The field of this invention lies in fixed and semi-fixed systems for the assistance of fire extinguishment and/or for addressing hazards and/or vapor suppression in industrial storage tanks, being particularly suited for large (at least greater than 60 foot diameter) industrial tanks storing flammable liquids and hydrocarbon products and the like. Such tanks may be more particularly differentiated by whether or not they have a fixed roof. The field of the invention lies in fire fighting nozzles for large industrial tanks, and more particularly in focused stream aerated foam projecting nozzles capable of projecting fire fighting foam in a substantially focused stream. The field of the invention lies in fixed and semi-fixed nozzle systems and methods for extinguishing fire in large industrial tanks, and more particularly, in fixed wand systems plus fixed center pointing nozzle(s) or a portable point and shoot monitor and nozzle system and method.
Industry Background
Williams Fire and Hazard Control, Inc. (Williams) has been a leader in the design, development, and production of specialty firefighting equipment and methodology for use on large industrial tank fires. A study published in a report by SP Fire Technology in 2004, written by Henry Persson and Anders Lonnermark, stated:
Historically, Williams has specialized in mobile equipment and methodology. “Fixed system” approaches to large tank fires, historically, have demonstrated limited success in the industry as well as high cost.
On the one hand, for “rim seal fires” (fire around the rim of a tank floating roof, around the roof seal) traditional fixed system approaches place a large number of “foam chambers” or “foam pourers” around the perimeter of the storage tank, every 40 feet or every 80 feet depending upon whether the “foam dam” on the floating roof is 12 or 24′ high. These devices drop or “pour” highly aerated fire fighting foam down the tank wall into the tank “periphery,” or area between the tank wall and the “foam dam” on the floating roof, by force of gravity. The cost for such system is high.
On the other hand, for “full surface liquid tank fires” in 100 foot plus diameter tanks, proven fixed systems have not existed. That is, to the inventor's best knowledge, no fixed system has put out a fully engaged full surface liquid tank fire in a 100 foot plus diameter tank.
Before the “Daspit Tool,” Williams successfully used fully portable devices and methods to extinguish “rim seal fires,” using a two part attack. In the first phase of the Williams attack a fire fighter approached the tank and hung a portable device (foam wand with a non-reactive nozzle design) over the top edge of the tank proximate a platform or landing. The wand largely dispensed foam directly under the device, suppressing the fire in the immediate vicinity, over a 30 to 40 foot length. After a “beachhead” was established, a “beachhead” of 30 to 40 feet of tank rim with no flames under a landing, fire fighters mounted the tank wall using the ladder leading to the landing, and carried up handheld nozzles and hoses. (The gpm's of handheld nozzles are roughly limited to 60 gpm for a one person nozzle and a 125 gpm for a two person nozzle.) These nozzles were the primary fire extinguishing tools for the seal fire. Having gained access to the top of the tank wall through use of a foam wand, the fire fighters extinguished the “seal fire” by walking the “wind girder” around the tank wall, using the portable nozzles in a known manner.
Subsequently, Williams developed a Daspit tool, a portable base for affixing a portable nozzle and monitor to the top of a tank rim or wall. With the Daspit tool, nozzles up to 2000 gpm could be attached to the top of a tank wall. Specifically again, on “a rim seal fire,” with this improved technique, a portable foam wand device was again used to dispense foam downward to establish a “beachhead” area. A fire fighter then carried a Daspit Tool™, (being a clamping device used to secure a temporary fire fighting monitor and nozzle to the top edge of a storage tank, or any other approved mounting location) and hose while climbing the ladder and attached the Tool to the tank rim above the beachhead. The monitor and nozzle were then pressurized with water/foam solution and directed by the fire fighter stationed at the landing to dispense foam inside the tank and shoot out fire located around the tank's perimeter. The entire attack could be set up and executed in a matter of minutes, after, of course, the responding fire fighters had arrived at the scene.
In September of 2004 Williams was called to Cushing, Oklahoma to assist in the extinguishment of a “full surface” 117 foot diameter crude tank fire. The Williams team arrived with portable foam wands and with “Daspit Tools,” monitors and nozzles. (Again, “Daspit Tools” permit staging a monitor and nozzle on a tank wall rim. The “Daspit Tool” provides a base for a monitor and nozzle.) Williams first used portable foam wands to extinguish the fire around an area under a platform and ladder along the wall of the tank. Having gained “control” of that limited area, Williams personnel mounted the ladder of the burning tank to the platform, secured a Daspit Tool there and directed its monitor and nozzle to extinguish the full surface crude tank fire. Thus, Williams provided evidence that a portable foam wand and sufficiently large portable monitor and nozzle (rendered useable by virtue of the Daspit Tool base) could be effectively used to extinguish a “full surface tank fire”, at least of crude in at least a 117 foot diameter tank.
Williams had long appreciated that a “fixed” system, performing appropriate tasks, would be faster and offer much lower risk of harm and danger to personnel. (Danger to personnel includes the clutter on a ladder provided by the hoses necessary to supply a portable monitor and a wand. Furthermore, if such hose were to break while it runs up the ladder, the personnel involved with the ladder and platform would be put in significant danger.)
A problem to solve, and a goal for Williams in industrial tank fire fighting, became to develop a cost-effective, reliable, fixed system for quickly and efficiently blanketing appropriate areas of a tank fire with foam, including not only the “periphery,” (which is the location of the “rim seal fire,”) but also a tank “full surface fire.” Such system, moreover, should perform satisfactorily for tanks of 200 and 300 and 400 feet diameter, and even greater, and include tanks with and/or without a fixed roof, and should not be prohibitively expensive.
The resulting Williams commercial embodiments, discussed below, were developed, tested and designed to solve these problems and meet these goals. The commercial embodiments were designed to protect: (1) floating roof only tanks against “rim seal fire” and vapor hazard; (2) floating roof only tanks against “rim seal fire” and full surface fire; and (3) fixed roof tanks against any surface hazard. The inventive systems are cost-effective and practical, for tank diameters from 100 feet to above 400 feet.
The instant inventors have demonstrated, in the development process, that the industry erred in certain prior assumptions regarding the proper expansion of foam needed for fixed systems, and regarding the capacity to throw or project and run an adequately expanded foam.
The instant inventors have demonstrated, with side by side testing, that “projecting” and “directionally discharging” an “aerated foam” (an expansion of between 2-to-1 and 8-to-1) from an aerated foam nozzle can produce a focused stream of at least 1100 gpm of aerated foam, with a significantly enhanced tight landing footprint, and with a surprising foam run, and including a surprising foam run speed and fire fighting effectiveness. The inventors have shown, with testing, that their aerated foam nozzles can reach a more extensive tank fire surface in a shorter period of time than can prior art “foam chambers.” The novel system can extinguish larger tanks with fewer units and is applicable not only to rim seal fires but also to full surface liquid tank fires, including of those of large tanks. The instant inventions, supported by test results, promise cost effective fixed systems to extinguish fires in tanks of diameters greater than 200 feet, greater than 300 feet, and greater than 400 feet. The instant fixed systems are designed to be attached along the tank outer wall, and to discharge into the tank from a point near a top tank wall portion, thereby enhancing the reliability as well as the cost effectiveness of the fixed system, in the event of a hazard.
The instant invention proceeded in several stages. A first determination was made, based on experience and testing, to actively pursue outer tank wall mounted units discharging proximate the tank wall upper rim. (The inventors have experimented with “bubble-up” or so-called Type I systems but have not yet been able to successfully test a satisfactory, practical and cost effective bubble-up system. Pipe-inside-the-tank systems, based on extensive experience, were deemed impractical given the prevalence of floating roofs and the complications inherent therein. In regard to roof mounted systems, either fixed roof or floating roof or systems that “extend-over” the top of the liquid, experience again indicated far too high a likelihood that such a fixed system would be placed out of service by the very incident that causes the fire or hazard.)
A second determination, based on testing, was to preferably discharge aerated foam from an aeration chamber proximate to and upstream of the nozzle, the aerated foam preferably having at least a 2-to-1 to 8-to-1 expansion ratio. A 3-to-1 to 5-to-1 ratio was preferred. A tubular jet ambient air aeration chamber provided a reliable structure for the aeration, able to perform while enduring heat and stress. It was determined by testing that this aerated foam could be significantly projected, could produce a significant foam run, and could run quickly without losing fire fighting effectiveness.
Thirdly, the inventors created a nozzle that could significantly, directionally, “project” and/or “forcefully project” a proper aerated foam in a “substantially focused stream,” to land in a focused pattern, with an enhanced tight landing footprint, and again with significant foam run and effective fire extinguishment characteristics. A key to this stage was a stream shaper.
One general belief in the industry had been that “forcefully projecting” aerated foam destroyed the bubbles and resulted in poor foam quality and poor foam run. Prior art fixed systems with aerated foam chambers did not “forcefully project” aerated foam. Rather, for rim seal fires and/or small tanks, they poured or dropped by gravity highly aspirated foam down the inside walls of the tank. This resulted in a low gpm of discharge and a poor foam run.
The instant inventors demonstrated that, with the instant nozzles, the expectation of poor bubble quality and poor foam run for “projected” or “forcefully projected” aerated foam was misplaced. Use of a stream shaper may be instrumental in helping to secure the good results and enhanced landing footprint.
Testing has shown that a stream shaper can significantly enhance the integrity and focus of thrown footprints of aerated foam. Aerated foam discharged through a proper stream shaper has non-destructively landed at least dozens of feet away, in tightly focused footprints, and run surprisingly further and quicker than industry predictions, while maintaining the fire fighting effectiveness of the bubbles. A 2-to-1 to 8-to-1 expanded foam, preferably a 3-to-1 to 5-to-1 expanded foam, can be non-destructively landed in tight target areas to a greater extent and further away than industry expectations. The stream shaper is one key why the instant system can land foam at least 20 feet away in a tank “periphery” and run the foam greater than 100 feet further in the periphery. In preferred embodiments a footprint-enhancing stream shaper for an aerated foam nozzle has four or greater fins, each fin having a longitudinal dimension greater than a radial dimension. Preferably each fin has a longitudinal dimension greater than twice its radial dimension. Preferably also the stream shaper fins are installed in a tip of a nozzle such that the downstream end of the fins is approximately flush with the nozzle tip discharge orifice.
The following use of terms is helpful in discussing the structure and performance of the instant inventions as they developed.
The term “riser” is used to refer to any pipe or line or system of such, affixed to or near or adjacent to an outer tank wall, installed to provide water, water and foam concentrate and/or fire fighting fluid to a top portion of a large industrial storage tank. Although risers are shown herein as vertical pipes, they could be any shape, and in particular, they could be a combination of vertical and/or circular portions. E.g. one or more fluid distribution rings could be installed around a tank, connecting with vertical riser portions. A riser can come in sections, as illustrated herein.
A “tip” of a nozzle is a nozzle barrel portion terminating in a discharge orifice, frequently including a swedge-down portion to enhance discharge pressure.
A “fin” (also referred to in the art as a vane) directs fluid flow in a conduit.
A “stream shaper” provides fins or vanes extending in a nozzle or conduit. A fin radial dimension is the dimension measured radially from a center axis of a barrel or conduit out toward the barrel or conduit wall. A fin longitudinal dimension is the dimension of the fin measured longitudinally in a nozzle or conduit, along a nozzle or conduit longitudinal axis or in the upstream/downstream direction of flow.
A “deflector,” as used herein, provides an obstruction in a fluid conduit, directing a portion of fluid flowing therein toward a discharge orifice or port.
A tank “periphery” is an annular area on a top of a floating tank roof, between the tank wall and the floating roof “foam dam.” Foam dams are usually 24 inches high or 12 inches high. A “rim seal fire” is a fire in the “periphery.” (A full surface fire can ensue when a floating roof fails, e.g. sinks or tilts.)
An “aerated foam nozzle” or an “aerated foam projecting nozzle” will be used to indicate a nozzle that discharges foam created from a foaming concentrate that has passed through an ambient air aeration chamber located at, proximate to, and/or just prior to, a nozzle.
Two nozzles discharging “in roughly opposing directions” will be used to mean discharging in roughly opposite directions, within at least +/−15° of a median “directly opposite” directional axis. By one measure, thus, the included angle between two discharge axes of two nozzles discharging in roughly opposing directions, taken in the direction of discharge, will be between 180° and 150°.
A “substantially focused” stream indicates a discharge of foam where at least 60% of the foam remains within a 20 degree cone around a discharge axis during flight.
A “projecting” nozzle means a nozzle that, if set at 00 inclination to the horizon and at a supply pressure of 100 psi, and if a landing footprint is measured on a horizontal plane five feet below the discharge orifice, and when throwing aerated foam with an expansion of between 3/1 and 5/1, then the nozzle can land at least 50% of the aerated foam greater than 5 feet from the discharge orifice and can land some foam greater than 20 feet. “Projecting” thus means landing at least 50% of foam, aerated with an expansion of between 3-to-1 to 5-to-1, greater than 5 feet from the nozzle discharge orifice and landing significant foam greater than 20 feet, if discharged horizontally and measured on a plane five feet below the discharge orifice.
A “forcefully projecting” nozzle means a nozzle that, if set at 00 inclination to the horizon and at a supply pressure of 100 psi, and if a landing footprint is measured on a horizontal plane five feet below the discharge orifice, and when throwing aerated foam with an expansion of between 3/1 and 5/1, then the nozzle can land at least 50% of the aerated foam greater than 50 feet from the discharge orifice and can land some foam greater than 80 feet. “Forcefully projecting” thus means landing at least 50% of foam, aerated with an expansion of between 3-to-1 to 5-to-1, greater than 50 feet from the discharge orifice and landing some foam greater than 80 feet, if discharged horizontally and with a landing footprint measured on a horizontal plane 5 feet below the discharge orifice.
The concepts of “substantially focused” stream and “projecting” and “forcefully projecting” together with “aerated foam nozzle” help distinguish the instant inventive nozzle and wand systems from aspirated foam discharge devices of the prior art. Prior art discharges from traditional “foam chambers” or “foam pourers” are not “substantially focused” or “projecting.” On the other hand, the term “aerated foam nozzle” distinguishes the instant nozzles from master stream nozzles of the prior art, for instance, nozzles that throw a water/foam concentrate liquid mixture where essentially all aeration takes place significantly after leaving the nozzle structure rather than in an associated upstream or in-nozzle aeration chamber.
Given the surprisingly good foam run results with the instant nozzle design and aerated foam, the inventors tested “opposing nozzle” fixed units, referred to by the inventors as “wand heads” and “wands.” “Two nozzle” and “three nozzle” fixed units, or “wand heads” or “wands,” were tested, discharging roughly horizontally and primarily left and/or right, and optionally, “toward the center.” For insertion through existing openings in a wall of a “fixed roof” tank, a conduit with a single center pointing nozzle plus dual non-obtrusive side ports with interior deflectors was tested, the unit suitable for inserting into existing fixed roof tank wall flanged openings.
The “wand heads” are adapted to be supplied by “risers,” mounted on, proximate to or about outside tank wall portions, the “wand heads” to be secured so as to discharge just inside a top tank wall portion, for enhanced reliability. The “wand heads” preferably include a proximally located ambient air aeration chamber providing properly aerated foam for the nozzle(s). The aeration chambers are served by water/foam concentrate line(s) or pipe(s), again typically referred to as “risers.” A fixed wand head with two opposing nozzles preferably directs discharges roughly left and right, projecting aerated foam substantially horizontally and in roughly opposing directions. A fixed separate riser and fitting can be provided, especially proximate a tank ladder and landing platform, to supply and support an additional fixed nozzle or portable monitor and nozzle, which can project foam toward the center of the tank or otherwise around the tank. Preferably a “three nozzle” fixed unit for open floating roof tanks can be installed to discharge left, right and roughly toward the center. For fixed roof tanks, a single center pointing nozzle with two conduit-located deflection ports can be installed, the ports functioning as side nozzles. The unit can be inserted through flanged openings typically provided in existing fixed roof tanks. The single conduit nozzle plus two “deflector ports” can discharge left, right and toward the center of a tank with a fixed roof.
(The inventors further teach, for alcohol or the like liquids, possibly not discharging both left and right but alternately discharging all left or all right, to establish a swirl pattern run, and to further bank the discharge against the wall to minimize plunge.)
(Preferably in most embodiments a fourth smaller orifice will discharge a relatively small amount of aerated foam, say less than 150 gpm, directly down the tank wall to land and cover tank surface directly under the unit. Frequently this small fourth discharge port may not be mentioned herein, and in many cases it appears unnecessary. However, it will likely be included in commercial units out of caution.)
The instant system thus offers a cost effective solution to a costly and dangerous problem. Providing first responding fire fighters with a proper means for successful extinguishment of at least tank rim seal fires, and preferably also means for full surface vapor suppression and means for extinguishing full surface liquid tank fires, by strategically and permanently fixing a relatively few inexpensive components onto a tank, as well as providing supporting tools (monitors, nozzles, hose, and pumps) should be paramount in considering how to best protect a hazard. Doing so ensures a good relationship with the first responders as well as provides a better solution to large tank hazards.
To recap and reflect on the development history, a Williams two stage “fully portable” attack for “rim seal fires,” and even for “full surface liquid tank fires,” has been successful. However, as required by the two stage “fully portable” attack, requiring humans to carry hoses up a tank ladder to the tank landing, and to charge the hoses around their feet in order to activate a primary system, presented a personnel risk that was not attractive. Unmanned or largely unmanned fixed systems presented a far more attractive personnel environment. However, any fixed or semi-fixed system must also approach the degree of reliability and flexibility and cost effectiveness as that provided by the two stage “portable” system.
A surprising discovery, that heightened the reliability, cost effectiveness and flexibility of the instant fixed systems, came with the testing of a landing footprint-enhanced, “aerated” foam nozzle “projecting” aerated foam. The aerated foam nozzle, with tight landing footprint-enhancement, tested to show that it could “throw” aerated foam significantly left and/or right while still landing a predominant portion of that foam in the narrow tank “periphery.” Further, the nozzle could throw or project aerated foam successfully for a significant distance, e.g. at least 20 feet, while landing the foam predominately in the periphery. And the momentum of the “throwing” or the projecting enabled the system to “run” foam, tests showed, a surprising distance, 120 feet both left and right of the nozzle, and to do so very quickly. As a result, a footprint-enhanced aerated foam nozzle could form a suitable cost effective primary fixed means for at least extinguishing rim seal fires. To compare with the Williams prior “portable system,” the prior portable foam wand was only used to establish a “beachhead” directly below the wand, which allowed humans to mount the tank wall at the wand position by the ladder and to put into place the primary fire extinguishing system, fed by hoses running up the ladder. To the contrary, with the instant novel fixed systems, a portable monitor and nozzle, if used, becomes secondary. A “fixed left and/or right wand” becomes the key element of the primary fire extinguishing system for the “rim seal fire.” A further fixed center pointing nozzle covers a full surface fire.
The problem of an effective practical reliable design for a fixed fire extinguishing system for tank fires, especially in tanks of diameter of greater than 100 feet and 200 feet, has existed for a long time. Search into existing solutions uncovered the following.
Foam Chambers—For example, Blomquist U.S. Pat. No. 3,876,010
For floating roof seal fires, “foam chambers” or “foam pourers,” discussed above, dropping highly aspirated foam between a tank wall and a floater roof “foam dam” have been a traditional fixed fire fighting system solution. These systems are inadequate to attack a “full surface” fire in a >200 foot diameter tank and likely inadequate for > a 100 foot diameter tank. Their foam run is typically less than 50 feet, so that a large number of such chambers are required. Given the degree of expansion imparted to the foam, the foam run is slow and short and the gpm is limited. Applicant experimented with the common foam chambers to confirm that the run of their highly aspirated foam was only about 40-50 feet in each direction around the tank perimeter or periphery (e.g. in the area between tank wall and the “foam dam” on the floating roof.) And this 40-50 foot run was also relatively slow.
A “Saval” apparatus was noticed on the Internet and a similar Knowsley apparatus discovered. This apparatus type proposes two 45° down pointing nozzles, “discharging” left and right, stationed along the wall rim, (as well as a small directly downward discharge). The two 45° nozzles do not discharge “significantly horizontally” and no nozzle is proposed to discharge “toward the center” of the tank. Further Saval's nozzles appear to “bank” their discharges against the tank wall. The effect of banking could be to soften the impact of landing on the liquid and/or to direct more of the foam into the periphery and/or to heighten the aeration. However, one of skill in the art knows that the “banking” technique lessens the lateral force behind the foam, wastes projection energy and reduces foam run capability. Neither Saval nor Knowsley claim a novel or exceptional “foam run” capability. This implies that Saval's and Knowsley's foam run is in the same order as that of the traditional “foam chambers” and/or “foam pourers.”
Uribe US Patent Publication No. US 2004/0140106
Uribe teaches a tank wall mounted fixed system nozzle with an aeration chamber. The degree of aeration is not mentioned. No stream shaper is disclosed. Uribe does not discharge right or left, but only toward the center, as with the Nihilator below. Uribe asserts that eventually his discharged foam will cover a whole tank surface. Since one of ordinary skill in the art knows that foam has a limited lifetime and a limited run, Uribe's statement implies that Uribe's tank is inherently of less diameter than 100 feet.
Reference to a Nihilator device was located, although the Nihilator appears to be no longer offered as a commercial product. One of ordinary skill might surmise that the Nihilator was not effective. The Nihilator is a center pointing nozzle apparently designed for a fixed roof tank and has an aeration chamber. The Nihilator discharges foam toward the center of the tank and suggests that it be used with traditional foam chambers.
The instant invention and its related embodiments have several major commercial embodiments.
For ease of reference, the current major commercial embodiments are given graphic names.
“Point and Shoot” (semi-fixed) System—Useful for:
“Ambush” (fixed) System—Useful For:
“Hollow Point” (fixed) System—Useful for:
Again, success of the above embodiments may be based in part upon the development of a stream shaper affixed in the tip of the nozzles, which facilitates providing a projecting and forcefully projecting foam nozzle, as well as developing a properly aerated foam for the context.
The invention, as introduced and discussed above, relates to various aspects and embodiments for fixed and semi-fixed systems and methods for extinguishing liquid tank fires in large industrial storage tanks. The invention covers tanks with and without fixed roofs and systems that are fixed or semi-fixed, and systems developed primarily for rim seal fires and for full surface liquid tank fires.
The Point and Shoot fixed wand and riser system is a semi-fixed system that can be used immediately for “rim seal fire” protection as well as for vapor suppression. The Point and Shoot fixed wand and riser system is predicated upon the successful rim-seal extinguishments made by Williams using fully portable equipment, as well as the subsequent Daspit Tool development. Given the further development of a proper aeration chamber and a stream shaped nozzle combination, aerated foam nozzle units, or “wands,” fixed to the wall of the tank become a cost-effective primary “rim seal fire” extinguishing means. A further fixed riser, for supplying fire fighting fluid to a portable monitor and nozzle, can provide redundancy in case of damage to the primary system as well as extra full surface vapor suppression capability. (And of course, further independent fixed risers with fixed center pointing nozzles offer a fully fixed full surface fire protection capability.)
Thus, the semi-fixed Point and Shoot wand and riser system and method provides safer and quicker extinguishment for rim seal fires, as well as a back-up for component disablement or vapor suppression.
This minimal fixed wand and riser system requires only strategically permanently affixing a few inexpensive components directly onto a tank. As a consequence of a proper combination of a footprint-enhanced nozzle with a properly aerated foam, the left and right nozzles of a wand can be fixed 220 to 240 feet apart, (as opposed to 40 to 80 feet apart with prior art foam chamber systems.) Thus, the footprint enhanced aerated foam nozzle wand system can be staged as a primary fire extinguishing system for the “rim seal fire” while one or more risers, installed proximate a tank landing and ladder for the quick attachment of portable monitor/nozzles, can be regarded as redundant backup rim seal fire protection, in case of damage to the primary system, and as a capability to provide full surface vapor suppression if a floating roof partially or totally sinks. This semi-fixed system permits attacking a seal fire quickly with much less risk to personnel.
The semi-fixed elementary system, called the Point and Shoot System, has a recommended layout as follows:
The Point and Shoot semi-fixed system is particularly applicable for large tanks with no fixed roof for “rim seal fires” and full surface vapor suppression. A major advantage is low cost. The Point and Shoot system is characterized by a pair of aerated foam projecting nozzles attached together in a fixed “wand,” structured to discharge in roughly opposing directions and roughly horizontally. The aerated foam tank wand has been demonstrated to be able to land and run foam approximately 120 feet in each direction in the tank “periphery,” that is the space between the “foam dam” and the tank wall of a floating roof. See below test results. Preferably in addition to the fixed foam wands risers attached to or about the tank wall, at least one additional at least four inch riser is attached to the tank wall to be associated with the tank landing ladder system. The additional riser is structured to communicate fire fighting fluid from approximately the ground to approximately the top of the tank and is structured with a fitting at its end, proximate the top of the tank, the fitting suitable for attaching a portable (at least 150 gpm at 100 psi) monitor and nozzle.
One new primary danger arises from the fact that industrial storage tanks for storing flammable liquids and hydrocarbon products are being constructed of ever greater diameters. Today 405′ diameter tanks, and greater, are being constructed. Large scale portable fire fighting nozzles, such as 10,000 gpm, 12,000 gpm or 14,000 gpm nozzles, capable of throwing fire extinguishing and hazard suppressing liquids (water and foam concentrate) over the top of the tank wall typically recite maximum ranges in the 400-500 foot range. Fire fighting foams from the large scale portable nozzles can be relied on to run, at best, approximately 100′. (Conservatively, the foam might only be reliably counted upon to run about 80 feet.) Thus, portable fire fighting nozzles effectively addressing a full surface, fully engaged flammable liquid tank fire in a 405′ diameter tank by throwing foam over the wall from an upwind location probably have to be staged within 100′ of a tank wall. Considerations of logistics as well as the existence of moats, buildings and other equipment and piping around the tanks, and especially considerations of heat and personnel safety, render extremely problematical any tactic requiring approaching a fully engaged full surface liquid tank fire in a 405′ diameter tank closer than 100′.
Further pressure for improvement comes from the fact that the value, to the tank owner, of a gallon of the product in the tank is also increasing dramatically. Owners of large tanks and of large tank products want the product and the tank to be protected from fire.
The above considerations incentivized the inventors to develop a fully fixed system, including one or more fixed center pointing nozzles plus an aerated foam wand, preferably a left and right discharging wand but possibly an all left or all right discharging wand. The system is known as the Ambush and provides a first defense for addressing fire and vapor hazards, including full surface liquid tank fires, in all tanks without a fixed roof, but especially in large diameter tanks.
The Ambush could be implemented in one fashion as a “fixed” Point and Shoot System. The Point and Shoot riser provided with a fitting for attaching a portable monitor and nozzle, located near the tank ladder and landing, could be provided instead with a permanently fixed center pointing nozzle, such as a master stream self-educting nozzle. The riser and nozzle could look and function much like the Hollow Point riser and nozzle, without however the lateral space constraints, the side ports and without the necessity of an aeration chamber. The adjustment of the nozzle could be fixed or set with respect to the tank size and other fixed wands such that the nozzle covers a relevant center portion of the tank surface with foam. No separate ambient air aeration chamber would be required, as known in the master stream fire fighting nozzle field. A separate fixed riser and nozzle need not be limited to being located near a tank ladder and landing. Only so many fixed center directed riser and nozzles need be included as will adequately cover the center portion of the tank surface with foam, in context.
An Ambush System provides a tailored design of three nozzle units, or wands, preferably with all nozzles using one or two proximate ambient air aeration chambers and all working off of one or two associated risers. These three nozzle units are designed to be installed as units around a tank.
The three nozzle, fixed, aerated foam wand system includes a set of fixed aerated foam nozzles. This set of nozzles, each referred to as a fixed “wand,” has left and/or right and over the top (toward the center) capability, all with enhanced landing footprints. Preferably the units of three nozzle wands are spaced around, and proximate to, the inner tank wall, each unit preferably providing two nozzles that discharge predominantly left and right, along inner tank wall portions, and a third nozzle that discharges toward the center. Preferably the “toward the center” nozzle discharges at least beyond an approximate 80′ annular ring of foam, anticipated to be created upon an open tank surface by the left and right discharging nozzles. (In some cases the three nozzle wand unit also provides a fourth small port or nozzle to discharge directly beneath the wand and on the inside of the tank wall.) Any disablement of a fixed wand due to a particular fire or hazard or incident can be supplemented by large portable nozzles staged on the ground, throwing foam over the tank wall, as is known in the art.
The perimeter of a 405′ tank runs approximately 1,250 feet. Testing shows that the instant novel fixed foam wands (Ambush System) should be able to direct foam to run at least 80′ to 90′ in each direction, preferably 120 feet, and to also run the foam 80′ or so inward toward the center of the tank. (Again, in addition, a small amount of foam may be discharged directly below the fixed foam wands.) These nozzles could cover the inner tank wall with a roughly 80′ wide annular foam ring, relatively quickly. A third nozzle attached to each fixed wand, preferably with its own aeration chamber, projects foam toward the center of the tank and at least toward the inside of the 80′ annular foam ring being established. Preferably, for a large tank, the third nozzle lands a footprint of foam with a footprint midpoint approximately 90 to 120 feet radially inward of the tank wall. The length of the landing footprint should preferably extend at least 20 to 30 feet forward and backward from the landing midpoint, along the discharge projection line. The landing footprint should preferably spread at least 15 to 20 feet laterally from the discharge projection line. Such a discharge of foam has been shown to be capable of running foam toward and through the center of a 405′ diameter tank. Taking the center projected foam together with the peripherally discharged foam, a total gpm of foam should be selected such that the surface of the tank would be covered with an adequately deep and lasting foam blanket. That is, the gpm of the wands and nozzles should take into account the desired and/or required application rate density for the tank surface.
This fixed three nozzle open system and methodology has an advantage of concentrating a foam blanket on portions of the tank liquid surface adjacent to the tank walls. The portions adjacent to the tank walls are important because the tank wall itself can retain significant heat. The tank wall typically needs the most cooling. For a 405 foot diameter tank, for instance, seven or eight large three nozzle fixed foam wands might be utilized, each large three nozzle foam wand discharging approximately 2,000 gpm of water/foam concentrate total from its nozzle cluster. In a preferred embodiment a nozzle discharging to the left and to the right might discharge approximately 700 gpm each. A nozzle directed toward the center might project approximately 500-900 gpm toward the center. A small port discharging immediately under the fixed wand might discharge approximately 100 gpm downward.
Again, to the extent that one or more fixed foam three nozzle wands are disabled by the fire or an explosion, large portable fire fighting nozzles can be staged on the ground and used to supplement the non-disabled portions of the fixed system.
In the three nozzle fixed aerated foam wand system the discharge orifices for the nozzles preferably contain fins, or stream shapers, to minimize the turbulence in the discharge of aerated foam out of the nozzles. Minimizing turbulence enhances the range and the run of the foam, and tightens the landing footprint.
One preferred three nozzle fixed aerated foam wand embodiment includes two aeration chambers. The aeration chamber(s) typically consist of tubular jets inserted inside of piping proximate a series of air intake ports, and the chamber is situated proximately upstream of the nozzle discharges. The jets, in a known manner, create a low pressure zone, sucking air in through the ports and mixing the water/foam concentrate with air to create an aerated foam for discharge. Bends incorporated in the conduit between an aeration chamber and a discharging nozzle may enhance the aeration of the foam. No bend may be included between an aeration chamber and a center projecting nozzle, however, to minimally aerate that foam in order to enhance foam throw and run. Discharge from that nozzle has a longer flight time in which to further aerate. Two aeration chambers enable tailoring the aeration more closely to the nozzle purpose.
Although the three nozzle system was initially designed to address the problem of a very large, fully engaged, full surface liquid tank fire (no fixed roof), such as a fire in an industrial tank having a diameter of 405 feet, the fixed three nozzles aerated foam wand system was quickly seen to have application to tanks of all diameter sizes, and in the situation of either a fully engaged fire or a rim seal fire or simply a need for vapor suppression. The large fixed wand is useful even if a floater remains in place and there is only a seal fire or a need for vapor suppression over the floater. A valve can be provided to eliminate foam discharged toward the center in the case of a rim seal fire.
A fixed roof fixed nozzle wand system has been designed as a direct response to the issues faced by foam chambers when installed on a closed roof tank for the purpose of full surface protection. One wand of the instant fixed roof fixed nozzle system projects foam directly toward the center of the tank as well as left and right to protect near the inner tank walls. The wand unit preferably incorporates a Teflon vapor seal to prevent tank vapors from escaping the tank via the aeration holes in the wand system's supply piping.
In contrast with foam chambers that simply pour foam onto the surface from the circumference of a tank, such that the foam must run across the liquid surface using only gravity as its means of propulsion via the static head from the piled up foam near the tank wall, the instant fixed roof aerated foam wand discharge head projects foam out into the tank with significant velocity, to push the foam toward the center of the tank. From the same wand foam from interior left/right discharge ports is projected to protect the area near the tank walls.
As foam accumulates in the center, it will begin to flow outwards back toward the tank walls. The foam at the tank walls will meet and flow toward the center of the tank, closing the gap between the two.
Each fixed roof wand discharge head is preferably designed to flow 1000 gpm; 600 gpm is delivered through the center stream projecting toward the center of the tank with 200 gpm projecting left and right against the tank wall. This flow rate can be regulated by an internal jet just upstream of the aeration holes. Air is introduced to the stream at the aeration holes by the Venturi effect created by the internal jet. This aerates the foam before it leaves the wand to allow for aerated foam to land on the liquid surface. The ambient air aeration chamber is preferably intended to create a relatively low expansion foam compared to other devices, in order to maintain small bubble foam. This foam is best suited for quickly and effectively running across a liquid surface, thus providing a quick coverage and extinguishment of the tank. One main objective of the fixed roof wand system is to improve upon current methods of closed roof storage tank protection. The fixed roof wand system does so by projecting foam, rather than pouring foam, and by carefully engineered discharge tip sizes and designs coupled with an efficient ambient air aerator and favorable flow rates, stream shapers and stream straighteners.
One fixed roof wand system recommended layout, for example, is as follow:
Alcohols and related liquids and polar solvents are known to attract water out of foam bubbles. Foam, therefore, is preferably landed “lightly” on alcohols or like fluids to minimize the depth of any plunge of the foam below the liquid surface. The inventors teach that a swirl pattern may be preferable for running foam landing on alcohol or the like liquids in the case of fire. Thus the inventors teach, for tanks of alcohol or related liquids or polar solvents, a method of banking discharged foam against inner tank walls prior to landing the foam on the liquid, and discharging the foam predominantly all left or all right, from a plurality of nozzles, to develop a swirl pattern run for the foam in the tank.
The preferred foam for producing the requisite aerated foam for the instant fixed systems is to use an ambient air aeration chamber located just upstream of the nozzles. It is known in the art to produce an aeration chamber just downstream of the nozzle discharge orifice gap. In this sense the word nozzle is used to reference the portion of the barrel that contains the gap, or the swedging down to the narrowest orifice, thereby recovering the greatest head pressure for discharge. Such nozzle discharge orifice gap can discharge into an aeration chamber where aerated foam is produced and is then discharged from the aeration chamber into the atmosphere. U.S. Pat. No. 5,848,752 to Kolacz, in particular
The Point and Shoot system, at a minimum, includes installing a one or two nozzle aerated foam wand system, as a fixed system, preferably every 100′ to 240′ around the perimeter of a tank, which should be sufficient to extinguish tank “rim seal fires.”
A good reason for also installing at least one fixed riser proximate a landing, for releasably affixing a portable monitor and nozzle, together with the above one or two nozzle system, would be to provide redundancy and backup foam protection, in case some fixed system units were damaged due to an explosion, and to provide as well a full surface foam “blanket” for “vapor suppression” should a floating roof of the tank sink. Such a fixed monitor riser would have a fire department connection at the bottom of the tank and a monitor quick disconnect fitting at the top. During an event, if needed, a firefighter could carry a lightweight aluminum monitor and nozzle to the top of a tank and install the monitor on the riser pipe using the quick disconnect fitting (approximately 2 minute installation). From this vantage point, the fire fighter could directly apply foam to needed areas. This maximizes the effectiveness of the resources available to the firefighter. The danger and hazard from laying fire hoses up a ladder on the side of the tank to implement a portable system are avoided. Williams recommends installing a fixed monitor riser pipe at locations near landings of the tank. This fixed monitor riser pipe could also be used to apply foam if necessary to any exposed areas due to a “cocked” roof or in the event a foam wand head has been compromised due to an explosion. This elementary semi-fixed system minimizes initial capital investment for protection of a tank without a fixed roof, at least from a rim seal fire and a sunken roof, while providing a proven system that is easy to operate and to maintain. The equipment eliminates the need to drag multiple hoses up a tank's ladder which impedes firefighters from getting onto or off of the tank quickly.
The Ambush system is a fixed system particularly applicable for full surface liquid tank fires and/or rim seal fires, including in large tanks, again as above, preferably for tanks without a fixed roof. The Ambush system preferably includes three nozzle aerated foam wands, with two nozzles that discharge in roughly opposing directions and that can be oriented with respect to a tank to discharge roughly horizontally. The third nozzle projects in a direction roughly perpendicular to the discharge axis defined by the first two nozzles. When oriented with respect to the tank, the third nozzle projects roughly toward the center of the tank with an appropriate angle of inclination. The third nozzle is preferably structured to land aerated foam at least 100 feet distant. All three nozzles significantly directionally project aerated foam.
The Hollow Point system is a fixed system particularly applicable to hazards and fire in large tanks with a fixed roof, and preferably can be installed in and through existing upper tank wall openings. The Hollow Point system is characterized by a conduit ending in a nozzle tip, the conduit having two side discharge ports with associated, largely interior “deflectors.” The ports, conduit and nozzle are structured to pass through existing tank wall openings and to be oriented with the ports discharging in roughly opposing directions, roughly horizontally, and the nozzle tip discharging roughly toward the center. Both the nozzle and ports preferably discharge a substantially focused stream.
The heightened projection capability and foam run capability of each system described above results in the installation and servicing of significantly fewer units per tank than with previous fixed systems. The new systems can protect significantly larger tanks with less fixed equipment and in less time. A stream shaper installed in the tip of the nozzles contributes to the heightened projection capability of the nozzles, and together with the development of a properly aerated foam, produces a focused stream and optimized foam run.
As discussed above, the current accepted fixed system for protecting storage tanks comprises “foam chambers” (sometimes called “foam pourers.”) Fixed foam chambers have limitations, one main limitation being their method of applying foam to a seal area. Either because of (1) the degree of aeration produced by the foam chamber and/or (2) a perceived delicacy of the foam bubble and/or the (3) dispersed footprint discharged, the chamber is structured to only gently “pour” a greatly expanded foam down onto a tank's seal. The foam chamber pours; it does not throw or project. The foam chamber relies on gravity and the head created by the pile of foam to push the foam left and right of the foam chamber. This system severely limits the distance the foam can “run,” left and right of the foam chamber in the seal rim periphery area. This system requires a tank to have a large number of foam chambers spaced around the circumference, every 40 or 80 feet, depending upon whether the “foam dams” of the floating roof are 12″ or 24″. Many tanks are now greater than 300 foot diameter. Some are greater than 400 foot diameter. A 400 foot diameter tank with a 12″ foam dam would require about 23 traditional foam chambers to protect the periphery. The instant invention requires only about 6 units to protect the same periphery.
In contrast with the currently accepted fixed systems, Williams has developed an improved aerated foam nozzle system to discharge a proven effective foam surprisingly farther, many times farther, in both left and right directions, than traditional foam chambers. Tests show, below, that the instant system covers a larger area in less time with foam that effectively extinguishes fire. Further, a rim mounted nozzle has been also demonstrated that can run foam to the center of a 400 foot diameter tank.
In December of 2010 a “proof of concept” test was run at the Williams Fire and Hazard Control test facilities. The purpose of the test was to compare and contrast, by observation, two foam application devices flowing into a simulated tank “rim seal periphery area,” the ones between a tank wall and a floating roof “foam dam.”
The purpose of the test was to determine whether the relative foam flow performance of the novel Williams projecting foam wand could provide the anticipated benefits compared to a conventional “foam chamber.” Foam from both devices was discharged into a simulated floating roof “periphery,” the ones between a tank wall and a floating roof foam dam. For each device the foam traveled through this simulated wall/foam dam “periphery” to reach and extinguish a liquid hydrocarbon pan fire, which was simulating a storage tank floating roof “rim seal fire.” Flow rates and distances were recorded as elements of performance along with the delivered foam quality, foam expansion ratio and drain time.
The concept being tested was whether the foam applied through a high flow rate projecting foam wand would cover the distance in the seal area more rapidly and protect a larger segment of a floating roof seal along the periphery.
The observed test confirmed the concept. Foam from the projecting foam wand traveled 3 times the distance (120 feet versus 20 feet) in 25% less time (74 seconds versus 101 seconds from the chamber.) Both successfully extinguished a pan fire at their terminus. The novel foam wand applied foam more rapidly on the target area than the conventional foam chamber. In addition, the novel foam wand provided a gpm per square foot application rate 50% greater (0.6 versus 0.4 US gpm per square foot) than the foam chamber. Simulated periphery dimensions were 2 four inches wide and 2 four inches deep.
To summarize the test and the results, a novel aerated foam nozzle was set up on a mock seal area with a foam dam and flowed alongside a traditional foam chamber. The NFPA recognized maximum distance for a traditional foam chamber to cover is 80′ total, 40′ to the left and right, for a 24″ foam dam. The traditional foam chamber was able to cover this distance in 1 minute 40 seconds. The novel aerated foam nozzle was able to cover an area three times greater in significantly less time. The aerated foam nozzle covered an area of 240′ (120′ to the left and right) in 1 minute 14 seconds. It was shown that foam applied through the novel high flow rate wand projecting left and right would cover a foam dam seal area more rapidly, travel further per device, and protect a larger segment of floating roof seal along the periphery.
Further testing of a fixed Hollow Point wand, discussed above, showed that a roughly 80′×170′ pond of water (13,600 square feet) could be covered in foam with a Hollow Point wand in approximately 1 minute and 25 seconds. The furthest corner of the tank from the nozzle was 145′ away. That furthest corner received ample foam coverage. The speed, run and authority of the foam was surprising.
Testing of the center nozzle of the Ambush wand, discussed above, also indicated a capacity to achieve an approximately 150′ end range of a center nozzle landing footprint with the mid-point of the landing footprint at about 130′.
In August 2011 a full Ambush system was tested on a 277 foot diameter empty tank. Six three nozzle wand units were spaced around the periphery of the tank. The total flow per device was 1500 gpm giving a total system flow of 9,000 GPM. The measured footprint size of the center pointing nozzle was approximately 60 feet long by 20 feet wide with a mid-point range of approximately 90′ away from the nozzle. By observation, the total surface of the tank floor was covered with foam. Photographs show testers wading knee deep in foam toward the middle of the tank.
The invention includes a nozzle for projecting fire fighting foam in a substantially focused stream particularly for use with fixed or semi-fixed systems. The invention preferably includes a nozzle structured for projecting at least 100 gpm (at 100 psi) of aerated foam, the nozzle having a tip portion defining a longitudinal axis and terminating, in contain preferred embodiments, in a solid bore discharge orifice. The tip portion has a stream shaper. The stream shaper can include at least four fins with a longitudinal dimension in the tip portion greater than a radial dimension in the tip portion and with the fins terminating substantially flush with a nozzle tip solid bore discharge orifice.
The invention also includes a nozzle for projecting fire fighting foam in a substantially focused stream including a nozzle structured for projecting at least 100 gpm (at 100 psi) aerated foam, the nozzle having a tip portion defining a longitudinal axis and terminating in a discharge orifice that is not necessarily a solid bore. This tip portion preferably has a stream shaper having greater than four fins, the four fins having a longitudinal dimension in the tip portion greater than twice a radial dimension in the tip portion, with the fins terminating substantially flush with the nozzle tip discharge orifice.
Preferably a focused stream, aerated foam projecting nozzle is proximately attached downstream of, and in fluid communication with, an ambient air aeration chamber. Preferably an ambient air aeration chamber, in combination with a nozzle, is structured to project foam with an expansion of between 2-to-1 to 8-to-1, and more preferably, with an expansion of between 3-to-1 to 5-to-1.
Preferably at least one aerated foam projecting nozzle is attached proximate the top of an at least a 100 foot diameter industrial tank wall and placed in fluid communication with a riser attached to, or proximate to, the at least 100 foot diameter industrial tank wall.
The invention preferably includes a wand having at least one aerated foam projecting nozzle for projecting foam in a substantially focused stream and in a roughly horizontal direction around an inside tank wall surface. The invention can include a first ambient air aeration chamber located upstream of, proximate to and in fluid communication with at least one aerated foam projecting nozzle, the aerated foam projecting nozzle having at least four fins and a tip portion, the fins having a longitudinal dimension greater than a radial dimension and terminating substantially flush with a nozzle tip discharge orifice. The aeration chamber is preferably structured together with a nozzle to project at least 100 gpm of aerated foam (at 100 psi) having an expansion of between 2-to-1 to 8-to-1. The nozzle and chamber are preferably attached to a riser for communicating water and foam concentrate and the at least one nozzle and riser are preferably structured in combination for attachment to a tank wall of at least 100 feet diameter such that the nozzle projects foam in a roughly horizontal direction around an interior top tank wall surface.
The invention can include a wand having at least one aerated foam projecting nozzle for projecting foam in a substantially focused stream in a roughly horizontal direction around an inside tank wall surface and a first ambient air aeration chamber, located upstream of, proximate to and in fluid communication with the at least one aerated foam projecting nozzle, the nozzle structured for projecting aerated foam in a substantially focused stream. The chamber is preferably structured together with a nozzle to project at least 100 gpm of aerated foam having an expansion of at least 2-to-1 to 8-to-1. The nozzle and chamber are preferably attached to a riser for communicating water and foam concentrate and the at least one nozzle and riser are preferably structured in combination for attachment to a tank wall of an at least a 100 foot diameter tank such that the nozzle projects foam in a roughly horizontal direction around an interior top tank wall surface.
Preferably the invention includes two aerated foam projecting nozzles, the two nozzles structured in combination to project in roughly opposing directions. Preferably the aeration chamber and nozzles are structured together to project aerated foam with an expansion of between 3-to-1 to 5-to-1.
Preferably a wand system includes an at least two inch riser structured to extend from proximate a ground location to a wand head located proximate an at least 45 foot high industrial tank top wall portion, and the system includes a plurality of such wands attached around the tank wall at at least 150 feet apart, or at at least 200 feet apart or at at least 220 feet apart or at least 240 feet apart.
Preferably included with a wand system is an at least four inch riser located proximate the tank wall having either a fitting for attaching a portable monitor and nozzle or having attached a fixed nozzle. A portable monitor and nozzle and/or fixed nozzle can provide a center pointing nozzle for discharging aerated foam toward the center of the tank.
The invention preferably includes a method for projecting a substantially focused stream of aerated foam that includes supplying water and foam concentrate to an ambient air aeration chamber proximately attached upstream of, and in fluid communication with, a fire fighting nozzle. The invention can include projecting aerated foam with an expansion of between 2-to-1 to 8-to-1 from the nozzle in a substantially focused stream, the nozzle having a tip with at least four fins, the fins having a longitudinal dimension greater than a radial dimension, and the fins terminating substantially flush with a nozzle tip solid bore discharge orifice.
The invention also preferably includes a method for projecting a substantially focused stream of aerated fire fighting foam that includes supplying water and foam concentrate to an ambient air aeration chamber proximally attached upstream of, and in fluid communication with, a fire fighting nozzle and projecting aerated foam with an expansion of between 2-to-1 to 8-to-1 from the nozzle in a substantially focused stream. The nozzle preferably has a tip with greater than four fins, the fins having a longitudinal dimension greater than twice a radial dimension and terminating substantially flush with a nozzle tip discharge orifice, which is not necessarily a solid bore.
The method preferably includes projecting foam with an expansion of 3-to-1 to 5-to-1 and projecting foam into an at least 100 foot diameter industrial tank from a position proximate a top tank wall portion, and wherein the nozzle is attached to a riser proximate the tank wall.
The invention can include a method of providing fixed wands around a tank wall for projecting foam against interior tank wall portions as well as providing risers and one or more center pointing nozzles for projecting foam toward the center of the tank.
A better understanding of the present invention can be obtained when the following detailed description of the preferred embodiments are considered in conjunction with the following drawings, in which:
The drawings are primarily illustrative. It would be understood that structure may have been simplified and details omitted in order to convey certain aspects of the invention. Scale may be sacrificed to clarity.
As is common in the industry each nozzle includes a swedge-down area SW for recovering head pressure in order to enhance the range of the discharge.
The nozzle of these preferred embodiments utilize a solid bore discharge orifice DO. However, it is anticipated that roughly equivalent nozzles can be constructed using an annular bore discharge nozzle. An annular bore discharge nozzle is illustrated in principle in
The three wand head embodiments of
As discussed above,
The foregoing figures illustrate various embodiments of an aerated foam projecting nozzle to project fire fighting foam in a substantially focused stream, and in particular a nozzle structured for projecting at least 100 gpm of aerated foam at 100 psi. As can be seen the nozzle has a tip portion defining a longitudinal axis and preferably terminating in a solid bore discharge orifice. However, an annular discharge orifice should also work. The tip portion of the nozzle incorporates a stream shaper and, as frequently included, a swedge-down portion. The stream shaper has at least four fins with a longitudinal dimension in the tip portion greater than the radial dimension in the tip portion. It can be seen that the fins terminate substantially flush with the nozzle tip discharge orifice in the preferred embodiments.
As further illustrated by the foregoing figures, a nozzle for projecting aerated fire fighting foam in a substantially focused stream is proximately attached downstream of, and in fluid communication with, an ambient air aeration chamber, AAAC. The ambient air aeration chamber preferably includes a tubular jet structure TJ, preferably also with crosshairs CW or a cross haired screen just downstream of the tubular jet structure TJ to further break up the flow. (See
Preferably the nozzle and ambient air aeration chamber are structured in combination to project foam with an expansion of between 2 to 1 to 8 to 1. More preferably, the nozzle and aeration chamber are structured in combination to project foam with an expansion of between 3 to 1 to 5 to 1.
The nozzles for projecting fire fighting foam in a substantially focused stream are particularly adapted for being attached proximate a top portion of an at least 100 foot diameter industrial tank wall, as illustrated in
In operation a substantially focused stream of aerated fire fighting foam is projected by supplying water and foam concentrate to an ambient air aeration chamber proximately attached upstream of, and in fluid communication with, an aerated foam projecting fire fighting nozzle, and by projecting aerated foam with an expansion of between 2 to 1 to 8 to 1 from the nozzle in a in a substantially focused stream, the nozzle having a tip of at least four fins, the fins having longitudinal dimension greater than a radial dimension and terminating substantially flush with a nozzle tip solid bore discharge orifice DO. (See
In operation also, a substantially focused stream of aerated fire fighting foam can be projected by supplying water and foam concentrate to an ambient air aeration chamber proximately attached upstream of and in fluid communication with an aerated foam projecting foam fire fighting nozzle. The method includes projecting aerating foam with an expansion of between 2 to 1 to 8 to 1 from the nozzle in a substantially focused stream with the nozzle having a tip of greater than four fins and the fins having a longitudinal dimension greater than twice the radial dimension, the fins terminating substantially flush with a nozzle tip discharge orifice.
Preferably the methodology includes projecting foam with an expansion of between 3 to 1 to 5 to 1 into an at least 100 foot diameter industrial tank from a position proximate a top portion of a tank wall.
Again,
Again,
In operation an aerated foam projecting nozzle would preferably project aerated foam roughly horizontally in a substantially focused stream around an inside top tank wall surface of an at least 100 foot diameter tank. The nozzle would produce aerated foam having an expansion of between 2-to-1 to 8-to-1. Preferably the foam would have an expansion of between have an expansion of between 3-to-1 to 5-to-1. Preferably two aerated foam projecting foam nozzles would be included, projecting roughly horizontally in substantially focused streams and in roughly opposing directions. Preferably the nozzle or nozzles would be affixed to an upper wall portion of an industrial storage tank.
In a point and shoot method, fire fighting fluid from approximately the ground is also provided to approximately the tank top through an at least four inch riser located proximate the tank wall, the at least four inch riser attachable to an at least 150 gpm portable monitor and nozzle by virtue of a fitting on a distal end of the at least four inch riser. Alternately an at least 150 gpm nozzle could be fixedly attached to the at least four inch riser. The fixed nozzle would be structured with the riser to discharge proximate to a tank top wall portion and toward the center of the tank. The portable monitor and nozzle can be aimed and turned by a fire fighter.
In the point and shoot method if the at least four inch riser is structured to releasably attach to a portable monitor and nozzle, then the at least four inch riser should be located proximate a landing at the top of the tank wall. Alternately, if the at least four inch riser is structured to fixedly attach to a fire fighting nozzle, then the riser can be located any place around the periphery around the tank including a plurality of places. The riser and the fixed nozzle would be structured such that the nozzle discharges roughly toward the center of the tank.
The foregoing description of preferred embodiments of the invention is presented for purposes of illustration and description, and is not intended to be exhaustive or to limit the invention to the precise form or embodiment disclosed. The description was selected to best explain the principles of the invention and their practical application to enable others skilled in the art to best utilize the invention in various embodiments. Various modifications as are best suited to the particular use are contemplated. It is intended that the scope of the invention is not to be limited by the specification, but to be defined by the claims set forth below. Since the foregoing disclosure and description of the invention are illustrative and explanatory thereof, various changes in the size, shape, and materials, as well as in the details of the illustrated device may be made without departing from the spirit of the invention. The invention is claimed using terminology that depends upon a historic presumption that recitation of a single element covers one or more, and recitation of two elements covers two or more, and the like. Also, the drawings and illustration herein have not necessarily been produced to scale.
This application is continuation of, is related to and claims priority to, co-pending U.S. Ser. No. 13/261,639, of same name and same inventors, filed Apr. 16, 2013 as a national stage application of PCT/US11/01769, filed Oct. 17, 2011, which relates to and claims priority to four co-pending provisional applications by the same inventors: US Ser. Nos. 61/455,367, 61/461,413, 61/463,296 and 61/519,071 filed Oct. 19, 2010, Jan. 18, 2011, Feb. 14, 2011 and May 16, 2011 and entitled “Rapid Tank Response, Equipment and Methodology;” “A Point and Shoot System (including as previously filed) An Ambush System and Method and a Hollow Point System and Method, all for Fighting Industrial Tank Hazards;” “Further Developments—Fixed System (Point and Shoot, Ambush and Hollow Point),” and “Fixed/Semi-Fixed Aerated Foam Systems for Industrial Tank Hazards,” respectively. The four co-pending applications are all herein and hereby incorporated by reference in their entirety to the extent permitted by law and regulation.
Number | Date | Country | |
---|---|---|---|
61455367 | Oct 2010 | US | |
61461413 | Jan 2011 | US | |
61463296 | Feb 2011 | US | |
61519071 | May 2011 | US |
Number | Date | Country | |
---|---|---|---|
Parent | 13261639 | Apr 2013 | US |
Child | 15474108 | US |