1. Field of the Invention
This invention relates to the field of engine cranking motors, and particularly to systems and methods for soft-starting cranking motors used in diesel-electric locomotive engines.
2. Description of the Related Art
High fuel costs and increasingly strict air pollution regulations have increased the frequency of engine starts in diesel-powered locomotives, highway trucks and off-road vehicles. More engine starts have increased the failure rate of the cranking motors and gears used to start these large engines.
Engines of this sort typically have one or two cranking motors. A schematic diagram for a conventional ‘contactor-switched hard-start’ system using one cranking motor is shown in
The spring loaded solenoid plunger retracts in response to the magnetic field produced by the hold and pull-in coil currents. In cooperation with the clevis and pawl linkage, the plunger retraction first moves pinion gear 8 into engagement with engine flywheel ring gear 9 and then closes solenoid contacts 7. The closure of the solenoid contacts also removes battery voltage from pull-in coil 6, thus eliminating the possibility of over-heating the short-time rated low resistance pull-in coil. In normal operation, the pinion gear 8 engages the ring gear 9, the pinion gear slides into mesh with the ring gear and the solenoid contacts 7 close to connect the motor to the battery. The longer-time rated hold coil keeps the solenoid plunger pulled in until the engine starts.
The momentary flow of pull-in coil current through the windings of cranking motor 2 produces a moderate amount of motor torque, which in turn causes pinion gear 8 to rotate slowly as it moves toward ring gear 9. This rotary motion is intended to reduce the probability of a “sticking” abutment in the event that the faces of the pinion and ring gears touch when the planes of the two gears meet. Sticking abutments frequently occur during locomotive engine cranking in spite of the low speed rotation provided by the pull-in coil current passing through the cranking motor windings. To reduce the probability of sticking abutments, locomotive cranking systems sometimes shunt the two pull-in coils with additional resistance to increase the net momentary current in the motor windings. This approach is illustrated in, for example, a locomotive service manual such as EMD SD70MAC Locomotive Service Manual, P.N. 500049EP.
Avoiding a sticking abutment by spinning the pinion gear before it engages the ring gear is problematic because: 1) high motor friction may result in insufficient torque to break the abutment, and 2) compensating for high friction by reducing the resistance between the battery and motor may result in motor over-speed if the pinion gear fails to move because of a stuck solenoid plunger.
The high moment of inertia of the engine and its load cause motor current and torque to reach extreme levels before the motor reaches a speed where its counter-EMF acts to reduce the current and torque. High initial current burns the cranking motor commutator bars and carbon brushes, and high initial torque accelerates the wear-out of the pinion and ring gears as well as the motor nose bearing. The problem of high initial current and torque is aggravated in the diesel-electric locomotive (and in stationary engine generator power plants as well) by the added moment of inertia of the traction alternator and the companion alternator. The rotating mass of these machines extends the duration of high current during the acceleration phase of the start sequence.
Curves of per-unit voltage 13, current 14 and torque 15 are sketched in
A hard-start system which employs two cranking motors is shown in
Two-motor cranking does not permit the solenoid contacts to be used for connecting the motor to the battery. Instead, a power contactor controlled by the solenoid contacts must be provided for that purpose. Solenoids 29 and 30 of
The sequence of operations for a hard-start system such as that shown in
1. A locomotive control computer (not shown) closes the start switch 20 which energizes the coil 22 of the 4-pole pilot relay.
2. Pilot relay contacts 23, 24, 25 and 26 close.
3. Battery voltage is applied to the two series-connected hold coils 27 and 28 of solenoids 29 and 30. Current to the two pull-in coils 31 and 32 is routed through the low resistance windings of the motors 18 and 19.
4. The magnetic forces created by the currents in the solenoid pull-in and hold coils cause the solenoid plungers to begin to retract into the solenoid cavities, compressing a spring in the process. The action of the pawl and clevis mechanisms causes the pinion gears 33 and 34, splined to the armature shafts, to begin to move forward toward the ring gear 35.
5. Simultaneous with the rectilinear motion of the pinion gears 33 and 34, the cranking motors 18 and 19 begin to rotate due to the current passing through the pull-in coils 31 and 32, augmented by current from two low resistance resistors 36 and 37.
6. When the plane of the pinion gear face reaches the plane of the ring gear face, the two gears either slide into mesh, or the edges of the gears abut (about 30% probability). If the motor's angular momentum combined with the torque produced by current in the low resistance resistors and the pull-in coils is sufficient, the abutment static friction is broken and the two gears slide into mesh.
7. Again referring to prior art circuit of
8. The contacts 42 and 43 of the two contactors close to apply the battery voltage to the positive and negative terminals of the two series-connected cranking motors 18 and 19 while removing battery voltage from the pull-in coils. The current in the hold coils remains to keep the solenoid plungers pulled in, thus maintaining the engagement of the pinion and ring gears.
9. If a cranking motor's angular momentum augmented by current through the pull-in coils and the low resistance resistors is insufficient to overcome the abutment friction, the rotation of pinion gears 33 and 34 stops and motor current increases to a limit set by the resistance of the parallel combination of the two pull-in coils and the two low resistance resistors. In this event, the locomotive control computer opens relay contacts 20 to abort the engine starting sequence.
The cranking operation is terminated after the engine speed reaches the firing speed by the opening of switch 20 and the subsequent removal of voltage from the pilot relay coil 22. The pilot relay contacts 23 and 24 open to de-energize the solenoid and pilot relay contacts 25 and 26 open to de-energize coils 40 and 41 of the two contactors. Contactor contacts 42 and 43 then open to remove the battery voltage from the motors. Motor rotation stops and the previously compressed spring in the solenoid pulls the pinion gears out of mesh with the ring gear 35.
Cranking is also terminated if engine firing has not been achieved before a time limit of typically 20 s is reached.
The start sequence is aborted if abutment occurs and is not broken by the momentum of the cranking motor's pre-engagement spin, or by torque from motor current.
The per-unit voltage, current and torque profiles (not shown) are similar to those for the single motor hard-start system shown in
An engine cranking motor soft-start system and method are presented which tends to: 1. increase the number of engine starts before the cranking motor wears out, and 2. reduce the probability of an aborted engine start caused by gear face abutment.
The present soft-start engine cranking system is for engines that employ an electric cranking motor to start an engine. The system includes at least one cranking motor and a switching power converter having an output which is coupled to the cranking motors such that the voltage across the cranking motors varies in proportion to the duty cycle at which the switching power converter is operated. The system is arranged such that the duty cycle of the switching power converter, and thereby the voltage across the cranking motors, is gradually increased over a predetermined period. This serves to limit the acceleration of the cranking motor, and thereby its peak current and torque, which serves to increase the service life of the motor.
The cranking motor is typically operatively coupled to drive a pinion gear which is brought into engagement with a ring gear when starting the engine. The system is preferably arranged such that the gradually increasing duty cycle of the switching power converter results in the torque of the cranking motor being sufficient to break an abutment that may be present between the pinion and ring gears.
The present system can be adapted for use with starting systems that employ a single cranking motor, or more than one cranking motor. The system may also be arranged to employ a cranking motor arrangement rated to operate at a voltage less than that provided by the battery, which may enable the use of less costly cranking motors. In this case, the duty cycle of the switching power converter is preferably arranged to limit the voltage across the cranking motor to no more than its rated value.
Novel features of the present system and method include:
1. Ramp voltage instead of step voltage reduces the current and torque required to accelerate the inertia of the engine and its load.
2. Charging the switching power converter bus capacitor through the solenoid pull-in coil(s) eliminates the need for a surge rated resistor(s).
3. Controlling the motor voltage with a buck converter provides motor current greater than battery current when motor voltage is less than battery voltage. Results: 1. Before the contactor contacts close and battery current is limited by the bus capacitor pre-charge resistance, enough motor current is available to break a gear abutment, and 2. Less battery charge is required to start the engine.
4. The power converter allows the use of twin 24 V motors in a 64 V cranking system. Motor cost is reduced and speed capability is increased.
Further features and advantages of the invention will be apparent to those skilled in the art from the following detailed description, taken together with the accompanying drawings.
a is a schematic diagram of a known contactor-switched hard-start system using one cranking motor.
b is a graph depicting current, torque and voltage for the cranking motor shown in
a is a schematic diagram of an engine cranking motor soft-start system per the present invention, which employs one cranking motor.
b is a graph depicting current, torque and voltage for the one motor soft-start cranking system shown in
a is a schematic diagram depicting a solenoid pull-in control circuit as might be used in an engine cranking motor soft-start system per the present invention.
b shows signal waveforms for the solenoid pull-in controller shown in
a is a schematic diagram of a PWM circuit that ramps up the motor voltage over a pre-set time period.
b shows the output PWM signal of the PWM controller device and the gate-to-cathode voltage of the high current MOSFET transistor that limits the peak cranking motor current.
a shows the circuit diagram of a cranking speed limit circuit per the present invention.
b depicts speed vs. time profiles with two 32 V motors connected in series and soft-started from a 32 cell fully charged battery.
a depicts diesel engine cranking speed with 32 V motors and a 32 cell battery with fully charged and partially charged batteries.
b depicts diesel engine cranking speed with 24 V motors and a 32 cell battery with fully charged and partially charged batteries.
The present engine cranking motor soft-start system is designed to increase the cranking motor service life by using power electronics to limit the acceleration of the engine, and thereby reduce the cranking motor's peak current and torque. One primary application relates to diesel-electric locomotive engines formerly manufactured by the Electro-Motive Division of the General Motors Corporation, and more recently by the Electro-Motive Diesel Division of the Caterpillar Corporation. These locomotives use two 32 V series-wound cranking motors connected in series, which are powered by a 32 cell 64 V lead-acid battery with a typical capacity of 500 A-h.
The acceleration of the engine being started is limited by using a switching power converter to gradually ramp up the voltage across the cranking motor. When implemented as described herein, the use of a switching power converter in this way serves to reduce peak cranking motor current and peak cranking motor torque, enables the engine to be started with reduced battery current and charge, and eliminates failure-to-crank due to gear abutment. The system can be used for single or multiple motor cranking systems; both single and two motor systems are described below.
The switching power converter output is coupled to the cranking motor or motors such that the voltage across the motor(s) varies with the duty cycle at which the switching power converter is operated. The system is then arranged such that the duty cycle of the converter, and thereby the voltage across the cranking motors, is gradually increased over a predetermined period. A circuit diagram of an exemplary embodiment of such a system for a single cranking motor is shown in
Converter 46 preferably consists of a switching transistor 51 (alternatively referred to herein as the ‘soft-start transistor’) connected between the negative terminal of cranking motor 2 and battery negative, a free-wheeling diode 52 connected in parallel with the cranking motor, a high capacitance (typically 0.1 F) DC bus capacitor 53 connected between battery negative and the-positive terminal of cranking motor 2, and a pulse width modulator (PWM) controller unit 54. The preferred switching transistor type is a high current (e.g., 1500+A rated) metal oxide semiconductor field effect transistor (MOSFET) module and the free-wheeling diode is preferably a high current fast recovery epitaxial diode (FRED) module, though these components may be implemented with transistor and diode technologies having reduced on-state voltages and switching losses as they are developed.
When the converter 46 is activated, PWM controller 54 increases the percentage on-time of soft-start transistor 51—and thus the converter's duty cycle—from, for example, 15% to 100% over a period of, for example, 6 seconds. This results in a ramp increase in cranking motor voltage. As is discussed in more detail below, this gradual increase in cranking motor voltage prevents the high cranking motor current and torque conditions that can occur with prior art hard-start systems.
A soft-start system in accordance with the present invention would typically also include a solenoid pull-in control circuit 57 shown in
Closing the start switch 10 applies battery voltage to coil 11 of the pilot relay to initiate the engine start sequence. The pilot relay contacts 12 close to apply battery voltage to the solenoid hold coil connected between the G and S solenoid terminals The hold coil return goes directly to battery negative via the G terminal. The closure of the pilot relay contacts also applies positive battery voltage to the positive end of the solenoid pull-in coil.
The pull-in coil return shown in
b shows the curves of pedestal plus ramp motor voltage 68, smoothly increasing battery and motor current 69 and 70, and torque 71. The end of the cranking process is indicated at time 72 where the voltage, currents and torque go to zero. Note that battery current is less than motor current when the motor voltage is less than the battery voltage. This means that the soft-start requires fewer battery amp-hours for an engine start compared to the hard-start method.
Bus capacitor 53 initially charges with a current limited by the pull-in coil resistance via pre-charge diode 62. If the bus capacitor inrush current is of sufficient amplitude and duration, this current may create enough force on the solenoid plunger to pull in the plunger and thus cause the solenoid contacts 7 to close and the subsequent closure of the power contactor contacts 64. This sequence of events causes full battery voltage to be applied to the bus capacitor. If the solenoid pulls in because of bus capacitor current in the pull-in coil, about 90 ms elapses from the time the pilot relay contacts close until the time that battery voltage is applied to the bus capacitor. During this time, the capacitor will have charged to about 90% of the battery voltage so that the inrush current caused by the closure of the contactor contacts is negligible.
If the bus capacitor charging current is insufficient to cause the solenoid to pull in, the closure of transistor 60 in the solenoid pull-in control circuit 57 ensures pull-in by connecting the battery voltage to the pull-in coil for 150 ms after the initial 150 ms delay. The resulting pull-in coil current will actuate the solenoid and close the solenoid contacts 7 resulting in the application of battery voltage to the power contactor coil 63, the bus capacitor 53 and the positive terminal 55 of the soft-start switch 51. Diode 61 provides a free-wheeling path for the pull-in coil current when transistor switch 60 opens.
In the event of an abutment between the end faces of the pinion gear and ring gear teeth, the solenoid contacts do not close. Following the charging of the bus capacitor through the pull-in coil resistance, the soft-start transistor operates at a low duty cycle of about 10%. The current into the buck converter is limited by the resistance of the pull in coil but the converter increases this current to create sufficient motor torque to break the abutment, thus allowing the solenoid to pull-in, the solenoid contacts to close and the cranking process to proceed. For example, assume the abutment breaks at a motor current of 100 A, the pull-in coil resistance is 0.4 ohm, the battery voltage is 24 V, the duty cycle is 0.1 and the current multiplier is 6. The converter input current is reduced to 100/6=16.7 A. The converter input voltage is 24−16.7*0.4=17.3 V. The motor voltage is 17.3*0.1=1.7 V. This voltage at 100 A will break the abutment by rotating the motor by a few degrees to allow the pinion gear to slip into mesh with the ring gear.
Also in
Expanding on the single motor soft-start circuit of
The PWM soft-start circuit is connected between the negative terminal of motor 19 and battery negative. The curves of cranking motor voltage, current and torque vs. time are the same as for the single motor soft-start shown in
A preferred sequence of events for the two cranking motor soft-start system in
1. Start switch 20 (typically activated by a locomotive control computer) energizes the coil 22 of the pilot relay.
2. Pilot relay contacts 23 and 24 close.
3. The voltage of 32 cell battery 17 is applied to hold coils 27 and 28 of solenoids 29 and 30.
4. Battery voltage is also applied to DC bus capacitor 53 through the pull-in coils of the solenoid and diodes 65 and 66, causing the capacitor to charge toward the battery voltage.
5. Transistor switch 60 in the pull-in control circuit 57 is switched on for 150 ms after a 150 ms delay to create current in the pull-in coils 31 and 32.
6. After the pull-in currents are present, the solenoid plungers begin to pull-in and in turn cause the pinion gears 33 and 34 to move toward engagement with the ring gear 35.
7. Soft-start transistor 51, gated by PWM generator 54, switches at a low duty cycle to produce approximately 2.0 V across and 100 A in the two cranking motors 18 and 19. Free-wheeling diode 52 conducts when the transistor switches off to maintain continuous motor current. The low motor voltage produces a safe no-load motor speed if a stuck solenoid causes one or both of the motors to remain unloaded.
9. With neither of pinion gears abutting the ring gear, the pinion gears slide into mesh with the ring gear.
10. Solenoid contacts 38 and 39 close, energizing contactor coils 40 and 41 which cause contactor contacts 42 and 43 to close.
11. The pull-in coils are effectively bypassed.
12. The bus capacitor voltage quickly rises to the battery voltage.
13. Motor rotation stops because current is initially insufficient to rotate the diesel engine.
14. The duty cycle of soft-start transistor 51 increases to 100% over a period of 6 to 10 seconds—this period being selected to minimize cranking motor inrush current and torque.
15. Current provided to the cranking motors increases up to the breakaway torque and the engine begins to rotate.
16. The motor voltage increases to 100% of the battery voltage, minus the on-state voltage drop of less than 0.5 V in the soft-start transistor.
17. The engine speed increases to the firing speed.
18. Fuel injection begins.
19. The engine fires and speed increases.
20. Start switch 20 is opened (typically by the locomotive control computer) to remove current from the coil 22 of the pilot relay when the engine speed exceeds a threshold speed.
21. Pilot relay contacts 23 and 24 open, causing current in the hold coils 27 and 28 to go to zero.
22. The spring loaded solenoid plunger extends, causing the solenoid contacts to open, the current in contactor coils 40 and 41 to go to zero and the pinion gears to dis-engage from the ring gear.
23. Contactor contacts 42 and 43 open to disconnect the battery from the two cranking motors.
1. If both pinion gears abut the ring gear, the motor current, with the solenoid pull-in coils un-bypassed by the solenoid contacts, produces enough torque to break the abutment.
2. Gears mesh and the solenoid contacts close.
3. The cranking process proceeds to completion
4. If one pinion abuts the ring gear, the associated motor spins unloaded at a safe speed until the locomotive computer aborts the cranking sequence by opening switch 20.
a shows the details of the solenoid pull-in control circuit 57. This circuit is suitable for use with one-motor or two-motor soft-start engine cranking systems.
For application to the one-motor soft-start described in
Current limiting resistor 76 of
The curves of voltage vs. time of
The 12 V supply voltage of
When the solenoid pull-in control circuit of
The two-motor soft-start requires that transistor switch 60 of
a shows the circuit details of one possible implementation of PWM soft-start control circuit 54. The circuit is preferably powered by an isolated dc-dc converter 101 which is sourced from the battery voltage via conductors 47 and 48. The converter preferably operates over an input voltage range of 18 V to 74 V, making it suitable for use with 12 cell or 32 cell batteries. The converter's 15 V output is preferably applied to the input of a 12 V linear voltage regulator 102 of the generic 78L12 type. The 12 V supply serves operational amplifiers 108 and 109, a voltage divider comprised of resistor 103 and potentiometers 104 and 105, and a pulse width modulator integrated circuit 113. The 15 V output of converter 101 is also supplied to the anode of a photo-diode 117 of a MOSFET driver integrated circuit 118 via 1.0 kΩresistor 119.
The voltage divider in
The integrator output E3 responds to the command voltage E2 when circuit power is applied as:
E
3
=E
2*(1+t/T)
The time constant T is the product of the 1.0 μF capacitance 107 and the 100 kΩresistance 106, or 0.10 s. The outputs of the operational amplifiers 108 and 109 are summed by equal value resistors 111 and 112 to form the PWM ramp command voltage E4 as:
E
4=0.5*(E1+E2+t/T)
The PWM IC 113, typically a TL594 or similar voltage-mode controller, responds to the PWM command to produce a MOSFET gate command duty cycle ranging from 0% at E4=0.5 V to 100% at E4=3.5 V. For typical values of E1=2.0 V and E2=0.07 V, 100% duty cycle is reached at a time of:
t=0.1*(3.5/0.5−2.0−0.07)/0.07=7.04s
The inverted PWM signal NOT(PWM) from PWM IC 113 is applied to the cathode of the photo-diode 117 of the MOSFET driver IC 118 through the 1.0 kΩ current limiting resistor 119. The high-current opto-coupled driver IC 118 is typically an Avago ACPL3130 device. The driver's high-side driver transistor 120 turns on when the photo-diode is conductive to produce a 15 V gate command (Vgs) between gate conductor 50 and source conductor 49 of the high current soft-start MOSFET (item 51 of
b shows the NOT(PWM) output of the PWM controller IC 113 and the soft-start MOSFET's gate-to-source voltage Vgs at the beginning and the end of the soft-start cranking motor voltage ramp.
The present soft-start engine cranking system may be arranged to use cranking motors rated to operate at a voltage less than that provided by the battery. For example, cranking motors for locomotives as discussed herein are typically rated to operate on 32V. However, it may be more economical to instead employ cranking motors rated for 24V, which are readily available and tend to be less expensive than 32V motors. The 24 V cranking motors used in large highway trucks and off-road construction vehicles are mechanically the same as the cranking motors used in EMD locomotives built from the 1940's up to the present time; however, because of the relatively low locomotive production level, the cost of a 32 V motor is much greater than that of a 24 V motor. Thus, a soft-start system in accordance with the present invention might employ, for example, a 64V battery and two 24V cranking motors.
However, cranking speed may become excessive when two 24 V motors operate from a 64 V battery. As such, it may be necessary to provide a speed limiting feature to avoid cranking at a speed corresponding to the torsional resonant frequency of the engine-generator combination.
V
OUT
=F
IN
*V
CC
*R1*C1
where C1 and R1 are identified in
FIN=220*40/60=147 Hz For a typical supply voltage of 12 V and with C1 and R1 values of 0.022 μF and 100 kΩ, respectively, the V/F converter output signal voltage is:
V
OUT=147*12*0.10*0.022=3.87V
The converter output voltage includes an AC component at twice the ring gear tooth frequency. This is attenuated by a single pole low pass filter comprised of R1 (278) and C2 (280). At 147 Hz (40 rpm), the attenuation factor is:
2*ω*R1*C1=4*π*147*0.10*0.1=9.10
The filtered crankshaft speed signal is fed to the inverting input of an integrating speed limit amplifier 282 via a resistor 284. The non-inverting input to this amplifier is supplied from a 5V source attenuated with a voltage divider made from a 10 kΩ resistor 286 and a 34.3 kΩ resistor 288, which produces a setpoint voltage of 3.87 V. The feedback circuit of speed limit amplifier 282 is suitably made from a 1.0 μF capacitor 290 in series with a 100 kΩresistor 292 and a diode 294. The cathode of diode 294 is connected to the output 296 of the speed limit amplifier and the anode is connected to feedback resistor 292 and to the junction of resistors 111 and 112 of the PWM ramp circuit shown in
PWM ramp circuit resistors 111 and 112 normally conduct the motor voltage ramp command signal E4 of
The speed vs. time profiles of
a shows possible speed vs. time profiles for a system with two 32 V motors connected in series and soft-started from a fully charged 32 cell 64 V battery, and from a partially charged battery. The sequence of events for the fully charged battery is:
1. Initial open loop voltage ramp produces the speed ramp 310.
2. Speed reaches 40 rpm (312) and is limited at that speed.
3. Fuel is injected, engine fires, speed rapidly increases (314), and the cranking system shuts down.
The sequence for a partially charged battery is:
1. Initial open loop voltage ramp produces a reduced speed ramp 316.
2. Speed reaches 30 rpm (318)
3. Speed droops as cranking time increases (320).
4. The cranking system shuts down (322) before the engine fires.
In
1. Initial open loop voltage ramp produces the speed ramp 330.
2. Speed reaches 50 rpm, fuel is injected, speed increases, cranking system shuts down at 332.
The sequence for a partially charged battery is:
1. Initial open loop voltage ramp produces the reduced speed ramp 334.
2. Speed reaches 40 rpm at 336.
3. Speed, initially 40 rpm, droops slightly until fuel is injected whereupon speed increases and cranking system shuts down at 338.
In comparing the use of a 24 V motor versus a 32 V motor, the speed of the 24 V motor is about 32/24=1.33 times higher for the same battery voltage. The soft-start converter exploits the speed overhead of the 24 V motor in two ways:
1. With a fully charged battery, cranking speed is increased, thus reducing the time to fire the engine.
2. With a partially charged battery, a cranking speed sufficient to fire the engine is reached in cases where the firing speed would not be reached with two 32 V motors directly connected to the battery.
The embodiments of the invention described herein are exemplary and numerous modifications, variations and rearrangements can be readily envisioned to achieve substantially equivalent results, all of which are intended to be embraced within the spirit and scope of the invention as defined in the appended claims.
This application claims the benefit of provisional patent application No. 61/532,242 to Bourbeau, filed Sep. 8, 2011.
Number | Date | Country | |
---|---|---|---|
61532242 | Sep 2011 | US |