This disclosure relates generally to a fire safety systems for buildings with overhead fans, and more specifically, to a system that disables a fan in response to a fire.
Ceiling mounted fans are often used for circulating air within large buildings such as warehouses, factories, gymnasiums, retail stores, auditoriums, convention centers, theaters, or other buildings with large open areas. For fire safety, a matrix of overhead sprinklers are usually installed to quench any fires that might occur within the building.
To detect a fire and control the operation of the fans and sprinklers appropriately, various types of fire sensors are available. They usually operate by optical detection (photoelectric), chemical reaction (ionization), or heat detection (fusible link or infrared sensor for radiation).
Some optical photoelectric smoke detectors comprise an infrared light beam passing at a right angle in front of a photodiode or other photoelectric light sensor. In the absence of smoke, the light beam passes undetected in front of the light sensor. Smoke particles, however, can scatter the light beam into the sensor and trigger the smoke detector.
In other types of optical photoelectric smoke detectors, known as projected beam detectors, an emitter projects a light beam across a room where a distant light receiver senses the intensity of the beam. When smoke disperses the beam, the receiver provides an alarm signal in response to sensing reduced light.
Ionization style smoke detectors emit alpha radiation to create a small electrically conductive ionized path between two electrodes. When smoke absorbs the alpha particles, the smoke disturbs the ionized path and interrupts the current between the electrodes, thereby triggering the detector.
Some fire detectors (e.g., heat detectors) are in the form of a fusible link incorporated within a sprinkler head. The fusible link holds a valve of the sprinkler closed until sufficient heat from the fire melts or otherwise destroys the link, thereby activating the sprinkler.
In many cases, the sprinklers are fed by a pressure vessel containing a limited supply of water that is at a pressure higher than that of the municipal water that fills the pressure vessel. This allows an individual sprinkler or a group of sprinklers in a single zone of a multi-zone system to rapidly and intensely focus high-pressure water at a localized area before the fire has time to spread.
If the location of the fire is not accurately determined and, as a result, the wrong sprinklers are activated, this can waste the high-pressure water on an area that does not need it. Depleting the limited supply of high-pressure water in this manner might allow the fire to spread with only lower pressure water, if any, left to suppress it.
Certain examples are shown in the above-identified figures and described in detail below. In describing these examples, like or identical reference numbers are used to identify common or similar elements. The figures are not necessarily to scale and certain features and certain views of the figures may be shown exaggerated in scale or in schematic for clarity.
A need exists for a fire safety system that can quickly sense a fire, accurately identify its location, and control a series of ceiling fans and overhead sprinklers to efficiently extinguish the fire.
Activation of a sprinkler means that a sprinkler valve opens or a “sprinkler turns on” to spray or otherwise discharge a fire-extinguishing fluid (e.g., water, or any other suitable substance). Deactivation of a fan means that a “fan turns off” (i.e., the fan blades decelerate and may stop rotating). Depending on the particular control scheme and type of sensors being used, sprinklers 14 in the vicinity of fire 16 can be selectively activated individually, in zone groups, or all of the sprinklers can be activated together. Likewise, the deactivation of fans 12 may be done selectively or as a group.
Examples of sensors that can sense or react to a characteristic associated with fire 16 include, but are not limited to, optical detectors, ionization detectors, heat detectors and combinations thereof. Information on various types of sensors is provided herein under the section entitled, “Background.”
In the illustrated example of
Still referring to the example of
In the illustrated example of
Should fire 16 occur near a floor 48 of the building or elsewhere, example fire safety system 10 may respond with the following sequence of events. Before sensors 18 or 36 detect fire 16, fans 12 are running normally while sprinklers 14 are inactive. As smoke 24 rises from fire 16, sensor 18a detects the smoke and deactivates fan 12a and fan 12b. With all of the fans 12 or at least the ones nearest fire 16 being inactive, air currents diminish (e.g. decrease). This calm period allows fire safety system 10 to more accurately determine the location of fire 16. With the fans 12a and/or 12b turned off, heat from fire 16 can rise in a more direct upward path. The rising heat thus is more likely to be detected by the sensor 36 that is closest to fire 16. In this example, sensor 36a is first to detect the heat, so sensor 36a transmits a signals that turns on sprinkler 14a while the other sprinklers remain inactive. Sprinkler 14a can then spray the full high-pressure volume of fluid 42 directly onto fire 16 without the other sprinklers wasting fluid 42 on areas that do not need it. In the illustrated example, as fluid 42 flows through a supply line 50, a flow detector 52 provides a signal 54 that triggers a fire alarm (not shown) and/or deactivates compressor 44.
In the illustrated example, although a time period with relatively calm air may elapse between the moment at which sensor 18a first detects smoke and the time at which sprinkler 14a turns on, this period can be minimized by stopping fan 12a as quickly as possible in response to sensor 18a detecting smoke. To do this, fans 12 can each be provided with a mechanical and/or electrical brake 54 (e.g., a frictional and/or dynamic brake). In some example implementations, to prolong the life of brake 54, the brake may only be activated when fan 12 is turned off in response to a fire (e.g., turned off in response to sensor 18); otherwise, fan 12 could be allowed to simply coast to a stop when deactivated under normal operating conditions.
To sense the occurrence of fire 16 more quickly and determine its location more accurately, an example fire safety system 56 of
For even greater response to fire 16, an example fire safety system 62 of
In cases where installing fire detectors near a floor is not feasible, an example fire safety system 74 of
In some example implementations, recognizing two limits of smoke concentration can be accomplished by installing two sets of smoke detectors, wherein one set of smoke detectors is more sensitive than the other. The more sensitive smoke detectors may deactivate fans 12, and the less sensitive smoke detectors may activate sprinklers 70. It is also conceivable and well within the scope of the disclosure to provide a single smoke detector with logic that distinguishes multiple levels of smoke concentration.
In operation, the fire safety systems of
The example process of
The controller then reads the output(s) of the sensor(s) in the area of the suspected fire to determine if a fire exists (block 514). If no fire is detected, control returns to block 510. An alarm may be sounded to request a manual check for fire and/or re setting the system.
If a fire is detected (block 514), the controller determines the approximate location of the fire within the building based on the outputs of the sensor(s) (block 516). The controller 30, 30′, 30″ then actuates one or more sprinkler(s) corresponding to the approximate location (block 518). Control then return to block 510 to monitor for fire starting in any other area(s) of the building.
The instructions represented by
The processor 612 of
The system memory 624 may include any desired type of volatile and/or non-volatile memory such as, for example, static random access memory (SRAM), dynamic random access memory (DRAM), flash memory, read-only memory (ROM), etc. The mass storage memory 625 may include any desired type of mass storage device including hard disk drives, optical drives, tape storage devices, etc.
The I/O controller 622 performs functions that enable the processor 612 to communicate with peripheral input/output (I/O) devices 626 and 628 and a network interface 630 via an I/O bus 632. The I/O devices 626 and 628 may be any desired type of I/O device such as, for example, a keyboard, a video display or monitor, a mouse, etc. The network interface 630 may be, for example, an Ethernet device, an asynchronous transfer mode (ATM) device, an 802.11 device, a DSL modem, a cable modem, a cellular modem, etc. that enables the processor system 610 to communicate with another processor system.
While the memory controller 620 and the I/O controller 622 are depicted in
At least some of the aforementioned examples include one or more features and/or benefits including, but not limited to, the following:
In some examples, a fire sensor is installed near the floor or at least below both a sprinkler and a fan.
In some examples, a fire safety system includes one fire sensor for disabling a fan and a second fire sensor for activating a sprinkler.
In some examples, a fire safety system disables a fan before activating a sprinkler.
In some examples, a fire safety system uses the time between disabling a fan and activating a sprinkler to help identify the location of a fire.
In some examples, a fire safety system includes a fan associated with a smoke detector and a sprinkler associated with a heat detector (e.g., fusible link).
In some examples, an overhead fan includes a brake for quickly stopping the fan in the event of a fire.
In some examples, a fire safety system coordinates the operation of a fan, a sprinkler, and a pressure vessel containing a certain volume of pressurized fire-extinguishing fluid.
In some examples, a fire sensor is positioned within the updraft of an overhead fan.
In some examples, a fire safety system includes a sensor system (one sensor or a plurality of sensors) responsive to two limits of smoke concentration.
Although certain example methods, apparatus and articles of manufacture have been described herein, the scope of coverage of this patent is not limited thereto. On the contrary, this patent covers all methods, apparatus and articles of manufacture fairly falling within the scope of the appended claims either literally or under the doctrine of equivalents.
Number | Name | Date | Kind |
---|---|---|---|
2311374 | Farmer et al. | Feb 1943 | A |
2586797 | Dunlop et al. | Feb 1952 | A |
5562164 | McMurray | Oct 1996 | A |
5607021 | Steele et al. | Mar 1997 | A |
20020155807 | Moor et al. | Oct 2002 | A1 |
20040084544 | Boyd et al. | May 2004 | A1 |
20070036654 | Fedeli et al. | Feb 2007 | A1 |
Number | Date | Country |
---|---|---|
19841934 | Mar 2000 | DE |
08126716 | May 1996 | JP |
Number | Date | Country | |
---|---|---|---|
20090178815 A1 | Jul 2009 | US |