The invention relates to electronic active impedances that can be used to decouple a device (designated in the following as the “victim device”) on an electric line, from the impedance that may occur on the line itself, either on the network side or on the load side. The invention is applicable to several devices that cannot tolerate too low impedances on the network in a determined frequency range, for example active filters. A special case of application is that of “smart” electricity meter devices that record consumption of electric energy and communicate the information to the electricity supplier through a powerline modem.
Automatic reading of energy metering is known in the art and rely on several data transmission technologies. In electric meters, powerline communication signals are typically injected between phase and neutral, i.e. in differential mode. The amplitude of the signals may be of about 10V peak or less with typical frequency range 35 kHz to 500 kHz.
Power line communication frequency bands suitable for the present invention are assigned as follows:
35 kHz to 91 kHz in Europe (part of CENELEC A band)
98 kHz to 122 kHz in Europe (part of CENELEC B band)
155 kHz to 403 kHz in Japan (part of the ARIB band)
155 kHz to 487 kHz in the USA (part of FCC band).
A problem with these devices is that the signals are attenuated by the load impedance existing on the powerline. When load impedance is too low, for example below 1 ohm, the signal is attenuated to critically low levels and communication can fail.
Furthermore, loads on the network generate disturbances and spurious signals in the signalling band of frequencies, which can result in transmission errors.
It is known to introduce a choke network, or another passive attenuation network, downstream to the smart meter, between this and the load, to generate an inductance that limits the signal attenuation at 35 kHz and above, without blocking the power current at 50/60 Hz. The choke must be large enough to avoid saturation, and necessarily introduces power losses.
The above situation is not limited to smart meters but it occurs whenever it is necessary to isolate a device on an electric network from the variation of impedance thereof, in a determined band of frequency, as it may be the case for active EMI filters, for example, in a smaller package and at lower cost than with known passive solutions.
The present invention presents an improved solution for stabilizing the line impedance downstream of a victim device in a predetermined band of frequency. In a use case, the victim device is a PLC modem or a smart meter transmitting in the aforesaid band of frequency. The invention overcomes the limitations of the known art, by an active decoupling impedance having the features of the first independent claim. The present invention proposes an active impedance with a transformer having a primary connectable on the electrical power line, like a current transformer, and whose secondary is loaded by an active burden circuit. The active burden circuit is arranged to present a low impedance at the power frequency, and a higher impedance in the targeted band. An additional advantage is that the transformer and burden are galvanically isolated from the power line.
Thanks to the inventive features, the voltage drop at power frequency is contained, due to the low burden value, such that magnetizing flux is contained and a small core is enough to prevent saturation. At the same time, the burden impedance in the targeted band is higher, such that the impedance seen from the primary side of the transformer is proportionally larger, and the signals are not attenuated. The device of the invention can be dimensioned to introduce an additional impedance in the targeted band, and in this way prevent excessive attenuation, irrespective of the load. This impedance is preferably resistive in nature, and its magnitude may be higher than 5 Ohm, or better 10 Ohm. In practical realization, values of about 50-100 Ohm are attainable.
The dependent claims relate to optional advantageous features including the frequency of the targeted band that, according to the standards mentioned above, may be from 35 kHz to 500 kHz; an advantageous active structure with an amplifier or an unity-gain buffer cancelling a current flowing in the burden network in the targeted band, responsive to the output of an high-pass filter; a burden network including a series of impedances. The burden network and the high-pass filter are dimensioned such that at power frequency the output current of the amplifier is essentially zero while, in the targeted band, the burden network draws no current from the transformer.
The invention will be better understood with the aid of the description of an embodiment given by way of example and illustrated by the figures, in which:
A smart meter 40 placed at the entry records the accumulated electrical consumption and transmits it, via the plc modem 45 and the data concentrator 47 to a server 60 of the electricity provider. The consumption information is used for billing and for controlling the network, for example. Bidirectional communication, from the server to the meter, is also possible.
The electronic decoupling impedance 20, placed between the meter 40 and the loads 32, prevents the line impedance from being pulled down by the load impedance, and avoid the attenuation of the communication signal and mitigate the noise emitter from the load mentioned in the introduction.
It is understood that, insofar as the object of the present invention is to decouple a device on an electric network from the variations of impedance on the network, its usefulness is not limited to smart meters, but extends to many situation in which it necessary to protect a device (denoted “victim device”) from the variation of the impedance on a network. Hence, the use case shown in
In the following description we consider a transformer model with all values referred to the primary side. The transformer model would normally include an ideal transformer where the turns-ratio is considered. For simplicity the transformer in this description is assumed to have a 1:1 turns-ratio. In most real use cases, the transformer will have a primary winding of 1 turn and multiple turns on the secondary. The power line sees the impedance of the burden network scaled by the square of the turn ratio: Zp=Zs·(Np/Ns)2; spurious components such as stray inductance, winding resistance and stray capacitance are also ignored in this description. For suitable circuit operation, the impedance of these components, within the operating frequency band, should be kept small compared to other circuit impedance parameters.
The transformer coupling coefficient, k, should be sufficiently close to 1. In this case the stray inductance will be small compared to other inductance values.
Vs Communication signal voltage
Zs Communication signal source impedance
Vm Received voltage at the victim device
Zm victim device input impedance
Zi decoupling impedance
Vn Noise voltage from load
Zn Noise source impedance from load
The received voltage at the victim device vm is the sum of communication signal from the network and noise voltage from the load. The voltage signal to noise ratio, denoted as SNR in the following, indicates device input impedance Zm is assumed to be high compared to the other impedances. In this approximation, the equivalent circuit of
Received signal voltage at victim device: Vm1=Vs·Zn/(Zs+Zn)
Received noise voltage at victim device: Vm2=Vn·Zn/(Zs+Zn)
SNR: Vm1/Vm2=Vs/Vn·Zn/Zs
Signal voltage at victim device: Vm3=Vs·(Zn+Zi)/(Zs+Zn+Zi)
Noise voltage at victim device: Vm4=Vn·Zs/(Zs+Zn)
SNR: Vm3/Vm4=Vs/Vn·(Zn+Zi)/Zs
The active decoupling impedance of the invention stabilizes the load impedance seen and yields an improvement of the voltage S/N ratio given by
Therefore, to improve voltage signal to noise ratio we must have Zi>>Zn
Similar considerations apply to the case in which the decoupling impedance 20 is on the network side, as in
The principle of operation will now be discussed with reference to
vp Primary voltage
ip Primary current
Lm Magnetizing inductance
im Core loss resistance
im Magnetizing current
Lb Burden inductance
ib Burden current
Rr Residual resistance
ir Residual current
ic Compensation current
The primary current is defined by ip=im+ib+ir−ic
Assume ic≈0 and ir≈0: an impinging current at power frequency gives ip=im+ib. When Lm>>Lb then ip≈ib, therefore the primary voltage will be vp=ip·jωLb and the magnetizing current im=vp/(jωLm). Then im·jωLm=ip·jωLb.
Therefore, ip/im=Lm/Lb and the transformer core has a saturation current of im. The addition of the burden allows the phase current to be ip=(Lm/Lb)·im.
Note that the above depends from the assumption that the total impedance of the stray inductance and all the winding resistances are significantly less than the impedance Lb at power frequency.
Make ic=im+ib, then ip=ir: an impinging signal voltage vp produces a current ir. The primary impedance is Zp=vp/ir. Moreover, ir=vp/Rr, therefore Zp=Rr.
Preferably, the transformer should have a significantly high coupling coefficient to realize the above expression. A lower coupling coefficient will result in a higher stray inductance which will diminish the effectiveness.
Open Loop Voltage-Controlled Embodiment (
vp Primary voltage
ip Primary current
Zmb Magnetizing and burden equivalent impedance
imb Magnetizing and burden equivalent current
Rr Residual resistance
ir Residual current
ic Compensation current
Av Loop voltage gain
We require Ic=Imb so that ip=ir. Then vp=ic·Zmb and v0=ic·(Z0+Zmb). Therefore, the loop voltage gain is Av=v0/vp=(Z0+Zmb)/Zmb and the resultant impedance on the primary is given by Zp=vp/ir=Rr.
Closed-Loop Current Controlled Embodiment (
Another possible example of realization includes, as represented, a controlled current source 114 that is driven by an amplifier 108 whose input is connected to current sensor 24, which may be an auxiliary current transformer. The filter 105 limits the action of the compensation circuit to the target band, such that, at power frequency, the decoupling impedance of the invention is equivalent to the circuit of
vp Primary voltage
ip Primary current
Zmb Magnetizing and burden equivalent impedance
imb Magnetizing and burden equivalent current
Rr Residual resistance
ir Residual current
ic Compensation current
Ai Loop current gain
We require ic=imb so that ip=ir. Then vp=ic·Zmb and ir=vp/Rr. Current loop gain is Ai=ic/ir=Rr/Zmb, and the resultant primary impedance is given by Zp=Vp/ir=Rr as in the previous example.
The active burden circuit of
Another possible example of realization includes, as represented, a controlled voltage source 112 of output vp that is driven by an amplifier 108 whose input is connected to current sensor 24, which may be an auxiliary current transformer as in the embodiment of
vp Primary voltage
ip Primary current
Zmb Magnetizing and burden equivalent impedance
imb Magnetizing and burden equivalent current
ic Compensation current
Zx Forward transimpedance
The forward transimpedance is
Currents are given by
So, the current drawn from voltage source 112 is
The resultant impedance measured on the primary is Zx
Number | Date | Country | Kind |
---|---|---|---|
18209935.8 | Dec 2018 | EP | regional |
Filing Document | Filing Date | Country | Kind |
---|---|---|---|
PCT/IB2019/059581 | 11/7/2019 | WO | 00 |