Aspects of the present invention generally relate to a fail-safe lockout trip mechanism in a circuit interrupting device.
Electrical power is distributed to loads throughout buildings using insulated conductors of different sizes appropriate for the amplitude of current being delivered to the load. The amount of current for continuous safe operation for a particular wire gage size is known as rated current. If the rated current is exceeded, then the conductor will overheat to a point that the insulation melts resulting in hazardous conditions of electrical shock due to exposed voltage potential energy and of flame ignition due to exposed heat energy. Initially fuses were implemented to prevent these hazardous conditions resulting from overloading the electrical circuit. Fuses were eventually replaced by circuit breakers which function as resettable switches. The circuit breaker typical has a robust main contactor that is spring loaded, but held in a closed switch position using a latch. For hazardous overload current situations greater than approximately 800% to 1000% of rated current on the electrical circuit, the hazardous overload current itself is used to generate a magnetic force to unlatch the latch releasing a spring to open the contactor switch removing power from the electrical circuit. For hazardous overload current situations greater than 135% but less than approximately 800% to 1000%, a bimetallic device in series with the electrical current is situated near the latch such that heat generated by the overload current causes the bimetallic device to warp generating a force to unlatch the latch releasing a spring to open the contactor switch removing power from the electrical circuit. Presently, and in the very near future, alternative methods of detecting hazardous overload current are being developed that utilize a solenoid or an electromagnet to generate a magnetic force to unlatch the latch releasing a spring to open the contactor switch removing power from the electrical circuit. In many applications the solenoid or electromagnet is energized by a solid-state switch. Typically, the current utilized to energize the solenoid or electromagnet exceeds the rating of the wire used on the winding of the solenoid or electromagnet and of the rating of the solid-state switch and could potentially damage the solenoid or electromagnet and the solid-state switch if the response of the unlatching mechanism is sluggish and fails to remove power within a few cycles of being energized, or worse, fails to remove power at all. Thus, there is a need for a mechanism to permanently remove power from the electrical circuit should the solenoid or electromagnet or the solid-state switch became damaged and/or inoperable.
However, a fail-safe backup mechanism is not present to permanently remove power from the electrical circuit should the solenoid or electromagnet or the solid-state switch became damaged and/or inoperable.
Therefore, there is a need for providing a fail-safe lockout trip mechanism in a circuit interrupting device.
Briefly described, aspects of the present invention relate to a fail-safe lockout trip mechanism that solves the above set forth problem by utilizing fusible metal such as solder or a low-melting point metal alloy to hold a plunger in place that has a constant force exerted on it by either a compressed or stretched spring. The device is located near a conductor that generates heat and configured such that when the fusible metal melts the plunger is released allowing the spring to convert its potential energy into kinetic energy, moving the plunger to generate a force to unlatch a latch releasing a spring to open main contactor switch removing power from an electrical circuit. Thereafter, the constant force generated by the spring on the plunger inhibits a circuit breaker from resetting which permanently prevents reconnecting power to the electrical circuit. The present invention provides a method and an apparatus to generate a force to unlatch the latch releasing a spring to open the main contactor removing power from the electrical circuit within the calibration trip time limits specified in UL489 should the solenoid or electromagnet or a thermal or solid-state switch became damaged and/or inoperable. In addition, the present invention also permanently prevents the device from being turned back on and re-applying power to the electrical circuit. This invention is simple in construction, easy to manufacture/assemble, and consists of low-cost components which makes the invention ideal for mass production. Ultimately, this invention provides a fail-safe backup mechanism to permanently remove power from the electrical circuit within the calibration trip time limits specified in UL489 should the solenoid or electromagnet or the thermal or solid-state switch became damaged and/or inoperable.
In accordance with one illustrative embodiment of the present invention, a circuit interrupting device is provided. It comprises an energizing conductor, a main contactor that is spring loaded but held in a closed switch position using a latch and a first electromagnetic device configured to instantaneously generate a magnetic force capable of unlatching the latch releasing a spring to open the main contactor removing power from an electrical circuit when an overload current exceeds a predetermined % of a rated load current. It further comprises a section of conductor that generates heat and a temperature sensing switch having contacts. The temperature sensing switch is located in close proximity to the section of conductor which closes the contacts when a temperature reaches a predetermined temperature threshold in response to an overload current less than the predetermined % of a rated load current. It further comprises a second electromagnet in the form of a first solenoid such that when the temperature sensing switch is closed the first solenoid is disposed across the energizing conductor and a connection to a neutral conductor and a temperature activated permanent lockout trip mechanism located in close proximity to the section of conductor that generates heat. The energized first solenoid generates a magnetic force capable of moving an armature that unlatches the latch releasing the spring to open the main contactor removing power from the electrical circuit. The temperature activated permanent lockout trip mechanism upon reaching a predetermined temperature which is higher than the predetermined temperature threshold of the temperature sensing switch also generates a mechanical force capable of moving the armature that unlatches the latch releasing the spring to open the main contactor removing power from the electrical circuit. Once activated, the temperature activated permanent lockout trip mechanism inhibits the latch from latching which prevents a reset of the circuit interrupting device thus the circuit interrupting device is permanently disabled as the main contactor cannot be closed, and power no longer be reconnected to the electrical circuit.
In accordance with one illustrative embodiment of the present invention, a method is provided for fail-safe lockout trip in a circuit interrupting device. The method comprises providing a energizing conductor, providing a main contactor that is spring loaded but held in a closed switch position using a latch and providing a first electromagnetic device configured to instantaneously generate a magnetic force capable of unlatching the latch releasing a spring to open the main contactor removing power from an electrical circuit when an overload current exceeds a predetermined % of a rated load current. The method further comprises providing a section of conductor that generates heat and providing a temperature sensing switch having contacts. The temperature sensing switch is located in close proximity to the section of conductor which closes the contacts when a temperature reaches a predefined temperature threshold in response to an overload current less than the predetermined % of a rated load current. The method further comprises providing a second electromagnet in the form of a first solenoid such that when the temperature sensing switch is closed the first solenoid is disposed across the energizing conductor and a connection to a neutral conductor. The method further comprises providing a temperature activated permanent lockout trip mechanism located in close proximity to the section of conductor that generates heat. The energized first solenoid generates a magnetic force capable of moving an armature that unlatches the latch releasing the spring to open the main contactor removing power from the electrical circuit. The temperature activated permanent lockout trip mechanism upon reaching a predefined temperature which is higher than the predetermined temperature threshold of the temperature sensing switch also generates a mechanical force capable of moving the armature that unlatches the latch releasing the spring to open the main contactor removing power from the electrical circuit. Once activated, the temperature activated permanent lockout trip mechanism inhibits the latch from latching which prevents a reset of the circuit interrupting device thus the circuit interrupting device is permanently disabled as the main contactor cannot be closed, and power no longer be reconnected to the electrical circuit.
In accordance with one another illustrative embodiment of the present invention, a circuit interrupting device is provided. A circuit interrupting device with a temperature activated permanent lockout trip mechanism is provided. The temperature activated permanent lockout trip mechanism is located in close proximity to a section of conductor that generates heat. An energized first solenoid generates a magnetic force capable of moving an armature that unlatches a latch releasing a spring to open a main contactor removing power from an electrical circuit. The temperature activated permanent lockout trip mechanism upon reaching a predetermined temperature which is higher than the predetermined temperature threshold of the temperature sensing switch also generates a mechanical force capable of moving the armature that unlatches the latch releasing the spring to open the main contactor removing power from the electrical circuit. Once activated, the temperature activated permanent lockout trip mechanism inhibits the latch from latching which prevents a reset of the circuit interrupting device thus the circuit interrupting device is permanently disabled as the main contactor cannot be closed, and power no longer be reconnected to the electrical circuit.
To facilitate an understanding of embodiments, principles, and features of the present invention, they are explained hereinafter with reference to implementation in illustrative embodiments. In particular, they are described in the context of a circuit interrupting device with a temperature activated permanent lockout trip mechanism. The temperature activated permanent lockout trip mechanism is located in close proximity to a section of conductor that generates heat. An energized first solenoid generates a magnetic force capable of moving an armature that unlatches a latch releasing a spring to open a main contactor removing power from an electrical circuit. The temperature activated permanent lockout trip mechanism upon reaching a predetermined temperature also generates a mechanical force capable of moving the armature that unlatches the latch releasing the spring to open the main contactor removing power from the electrical circuit. Once activated, the temperature activated permanent lockout trip mechanism inhibits the latch from latching which prevents a reset of the circuit interrupting device thus the circuit interrupting device is permanently disabled, and power can no longer be reconnected to the electrical circuit. Embodiments of the present invention, however, are not limited to use in the described devices or methods.
The components and materials described hereinafter as making up the various embodiments are intended to be illustrative and not restrictive. Many suitable components and materials that would perform the same or a similar function as the materials described herein are intended to be embraced within the scope of embodiments of the present invention.
These and other embodiments of the circuit interrupting device according to the present disclosure are described below with reference to
Consistent with one embodiment of the present invention,
The circuit interrupting device 105 further comprises a temperature sensing switch 127 having contacts 130. The temperature sensing switch 127 is located in close proximity to the section of conductor 125 that generates heat and closes the contacts 130 when a temperature reaches a first predetermined temperature threshold 132 in response to a hazardous overload current less than the predetermined % of a rated load current. The circuit interrupting device 105 further comprises a second electromagnetic device or a second electromagnet 115(2) in the form of a first solenoid such that when the contact 130 of the temperature sensing switch 127 is closed the first solenoid is disposed across the hot conductor 107 and a connection to a neutral conductor 135. The circuit interrupting device 105 further comprises a temperature activated permanent lockout trip mechanism 140 located in close proximity to the section of conductor 125 that generates heat.
The energized first solenoid generates a magnetic force capable of moving an armature 142 that unlatches the latch 112 releasing the spring 117 to open the main contactor 110 removing power from the electrical circuit 120. The temperature activated permanent lockout trip mechanism 140 upon reaching a second predetermined temperature threshold 160 which is higher than the first predetermined temperature threshold 132 of the temperature sensing switch 127 also generates a mechanical force capable of moving the armature 142 that unlatches the latch 112 releasing the spring 117 to open the main contactor 110 removing power from the electrical circuit 120. Once activated, the temperature activated permanent lockout trip mechanism 140 inhibits the latch 112 from latching which prevents a reset of the circuit interrupting device 105 thus the circuit interrupting device 105 is permanently disabled, and power can no longer be reconnected to the electrical circuit 120.
The temperature activated permanent lockout trip mechanism 140 is a fail-safe backup mechanism to permanently remove power from the electrical circuit 120 within calibration trip time limits specified in UL489 should the first solenoid or the second electromagnet 115(2) or a thermal or a solid-state switch or temperature sensing switch 127 becomes damaged and/or inoperable. The temperature activated permanent lockout trip mechanism 140 comprises fusible metal 150 to hold a plunger 152 in place that has a constant force exerted on it by either a compressed or a stretched spring 155. The fusible metal 150 is located near the section of conductor 125 that generates heat and configured such that when the fusible metal 150 melts the plunger 152 is released allowing the spring 155 to convert its potential energy into kinetic energy, moving the plunger 152 to generate a mechanical force to unlatch the latch 112 releasing the spring 117 to open the main contactor 110 removing power from the electrical circuit 120.
In one embodiment, the temperature activated permanent lockout trip mechanism 140 comprises a low-melting point metal or metal alloy. In another embodiment, the temperature activated permanent lockout trip mechanism 140 comprises solder or Indium 100.
The temperature sensing switch 127 is a normally open “make” switch that closes the contacts 130 at the first predetermined temperature threshold 132. The first predefined temperature threshold 132 and the second predetermined temperature threshold 160 are selected to ensure compliance with a safety standard UL489. The first predefined temperature threshold 132 of the temperature sensing switch 127 is selected to ensure compliance of a safety standard UL489, but at a lower temperature than the second predefined temperature threshold 160 of the temperature activated permanent lockout trip mechanism 140.
This enables the circuit interrupting device 105 to then be reset under normal operation after a response to a hazardous overload current condition 162 by latching the latch 112 again and once reset, the circuit interrupting device 105 can be turned back on by moving a handle, applying power to the electrical circuit 120 once again by closing the main contactor 110.
According to one embodiment, the temperature activated permanent lockout trip mechanism 140 consists of the non-metallic plunger 152, the metal spring 155 and a metallic washer 165. In one embodiment, the fusible metal 150 is fused to the metallic washer 165 in two places positioned in grooves of the non-metallic plunger 152 such that when the temperature of the fusible metal 150 reaches its melting point the fusible metal 150 becomes a liquid and is no longer affixed to the metallic washer 165, allowing the non-metallic plunger 152 to move in the direction of the trip armature 142.
The circuit interrupting device 105 further comprises the trip armature 142 that is configured to unlatch the latch 112 when force is applied by the non-metallic plunger 152, releasing the spring 117 to open the main contactor 110 thus removing power from the electrical circuit 120. The circuit interrupting device 105 further comprises a non-metallic enclosure 170 for the circuit interrupting device 105 that holds the temperature activated permanent lockout trip mechanism 140 in place and provides a fixed-point reference for a spring force.
The first predefined temperature threshold 132 of the thermal sensing switch 127 is selected to ensure that the circuit interrupting device 105 complies with safety standard UL489. The second predefined temperature threshold 160 of the temperature activated permanent lockout trip mechanism 140 is also selected to ensure compliance of safety standard UL489, but at a higher temperature than the first predefined temperature threshold 132 of the temperature sensing switch 127. This allows the temperature sensing switch 127 to energize the solenoid generating a force that unlatches the latch 112 releasing the spring 117 to open the main contactor 110 removing power from the electrical circuit 120 prior to activation of the temperature activated permanent lockout trip mechanism 140 during the hazardous overload current condition 162 as the temperature of the heat generating conductor 125 rises. The temperature of the heat generating conductor 125 recedes once power is removed from the load ending the hazardous overload current condition 162 and leaving the temperature activated permanent lockout trip mechanism 140 inactivated. The contacts 130 of the temperature sensing switch 127 re-open as the temperature recedes below the first predetermined temperature threshold 132. The circuit interrupting device 105 can then be reset by latching the latch 112 again. Once reset, the circuit interrupting device 105 can be turned back on, applying power to the electrical circuit 120 once again by closing the main contactor 110. Obviously, it is recommended to investigate and remove the hazardous overload current condition 162 in the electrical circuit 120 prior to resetting a circuit breaker and turning it back on. However, should the temperature sensing switch 127 or the solenoid become damaged or reach its end of life, the solenoid does not become energized or does not generate sufficient force to unlatch the latch 112. Thus, the main contactor 110 remains closed and the hazardous overload current condition 162 persists. As a result, the temperature of the heat generating conductor 125 continues to rise until it reaches a predefined temperature of the temperature activated permanent lockout trip mechanism 140, at which point the temperature activated permanent lockout trip mechanism 140 generates a force moving an armature 142 that unlatches the latch 112 releasing the spring 117 to open the main contactor 110 removing power from the electrical circuit 120. The temperature activated permanent lockout trip mechanism 140 also inhibits the latch 112 from latching again preventing the circuit interrupting device 105 from being reset, permanently disabling the device from ever closing the main contactor 110 and reconnecting power to the electrical circuit 120.
Referring to
A “Reset” state is accomplished by moving the handle 215 from the “Tripped” position shown in
Paragraph 7.1.2. in UL489 describes a calibration test for a circuit interrupting device or a circuit breaker. So for the 200 percent calibration test and the 135 percent calibration test which are performed at 25° C. ambient temperature, a 15 A to 30 A rated circuit breaker must trip within 2 minutes while carrying 200 percent of its rated current, and within 1 hour while carrying 135 percent of its rated current. And for the 100 percent calibration test which is performed at 40° C. ambient temperature, the circuit breaker shall not trip while carrying 100 percent of its rated current until its temperatures have stabilized.
As seen in
As shown in
One embodiment of the temperature activated permanent lockout trip mechanism 605 is described in
The circuit interrupting device 1105 further comprises a second electromagnet in the form of a first solenoid 1122 such that when a temperature sensing switch is closed it is disposed across the hot conductor 1115 and a connection to a neutral conductor 1127. The temperature activated permanent lockout trip mechanism 1130 utilizing the fusible metal ‘Indium 100’ as described above in
The Thermal Reed Switch 1112 (part number TRS3-120MCR00VU manufactured by Kemet Electronics Corporation) which makes closed contact at 120° C. is selected to ensure compliance of safety standard UL489. ‘Indium 100’ which has a melting point of 157° C. is selected to activate the temperature activated permanent lockout trip mechanism 1130 at a higher temperature than the Thermal Reed Switch 1112 and still ensure compliance of safety standard UL489 should the Thermal Reed Switch 1112 or the solenoid 1122 become damaged or reach its end of life such that the solenoid 1122 does not become energized or does not generate sufficient force to unlatch the latch. This allows the Thermal Reed Switch 1112 to energize the solenoid 1122 generating a force that unlatches the latch releasing a spring to open the main contactor 1117 removing power from the electrical circuit prior to activation of the temperature activated permanent lockout trip mechanism 1130 during a hazardous overload current condition when the Thermal Reed Switch 1112 and the solenoid 1122 are not damaged and are functioning properly. The temperature of the heat generating conductor 1120 recedes once power is removed from the load ending the hazardous overload current condition and leaving the temperature activated permanent lockout trip mechanism 1130 inactivated. The circuit interrupting device 1105 can then be reset by latching the latch again and turned back on applying power to the electrical circuit once again by closing the main contactor 1117. Obviously, it is recommended to investigate and remove the hazardous overload current condition in the electrical circuit prior to resetting the circuit interrupting device 1105 and turning it back on. However, should the temperature sensing switch 1125 or the solenoid 1122 become damaged or reach its end of life, the solenoid 1122 does not become energized or does not generate sufficient force to unlatch the latch. Thus, the main contactor 1117 remains closed and the hazardous overload current condition persists. As a result, the temperature of the heat generating conductor 1120 continues to rise until it reaches the predefined temperature of the temperature activated permanent lockout trip mechanism 1130, at which point the solder melts and the temperature activated permanent lockout trip mechanism 1130 generates a force moving an armature that unlatches the latch releasing a spring to open the main contactor 1117 removing power from the electrical circuit. The temperature activated permanent lockout trip mechanism 1130 also inhibits the latch from latching which permanently prevents a reset, disabling the main contactor 1117 from ever closing again and reconnecting power to the electrical circuit.
Suppose the current required to energize the solenoid 1122 exceeds the current rating of the Thermal Reed Switch 1112. Instead of utilizing a custom designed Temperature Sensing Switch or a Thermal Reed Switch that has a current rating to safely and repeatedly supply the current required to energize the solenoid 1122, an off-the-shelf Thermal Reed Switch can be utilized to turn on a solid state switch that has a current rating to safely and repeatedly supply the current required to energize the solenoid 1122 and trip the circuit interrupting device 1105.
The electronic overload current detection circuit 1305 is configured to detect a hazardous overload current typically according to a calculation of the current squared times time exceeds a predefined constant to ensure that the circuit interrupting device 1310 complies with safety standard UL489. A predefined temperature threshold of the temperature activated permanent lockout trip mechanism 1355 is also selected to ensure compliance of safety standard UL489, but at a temperature higher than the typical temperature that the heat generating conductor 1317 reaches upon detection of a hazardous overload current condition by the electronic overload current detection circuit 1305. This allows the electronic overload current detection circuit 1305 to detect a hazardous overload current and assert a trip signal to the gate of SCR 1335 to energize the solenoid 1330 generating a force that unlatches the latch releasing a spring to open the main contactor 1315 removing power from the electrical circuit prior to activation of the temperature activated permanent lockout trip mechanism 1355 during a hazardous overload current condition as the temperature of the heat generating conductor 1317 rises. The temperature of the heat generating conductor 1317 recedes once power is removed from the load ending the hazardous overload current condition and leaving the temperature activated permanent lockout trip mechanism 1355 inactivated. The circuit interrupting device 1310 can then be reset by latching the latch again. Once reset, the circuit interrupting device 1310 can be turned back on, applying power to the electrical circuit once again by closing the main contactor 1315. Obviously, it is recommended to investigate and remove the hazardous overload current condition in the electrical circuit prior to resetting a circuit breaker and turning it back on. However, should the electronic overload current detection circuit 1305, the power supply 1320, the current sensor 1325, the SCR 1335, or the solenoid 1330 become damaged or reach its end of life, the solenoid 1330 does not become energized or does not generate sufficient force to unlatch the latch. Thus, the main contactor 1315 remains closed and the hazardous overload current condition persists. As a result, the temperature of the heat generating conductor 1317 continues to rise until it reaches the predefined temperature of the temperature activated permanent lockout trip mechanism 1355, at which point the temperature activated permanent lockout trip mechanism 1355 generates a force moving an armature that unlatches the latch releasing a spring to open the main contactor 1315 removing power from the electrical circuit. The temperature activated permanent lockout trip mechanism 1355 also inhibits the latch from latching again preventing the circuit interrupting device 1310 from being reset, permanently disabling the circuit interrupting device 1310 from ever closing the main contactor 1315 and reconnecting power to the electrical circuit.
The method 1500 comprises a step 1505 of providing a hot or energizing conductor. The method 1500 further comprises a step 1510 of providing a main contactor that is spring loaded but held in a closed switch position using a latch. The method 1500 further comprises a step 1515 of providing a first electromagnetic device configured to instantaneously generate a magnetic force capable of unlatching the latch releasing a spring to open the main contactor removing power from an electrical circuit when a hazardous overload current exceeds a predetermined % of a rated load current. The method 1500 further comprises a step 1520 of providing a section of conductor that generates heat.
The method 1500 further comprises a step 1525 of providing a temperature sensing switch having contacts. The temperature sensing switch is located in close proximity to the section of conductor which closes the contacts when a temperature reaches a predefined temperature threshold in response to a hazardous overload current exceeding a predetermined % of a rated load current which is less than the predetermined % of rated load current mentioned in step 1515. The method 1500 further comprises a step 1530 of providing a second electromagnet in the form of a first solenoid such that when the temperature sensing switch is closed the first solenoid is disposed across the hot conductor and a connection to a neutral conductor. The method 1500 further comprises a step 1535 of providing a temperature activated permanent lockout trip mechanism located in close proximity to the section of conductor that generates heat.
The energized first solenoid generates a magnetic force capable of moving an armature that unlatches the latch releasing the spring to open the main contactor removing power from the electrical circuit. The temperature activated permanent lockout trip mechanism upon reaching a predefined temperature also generates a mechanical force capable of moving the armature that unlatches the latch releasing the spring to open the main contactor removing power from the electrical circuit. Once activated, the temperature activated permanent lockout trip mechanism inhibits the latch from latching which prevents a reset of the circuit interrupting device 105 thus the circuit interrupting device 105 is permanently disabled, and power can no longer be reconnected to the electrical circuit.
While a fused metal-based temperature activated permanent lockout trip mechanism is described here a range of one or more other types of temperature activated permanent lockout trip mechanisms or other forms of temperature activation are also contemplated by the present invention. For example, other types of temperature activation components may be implemented based on one or more features presented above without deviating from the spirit of the present invention.
The techniques described herein can be particularly useful for an electronic ground fault and/or arc fault circuit interrupter. While particular embodiments are described in terms of specific ground fault and/or arc fault configuration and specific circuit breakers, the techniques described herein are not limited to such a limited configuration and circuit breakers but can also be used with other configurations and circuit breakers.
While embodiments of the present invention have been disclosed in exemplary forms, it will be apparent to those skilled in the art that many modifications, additions, and deletions can be made therein without departing from the spirit and scope of the invention and its equivalents, as set forth in the following claims.
Embodiments and the various features and advantageous details thereof are explained more fully with reference to the non-limiting embodiments that are illustrated in the accompanying drawings and detailed in the following description. Descriptions of well-known starting materials, processing techniques, components and equipment are omitted so as not to unnecessarily obscure embodiments in detail. It should be understood, however, that the detailed description and the specific examples, while indicating preferred embodiments, are given by way of illustration only and not by way of limitation. Various substitutions, modifications, additions and/or rearrangements within the spirit and/or scope of the underlying inventive concept will become apparent to those skilled in the art from this disclosure.
As used herein, the terms “comprises,” “comprising,” “includes,” “including,” “has,” “having” or any other variation thereof, are intended to cover a non-exclusive inclusion. For example, a process, article, or apparatus that comprises a list of elements is not necessarily limited to only those elements but may include other elements not expressly listed or inherent to such process, article, or apparatus.
Additionally, any examples or illustrations given herein are not to be regarded in any way as restrictions on, limits to, or express definitions of, any term or terms with which they are utilized. Instead, these examples or illustrations are to be regarded as being described with respect to one particular embodiment and as illustrative only. Those of ordinary skill in the art will appreciate that any term or terms with which these examples or illustrations are utilized will encompass other embodiments which may or may not be given therewith or elsewhere in the specification and all such embodiments are intended to be included within the scope of that term or terms.
In the foregoing specification, the invention has been described with reference to specific embodiments. However, one of ordinary skill in the art appreciates that various modifications and changes can be made without departing from the scope of the invention. Accordingly, the specification and figures are to be regarded in an illustrative rather than a restrictive sense, and all such modifications are intended to be included within the scope of invention.
Although the invention has been described with respect to specific embodiments thereof, these embodiments are merely illustrative, and not restrictive of the invention. The description herein of illustrated embodiments of the invention is not intended to be exhaustive or to limit the invention to the precise forms disclosed herein (and in particular, the inclusion of any particular embodiment, feature or function is not intended to limit the scope of the invention to such embodiment, feature or function). Rather, the description is intended to describe illustrative embodiments, features and functions in order to provide a person of ordinary skill in the art context to understand the invention without limiting the invention to any particularly described embodiment, feature or function. While specific embodiments of, and examples for, the invention are described herein for illustrative purposes only, various equivalent modifications are possible within the spirit and scope of the invention, as those skilled in the relevant art will recognize and appreciate. As indicated, these modifications may be made to the invention in light of the foregoing description of illustrated embodiments of the invention and are to be included within the spirit and scope of the invention. Thus, while the invention has been described herein with reference to particular embodiments thereof, a latitude of modification, various changes and substitutions are intended in the foregoing disclosures, and it will be appreciated that in some instances some features of embodiments of the invention will be employed without a corresponding use of other features without departing from the scope and spirit of the invention as set forth. Therefore, many modifications may be made to adapt a particular situation or material to the essential scope and spirit of the invention.
Respective appearances of the phrases “in one embodiment,” “in an embodiment,” or “in a specific embodiment” or similar terminology in various places throughout this specification are not necessarily referring to the same embodiment. Furthermore, the particular features, structures, or characteristics of any particular embodiment may be combined in any suitable manner with one or more other embodiments. It is to be understood that other variations and modifications of the embodiments described and illustrated herein are possible in light of the teachings herein and are to be considered as part of the spirit and scope of the invention.
In the description herein, numerous specific details are provided, such as examples of components and/or methods, to provide a thorough understanding of embodiments of the invention. One skilled in the relevant art will recognize, however, that an embodiment may be able to be practiced without one or more of the specific details, or with other apparatus, systems, assemblies, methods, components, materials, parts, and/or the like. In other instances, well-known structures, components, systems, materials, or operations are not specifically shown or described in detail to avoid obscuring aspects of embodiments of the invention. While the invention may be illustrated by using a particular embodiment, this is not and does not limit the invention to any particular embodiment and a person of ordinary skill in the art will recognize that additional embodiments are readily understandable and are a part of this invention.
It will also be appreciated that one or more of the elements depicted in the drawings/figures can also be implemented in a more separated or integrated manner, or even removed or rendered as inoperable in certain cases, as is useful in accordance with a particular application.
Benefits, other advantages, and solutions to problems have been described above with regard to specific embodiments. However, the benefits, advantages, solutions to problems, and any component(s) that may cause any benefit, advantage, or solution to occur or become more pronounced are not to be construed as a critical, required, or essential feature or component.
Number | Name | Date | Kind |
---|---|---|---|
3163732 | Abbott et al. | Dec 1964 | A |
6014297 | Clarey | Jan 2000 | A |
20170256934 | Kennedy et al. | Sep 2017 | A1 |
20200211791 | Manahan et al. | Jul 2020 | A1 |
Number | Date | Country |
---|---|---|
0232172 | Aug 1987 | EP |
Number | Date | Country | |
---|---|---|---|
20220102097 A1 | Mar 2022 | US |