The present application relates to the use of phasor measurements in electrical power system state estimation. It finds particular application to the integration of voltage and current phasors in the state estimation process.
Power system state information plays an important role in the operation and analysis of electrical power systems. Indeed, state information can be used for a number of purposes, including system security and contingency analyses, system optimization, and even the creation and operation of markets for electrical energy.
Traditionally, state estimators have performed an indirect estimation of the power system state (i.e., voltage magnitude and angles at the network buses, tap positions of tap changing transformers, etc.) using non-phasor measurements such as power flows and voltage and current magnitudes, to name a few. More recently, however, phasor measurement units (PMUs) have been developed. PMUs provide time-stamped measurements of voltage and current phasors at various locations in the power system. This additional information can be used to improve the network state estimation.
One of the difficulties inherent in providing phase angle measurements in a widely dispersed system, however, is the need to synchronize the measurements to a common reference frame. To this end, PMUs have provided phasor measurements which are synchronized based on time signals from the global positioning system (GPS). Moreover, the Institute of Electrical and Electronics Engineers (IEEE) Synchrophasor standard defines a phasor's instantaneous phase angle in relation to Universal Time Coordinated (UTC), hence fixing the frame of reference for the PMU phasor measurements.
Due to the nature of power system networks, where the power flows on branches on the network are a function of the differences of the voltage phase angles across the branches, a reference or slack bus is chosen in order to render the state estimation problem solvable. Thus, a common reference angle, known as the slack bus angle, has been selected for the state estimation process. While it is generally possible to assign the slack bus angle to an arbitrary value, it is typically set to zero.
As will be appreciated, it is necessary to reconcile the phasor measurement and state estimator reference frames. This can be accomplished by requiring that a reference PMU be placed at the location of the slack bus and computing the angles of the various PMUs with respect to the reference PMU. Unfortunately, however, such an arrangement renders the system vulnerable to the loss of the signal provided by the reference PMU, for example due to an outage at a measurement location, a failure of the reference PMU, or a communication failure. While it is possible to compensate for such a loss, the process for doing so is relatively time-consuming and complex.
Aspects of the present application address these matters, and others.
According to a first aspect, a method includes estimating a state of an electrical power system and generating an output indicative of the estimated state. The estimation is performed in a state-estimator reference frame using phasor measurement data referenced to a phasor measurement reference frame.
According to another aspect, an apparatus includes a state estimator and means for generating an output indicative of the estimated state. The state estimator estimates a state of an electrical power system in a state-estimator reference frame using phasor measurement data referenced to a phasor measurement reference frame.
According to another aspect a computer readable storage medium contains instructions which, when executed by a computer, cause the computer to carry out a method. The method includes obtaining measurement data functionally related to a state of an electrical power system and using the measurement data to estimate the power system state. The measurement data includes phasor measurements referenced to a phasor measurement reference frame and the estimation is performed in a state-estimator reference frame.
According to another aspect, a method of electrical power system state estimation includes obtaining voltage and current phasor measurements functionally related to a state of an electrical power system. The voltage and current phasor measurements are referenced to a phasor measurement reference frame. The method also includes reconciling the phasor measurement reference frame and a state-estimator reference frame and estimating the power system state.
Those skilled in the art will appreciate still other aspects of the present invention upon reading and understanding the attached figures and description.
The present application is illustrated by way of example and not limitation in the figures of the accompanying drawings, in which like references indicate similar elements and in which:
Time signals measured in a power system network, in their ideal form, are sinusoidal and for instance the voltage at a particular node as a function of time ideally would be of the form:
vi(t)=√{square root over (2)}Vi cos(2πfsyst+θi) Equation 1
where i is the node, t is time, vi(t) is the time varying voltage, Vi is the root mean square (RMS) magnitude of the voltage, fsys is the system frequency, and θi is a phase angle. Phasor calculus is used to simplify power system analysis. The RMS magnitude and the phase angle of the voltage signal vi(t) are gathered to form a phasor Vie√{square root over (−1)}θ
For clarity of explanation, the use of phasor measurements in power system state estimation will be described in the context of a fully connected balanced power system that is devoid of equipment such as phase shifting transformers. Such a system with n nodes (also called buses) adheres to the physical laws of Kirchoff and can be described by way of 2n−1 variables that reflect the status of the system. These latter variables are referred to as the states of the power system and they can be denoted as follows:
where
Furthermore, various quantities can be expressed as a function of the system state as follows:
where the elements of
has rank 2n−1.
Elements of
The power-flow equations of the network are a particular minimal representation of
As part of the power system state estimation problem a redundant subset,
The measurements of the elements of
where
The aim of power system state estimation is to find the estimate of
While the above discussion has focused on a framework for estimating the power system state using non-phasor measurements,
In addition, phasor measurement devices such as PMUs 108 calculate phasor measurements at desired locations in the system, with the number and placement of the PMUs generally a function of the network topology, system observability, economics, and other relevant factors. The PMUs 108 provide streams of measurement data which typically include a time stamp, voltage and/or current phasors, and the power system frequency. Where the phasor data is presented in a polar coordinate system, the phasor data includes a phasor angle and magnitude. In the case of a rectangular coordinate system, the phasor data includes the phasor real and imaginary components. As noted above, the phasor data is presented with respect to a phasor measurement reference frame such as a temporal reference frame synchronized with respect to time signals obtained from the GPS system 110. In one implementation, the phasor data is provided according to the IEEE Synchrophasor standard, although other techniques could be used. Some or all of the phasor data may also be obtained from other sources, for example through the known Wide Area Measurement System (WAMS) 112.
As illustrated, the relevant phasor 114 and non-phasor data 116 is stored in a database 118 such as the SCADA system real time database (RTDB) 118 contained in a suitable computer readable memory or memories. A state estimator 120 uses the data 114, 116 to estimate the state of the system, for example using iterative state estimation techniques as are generally known in the art. In one such implementation, the state estimator 120 is implemented by way of computer readable instructions which are stored on a computer readable storage medium accessible to a computer. When executed by the computer, the instructions cause the computer processor(s) to estimate the power system state.
More particularly, and as will be described in greater detail below, the phasor data 116 is advantageously used to augment the traditional, non-phasor measurement based power system state estimation process by appending the phasor data to the non-phasor measurement set to create a combined measurement vector:
where
The state estimator 120 output is stored to a computer readable memory, for example in the database 118 or otherwise. Some or all of the state estimate information may also be presented in a human perceptible form, for example via a suitable human machine interface (HMI) 122.
Turning now to
δi=αi−αUTC. Equation 7
To use the phasor Xi′ in the state estimation process, however, it is desirable that the phase angles αi and αUTC be mapped to the state-estimator reference frame that is fixed when the value of θn is chosen.
The relationship between these reference frames is depicted in
αiθk−θn
αUTCθUTC−θn Equation 8
From which we see that ΦPMUsSE|slack=θUTC−θn.
Thus the phasor voltage angle measurement for each PMU as expressed in the state estimator reference frame can be written as:
δi+(θUTC−θn)=(θk−θn) for some k∈[1,n] Equation 9
Considering the case where the local system frequency fi, evident in the cosine time waveform where a phasor measurement is computed according to the IEEE Synchrophasor standard, is different from f0 then an additional term should be added to Equation 7 on the left hand side in order to account for an additional angle due to this off-nominal frequency operation. In the IEEE Synchrophasor standard this additional angle is given as:
b(fi,f0,t)=2π(fi−f0)t Equation 10
The local frequency fi can be computed (such measurements typically being performed by the various phasor measuring devices or other intelligent electronic devices placed at the same bus), and an angular offset of the form b(fi,f0,t) can be compensated for at the phasor measurement device level, the phasor data concentrator (PDC) level, or otherwise. For clarity of the following discussion, it will be assumed that the compensation is performed at the PMU level such that the angular offset due to off-nominal frequency operation is equal to zero. Hence, for the purposes of the present discussion, and neglecting measurement errors, the phasor voltage angle measurement for each PMU can be written as:
δi=(θk−θn)+θREF for some k∈[1,n] Equation 11
where θREF=(θn−θUTC).
Thus, the reference or translational angle θREF, which reflects the reconciliation of the phasor measurement reference frame with the reference frame of the state estimator should be accounted for when phase angle measurements from phasor measurement devices are integrated into the state estimator.
One approach for mapping or reconciling the phasor measurement and state-estimator reference frames is to generate a set of pseudo-measurements which describe the angular differences between the outputs of the various phasor measurement devices in the measurement reference frame. The set of angular differences can be described by the following vector:
where i,j∈[1,m] and there are no restrictions on m (i.e., multiple phasor measurement devices can be located at the same bus). In the equation above the angular differences for each i,j∈[1,m] is of the form
δi−δj=θk−θm, Equation 13
for k,m∈[1,n], and in the case that i and j are placed at the same electrical bus then k=m and the angular-difference pseudo-measurement is zero and is excluded from
where
By appending this additional pseudo-measurement vector
According to another approach, the measurement and state-estimator reference frames can be directly reconciled. A method to achieve this reconciliation is to view the reference angle θREF as an additional state variable that also needs to be estimated, for example by appending θREF to the state variable vector as follows:
where
The voltage phase angle measurements can be expressed as the following vector:
where
By appending this additional measurement vector
Another approach to the phasor-assisted state estimation problem is to perform the state estimation in the measurement reference frame. Thus, rather than establishing the state-estimator reference frame with respect to a spatial location in the power system network, the measurement reference frame is used as the state-estimator reference frame. For this choice of reference the state vector can be expressed as:
from which we note that the dimension of
It is evident that for this choice of reference that the phase angle measurements from the PMUs or other phasor measurement devices can be directly integrated into the state estimator problem. Investigating Equation 14 it is evident that:
where
By appending this additional measurement vector
The above-described approaches will now be further illustrated with reference to
While the above discussion has focused on the use of voltage phase angle measurements, current angle measurements from phasor measurement devices may also be provided in relation to the phasor measurement set reference frame. A current angle measurement can be expressed as:
ψs=φkm(
where ψs is a current angle measurement from a phasor measurement device such as a PMU, and φkm (which is a function of
The integration of these current angle measurements into the above-described voltage phasor assisted power system state estimation techniques will be discussed next. In each case, the measurement vector includes additional current angle measurements
In the case of the pseudo-measurement technique, the reference angle θREF can be eliminated from the measurement expressions by creating by evaluating the following angular differences to create a further pseudo-measurement set:
and
ψs−δi=φkm(
from which we note that θREF has been eliminated from the expression.
By analogy to Equation 6, the current phasor measurements
which is then used in combination with a system model to find the estimate of
Where the translational angle between the two reference frames are directly reconciled, current angle measurements of the form:
are included in the measurement vector to form a measurement vector analogous to that shown in Equation 22. The measurement vector
Where the state estimation is performed in the measurement reference frame, current measurements are of the form:
are included in the measurement vector to form a measurement vector analogous to that shown in Equation 22. The measurement vector
While the foregoing discussion has focused on a system that is electrically connected, hence having a single electrical island, it is also applicable to systems having two (2) or more electrical islands 3021, 3022 . . . 302c as illustrated in
θREF,i=−ΦPMUsSE|slack,i, Equation 25
for each electrical island i∈[1,c] exists. The state vector for the system with multiple electrical islands is expressed as:
where there are j network buses connected in area/island 1,
Integrating phase angle measurements from phasor measurement units using the method of angular differences as described with Equations 12 and 16 for the case where the system have more than one electrical island can be accomplished using a set of pseudo-measurements whose elements are angular differences of measurements of devices located in the same electrical island. In doing so, θREF,i will be eliminated from the respective expressions. Once the pseudo-measurement set is constructed and appended to the measurement vector, the estimate of
In the case of the direct reconciliation technique, the various reference angles θREF,i are included in the state vector as follows:
The phase angle measurements (i.e., the voltages and/or current phasors) from phasor measurement devices are again appended to the measurement vector, and this information in conjunction with knowledge of the system (i.e., topology and system model) is then used to find the estimate of
In the third method when the reference for the integrated estimation problem is chosen as θUTC, it can be shown that the state vector
Operation will now be described in relation to
A measurement data vector is generated at step 404. As described above, the data includes vector includes both non-phasor and phasor data. The phasor data, which may include voltage and/or current phasors, is referenced to a reference frame other than the state-estimator reference frame, for example a measurement reference frame synchronized to UTC. Where angular difference pseudo-measurements are used, the phasor data includes a set of angular differences between the various phasor measurements. In the case of a direct reconciliation, or where the state estimation is performed in relation to the measurement reference frame, the various phasor measurements may be used directly.
The power system state is calculated at step 406, for example using a conventional iterative state estimation algorithm which operates on the measurement data vector. In the case of the direct reconciliation approach, a reconciliation angle θREF which reconciles the state estimation and measurement is treated as an additional state variable to be estimated.
An output indicative of the power system state is generated at step 408 and optionally presented in human readable form via a suitable HMI.
Of course, modifications and alterations will occur to others upon reading and understanding the preceding description. It is intended that the invention be construed as including all such modifications and alterations insofar as they come within the scope of the appended claims or the equivalents thereof.
Number | Name | Date | Kind |
---|---|---|---|
6694270 | Hart | Feb 2004 | B2 |
6985800 | Rehtanz et al. | Jan 2006 | B2 |
7233843 | Budhraja et al. | Jun 2007 | B2 |
Number | Date | Country | |
---|---|---|---|
20080140326 A1 | Jun 2008 | US |