This invention relates generally to refrigeration devices, and more particularly, to control systems for refrigerators.
Current appliance revitalization efforts require electronic subsystems to operate different appliance platforms. For example, known household refrigerators include side-by-side single and double fresh food and freezer compartments, top mount, and bottom mount type refrigerators. A different control system is used in each refrigerator type. For example, a control system for a side-by-side refrigerator-controls the freezer temperature by controlling operation of a mullion damper. Such refrigerators may also include a fresh food fan and a variable or multi-speed fan-speed evaporator fan. Top mount refrigerators and bottom mount refrigerators are available with and without a mullion damper, the absence or presence of which affects the refrigerator controls. Therefore, control of the freezer temperature in top and bottom mount type refrigerators is not via control of a mullion damper. In addition, each type of refrigerator, i.e., side-by-side, top mount, and bottom mount, have different optimal control algorithms for most efficiently controlling refrigerator operation. Conventionally, different control systems have been employed to control different refrigerator platforms, which is undesirable from a manufacturing and service perspective. Accordingly, it would be desirable to provide a configurable control system to control various appliance platforms, such as side-by-side, top mount, and bottom mount refrigerators.
In addition, typical refrigerators require extended periods of time to cool food and beverages placed therein. For example, it typically takes about 4 hours to cool a six pack of soda to a refreshing temperature of about 45° F. or less. Beverages, such as soda, are often desired to be chilled in much less time than several hours. Thus, occasionally these items are placed in a freezer compartment for rapid cooling. If not closely monitored, the items will freeze and possibly break the packaging enclosing the item and creating a mess in the freezer compartment.
Numerous quick chill and super cool compartments located in refrigerator fresh food storage compartments and freezer compartments have been proposed to more rapidly chill and/or maintain food and beverage items at desired controlled temperatures for long term storage. See, for example, U.S. Pat. Nos. 3,747,361, 4,358,932, 4,368,622, and 4,732,009. These compartments, however, undesirably reduce refrigerator compartment space, are difficult to clean and service, and have not proven capable of efficiently chilling foods and beverages in a desirable time frame, such, as for example, one half hour or less to chill a six pack of soda to a refreshing temperature. Furthermore, food or beverage items placed in chill compartments located in the freezer compartment are susceptible to undesirable freezing if not promptly removed by the user.
Attempts have also been made to provide thawing compartments located in a refrigerator fresh food storage compartment to thaw frozen foods. See, for example, U.S. Pat. No. 4,385,075. However, known thawing compartments also undesirably reduce refrigerator compartment space and are vulnerable to spoilage of food due to excessive temperatures in the compartments.
Accordingly, it would further be desirable to provide a quick chill and thawing system for use in a fresh food storage compartment that rapidly chills food and beverage items without freezing them, that timely thaws frozen items within the refrigeration compartment at controlled temperature levels to avoid spoilage of food, and that occupies a reduced amount of space in the refrigerator compartment.
In order to provide a quick chill and thawing system it would be desirable to have an electronic controller that controls the operation of the refrigerator and controls the operations of the quick chill thaw compartments.
In an exemplary embodiment, an electronic control system is provided for a refrigeration system including at least one refrigeration compartment and a quick chill/thaw pan located in the refrigeration compartment. The control system includes a main controller board, a temperature adjustment board, a dispenser board, and a serial communications bus. The main controller board is electrically connected to the temperature adjustment board and the dispenser board through the serial communications bus for controlling the temperature of the refrigeration compartment and the quick chill/thaw pan. The control system transmits commands over the serial communications bus to the dispenser board and the temperature adjustment board. The control system accepts a plurality of inputs including a refrigeration compartment temperature and a quick chill/thaw mode, determines a state of the refrigeration system, transmits commands over the serial communications bus, and executes a plurality of algorithms to control the refrigeration compartment and the quick chill/thaw pan over the serial communications bus.
The control system further includes a human machine interface board operatively coupled to the main controller board for user manipulation to select features of the refrigeration system, such as operation mode of the quick chill/thaw pan, to input user-selected operating setpoints such, as for example, a desired refrigeration compartment temperature, and to display actual temperature conditions and selected features of the refrigerator system.
The control system is configured to acquire status information from a variety of refrigeration components to make control decisions, included but not limited to status of a fresh food fan, a condenser fan, an evaporator fan, a quick chill/thaw pan fan, a compressor, a heater, an alarm, a cradle, various timers, and refrigeration compartment opened or closed door conditions. Based upon the status of the refrigeration system, the control system operates the refrigeration components according to a plurality of modes, e.g., an initialize mode, a prechill mode, a normal cooling mode, an abnormal cooling mode, a defrost mode, a diagnostic mode, and a dispense mode. A plurality of software algorithms are executed by the control system for the applicable modes, including but are not limited to a sealed system algorithm, a sensor-read-and-rolling-average algorithm, and a defrost algorithm.
The sealed system algorithm controls operation of a defrost heater, an evaporator fan, a compressor, and a condenser fan; a fresh food fan algorithm to control operation of a fresh food fan based on door opened and closed conditions. The sensor-read-and-rolling-average algorithm is used calibrate various thermistors and sensors and store associated data to accurately determine operating conditions of the refrigeration system. Additional control algorithms are executed to control the operation of resetting a water filter, dispensing water from the refrigeration system, dispensing crushed ice, dispensing cubed ice, activating and deactivating a light, and locking a dispenser keypad interface.
Refrigerator 100 includes a fresh food storage compartment 102 and freezer storage compartment 104. Freezer compartment 104 and fresh food compartment 102 are arranged side-by-side. A side-by-side refrigerator such as refrigerator 100 is commercially available from General Electric Company, Appliance Park, Louisville, Ky. 40225.
Refrigerator 100 includes an outer case 106 and inner liners 108 and 110. A space between case 106 and liners 108 and 110, and between liners 108 and 110, is filled with foamed-in-place insulation. Outer case 106 normally is formed by folding a sheet of a suitable material, such as pre-painted steel, into an inverted U-shape to form top and side walls of case. A bottom wall of case 106 normally is formed separately and attached to the case side walls and to a bottom frame that provides support for refrigerator 100. Inner liners 108 and 110 are molded from a suitable plastic material to form freezer compartment 104 and fresh food compartment 102, respectively. Alternatively, liners 108, 110 may be formed by bending and welding a sheet of a suitable metal, such as steel. The illustrative embodiment includes two separate liners 108, 110 as it is a relatively large capacity unit and separate liners add strength and are easier to maintain within manufacturing tolerances. In smaller refrigerators, a single liner is formed and a mullion spans between opposite sides of the liner to divide it into a freezer compartment and a fresh food compartment.
A breaker strip 112 extends between a case front flange and outer front edges of liners. Breaker strip 112 is formed from a suitable resilient material, such as an extruded acrylo-butadiene-styrene based material (commonly referred to as ABS).
The insulation in the space between liners 108, 110 is covered by another strip of suitable resilient material, which also commonly is referred to as a mullion 114. Mullion 114 also preferably is formed of an extruded ABS material. It is will be understood that in a refrigerator with separate mullion dividing a unitary liner into a freezer and a fresh food compartment, a front face member of mullion corresponds to mullion 114. Breaker strip 112 and mullion 114 form a front face, and extend completely around inner peripheral edges of case 106 and vertically between liners 108, 110. Mullion 114, insulation between compartments, and a spaced wall of liners separating compartments, sometimes are collectively referred to herein as a center mullion wall 116.
Shelves 118 and slide-out drawers 120 normally are provided in fresh food compartment 102 to support items being stored therein. A bottom drawer or pan 122 partly forms a quick chill and thaw system (not shown in
A freezer door 132 and a fresh food door 134 close access openings to fresh food and freezer compartments 102, 104, respectively. Each door 132, 134 is mounted by a top hinge 136 and a bottom hinge (not shown) to rotate about its outer vertical edge between an open position, as shown in
In accordance with known refrigerators, machinery compartment 164 at least partially contains components for executing a vapor compression cycle for cooling air. The components include a compressor (not shown), a condenser (not shown), an expansion device (not shown), and an evaporator (not shown) connected in series and charged with a refrigerant. The evaporator is a type of heat exchanger which transfers heat from air passing over the evaporator to a refrigerant flowing through the evaporator, thereby causing the refrigerant to vaporize. The cooled air is used to refrigerate one or more refrigerator or freezer compartments.
In an alternative embodiment, air handler 162 is adapted to discharge air at other locations in pan 122, so as, for example, to discharge air at an upward angle from below and behind quick chill and thaw pan 122, or from the center or sides of pan 122. In another embodiment, air handler 162 is directed toward a quick chill pan 122 located elsewhere than a bottom portion 182 of fresh food compartment 102, and thus converts, for example, a middle storage drawer into a quick chill and thaw compartment. Air handler 162 is substantially horizontally mounted in fresh food compartment 102, although in alternative embodiments, air handler 162 is substantially vertically mounted. In yet another alternative embodiment, more than one air handler 162 is utilized to chill the same or different quick chill and thaw pans 122 inside fresh food compartment 102. In still another alternative embodiment, air handler 162 is used in freezer compartment 104 (shown in
A forward portion 278 of air handler 162 is sloped downwardly from a substantially flat rear portion 280 to accommodate sloped outer wall 180 of machinery compartment 164 (shown in
Air handler 162 is modular in construction, and once air handler cover 196 is removed, single damper element 266, dual damper element 260, fan 274, vane 192 (shown in
In one embodiment, dampers 260 and 266 are selectively operated in a fully opened and fully closed position. In alternative embodiments, dampers 260 and 266 are controlled to partially open and close at intermediate positions between the respective fully open position and the fully closed position for finer adjustment of airflow conditions within pan 122 by increasing or decreasing amounts of freezer air and re-circulated air, respectively, in air handler supply flow path 252. Thus, air handler 162 may be operated in different modes, such as, for example, an energy saving mode, customized chill modes for specific food and beverage items, or a leftover cooling cycle to quickly chill meal leftovers or items at warm temperatures above room temperature. For example, in a leftover chill cycle, air handler may operate for a selected time period with damper 260 fully closed and damper 266 fully open, and then gradually closing damper 266 to reduce re-circulated air and opening damper 266 to introduce freezer compartment air as the leftovers cool, thereby avoiding undesirable temperature effects in freezer compartment 104 (shown in
It is recognized, however, that because restricting the opening of damper 266 to an intermediate position limits the supply of freezer air to air handler 162, the resultant higher air temperature in pan 122 reduces chilling efficacy.
Dual damper element airflow ports 262, 264 (shown in
In a specific embodiment of the invention, it was empirically determined that an average air temperature of 22° F. coupled with a convection coefficient of 6 BTU/hr.ft.2° F. is sufficient to cool a six pack of soda to a target temperature of 45° or lower in less than about 45 minutes with 99% confidence, and with a mean cooling time of about 25 minutes. Because convection coefficient is related to volumetric flow rate of fan 274, a volumetric flow rate can be determined and a fan motor selected to achieve the determined volumetric flow rate. In a specific embodiment, a convection coefficient of about 6 BTU/hr.ft.2° F. corresponds to a volumetric flow rate of about 45 ft/min. Because a pressure drop between freezer compartment 104 (shown in
Investigation of the required mullion center wall 116 opening size to establish adequate flow communication between freezer compartment 104 (shown in
Thus, convective flow in pan 122 produced by air handler 162 is capable of rapidly chilling a six pack of soda more than four times faster than a typical refrigerator. Other items, such as 2 liter bottles of soda, wine bottles, and other beverage containers, as well as food packages, may similarly be rapidly cooled in quick chill and thaw pan 122 in significantly less time than required by known refrigerators.
Heater element 270 is energized to heat air within air handler 162 to produce a controlled air temperature and velocity in pan 122 to defrost food and beverage items without exceeding a specified surface temperature of the item or items to be defrosted. That is, items are defrosted or thawed and held in a refrigerated state for storage until the item is retrieved for use. The user therefore need not monitor the thawing process at all.
In an exemplary embodiment, heater element 270 is energized to achieve an air temperature of about 40° to about 50°, and more specifically about 41° for a duration of a defrost cycle of selected length, such as, for example, a four hour cycle, an eight hour cycle, or a twelve hour cycle. In alternative embodiments, heater element 270 is used to cycle air temperature between two or more temperatures for the same or different time intervals for more rapid thawing while maintaining item surface temperature within acceptable limits. In further alternative embodiments, customized thaw modes are selectively executed for optimal thawing of specific food and beverage items placed in pan 122. In still further embodiments, heater element 270 is dynamically controlled in response to changing temperature conditions in pan 122 and air handler 162.
A combination rapid chilling and enhanced thawing air handler 162 is therefore provided that is capable of rapid chilling and defrosting in a single pan 122. Therefore, dual purpose air handler 162 and pan 122 provides a desirable combination of features while occupying a reduced amount of fresh food compartment space.
When air handler 162 is neither in quick chill mode nor thaw mode, it reverts to a steady state at a temperature equal to that of fresh food compartment 102. In a further embodiment, air handler 162 is utilized to maintain storage pan 122 at a selected temperature different from fresh food compartment 102. Dual damper element 260 and fan 274 are controlled to circulate freezer air to maintain pan 122 temperature below a temperature of fresh food compartment 102 as desired, and single damper element 266, heater element 270, and fan 274 are utilized to maintain pan 122 temperature above the temperature of fresh food compartment 102 as desired Thus, quick chill and thaw pan 122 may be used as a long term storage compartment maintained at an approximately steady state despite fluctuation of temperature in fresh food compartment 102.
handler 162 (see
Controller 320 includes a diagnostic port 322 and a human machine interface (HMI) board 324 coupled to a main control board 326 by an asynchronous interprocessor communications bus 328. An analog to digital converter (“A/D converter”) 330 is coupled to main control board 326. A/D converter 330 converts analog signals from a plurality of sensors including one or more fresh food compartment temperature sensors 332, feature pan (i.e., pan 122 described above in relation to FIGS. 1,2,6) temperature sensors 276 (shown in
In an alternative embodiment (not shown), A/D converter 320 digitizes other input functions (not shown), such as a power supply current and voltage, brownout detection, compressor cycle adjustment, analog time and delay inputs (both use based and sensor based) where the analog input is coupled to an auxiliary device (e.g., clock or finger pressure activated switch), analog pressure sensing of the compressor sealed system for diagnostics and power/energy optimization. Further input functions include external communication via IR detectors or sound detectors, HMI display dimming based on ambient light, adjustment of the refrigerator to react to food loading and changing the air flow/pressure accordingly to ensure food load cooling or heating as desired, and altitude adjustment to ensure even food load cooling and enhance pull-down rate of various altitudes by changing fan speed and varying air flow.
Digital input and relay outputs 338 correspond to, but are not limited to, a condenser fan speed 340, an evaporator fan speed 342, a crusher solenoid 344, an auger motor 346, personality inputs 348, a water dispenser valve 350, encoders coupled to a pulse width modulator 362 for controlling the operating speed of a condenser fan 364, a fresh food compartment fan 366, an evaporator fan 368, and a quick chill system feature pan fan 274 (shown in
Processor 370 is coupled to a power supply 372 which receives an AC power signal from a line conditioning unit 374. Line conditioning unit 374 filters a line voltage which is, for example, a 90-265 Volts AC, 50/60 Hz signal. Processor 370 also is coupled to an Electrically Erasable Programmable Read Only Memory (EEPROM) 376 and a clock circuit 378.
A door switch input sensor 380 is coupled to fresh food and freezer door switches 382, and senses a door switch state. A signal is supplied from door switch input sensor 380 to processor 370, in digital form, indicative of the door switch state. Fresh food thermistors 384, a freezer thermistor 386, at least one evaporator thermistor 388, a feature pan thermistor 390, and an ambient thermistor 392 are coupled to processor 370 via a sensor signal conditioner 394. Conditioner 394 receives a multiplex control signal from processor 370 and provides analog signals to processor 370 representative of the respective sensed temperatures. Processor 370 also is coupled to a dispenser board 396 and a temperature adjustment board 398 via a serial communications link 400. Conditioner 394 also calibrates the above-described thermistors 384, 386, 388, 390, and 392.
Processor 370 provides control outputs to a DC fan motor control 402, a DC stepper motor control 404, a DC motor control 406, and a relay watchdog 408. Watchdog 408 is coupled to an AC device controller 410 that provides power to AC loads, such as to water valve 350, cube/crush solenoid 344, a compressor 412, auger motor 346, a feature pan heater 414, and defrost heater 356. DC fan motor control 402 is coupled to evaporator fan 368, condenser fan 364, fresh food fan 366, and feature pan fan 274. DC stepper motor control 404 is coupled to mullion damper 360, and DC motor control 406 is coupled to feature pan dampers 260, 266.
Processor logic uses the following inputs to make control decisions:
Appendix Tables 1 through 11 define the input and output characteristics of one specific implementation of control board 326. Specifically, Table 1 defines the thermistors and personality pin input/output for connector J1, Table 2 defines the fan control input/output for connector J2, Table 3 defines the encoders and mullion damper input/output for connector J3, Table 4 defines communications input/output for connector J4, Table 5 defines the pan damper control input/output for connector J5, Table 6 defines the flash programming input/output for connector J6, Table 7 defines the AC load input/output for connector J7, Table 8 defines the compressor run input/output for connector J8, Table 9 defines the defrost input/output for connector J9, Table 10 defines the line input input/output for connector J11, and Table 11 defines the pan heater input/output for connector J12.
Quick Chill/Thaw
Referring now to
As noted above with respect to
In temperature zone mode, dampers 260, 266, heater 270 and fan 274 are dynamically adjusted to hold pan 122 at a fixed temperature that is different the fresh food compartment 102 or freezer compartment 104 setpoints. For example, when pan temperature is too warm, dual damper 260 is opened, single damper 266 is opened, and fan 274 is turned on. In further embodiments, a speed of fan 274 is varied and the fan is switched on and off to vary a chill rate in pan 122. As a further example, when pan temperature is too cold, dual damper 260 is closed, single damper 266 is opened, heater 270 is turned on, and fan 274 is also turned on. In a further embodiment, fan 270 is turned off and energy dissipated by fan 274 is used to heat pan 122.
In thaw mode, as explained above with respect to
Heater 270 is controlled by a solid state relay located off of main control board 326 (shown in
Referring to
Once initialization time ti has expired, a Position Damper state 420 is entered. Specifically, in the Position Damper state 420, fan 274 is turned off, dual damper 260 is opened, and single damper 266 is closed. Fan 274 is turned off while positioning dampers 260 and 266 for power management, and fan 274 is turned on when dampers 260, 266 are in position.
Once dampers 260 and 266 are positioned, a Chill Active state 422 is entered and quick chill mode is maintained until a chill time (“tch”) expires. The particular time value of tch is dependent on the chill mode selected by the user.
When Chill Active state 422 is entered, another timer is set for a delta time (“td”) that is less than the chill time tch. When time td expires, air handler thermistors 276 (shown in
After time tch expires, operation advances to a Terminate state 426. In the Terminate state, both dampers 260 and 266 are closed, fan 274 is turned off, and further operation is suspended.
Referring to
Once initialization time ti has expired, a Position Dampers state 434 is entered. In the Position Dampers state 434, fan 274 is shut off, single damper 266 is set to open, and dual damper 260 is closed. Fan 274 is turned off while positioning dampers 260 and 266 for power management, and fan 274 is turned on once dampers are positioned.
When dampers 260 and 266 are positioned, operation proceeds to a Pre-Heat state 436. The Pre-Heat state 436 regulates the thaw pan temperature at temperature Th for a predetermined time tp. When preheat is not required, tp may be set to zero. After time tp expires, operation enters a LowHeat state 438 and pan temperature is regulated at temperature T1. From LowHeat state 438, operation is directed to a Terminate state 440 when a total time tt has expired, or a HighHeat state 442 when a low temperature time t1 has expired (as determined by an appropriate heating profile). When in the HighHeat state 442, operation will return to the LowHeat state 438 when a high temperature time th expires, (as determined by an appropriate heating profile). From the HighHeat state 442, the Terminate state 440 is entered when time tt expires. In the Terminate state 440, both dampers 260, 266 are closed, fan 274 is shut off, and further operation is suspended. It is understood that respective set temperatures Th and T1 for the HighHeat state and the LowHeat state are programmable parameters that may be set equal to one another, or different from one another, as desired.
As explained below, sensing a thawed state of a frozen package in pan 122, such as meat or other food item that is composed primarily of water, is possible without regard to temperature information about the package or the physical properties of the package. Specifically, by sensing the air outlet temperature using sensor 276 (shown in
An amount of heat required by quick chill and thaw system 160 (shown in
Q=ha(tair−tsurface)+A/R(tair−tff) (1)
where ha is a heater constant, tsurface is a surface temperature of the thawing package, tair is the temperature of circulated air in pan 122, tff is a fresh food compartment temperature, and A/R is an empirically determined empty pan heat loss constant. Package surface temperature tsurface will rise rapidly until the package reaches the melting point, and then remains at a relatively constant temperature until all the ice is melted. After all the ice is melted. tsurface rapidly rises again.
Assuming that tff is constant, and because air handler 162 is configured to produce a constant temperature airstream in pan 122, tsurface is the only temperature that is changing in Equation (1). By monitoring the amount of heat input Q into pan 122 to keep tair constant, changes in tsurface may therefore be determined.
If heater 270 duty cycle is long compared to a reference duty cycle to maintain a constant temperature of pan 122 with an empty pan, tsurface is being raised to the package melting point. Because the conductivity of water is much greater than the heat transfer coefficient to the air, the package surface will remain relatively constant as heat is transferred to the core to complete the melting process. Thus, when the heater duty cycle is relatively constant, tsurface is relatively constant and the package is thawing. When the package is thawed, the heater duty cycle will shorten over time and approach the steady state load required by the empty pan, thereby triggering an end of the thaw cycle, at which time heater 270 is de-energized, and pan 122 returns to a temperature of fresh food compartment 102 (shown in
In a further embodiment, tff is also monitored for more accurate sensing of a thawed state. If tff is known, it can be used to determine a steady state heater duty cycle required if pan 122 were empty, provided that an empty pan constant A/R is also known. When an actual heater duty cycle approaches the reference steady state duty cycle if the pan were empty, the package is thawed and thaw mode may be ended.
Firmware
In an exemplary embodiment the electronic control system performs the following functions: compressor control, freezer temperature control, fresh food temperature control, multi speed control capable for the condenser fan, multi speed control capable for the evaporator fan (closed loop), multi speed control capable for the fresh food fan, defrost control, dispenser control, feature pan control (defrost, chill), and user interface functions. These functions are performed under the control of firmware implemented as small independent state machines.
User Interface/Display
In an exemplary embodiment, the user interface is split into one or more human machine interface (HMI) boards including displays. For example,
In an exemplary embodiment, the temperature setting system is substantially the same for each HMI user interface. When fresh food door 134 (shown in
Referring to
Once the SET LED is illuminated, if freezer slew keys 468 are not pressed within a few seconds, such as, for example, within ten seconds, the SET LED will turn off and the current freezer set temperature will be maintained. After this period the user will be unable to change the freezer setting unless one of freezer slew keys 468 is again pressed to re-illuminate the SET LED.
If the freezer temperature is set to a predetermined temperature outside of a standard operating range, such as 7° F., both fresh food and freezer displays 466 will display an “off” indicator, and controller 160 shuts down the sealed system. The sealed system may be reactivated by pressing the freezer colder/slew-down key 468 so that the freezer temperature display indicates a temperature within the operating range, such as 6° F. or lower.
In one embodiment, freezer temperature may be set only in a range between −6° F. and 6° F. In alternative embodiments, other setting increments and ranges are contemplated in lieu of the exemplary embodiment described above.
In a further alternative embodiment, such as that shown in
Similarly, and referring back to
Once the SET LED is illuminated, if the fresh food compartment slew keys 468 are not pressed within a predetermined time interval, such as, for example, one to ten seconds, the SET LED will turn off and the current fresh food set temperature will be maintained. After this period the user will be unable to change the fresh food compartment setting unless one of slew keys 468 are again pressed to re-illuminate the SET LED.
If the user attempts to set the fresh food temperature above the normal operating temperature range, such as 46° F., both fresh food and freezer displays 466 will display an “off” indicator, and controller 160 shuts down the sealed system. The sealed system may be reactivated by pressing the colder/slew-down key so that the set fresh food compartment set temperature is within the normal operating range, such as 45° F. or lower.
In one embodiment, freezer temperature may be set only in a range between 34° F. and 45° F. In alternative embodiments, other setting increments and ranges are contemplated in lieu of the exemplary embodiment described above.
In a further alternative embodiment, such as that shown in
Once fresh food compartment and freezer compartment temperatures are set, actual temperatures (for the embodiment shown in
Normal Operation Display
For temperature settings, and as further described below, a normal operation mode in an exemplary embodiment is defined as closed door operation after a first state change cycle, i.e., a change of state from “warm” to “cold” or vice versa, due to a door opening or defrost operation. Under normal operating conditions, HMI board 462 (shown in
Outside the dead band, however, HMI board 462 displays an actual average temperature for fresh food and freezer compartments 102, 104. For example, for a 37° F. fresh food temperature setting and a dead band of +/−2° F., actual and displayed temperature is as follows.
Thus, in accordance with user expectations, actual temperature displays 466 are not changed when actual temperature is within the dead band, and the displayed temperature display quickly approaches the actual temperature when actual temperatures are outside the dead band. Freezer settings are also displayed similarly within and outside a predetermined dead band. The temperature display is also damped, for example, by a 30 second time constant if the actual temperature is above the set temperature and by a predetermined time constant, such as 20 seconds, if the actual temperature is below the set temperature.
Door Open Display
A door open operation mode is defined in an exemplary embodiment as time while a door is open and while the door is closed after a door open event until the sealed system has cycled once (changed state from warm-to-cold, or cold-to-warm once), excluding a door open operation during a defrost event. During door open events, food temperature is slowly and exponentially increasing. After door open events, temperature sensors in the refrigerator compartments determine the overall operation and this is to be matched by the display.
Fresh Food Display
During door open operation, in an exemplary embodiment temperature display for the fresh food compartment is modified as follows depending on actual compartment temperature, the set temperature, and whether actual temperature is rising or falling.
When actual fresh food compartment temperature is above the set temperature and is rising, the fresh food temperature display damping constant is activated and dependent on a difference between actual temperature and set temperature. For instance, in one embodiment, the fresh food temperature display damping constant is, for example, five minutes for a set temperature versus actual temperature difference of, for example 2° F. to 4° F., the fresh food temperature display damping constant is, for example, ten minutes for a set temperature versus actual temperature difference of, for example, 4° F. to 7° F., and the fresh food temperature display damping constant is, for example, twenty minutes for a set temperature versus actual temperature difference of, for example, greater than 7° F.
When actual fresh food compartment temperature is above the set temperature and falling, the fresh food temperature display damping delay constant is, for example, three minutes.
When actual fresh food compartment temperature is below the set temperature and rising, the fresh food temperature display damping delay constant is, for example, three minutes.
When actual fresh food compartment temperature is below the set temperature and falling, the damping delay constant is, for example, five minutes for a set temperature versus actual temperature difference of, for example, 2° F. to 4° F., the damping delay constant is, for example, ten minutes for a set temperature versus actual temperature difference of, for example, 4° F. to 7° F., and the damping delay constant is, for example, 20 minutes for a set temperature versus actual temperature difference of, for example, greater than 7° F.
In alternative embodiments, other settings and ranges are contemplated in lieu of the exemplary settings and ranges described above.
Freezer Display
During door open operation, in an exemplary embodiment the temperature display for the freezer compartment is modified as follows depending on actual freezer compartment temperature, the set freezer temperature, and whether actual temperature is rising or falling.
In one example, when actual freezer compartment temperature is above the set temperature and rising, the damping delay constant is, for example, five minutes for a set temperature versus actual temperature difference of, for example, 2° F. to 8° F., the damping delay constant is, for example, ten minutes for a set temperature versus actual temperature difference of, for example, 8° F. to 15° F., and the damping delay constant is, for example, twenty minutes for a set temperature versus actual temperature difference of, for example, greater than 15° F.
When actual freezer compartment temperature is above the set temperature and falling, the damping delay constant is, for example, three minutes.
When actual freezer compartment temperature is below the set temperature and increasing, the damping delay constant is, for example, three minutes.
When actual freezer compartment temperature is below the set temperature and falling, the damping delay constant is, for example, five minutes for a set temperature versus actual temperature difference of, for example, 2° F. to 8° F., the damping delay constant is, for example, ten minutes for a set temperature versus actual temperature difference of, for example, 8° F. to 15° F., and the damping delay constant is, for example, twenty minutes for a set temperature versus actual temperature difference of, for example, greater than 15° F.
In alternative embodiments, other settings and ranges are contemplated in lieu of the exemplary settings and ranges described above.
Defrost Mode Display
A defrost operation mode is defined in an exemplary embodiment as a pre-chill interval, a defrost heating interval and a first cycle interval. During a defrost operation, freezer temperature display 4666 shows the freezer set temperature plus, for example, 1° F. while the sealed system is on and shows the set temperature while the sealed system is off, and fresh food display 466 shows the set temperature. Thus, defrost operations will not be apparent to the user.
Defrost Mode, Door Open Display
A mode of defrost operation while a door 132, 134 (shown in
User Temperature Change Display
A user change temperature mode is defined in an exemplary embodiment as a time from which the user changes a set temperature for either the fresh food or freezer compartment until a first sealed system cycle is completed. If the actual temperature is within a dead band and the new user set temperature also is within the dead band, one or more sealed system fans are turned on for a minimum amount of time when the user has lowered the set temperature so that the sealed system appears to respond to the new user setting as a user might expect.
If the actual temperature is within the dead band and the new user set temperature is within the dead band, no load is activated if the set temperature is increased. If the actual temperature is within the dead band and the new user set temperature is outside the dead band, then action is taken as in normal operation.
High Temperature Operation
If the average temperature of both the fresh food temperature and the freezer temperature is above a predetermined upper temperature that is outside of normal operation of refrigerator 100, such as 50° F., then the display of both fresh food actual temperature and freezer actual temperature is synchronized to the fresh food actual temperature. In an alternative embodiment, both displays are synchronized to the freezer actual temperature when the average temperature of both the fresh food temperature and the freezer temperature is above a predetermined upper temperature that is outside a normal range of operation.
Showroom Mode
A showroom mode is entered in an exemplary embodiment by selecting some odd combination of buttons 464, 472 (shown in
Temperature Controls
In an exemplary embodiment, temperature controls operate as normal (without turning on fans or compressor) i.e., when door is opened, temperature displays “actual” temperature, approximately 70°. Selecting the Quick Chill or Quick Thaw button (shown in
Dispenser Controls
In addition, in an exemplary embodiment the dispenser operates as normal, and all functions “reset” when door is closed (i.e., fans and LED's turn off). The demo mode is exited by either unplugging the refrigerator or selecting a same combination of buttons used to enter the demo mode.
The water/crushed/cubed dispensing functions are exclusively linked by the firmware. Specifically, selecting one of these buttons selects that function and turns off the other two functions. When the function is selected, its LED is lit. When the target switch is depressed and the door is closed, the dispense occurs according to the selected function. The water selection is the default at power up.
For example when the user presses the “Water” button (see
When the user hits the dispenser target switch, a light coupled to dispenser board 396 (shown in
A “Door Alarm” switch (see
Selecting a “Light” button (see
When the interface is locked, no dispenser key presses will be accepted including the target switch, which prevents accidental dispensing that may be caused by children or pets. Key presses with the system locked are acknowledged with, for example, three pulses of the Lock LED accompanied by audible tone in one embodiment.
The “Water Filter” LED (see
Turbo Cool
Selecting the “Turbo Cool” button (see
When the turbo cool mode is complete, the fresh food set point reverts to the user-selected set point and the fans revert to an appropriate lower speed. The turbo mode is terminated if the user presses the turbo button a second time or at the end of the eight-hour period. The turbo cool function is retained through a power cycle.
Quick Chill/Thaw
For thaw pan 122 operation the user presses the “Thaw” button (see
Service Diagnostics
Service diagnostics are accessed via the cold control panel (see
To access the diagnostic modes, in one embodiment, all four slew keys (see
At the end of a test session, the technician enters, for example, “14” in on the display and then presses Chill to execute a system restart in one embodiment. A second option is to unplug the unit and plug it back into the outlet. As a cautionary measure, the system will automatically time out of the diagnostic mode after 15 minutes of inactivity.
Self-test
An HMI self-test applies only to the temperature control board inside the fresh food compartment. There is no self-test defined for the dispenser board as the operation of the dispenser board can be tested by pressing each button.
Once the HMI self-test is invoked, all of the LEDs and numerical segments illuminate. When the technician presses the Thaw button (shown in
In one embodiment, the HMI test checks six thermistors (see
The warmer/colder arrows can be pressed to move onto the next thermistor. In an exemplary embodiment, the order of the thermistors is as follows:
Fresh Food 1
Fresh Food 2
Freezer
Evaporator
Feature Pan
Other (if any).
In various embodiments, “Other” includes one or more of, but is not limited to, a second freezer thermistor, a condenser thermistor, an ice maker thermistor and an ambient temperature thermistor
Factory Diagnostics
Factory diagnostics are supported using access to the system bus. There is a 1-second delay at the beginning of the diagnostics operation to allow interruption. Appendix Table 14 illustrates the failure management modes that allow the unit to function in the event of soft failures. Table 14 identifies the device, the detection used, and the strategy employed. In the event of a communication break, the dispenser and main boards have a time-out that prevents water from dumping on the floor.
Each fan 274, 364, 366, 368 (see
Communications
Main control board 326 (shown in
The sensor state command returns a byte. The bits in the byte correspond to the values set forth in Appendix Table 21. The state of the refrigerator state returns the bytes as set forth in Appendix Table 17.
HMI board 324 (shown in
Dispenser board 396 (shown in
Regarding HMI board 324 (shown in
Main control board 326 (shown in
Operating Algorithms
Power Management
Power management is handled through design rules implemented in each algorithm that affects inputs/outputs I/O. The rules are implemented in each I/O routine. A sweat heater (see
Watchdog Timer
Both HMI board 324 (shown in
Timer Interrupt
Software is used to check if the timer interrupt is still functioning correctly. The main portion of the code periodically monitors a flag, which is normally set by the timer interrupt routine. If the flag is set, the main loop clears the flag. However if the flag is clear, there has been a failure and the main loop reinitializes the microprocessor.
Magnetic H Bridge Operation
An H bridge on dispenser board 324 (shown in
To disable the magnet, the enable signal is driven high and a delay of 2.5 mS occurs before the direction signal is driven low.
To enable the magnet in one direction, the enable signal is driven high and a delay of 2.5 mS occurs before the direction signal is driven low. A second 2.5 mS delay occurs before the enable signal is driven low.
To enable the magnet in the other direction, the enable signal is driven high and a delay for 2.5 mS occurs before the direction signal is driven high. A second 2.5 mS delay occurs before the enable signal is driven low.
At initialization (reset) the disable magnet process should be executed.
Keyboard Debounce
A keyboard read routine is implemented as follows in an exemplary embodiment. Each key is in one of three states: not pressed, debouncing, and pressed. The state and current debounce count for each key are stored in an array of structures. When a keypress is detected during a scan, the state of the key is changed from not pressed to debouncing. The key remains in the debouncing state for 50 milliseconds. If, after the 50 millisecond delay, the key is still pressed during a scan of that keys row, the state of the key is changed to pressed. The state of the key remains pressed until a subsequent scan of the keypad reveals that the key is no longer pressed. Sequential key presses are debounced for 60 milliseconds.
The following
Sealed System
If the freezer needs to be defrosted, the electronics stop the condenser fan, compressor, evaporator fan and turn on the defrost heater. As further described below, the sealed system also starts and stops the defrost heater when signaled to do so by defrost control. The sealed system also inhibits evaporator fan operation when a fresh food door or freezer door is opened.
Fresh Food Fan
Dispenser
When the user selects cubed ice, a cradle switch is activated and the dispenser calls the crusher bypass routine to dispense ice.
When the user selects crushed ice, the cradle switch is activated, and the dispenser calls the electromagnet and auger motor routines to control the operation of the duct door, auger motor, and crusher. Upon activating the cradle switch, the electromagnet routine opens the duct door and the auger motor routine starts the auger motor and the crusher is operated. When the cradle switch is released for a predetermined time, such as five seconds in an exemplary embodiment, the dispenser closes the duct door and the auger motor stops.
When the user selects water, the cradle switch is activated, the electronics sends activate the water valve signal to the dispenser, which calls the water valves routine to open the water valve until the cradle switch is deactivated.
When the user selects activate light, the electronics sends a toggle light signal to the dispenser, which calls the light routine to toggle the light. Also, the light is activated during any dispenser function.
The user must depress “lock” for at least two seconds to select to lock the keypad, then the electronics set the keypad to lockout mode.
The user must depress the water filter “reset” for at least two seconds to reset the water filter timer. The electronics then will reset the water filter timer and turn off the LED.
Interface
Dispenser Interaction
The user selects water to be dispensed and depresses the cradle or target switch. Once water is selected and the target switch is depressed, a delay timer is initialized, and a request is made by HMI board 324 (shown in
If the user releases the target switch during dispensing or the freezer door is opened, the water relay will be opened. Initially, HMI board 326 (shown in
Main control board 326 acknowledges that it received the start auger command from HMI board 324 over the communications port and activates the auger relay to start auger motor 346. Control board 326 then restarts the delay timer and starts the watchdog timer of the dispenser. When the watchdog timer expires, the auger relay is opened, auger motor 346 is stopped.
If the target switch is released at any time during this process, HMI board 324 requests that the auger and the dispenser light be turned off and that the duct door be closed. Also, if the freezer door is opened auger motor 346 is stopped and the duct door is closed.
Main control board 326 acknowledges that it received the start auger command from HMI board 324 over the communications port and activates the auger relay to start auger motor 346. Main control board 326 then restarts the delay timer and starts the watchdog timer of the dispenser. When the watchdog timer expires, the auger relay is opened, auger motor 346 is stopped.
If the target switch is released at any time during this process, HMI board 324 will request auger motor 346 and the dispenser light be turned off and the duct door be closed. Also, if freezer door 132 (shown in
Temperature Setting
Quick Chill Interaction
Turbo Mode Interaction
If the user depresses the turbo cool button a second time, or when the eight hour timer has expired, the communications port will send an exit turbo mode command to main control board 326. Main control board 326 will acknowledge the command request and place the refrigerator in normal operating mode and deactivate the turbo cool LED.
Freshness Filter
HMI board 324 also resets the freshness filter timer for a period of at least six months. When the time period expires, the freshness filter light on the refrigerator is turned on. On a daily basis, HMI board 324 updates timer values based on the six month timer. The daily timer updates are transferred by HMI board 324 through the communications port to main control board 326, where the daily timer updates are logged as new timer values in the EEPROM 376 (shown in 9
Water Filter
HMI board 324 also resets the water filter timer for a period of at least six months. When the time period expires, the water filter light on the refrigerator is turned on to remind the user to replace the water filter. On a daily basis, HMI board 324 updates timer values based on the timer. The daily timer updates are transferred by HMI board 324 through the communications port to main control board 326 (shown in
Door Interaction
A door sensor input 358 (shown in
Sealed System State
Dispenser Control
Defrost Control
Fan Speed Control
K values, i.e. controls Kp, Ki, and Kd, then are set as either high or low-depending on, e.g. freezer compartment and ambient temperatures, sealed system run time, and whether the refrigerator is in turbo mode. A PWM duty cycle then is set in accordance with the relationship:
D=KpV+KiA+KdD (2)
If the sealed system is turned on, the condenser fan is enabled to the output of the pulse width modulator and the evaporator may be checked, depending on the mode setting, to see it is cool or the timeout has elapsed, and the evaporator fan is enabled. Otherwise, the evaporator fan is enabled. If the sealed system is turned off, the condenser fan is turned off, and the evaporator is checked, depending on the mode setting, to see if it is warm or the timeout has elapsed. The evaporator fan is turned off.
When a diagnostic mode has been specified, the circuit diagnostic capability is enabled as described above. Both voltages around resistor Rsense are read and motor power is calculated in accordance with the relationship:
(V1−V2)2/Rsens (3)
An expected motor wattage and tolerance are read from EEPROM 376 (shown in
Turbo Mode Control
If the turbo LED is not on when the user depressed the turbo button, the LED is illuminated for at least eight hours, and the refrigerator is placed in turbo mode. All fans are set to high speed mode and the refrigerator temperature fresh food temperature set point is set to the user's selected value, the value being less than or equal to 35° F., for at least an eight hour period. If the refrigerator is in defrost mode, the condenser fan is turned on for at least ten minutes; otherwise, the compressor and all fans are turned on for at least ten minutes.
Filter Reminder Control
Sensor Calibration
SensorVal=SensorVal*m+b (4)
The slope-and-offset-adjusted sensor value then is incorporated into an adjusted corresponding rolling average for each cycle in accordance with the relationship:
RollingAVGn=alpha*SensorVal+(1−alpha)*RollingAVG(n−1) (5)
where n corresponds to the current cycle and (n−1) is the previous cycle.
Main Controller Board State
In normal operation, the command processor routine interfaces with the system mode data store. The command processor routine also transmits commands and receives status information from the protocol data transmit routine and protocol data pass routines. The protocol data pass routine exchanges status information with the clear buffer routine and the protocol packet ready routine. All three routines interface with the Rx buffer data store. The Rx buffer data store also interfaces with the physical get Rx character routine. The protocol data transmit routine exchanges status information with the physical transmit char routine and transmit port routine. A communication interrupt is provided to interrupt the command processor, physical get Rx character, Physical xmt character, and transmit port routines.
The main routine provides status information during normal operation with the update rolling average routine. The update rolling average routine interfaces with the rolling average buffer data store. This routine exchanges sensor numbers, state code and value with the apply calibration constants and linearize routine. The linearize routine exchanges sensor numbers, status code and analog-digital (A/D) information with the read sensor routine.
Also, the main routine during normal operation provides status information to the fresh food fan speed and control routine, fresh food light routine, defrost routine, and the sealed system routine.
The fresh food fan speed and control routine provides status code, set/clear command, and pointer to device list to the I/O drives routine. I/O drives routine further interfaces with the defrost, sealed system, dispenser, and update fan speeds routines.
The sealed system routine provides status code to the set/select fan speeds routine, and the sealed system routine provides time and state code information to the delay routine.
A timer interrupt interfaces with the dispenser, update fan speeds, and update times routines. The dispenser routine interfaces with the dispenser control data store. The update fan speeds routine interfaces with the fan status/control data store.
The main routine during initialization provides state code information to the update time routine, which in turn updates the defrost timer, fresh food door open timer, dispenser time out, sealed system off timer, sealed system on timer, freezer door open timer, timer status flag, daily rollover, and quick chill data stores.
Interface Main State
The Command Processor routine interfaces with Protocol Data Parse, Protocol Data Xmit, and LED Control. The Dispense routine interfaces with the Protocol Data Parse, Protocol Data Xmit, LED Control, and Keyboard Scan routines. The Diagnostic routine interfaces with the Protocol Data Parse, Protocol Data Xmit, LED Control, Keyboard scan routines, as well as the OneMinute data store. The HMI Diagnostic routine interfaces with LED Control and Keyboard scan routines and the OneMinute data store. The Setpoint adjust routine interfaces with Protocol Data Parse, Protocol Data Xmit, LED Control, Keyboard scan and the OneMinute data store. The Protocol Data Parse routine interfaces with Clear Buffer and Protocol Packet Ready routines and the RX buffer data store. Protocol Data Xmit interfaces with Physical Xmit Char and Xmit Port avail routines. Both Physical Xmit Char and Xmit Port Avail routines disable interrupts.
There are two sets of interrupts: communications interrupt and timer interrupts. Timer interrupt interfaces with data stores DayCount, Daily Rollover, Quick Chill Timer, OneMinute, and Turbo Timer. On the other hand, communication interrupt interfaces with software routines Physical Get RX Character, Physical Xmit Char, and Xmit Port Avail.
To achieve control of energy management and temperature performance, main controller board 326 (shown in
Hardware Schematics
Microcontroller 540 is electrically connected to crystal clock circuitry 542, reset circuitry 544, evaporator/condenser fan control 546, DC motor drivers 548 and 550, EEPROM 552, stepper motor 554, communications circuitry 556, interrupt circuitry 558, relay circuitry 560, and comparator circuitry 562.
Clock circuitry 542 includes resistor 564 electrically connected in parallel with a 5 MHz crystal 566. Clock circuitry 542 is connected to microcontroller 540's clock lines 568.
Reset circuitry 544 includes a 5V supply connected to a plurality of resistors and capacitors. Reset circuitry 544 is connected to microcontroller 540 reset line 570.
Evaporator/Condenser fan control 546 includes both 5V and 12 V power, and is connected to microcontroller 540 lines at 572.
DC motor drives 548 and 550 are connected to 12V power. DC motor drive 548 is connected to microcontroller 540 at lines 574, and DC motor 550 is connected to microcontroller 540 at lines 576.
Stepper motor 554 is connected to 12V power, zener diode 578, and biasing circuitry 580. Stepper motor 554 is connected to microcontroller 540 at lines 582.
Interrupt circuitry 558 is provided at two places on main controller board 326. A resistive capacitive divider network 584 is connected to microcontroller 540 INT2, INT3, INT4, INT5, INT6, and INT7 on lines 586. In addition, interrupt circuitry 558 includes a network including a pair of optocouplers 588; this network is connected to microcontroller 540 INT0 and INT1 on lines 590.
Communications circuitry 556 includes transmit/receive circuitry 592 and test circuitry 596. Transmit/receive circuitry 592 is connected to microcontroller 540 at lines 594. Test circuitry 596 is connected to microcontroller 540 at lines 598.
Comparator circuitry 562 includes a plurality of comparators to verify input signals with a reference source. Each comparison circuit is connected to microcontroller 540.
Electrical power to main controller board 326 is provided by power supply circuitry 536. Power supply circuitry 536 includes a connection to AC line voltage at terminal 600 and neutral terminal 602. AC line voltage 600 is connected to a fuse 604 and to high frequency filter 606. High frequency filter 606 is connected to fuse 604 and to filter 608 at node 610. Filter 608 is connected to a full-wave bridge rectifier 612 at nodes 614 and node 616. Capacitor 618 and capacitor 620 are connected in series and connected to node 622. Connected between nodes 622 and node 624 are capacitors 626 and 628. Also connected to node 622 is diode 630. Connected to diode 630 is diode 632. Diode 632 is connected to node 634. Also connected to node 634 is the drain of IC 636. Source of IC 636 is connected to node 642, and Control is connected to the emitter output of optocoupler 638. Connected between nodes 622 and node 634 is primary winding of transformer 640. Transformer 640 is a step-down transformer, and its secondary windings include a node 642. Connected to the top-half of transformer 640's secondary winding is diode 644. Diode 644 is connected to node 646 and inductive capacitive filter network 648. Node 646 supplies main controller board 326 12VDC. Connected to the bottom-half of transformer 640's secondary winding is a half-wave rectifier 650. Half-wave rectifier 650 includes diode 652 connected to node 656 and capacitor 654. Capacitor 654 is also connected to node 656. Connected to node 656 is optocoupler 638. At node 658, cathode of diode 660 of optocoupler 638 is connected to zener diode 662. Optocoupler 638 output is connected to nodes 656 and to IC 636 control. In addition, optocoupler 638 emitter output is connected to RC filter network 664. Connected to the anode of zener diode 662 is a 5V generation network 666. 5V generation network 666 takes 12V generated at node 668 and converts it to 5V, and then network 666 supplies 5V to main controller board 326 from node 667.
Biasing circuit 538 includes a plurality of transistors and MOSFETs connected together to 12V and 5V supply to provide power to main controller board 326 to power condenser fan 364 (shown in
Power Supply circuitry 536 functions to convert nominally 85 VAC to 265 VAC to 12VDC and 5VDC and provide power to main controller board 326. AC voltage is connected to power supply circuitry 536 at the line terminal 600 and neutral terminal at 602. Line terminal 600 is connected to fuse 604 which functions to protect the circuit if the input current exceed 2 amps. The AC voltage is first filtered by high frequency filter 606 and then converted to DC by full-wave bridge rectifier 612. The DC voltage is further filtered by capacitors 626 and 628 before being transferred to transformer 640. The series combination of diodes 630 and 632 serves to protect transformer 640. If the voltage at node 622 exceeds the 180 volts rated voltage of diode 630.
The output of the top-half of the secondary coil of transformer 640 is tested at node 646. If the voltage drops at node 646 such that a high current condition exists at node 646, optocoupler 638 will bias IC 636 on. When IC 636 is turned on, high current is drawn through IC 636 drain, which protects transformer 640 and also stabilizes the output voltage.
Main controller board 326 controls the operation of refrigerator 100. Main controller board 326 includes electrically erasable and programmable microcontroller 540 which stores and executes a firmware, communications routines, and behavior definitions described above.
The firmware functions executed by main controller board 326 are control functions, user interface functions, diagnostic functions and exception and failure detection and management functions. The user interface functions include: temperature settings, dispensing functions, door alarm, light, lock, filters, turbo cool, thaw pan and chill pan functions. The diagnostic functions include service diagnostic routines, such as, HMI self test and control and Sensor System self test. The two Exception and Failure Detection and Management routines are thermistors and fans.
The communications routine functions to physically interconnect main controller board 326 (shown in
The behavioral definitions include the sealed system 480 (shown in
In addition to the core functions such as firmware, communications, and behavior, main controller board 326 stores in microcontroller 540 key operating algorithms such as power management, watchdog timer, timer interrupt, keyboard debounce, dispenser control 508 (shown in
Main controller board 326 also controls interactions between a user and various functions of refrigerator 100 such as dispenser interaction, temperature setting interaction 494 (shown in
Microcontroller 670 is powered by 5VDC and is connected to reset circuitry 672 at reset line 692.
Clock circuitry 674 includes a resistor 694 connected in parallel with a crystal 696 and connected to microcontroller 670 at clock input 698.
Alarm circuitry 676 includes a speaker 700 connected to a biasing network 702. Alarm circuitry 676 is connected to microcontroller 670 line 704.
Lamp circuitry 678 includes resistor 706 connected to MOSFET 708, which is connected to diode 710 and resistor 712. Diode 710 is connected to a 12V supply at node 714. Node 714 and resistor 712 are connected to junction2716. Lamp circuitry 678 is connected to microcontroller 670 at 718.
Heater control circuitry 680 includes resistor 720 connected in series to MOSFET 722, which is connected to junction2716 and junction4724. Heater control circuitry 680 is connected to microcontroller 670 at 726.
Cup switch circuitry 682 includes a zener diode 728 connected in parallel to a resistor 730 and capacitor 732 at node 734. Node 734 is connected to a resistor 736 and junction2678. Cup switch circuitry 682 is connected to microcontroller 670 at 738.
Microcontroller 670 is also connected to communications circuitry 684. Communications circuitry 684 is connected to junction4724 and to test circuitry 686. Communications circuitry 684 transmit line is connected to microcontroller 670 at 740 and communications circuitry 684 receive line is connected at 742. Test circuitry 686 transmit and receive lines are also connected to microcontroller 670 at lines 740 and 742, respectively.
Microcontroller 670 also is connected to dispenser selection circuitry 688. Dispenser selection circuitry 688 includes a push button connected to 5V and connected to a resistor, which is connected to microcontroller 670 and a switch through junction6744. A plurality of push buttons is connected to a plurality of resistors and switches for each dispenser function: water filter, cubed ice, light, crushed ice, door alarm, water, and lock. Dispenser selection circuitry is connected to microcontroller 670 at lines 746.
LED driver circuitry 690 includes an inverter connected in series to a resistor which is connected to a LED through junction 744. LED driver circuitry 690 includes a plurality of inverters connected to a resistors and LEDs for the following functions: a water filter LED, a cubed ice LED, a crushed ice LED, a door alarm LED, a water LED, and a lock LED. LED driver circuitry 690 is connected to microcontroller 670 at 748.
Furthermore, microcontroller 670 functions to store and execute firmware routines for a user to select, such as, resetting a water filter, dispensing cubed ice, dispensing crushed ice, setting a door alarm, dispensing water, and locking as described above. Microcontroller 670 also includes firmware to control turning on and off an alarm, a light, a heater. In addition, dispenser 396 cup switch circuitry 682 determines if a cup depresses a cradle switch for when a user wants to dispense ice or water. Lastly, Dispenser 396 includes communication circuitry 684 to communicate with main controller board 326.
Microcontroller 750 is powered by 5VDC and is connected to reset circuitry 752 at reset line 766.
Clock circuitry 754 includes a resistor 768 connected in parallel with a crystal 770 and connected to microcontroller 750 at clock inputs 772 and 774.
Alarm circuitry 756 includes a speaker 776 connected to a biasing network 778. Alarm circuitry 756 is connected to microcontroller 750 line 780.
Microcontroller 750 is also connected to communications circuitry 758. Communications circuitry 758 is connected to junction2782 and to test circuitry 760. Communications circuitry 758 transmit line is connected to microcontroller 750 at 784 and communications circuitry 758 receive line is connected at 786. Test circuitry 760 transmit and receive are also connected to microcontroller 750 at lines 784 and 786, respectively.
Level shifting circuitry 762 includes a plurality of level shifting circuits, where each circuit includes a plurality of transistors configured to shift the voltage from 5V to 12V to drive thermistors. Each level shifting circuit is connected to microcontroller 750 at 766 at one end and junction1790 at the other.
Driver circuitry 764 includes a plurality of driver circuits, where each circuit includes a plurality of transistors configured as emitter-followers. Each driver circuit is connected to microcontroller 750 at 792 and junction1790.
While the invention has been described in terms of various specific embodiments, those skilled in the art will recognize that the invention can be practiced with modification within the spirit and scope of the claims.
This application is a Divisional of U.S. patent application Ser. No. 09/742,545, filed Dec. 22, 2000, now U.S. Pat. No. 6,782,706 which is hereby incorporated by reference in its entirety.
Number | Name | Date | Kind |
---|---|---|---|
3759053 | Swaneck, Jr. | Sep 1973 | A |
4002199 | Jacobs | Jan 1977 | A |
4358932 | Helfrich, Jr. | Nov 1982 | A |
4368622 | Brooks | Jan 1983 | A |
4387578 | Paddock | Jun 1983 | A |
4490986 | Paddock | Jan 1985 | A |
4535598 | Mount | Aug 1985 | A |
4555057 | Foster | Nov 1985 | A |
4566285 | Tershak et al. | Jan 1986 | A |
4573325 | Chiu et al. | Mar 1986 | A |
4604871 | Chiu et al. | Aug 1986 | A |
4646528 | Marcade et al. | Mar 1987 | A |
4707684 | Janke et al. | Nov 1987 | A |
4834169 | Tershak et al. | May 1989 | A |
4841735 | Oike | Jun 1989 | A |
4949550 | Hanson | Aug 1990 | A |
4966004 | Midlang et al. | Oct 1990 | A |
4969576 | Merrill et al. | Nov 1990 | A |
4970870 | Midlang et al. | Nov 1990 | A |
5033273 | Buchser et al. | Jul 1991 | A |
5123253 | Hanson et al. | Jun 1992 | A |
5136865 | Aoki et al. | Aug 1992 | A |
5187941 | Tershak et al. | Feb 1993 | A |
5337575 | Ishihara | Aug 1994 | A |
5398251 | Shim | Mar 1995 | A |
5437163 | Jurewicz et al. | Aug 1995 | A |
5454230 | Janke et al. | Oct 1995 | A |
5476672 | Kim | Dec 1995 | A |
5787718 | Jeong | Aug 1998 | A |
5872721 | Huston et al. | Feb 1999 | A |
5886430 | Ralson et al. | Mar 1999 | A |
6401481 | Hiraoka et al. | Jun 2002 | B2 |
6405544 | Hiraoka et al. | Jun 2002 | B2 |
6405547 | Hiraoka et al. | Jun 2002 | B2 |
6405548 | Hollenbeck | Jun 2002 | B1 |
6526766 | Hiraoka et al. | Mar 2003 | B1 |
6655158 | Wiseman et al. | Dec 2003 | B1 |
6662574 | Loibl et al. | Dec 2003 | B2 |
6802369 | Zentner et al. | Oct 2004 | B2 |
6865900 | Ozawa et al. | Mar 2005 | B2 |
7036334 | Ko et al. | May 2006 | B2 |
7051549 | Kim et al. | May 2006 | B2 |
20020011072 | Hiraoka et al. | Jan 2002 | A1 |
Number | Date | Country |
---|---|---|
04161775 | Jun 1992 | JP |
04187970 | Jul 1992 | JP |
04244569 | Sep 1992 | JP |
06213547 | Aug 1994 | JP |
07174453 | Jul 1995 | JP |
11223444 | Aug 1999 | JP |
Number | Date | Country | |
---|---|---|---|
20050011205 A1 | Jan 2005 | US |
Number | Date | Country | |
---|---|---|---|
Parent | 09742545 | Dec 2000 | US |
Child | 10919081 | US |