This application claims the benefit of my provisional application having Ser. No. 60/994,994, filed Sep. 24, 2007, which discloses substantially the same materials as disclosed in my co-pending Patent Cooperation Treaty application having the same tiled and having serial number PCT/US2008/010850, filed Sep. 18, 2008.
(a) Field of the Invention
This application relates to a multiple system and methods for controlling the flow and residence time of gases and emissions through an exhaust flue. More particularly, but not by way of limitation, to an adjustable co-axial flue flow adjustment system.
(b) Discussion of Known Art
It is well recognized that adjusting the residence time of the exhaust gases moving along the flue can optimize the efficiency of devices such as furnaces. Optimized combustion results in reduced harmful emissions, such as carbon monoxide, shorter on cycles, longer off cycles and reduction in the amount of fuel and electricity consumed. However, the problem of how to achieve this optimization has proven difficult to solve due to the unpredictable nature of fluid flows and to limitations imposed by regulatory authorities.
As to regulatory limitations, flue ducting may not be restrictive in any location. This means that the cross-sectional area of the flue may not be reduced anywhere along the flue. Thus, the problem of how to increase residence time of the exhaust gases while reducing emissions traveling along the flue, without introducing restrictions to the flow.
Some known examples include U.S. Pat. No. 4,836,184 to Senne and U.S. Pat. No. 4,499,891 to Seppamaki provide baffles that extend into the flow, and thus disturb the laminar flow in order to create turbulence and increase the residence time of the flow within the flue. The tuning of these known devices is carried out by simply increasing or decreasing the extension of the baffle in order to increase or decrease the projected area of the baffle as seen by the flow.
Other known devices include U.S. Pat. No. 5,666,942 to Kazen and U.S. Pat. No. 5,411,013 to Kazen. The approaches in these devices was to increase residence time by placing a spiral ribbon in a section of flue duct, and thus force the flow to follow the ribbon in order to increase the residence time of the exhaust gases in the flue. Kazen's devices, along with other known prior art, because they were installed directly within the exhaust system and not within an expansion system, are restrictive by design and prohibited under regulatory guidelines.
Problems associated with known devices include that due to the fact they work well in only certain boiler systems, and not in forced air systems, and visa-versa. For instance the device to Senne was relatively simple to install in industrial boilers, but difficult to install in home applications, where forced air systems are more predominant. Senne's applications for boiler systems could be pre-calculated or pre-set for providing optimal performance to a specific boiler system, but had to be tuned in the field for forced air systems. This in turn required that highly trained technicians be used for home applications. Still further, home applications are typically found in tight spaces, which can rule out the use of the Senne device.
Still further, as shown in
Accordingly, the specific requirements for the configuration for application to both home and industry are:
1. Comply with the accepted standard that all exhaust ductwork not be restrictive in any location. This translates to the statement that the minimum flow area in the device be greater than the inlet duct area, Amin/Ainlet≧1.0;
2. Do not reduce the draft by 50%, stay in the range of 20 to 30%.
3. Maintain furnace temperatures Tfurnace≦250° F.
4. For home use provide a fixed position of the deflector plate inside the disclosed invention in order to use as is, and also to provide a safety measure which prevents untrained installers from altering the device. For industrial use, provide capability for adjustable vernier settings.
5. Reduce the footprint in recognition of the tight spacing of the home exhaust duct network.
6. Installation of the disclosed invention shall be no closer than 1 foot from the exit of the gas fired appliance.
7. Construction is made of stainless steel in order to combat corrosion.
8. Absolutely no leakage.
9. Absolutely nothing can come loose and fall down the flue.
10. Maintain open area without screens/porous baffles, which can clog with soot.
11. Use standard size ducts and connections for ease of installation.
12. Design and manufacture the product so that no retrofitting to the gas fired appliance is required at the time of installation
13. Provide capability for both draft hood systems and induction fan systems.
The last requirement implies a wide range of capability of the configuration. This will necessarily force two examples that include the inventive aspects disclosed here, since the two systems operate quite differently. The two applications will be addressed in the system performance section.
It has been discovered that the problems left unanswered by known art can be solved by providing a flue tuning and emissions saving system that includes:
An inlet duct having an inlet cross-sectional area;
An outlet duct having an outlet cross-sectional area that is the same as the inlet cross-sectional area;
An outer duct that is of an outer duct cross-sectional area, the outer duct cross-sectional area being greater than the inlet cross-sectional area and the outlet cross-sectional area, the outer duct being sealingly connected to the inlet duct and the outlet duct, while separating the inlet duct and the outlet duct; and at least one disc that is positioned at a specified distance S between the inlet duct and at the same S to the outlet duct and centered in the outer duct, the disk having a specified disc area so that flow of an exhaust gas entering the system through the inlet duct will be diverted by the disc into the outer duct before the flow continues to the outlet duct without encountering a restriction in flow cross-sectional area. When two or more discs are used, an annular fin 22 that extends from the outer duct to the inlet duct diameter separates the discs.
It should also be understood that while the above and other advantages and results of the present invention will become apparent to those skilled in the art from the following detailed description and accompanying drawings, showing the contemplated novel construction, combinations and elements as herein described, and more particularly defined by the appended claims, it should be clearly understood that changes in the precise embodiments of the herein disclosed invention are meant to be included within the scope of the claims, except insofar as they may be precluded by the prior art.
The accompanying drawings illustrate preferred embodiments of the present invention according to the best mode presently devised for making and using the instant invention, and in which:
While the invention will be described and disclosed here in connection with certain preferred embodiments, the description is not intended to limit the invention to the specific embodiments shown and described here, but rather the invention is intended to cover all alternative embodiments and modifications that fall within the spirit and scope of the invention as defined by the claims included herein as well as any equivalents of the disclosed and claimed invention.
Turning now to
The parameters that can be varied in order to optimize the performance are shown in
The minimum flow area in the device relative to the duct flow area is the lesser of the cylindrical area at the top of the disc (2.1), or the area between the disc and the duct outlet/inlet which is calculated as the curved surface area of the frustum of a right cone (2.2).
For the case Ddisc=D, Acone is the circumferential area πDS.
The variation shown below of Amin/Ainlet with Douter and D illustrate the benefits of an axially symmetric design. Diameters in inches, and Ddisc=D.
The specific dimensions and parameters of the design are dictated by their performance such that the design choices must be based upon either analysis or experiment. Analytical methods are only starting to be used for this type of problem, but code costs, set up time, checkout time, run costs, and validation efforts rule out an analytical approach; therefore, design guidance is obtained experimentally.
The exhaust ductwork is a classic problem of fluid flow in pipes. The fundamental equations between two points in the pipes are; from [1], the continuity equation in terms of the volume flowrate Q is shown in (3.1)
Q=A1V1=A2V2 (3.1)
The energy equation expressed for isothermal flow of a perfect gas becomes the Bernoulli equation [5, p90]. When an accounting of non isentropic loss effects are included through the loss coefficient K, the balance of total pressures is:
We assume here incompressible flow such that the density does not change significantly from the reservoir to any point,
ρ0≈ρ1≈ρ2=ρ.
The term K is a measure of the pressure drop from non isentropic changes from friction, expansion, turning, and turbulence, and is normalized by the dynamic pressure at the inlet
The loss term K is additive [2] and is determined by the length between points 1 and 2 as well as the number and kinds of bends, valves, fittings, or diameter changes. For typical hardware, the most detailed definition of the contribution of these factors is in the Crane handbook [3]. For the disclosed invention design the K values must be obtained analytically or experimentally. Reforming (3.2) for the local K of the disclosed invention, we find:
The pressures and dynamic pressures can be measured in the duct on both sides of the disclosed invention through static pressure taps on the duct walls, and pitot probes located at the centerline of the duct.
A bench test setup was constructed to measure the static and pitot pressures using a manometer board. A four inch duct was supplied by a two horsepower fan which has two speed settings. Various test sections and deflector plate shapes were installed and tested.
The pitot tube measures total pressure relative to ambient pressure , and the static pressure is also relative to ambient:
The dynamic pressure upstream to the test section is
and KSaverII is then defined by the measurements as:
The Senne design was tested extensively in order to improve its performance. Thirty variations in the plate size and shape were tested. After 9 checkout runs, 78 initial tests were conducted on a commercial T test section which had two intersecting cylinders without the 45 degree transition. The Senne design itself was used for 18 subsequent tests. The next 171 tests of the disclosed invention design were then conducted to provide design guidance, for definition of its performance, and for comparison with the Senne design. The disclosed invention was investigated in 24 tests, giving a total of 300 tests for the disclosed invention development.
The performance of each configuration tested is measured by K and also by the minimum flow area to duct area Amin/Ainlet. For the Senne design the areas are calculated by the two planes discussed above: a partial circular area up to the top of the plate, and one half of an elliptical area from the plate top to the 45 degree transition. For the disclosed invention, equations (2.1) and (2.2) are used.
The most striking fact revealed by the data is that the disclosed invention design has excellent performance for K, while the ratio Amin/Ainlet is controlled by design to be greater than one. The Senne design was restrictive and limited in design options to meet all of the design requirements, while the Saver II offers a great deal of design latitude and a wide range of application.
4.1. Dual Designs. For optimum performance improvement, applications to a draft hood system require K values around 3.0, while systems with an induction fan require K values approximately 16 times larger for the same performance improvement. The test data does not show K values this large so the induction fan systems will have reduced performance improvement compared to the draft hood system. The test data derived optimum designs for the Saver II-A, the Saver II-F, and the Saver III are listed below.
4.2. Saver II-A. The draft hood version illustrated in
Provision is made to adjust the plate angle for vernier control if necessary, and a locking mechanism is in place to secure the settings. If necessary, additional control can be achieved with longer S values and smaller disc diameters. The range of these parameters is contained within the bench test data scatter in
4.3. Saver II-F. The induction fan version, illustrated in
The goal is also to be away from the restrictive limit with a flow area greater than the inlet, or Amin/Ainlet>1.0. The test data of
Amin/Ainlet=1.125, Ddisc=1.0625D
Douter=1.5D θadapter=30°
s=0.28125D Louter=1.5D
4.4 Saver III. It is also important to note that for even higher performance, we will utilize the principle of the disclosed invention design and go to a design shown in
Amin/Ainlet=1.10, Ddisc=D
Douter=1.5D θadapter=30°
s=0.25D Louter=1.5D
IDfin=D ODfin=1.5D
4.5. Flue Tuning. For all Savers, provision is made to adjust the plate angle for vernier control if necessary, and a locking mechanism is in place to secure the settings. These features are shown in
For all designs, the inlet female fitting and outlet male fitting are sized to attach to standard duct sizes with a minimum of 0.125 inches gap. In addition, in order for the device to fit properly during installation, the male fitting is crimped (following standard practice for ductwork). The 30 degree transition 24 is based upon a standard ductwork adapter going from D to 1.5D. All seams are welded so that no gas can escape under pressure. The material is 304L stainless steel in order to combat corrosion, and the thickness is 20 Gauge. Savers for ducts greater than 8 inches will be thicker, 18 to 16 Gauge.
The discs are welded to the front of the rods and are centered along the axis. The standoff distance S refers to the distance from the disc face to the inlet/outlet ducts. This makes the rods slightly off center. The shaft collars have a set screw to hold the rod at the desired angle setting. The bottom shaft collar has a closed end to prevent slippage of the rod during the initial setting at installation. After installation, the set screws are securely tightened and the top shaft collar is covered with a push nut.
The performance of the disclosed invention installed in a facility is dependent upon its integrated performance. Each facility will have its own characteristics and fuel savings will vary. Two examples are demonstrated in this section; a typical home furnace of 100000 Btu per hour output, and a typical home water heater of 35500 Btu per hour.
For every cubic feet of natural gas, 1040 Btu of heat is released; thus, 1.603 cfm of natural gas is used in the furnace and 0.569 cfm in the water heater. Burners operating at the stoichiometric air to fuel ratio produce 9.8648 ft3 of combustion products for each ft3 of fuel. This translates to 17.41 cfm in the furnace flue and 6.18 cfm in the water heater flue. Operation off the stoichiometric value will produce greater amounts.
The furnace has injector nozzles to supply the stoichiometric vales (s.v.) of air and also an opening at the burner box which supplies excess air. The total for this example is 160% for the furnace. The water heater draws in about 150% at the burner but this amount is roughly doubled at the top of the heater by the draft hood,
The furnace induction fan is assumed to operate wide open at 200% of the stoichiometric value and has a maximum total pressure of 0.1175 inches of water. The system characteristic is
and intersects the fan characteristic at 26.9 cfm. The addition of the disclosed invention-F gives a system characteristic of
The ductwork K coefficient for the furnace system is outlined in Crane [3] with the value Kflue=0.655. As mentioned above, the Saver K coefficient is reduced by the different pipe IDs, fan to duct, [3]:
Thus, for a 2 inch fan outlet and a 4 inch duct, and using the experimentally derived coefficient KSaverII-F=7.6166 we have Kfan=7.62/16=0.476. The resulting system performance is shown in
The effect of adding the disclosed invention to a typical home furnace system is a reduction of the gas flow and emissions up and out of the flue. This example shows that the flowrate is reduced to 23.6 cfm, or 83.7% of the pre-installation value of 26.9 cfm. The 23.6 cfm represents 139.1% of the s.v. and is much more efficient. The fuel savings realized is addressed below in Energy Savings.
The water heater burner is assumed to operate at 150% of the stoichiometric value. After combustion, the gases rise up in an internal flue or standpipe typically about 5 feet in length and 4 inches in diameter. Most models have flue baffles, much like a twisted ribbon, which distribute the heat to the walls to further supply heat to the surrounding water tank. The increased surface area is included in the K factor. At the top of the standpipe a flue restrictor redirects the flow axially into a 6-inch draft hood and then into a smaller 3-inch vent pipe. The static pressure at the standpipe exit is slightly below ambient therefore the draft hood draws in an amount of air that roughly doubles the flowrate to around 288%.
The ductwork K coefficient for the water heater system is computed from [3] with the value Kw.h.flue=3.88. From the bench tests, the disclosed invention-A coefficient is KSaverII-A=2.4351. The water heater system characteristic is
and intersects 16.67 cfm at a head loss of 0.0294 inches of water. Adding of the disclosed invention-A gives a system characteristic of
Without a fan, the system energy remains the same and the flow rate is reduced to 13.07 cfm as shown in
Addition of the disclosed invention reduces the burn time of the appliance (through increased heat transfer in the heat exchanger due to increased velocities and increased driving temperatures), reduces the oxygen content in the exhaust with more efficient combustion, and consequently reduces the stack losses. The savings is in the cost of the fuel as well as the cost of fan electricity, but most significantly in the reduction of CO2, CO, SO2, and NOx out the stack. The measure of all savings is through the energy saved by reducing losses out the flue. The energy of the flue system is obtained by the power of the throughput. Power is proportional to the cube of the speed, which relates to the duct flow rate through (3.1). Consequently the energy saved from addition of the disclosed invention device is:
6.1. Induction Fan Boilers. For these applications, the disclosed invention “Server II-P is used and the example shown in
Significant savings of induction fan systems are more difficult to obtain and require application of a different design than draft hood systems
6.2. Atmospheric Boilers. The draft hood system of the water heater is in a general class of atmospheric boilers of any size. The example of
Note that the flow rate is reduced by 21.6% and if the system needs to be at 20% the angle adjustment can be used to lower the K value.
6.3. General Relationship. For induction fan systems, the fan characteristics dictate the change in power and are more difficult to model. For draft hood systems, we have a given flow rate Q1 in the flue and the pressure drop is
With increased resistance to the system the system pressure drop is the same for draft appliances, and the velocity and flow rate must decrease to VS and to QS:
The draft flow rate reduction of the disclosed invention is thus relative to the K of the flue.
The energy savings of the disclosed invention-A then becomes:
6.4. Reduction of Excess Air. The savings can also be related to the changes of the excess air through the changes in the stoichiometric value. This is especially useful to avoid over correcting the system and reducing safety margins (like requirement #2).
Combining (6.1) with the system characteristic we can construct a savings map and show the effect of the various design choices in
The specific points illustrated in
The design for disclosed invention shown on
Installation. The disclosed invention devices are designed for two separate applications and should never be used for both. Installation of either device after the vent pipes are joined at a Y-junction should never be done. The disclosed invention-A is for draft hood appliances only, and the disclosed invention-F for induction fan appliances only.
Adjustments. The disclosed invention will come from the factory with the normal of the deflector disc aligned along the centerline. Adjustments to the K factor are accomplished by changing the angle setting on the disclosed invention,
The angle nomenclature used here is that 90 degrees represents the disc normal to the flow. The angle sensitivity shown in
Locking. After adjustment by an HVAC installer, the device should be locked from any further adjustments. This is to prevent untrained workers from attempts to increase performance to the point that a hazardous situation may result.
Maintenance. Annually the device should be inspected to assure that it is not clogged with soot or condensate build-up, and that the setting is appropriate. In addition, several system checks should be made to assure that the burners are cleaned and adjusted, that there is no CO build-up, that the ductwork is tight and without rust holes or corrosion, that there are no obstructions to the airflow inlet screens or panels, that the draft hood is clear of debris, that the draft hood is drafting properly, and that fresh intake air meets code.
The disclosed invention provides important benefits that could not be achieved with known devices. For the draft hood system, the disclosed invention as shown in
Thus it can be appreciated that the above-described embodiments are illustrative of just a few of the numerous variations of arrangements of the disclosed elements used to carry out the disclosed invention. Moreover, while the invention has been particularly shown, described and illustrated in detail with reference to preferred embodiments and modifications thereof, it should be understood that the foregoing and other modifications are exemplary only, and that equivalent changes in form and detail may be made without departing from the true spirit and scope of the invention as claimed, except as precluded by the prior art.
Number | Name | Date | Kind |
---|---|---|---|
164712 | Bowman | Jun 1875 | A |
172914 | Culveyhouse | Feb 1876 | A |
403672 | Humphrey | May 1881 | A |
346794 | Whitmarsh | Aug 1886 | A |
368485 | Oblinger | Aug 1887 | A |
393313 | Romang | Nov 1888 | A |
589610 | McPhaill | Sep 1897 | A |
713055 | Burton | Nov 1902 | A |
1319621 | Roughen | Oct 1919 | A |
1417987 | Griffith | May 1922 | A |
1438611 | Ryerson | Dec 1922 | A |
1794724 | Meyer | Mar 1931 | A |
1837581 | Peterson | Dec 1931 | A |
1840621 | Howie | Jan 1932 | A |
1891600 | Lancaster | Dec 1932 | A |
1966360 | Schaffer | Jul 1934 | A |
1971336 | Butler | Aug 1934 | A |
2180212 | Morrow | Nov 1939 | A |
2222663 | Handley | Nov 1940 | A |
2244936 | Bird | Jun 1941 | A |
2359465 | Coburn et al. | Oct 1944 | A |
2611361 | Lockhart | Sep 1952 | A |
2734501 | Fauser, Jr. | Feb 1956 | A |
2735385 | Ascentiis | Feb 1956 | A |
2882023 | Rizzo | Apr 1959 | A |
3736961 | Walsh | Jun 1973 | A |
4009705 | Smith | Mar 1977 | A |
4079727 | Smith | Mar 1978 | A |
4136676 | McCown et al. | Jan 1979 | A |
4187833 | Zahora et al. | Feb 1980 | A |
4215814 | Ebert | Aug 1980 | A |
4249883 | Woolfolk | Feb 1981 | A |
4291671 | Senne | Sep 1981 | A |
4318367 | Antonucci | Mar 1982 | A |
4320869 | Elbert | Mar 1982 | A |
4334897 | Brady et al. | Jun 1982 | A |
4337892 | Diermayer et al. | Jul 1982 | A |
4372289 | Funke | Feb 1983 | A |
4373510 | Smith | Feb 1983 | A |
4497310 | Funke | Feb 1985 | A |
4499891 | Seppamaki | Feb 1985 | A |
4524754 | Schubert | Jun 1985 | A |
4603681 | Clawson | Aug 1986 | A |
4681085 | Clawson | Jul 1987 | A |
RE32671 | Seppamaki | May 1988 | E |
4751910 | Allen et al. | Jun 1988 | A |
4803931 | Carson | Feb 1989 | A |
4836184 | Senne | Jun 1989 | A |
4850336 | Hagan | Jul 1989 | A |
RE33077 | Van Dewoestine | Oct 1989 | E |
4953535 | Hagan | Sep 1990 | A |
5005428 | Tanis | Apr 1991 | A |
5411013 | Kazen | May 1995 | A |
5666942 | Kazen | Sep 1997 | A |
5772774 | Chabot | Jun 1998 | A |
5857324 | Scappatura et al. | Jan 1999 | A |
6159429 | Bemel | Dec 2000 | A |
6422179 | Hughes et al. | Jul 2002 | B2 |
6564902 | Saberi | May 2003 | B1 |
6890149 | Metz et al. | May 2005 | B2 |
6955756 | Fallon | Oct 2005 | B2 |
6974303 | Wang | Dec 2005 | B2 |
7104359 | Zelinski | Sep 2006 | B1 |
7451854 | Suzuki et al. | Nov 2008 | B2 |
7610993 | Sullivan | Nov 2009 | B2 |
20070095605 | You | May 2007 | A1 |
Number | Date | Country | |
---|---|---|---|
20090101131 A1 | Apr 2009 | US |