herein may be implemented through use of software and/or firmware executed by the one or more controllers (or processors) and/or may be executed via the use of one or more dedicated hardware modules. The computer code may consist of computer-readable instructions stored in a non-transitory computer-readable medium that may be executed by one or more controllers (or processors), whether off-the-shelf or custom manufactured. The controller(s) may be used to execute instructions (e.g., program code or software) for causing the controller(s) to execute the computer code for implementing the functionality described herein.
An exemplary controller 204 may include one or more processing units (generally processor apparatus). The processor apparatus may include, for example, a central processing unit (CPU), a graphics processing unit (GPU), a digital signal processor (DSP), a controller, a state machine, one or more application specific integrated circuits (ASICs), one or more radio-frequency integrated circuits (RFICs), or any combination of the foregoing. The controller(s) may also include a main memory. The controller(s) 204 may also include a storage unit. The controller(s), memory and the storage unit may communicate via a bus.
The storage unit includes a non-transitory computer-readable medium on which is stored instructions (e.g., software) embodying any one or more of the methodologies or functions described herein. The instructions may also reside, completely or at least partially, within the main memory or within the controller(s) (e.g., within a processor's cache memory) during execution thereof by the computing system, the main memory and the processor also constituting non-transitory computer-readable media. The instructions may be transmitted or received over a network via a communication interface.
While non-transitory computer-readable medium is shown in an example embodiment to be a single medium, the term “non-transitory computer-readable medium” should be taken to include a single medium or multiple media (e.g., a centralized or distributed database, or associated caches and servers) able to store the instructions. The term “non-transitory computer-readable medium” shall also be taken to include any medium that is capable of storing instructions for execution by the computing system and that cause the computing system to perform, for example, one or more of the methodologies disclosed herein.
The controller(s) 204 may receive as input, measurements received from respective current transducers 208. These current transducers 208 may provide the controller(s) 204 with information pertaining to the amount of load being drawn from the dynamic transformer loading system 200 via, for example, the distribution block 212. These current transducers 208 may convert one form of energy into another (e.g., the current measured in amperes may be converted into a representative standard analog (or digital) signal which is indicative of, for example, the amount of current being drawn by the load). In some implementations, these current transducers 208 may transmit their representative standard signals to a processor, and/or a processor may read these representative standard signals from the current transducers 208, and the processor may then convert these representative standard signals to another format and then transmit these formatted signals to the controller 204.
The dynamic transformer loading system 200 may also include circuit breakers 210 positioned on one or both sides of the transformers 202 to enable a given transformer 202 to be taken offline (or be placed online) should it be deemed necessary. The dynamic transformer loading system 200 may not only react to fluctuations within the load of the system that the dynamic transformer loading system 200 is intended to service but may also provide demand response and demand control in accordance with, for example, Title 24 Demand Response Requirements. In other words, in response to a signal provided by, for example, a utility, the dynamic transformer loading system 200 may shut down the load provided by the system 200 (or may shut down a subset of transformers 202 for the system 200). For example, in response to signals received from a utility, the system 200 may provide a signal to the contactors 206, thereby shutting off the power provided to the load.
Table 1 reproduced below illustrates one exemplary daily operating scenario for a dynamic transformer loading (“DTL”) system 200 as compared with a conventional 75 kVA transformer system.
Table 1 illustrates the operational load over a typical 24-hour period of time for both a conventional 75kVA system as well as a dynamic transformer loading system 200 in accordance with the principles of the present disclosure. In the example illustrated above, the operational load is at 20% capacity for four (4) hours of the day; at 25% capacity for two (2) hours of the day; at 30% capacity for two (2) hours of the day; at 35% capacity for two and a half (2.5) hours of the day; at 40% capacity for three (3) hours of the day; at 45% capacity for three (3) hours of the day; at 50% capacity for one (1) hour of the day; at 55% capacity for one and a quarter (1.25) hours of the day; at 60% capacity for two (2) hours of the day; at 65% capacity for one (1) hour of the day; at 70% capacity for one and a quarter (1.25) hours of the day; and at 75% capacity for one (1) hour of the day.
Under this operating scenario, a conventional 75 kVA system might consume 32.67 kWh of energy from a utility in an exemplary day, while an exemplary dynamic transformer loading system 200 might consume 30.43 kWh of energy from the same utility, under the same loading conditions, in a given day. Accordingly, the energy savings over a period of one year will save on the order of roughly 816 kWh per year in this example. Additionally, and assuming a cost of $0.25 per kWh, a consumer would expect to save roughly $200 per year operating under a dynamic transformer loading system 200 as compared with a conventional 75 kVA system.
Where certain elements of these implementations can be partially or fully implemented using known components, only those portions of such known components that are necessary for an understanding of the present disclosure are described, and detailed descriptions of other portions of such known components are omitted so as not to obscure the disclosure.
In the present specification, an implementation showing a singular component should not be considered limiting; rather, the disclosure is intended to encompass other implementations including a plurality of the same component, and vice versa, unless explicitly stated otherwise herein.
Further, the present disclosure encompasses present and future known equivalents to the components referred to herein by way of illustration.
It will be recognized that while certain aspects of the technology are described in terms of a specific sequence of steps of a method, these descriptions are only illustrative of the broader methods of the disclosure and may be modified as required by the particular application. Certain steps may be rendered unnecessary or optional under certain circumstances. Additionally, certain steps or functionality may be added to the disclosed implementations, or the order of performance of two or more steps permuted. All such variations are considered to be encompassed within the disclosure disclosed and claimed herein.
While the above detailed description has shown, described, and pointed out novel features of the disclosure as applied to various implementations, it will be understood that various omissions, substitutions, and changes in the form and details of the device or process illustrated may be made by those skilled in the art without departing from the disclosure. The foregoing description is of the best mode presently contemplated of carrying out the principles of the disclosure. This description is in no way meant to be limiting, but rather should be taken as illustrative of the general principles of the technology. The scope of the disclosure should be determined with reference to the claims.
This application claims the benefit of priority to U.S. Provisional Patent Application Ser. No. 63/394,032 filed Aug. 1, 2022, entitled “Dynamic Transformer Loading Systems and Methods of Operation”, the contents of which being incorporated herein by reference in its entirety.
Number | Date | Country | |
---|---|---|---|
63394032 | Aug 2022 | US |