No cross references to related applications.
No federally sponsored development is involved.
No reference to sequence listing or computer program listing or computer disc appendix.
This invention is involved in the moving of supply and exhaust/return air under low pressure, maximum of 10 inches water column, for the purpose of conditioning of space and space pressurization, positive or negative. To date other methods have been attempted that are either very expensive or don't perform or both in the stable controlled decoupling of the fans at a low cost.
The purpose of the invention is to synchronize supply fan 15 and exhaust fan 16 flows so that a set flow differential is maintained between the two fans without one fan or the other affecting the stability of the flow difference desired and set between the fans allowing the fans to be decoupled and prevented from series flow operation.
The fan flow synchronizer invention receives air flow input from the supply duct static pressure receiver 3 into a small tube 5, 2″ IPS maximum, and allows flow through the tube 5 past an adjustable ball valve 4 to the pitot tube 2 mounted in line 5. The pitot sensor 2 produces a differential flow signal which is sent to the differential receiver 6 then to the differential transmitter 7.
A proportional, integral, derivative controller 8 sends a continuous output control signal 9 to the exhaust/recirc fan's 16 variable flow control device 13. This device can be a variable speed motor, inlet vanes, vortex vanes or outlet damper 14. This control is set to produce a CFM that is less than the supply fan 15 CFM and to hold the CFM difference through the full operating range of the system. This operation allows stable building positive pressure and prevents unstable series fan connection. The supply fan 15 is controlled from a static pressure sensor 10 which output transmitter 11 sends signal to the variable flow device 14 similar to those listed for the exhaust/recirc fan 16 above.
The supply fan 15 is set to control the system pressure at a constant point as it responds to the variable flow of the users 17 and maintains a positive building pressure compared to outside atmosphere.
To cause a negative building pressure see drawing 2/6 where the exhaust fan 16 draws air from the building and variable flow user 17 to produce a negative pressure versus atmosphere. Static pressure is sensed at static pressure sensor 3 in the exhaust fan 16 discharge duct. Air flow from sensor 3 through the full port ball valve 4 then through the 2′ IPS pipe 5 then through the pitot flow sensor 2 then into the supply fan 15 suction. A differential flow signal comes from pitot 2 to the differential sensor 6. A differential pressure transmitter 7 receives the signal and sends it to the proportional, integral, derivative controller 8 which outputs a control signal 9 to the variable speed motor 14 to control the supply fan 15 speed to synchronize the supply fan 15 to the exhaust fan 16 at a fixed CFM flow difference.
This prevents the fans 15 and 16 from operating in series which causes unstable system and building pressure conditions.