This disclosure relates to firestop collars. More particularly, the disclosure relates to firestop collars which provide a water and gas sealing post-fire exposure.
It is commonplace in building structures for the need to pass cables, conduits and the like through construction barriers such as walls, floors and ceilings. However, the presence of an opening through such barriers raises a potential hazard in that a fire can use those opening to pass through the construction barrier, which of itself is an effective fire barrier, and the fire can then spread to adjoining areas of the building. As such, firestop systems are normally located within the openings that are designed to prevent the passage of fire through those openings.
Additional considerations and requirements occur when the building structure is subject to potential high pressure, for example, in marine applications. It is common to test firestop systems in marine applications for water and gas tightness. This is typically a pressure test where the seal is subjected to a certain head pressure for a period prior to a fire test. The idea was to evaluate water-tightness of the seals where breeches occur in bulkheads and decks that could cause compartment flooding and stability issues onboard large vessels.
In June 2017, SOLAS (Safety of Life At Sea) Regulations were amended to require pressure testing to be conducted after fire exposure. The intent behind the new criteria was to evaluate if after fire exposure, the seals could still maintain the integrity of the water-tight compartment.
After modification of SOLAS regulations, the market responded by using longer sleeves that would push the firestop sealing systems further away from the heat source. However, using longer lengths of sleeves can be challenging because it adds significant weight and, in some cases, there is insufficient space to allow the sleeves to be installed as detailed to achieve performance. Traditional watertight collars do not work for pressure-after-fire because the seals degrade from the intense heat of the fire exposure, therefore, the only way to protect them is to keep them away from the heat source.
In at least one embodiment, the present disclosure provides a firestop assembly configured for sealing about a pipe extending through a passage in a building structure division with a sealing element sealing the passage about the pipe. The firestop assembly includes a tube configured to be positioned about the pipe and secured relative to the building structure division. An intumescent material is positioned within the tube. A heat reduction insulation is supported by the tube such that the heat reduction insulation extends about the sealing element and minimizes heating of the sealing element.
In at least one embodiment, the heat reduction insulation is an endothermic material configured to release chemically bound water.
In at least one embodiment, the heat reduction insulation is in the form of a panel configured to positioned between the tube and the division. Furthermore, the heat reduction insulation may additionally be in the form of a sleeve positioned between the tube.
In at least one embodiment, the heat reduction insulation is in the form of a sleeve positioned between the tube.
The accompanying drawings, which are incorporated herein and constitute part of this specification, illustrate the presently preferred embodiments of the disclosure, and, together with the general description given above and the detailed description given below, serve to explain the features of the invention. In the drawings:
In the drawings, like numerals indicate like elements throughout. Certain terminology is used herein for convenience only and is not to be taken as a limitation on the present disclosure. The following describes preferred embodiments of the present disclosure. However, it should be understood, based on this disclosure, that the invention is not limited by the preferred embodiments described herein.
Referring to
Referring to
The heat reduction insulation panel 102 is manufactured from an insulation material configured to reduce transmission of heat and/or provide a cooling effect. An illustrative material is E-Wrap™ endothermic wrap available from Specified Technologies Inc., Somerville, N.J. The E-Wrap™ endothermic wrap is configured to release chemically bound water to have a cooling effect. While an insulation which releases a cooling agent is described, the invention is not limited to that and other insulation materials may be utilized.
The collar assembly 130 includes a tube 134 enclosing intumescent material 124 and additional heat reduction insulation 128. The tube 134 is manufactured from a fire resistant, generally rigid structure, for example, steel, another metal or the like. In the illustrated embodiment, an optional resilient foam insert 120 is positioned between the intumescent material 124 and the pipe 14 to accommodate variations in outer diameter and to allow the collar assembly 130 to be adjustable or range taking. The additional heat reduction insulation 128 may be manufactured from a material similar to that described above with respect to the panel 102. The intumescent material 124 is designed to expand rapidly responsive to fire and heat for the purpose of sealing off the passage 12. The intumescent material 124 preferably includes a foam component chosen of one of various polymers such as polyurethane or silicone or any other polymer which has the capability of forming a soft resilient foam. The intumescent component of the foam may include expandable graphite, sodium silicate or any other commonly used expansion ingredient which is compatible for use with the basic foam carrier construction.
As illustrated in
When the firestop assembly 100 is exposed to fire and/or excessive heat, the intumescent material 124 expands to collapse the plastic pipe 14 and squeeze it off. The insulation materials 102, 128 keep the bulkhead or deck passage 12 well insulated throughout the fire exposure, but most importantly, keeps the seal element 16 within the bulkhead or deck passage 12 from being distressed due to heat. By insulating the seal element 16 at the division interface, the pipe 14 remains independently sealed even after exposure to fire. It is not necessary to install the sealing systems at the ends of long sleeves which project a significant distance from the bulkhead, as required in current systems. The firestop assembly 100 does not require an extended sleeve which saves on space and no added weight. Additionally, the firestop assembly 100 does not require continuous welds to the division which saves on installation time and labor.
Having generally described the components of the firestop assembly 100, an illustrative method of installation thereof will be described with reference to
Moving to
Referring to
Referring to
In the present embodiment, the collar assembly 230 is provided as a unitary structure with the tube 234 extending 360° about the pipe 14. However, it is understood that the collar assembly 230 may be provided in multiple components similar to the structure described above with respect to the previous embodiment. Additionally, while not shown in the illustrated embodiment, an optional resilient foam insert may be positioned between the intumescent material 224 and the pipe 14 to accommodate variations in outer diameter and to allow the collar assembly 230 to be adjustable or range taking.
A plurality of mounting tabs 235 extend from one end of the tube 234 and are configured to be positioned against the division 10. Welds 237 or the like may be utilized to secure the tabs 235 to the division 10. Radially inward extending tabs 236 extend from the opposite end of the tube 234 to help retain the intumescent material 224 and insulation 228 within the tube 234.
When the firestop assembly 200 is exposed to fire and/or excessive heat, the intumescent material 224 expands to collapse the plastic pipe 14 and squeeze it off. The insulation material 228 keeps the bulkhead or deck passage 12 well insulated throughout the fire exposure, but most importantly, keeps the seal element 16 within the bulkhead or deck passage 12 from being distressed due to heat. By insulating the seal element 16 at the division interface, the pipe 14 remains independently sealed even after exposure to fire. It is not necessary to install the sealing systems at the ends of long sleeves which project a significant distance from the bulkhead, as required in current systems. The firestop assembly 200 does not require an extended sleeve which saves on space and no added weight. Additionally, the firestop assembly 200 does not require continuous welds to the division 10 which saves on installation time and labor.
Having generally described the components of the firestop assembly 200, an illustrative method of installation thereof will be described with reference to
Moving to
The sealing element 16 is enclosed within and protected by the heat reduction insulation 228. As explained above, when the firestop assembly 200 is exposed to fire and/or excessive heat, the intumescent material 224 expands to collapse the plastic pipe 14 and squeeze it off. The insulation material 228 keeps the bulkhead or deck passage 12 well insulated throughout the fire exposure, but most importantly, keeps the seal element 16 within the bulkhead or deck passage 12 from being distressed due to heat.
These and other advantages of the present invention will be apparent to those skilled in the art from the foregoing specification. Accordingly, it will be recognized by those skilled in the art that changes or modifications may be made to the above-described embodiments without departing from the broad inventive concepts of the invention. It should therefore be understood that this invention is not limited to the particular embodiments described herein, but is intended to include all changes and modifications that are within the scope and spirit of the invention as defined in the claims.
This application is the national phase of Appln. No. PCT/US21/43877, filed Jul. 30, 2021, which claims the benefit of U.S. Prov. Appln. No. 63/058,590, filed on Jul. 30, 2020, the contents of each of which are incorporated herein by reference.
Filing Document | Filing Date | Country | Kind |
---|---|---|---|
PCT/US2021/043877 | 7/30/2021 | WO |
Number | Date | Country | |
---|---|---|---|
63058590 | Jul 2020 | US |