HEAT TRANSFER COMPOSITIONS

Abstract
The invention provides a heat transfer composition comprising (i) a first component selected from trans-1,3,3,3-tetrafluoropropene (R-1234ze(E)), cis-1,3,3,3-tetrafluoropropene (R-1234ze(Z)) and mixtures thereof; (ii) carbon dioxide (R-744); and (iii) a third component selected from difluoromethane (R-32) 1,1,1,2-tetrafluoroethane (R-134a) and mixtures thereof.
Description
FIELD

The invention relates to heat transfer compositions, and in particular to heat transfer compositions which may be suitable as replacements for existing refrigerants such as R-134a, R-152a, R-1234yf, R-22, R-410A, R-407A, R-407B, R-407C, R507 and R-404a.


BACKGROUND

The listing or discussion of a prior-published document or any background in the specification should not necessarily be taken as an acknowledgement that a document or background is part of the state of the art or is common general knowledge.


Mechanical refrigeration systems and related heat transfer devices such as heat pumps and air-conditioning systems are well known. In such systems, a refrigerant liquid evaporates at low pressure taking heat from the surrounding zone. The resulting vapour is then compressed and passed to a condenser where it condenses and gives off heat to a second zone, the condensate being returned through an expansion valve to the evaporator, so completing the cycle. Mechanical energy required for compressing the vapour and pumping the liquid is provided by, for example, an electric motor or an internal combustion engine.


In addition to having a suitable boiling point and a high latent heat of vaporisation, the properties preferred in a refrigerant include low toxicity, non-flammability, non-corrosivity, high stability and freedom from objectionable odour. Other desirable properties are ready compressibility at pressures below 25 bars, low discharge temperature on compression, high refrigeration capacity, high efficiency (high coefficient of performance) and an evaporator pressure in excess of 1 bar at the desired evaporation temperature.


Dichlorodifluoromethane (refrigerant R-12) possesses a suitable combination of properties and was for many years the most widely used refrigerant. Due to international concern that fully and partially halogenated chlorofluorocarbons were damaging the earth's protective ozone layer, there was general agreement that their manufacture and use should be severely restricted and eventually phased out completely. The use of dichlorodifluoromethane was phased out in the 1990's.


Chlorodifluoromethane (R-22) was introduced as a replacement for R-12 because of its lower ozone depletion potential. Following concerns that R-22 is a potent greenhouse gas, its use is also being phased out.


Whilst heat transfer devices of the type to which the present invention relates are essentially closed systems, loss of refrigerant to the atmosphere can occur due to leakage during operation of the equipment or during maintenance procedures. It is important, therefore, to replace fully and partially halogenated chlorofluorocarbon refrigerants by materials having zero ozone depletion potentials.


In addition to the possibility of ozone depletion, it has been suggested that significant concentrations of halocarbon refrigerants in the atmosphere might contribute to global warming (the so-called greenhouse effect). It is desirable, therefore, to use refrigerants which have relatively short atmospheric lifetimes as a result of their ability to react with other atmospheric constituents such as hydroxyl radicals, or as a result of ready degradation through photolytic processes.


R-410A and R-407 refrigerants (including R-407A, R-407B and R-407C) have been introduced as a replacement refrigerant for R-22. However, R-22, R-410A and the R-407 refrigerants all have a high global warming potential (GWP, also known as greenhouse warming potential).


1,1,1,2-tetrafluoroethane (refrigerant R-134a) was introduced as a replacement refrigerant for R-12. R-134a is an energy efficient refrigerant, used currently for automotive air conditioning. However it is a greenhouse gas with a GWP of 1430 relative to CO2 (GWP of CO2 is 1 by definition). The proportion of the overall environmental impact of automotive air conditioning systems using this gas, which may be attributed to the direct emission of the refrigerant, is typically in the range 10-20%. Legislation has now been passed in the European Union to rule out use of refrigerants having GWP of greater than 150 for new models of car from 2011. The car industry operates global technology platforms, and in any event emission of greenhouse gas has global impact, thus there is a need to find fluids having reduced environmental impact (e.g. reduced GWP) compared to HFC-134a.


R-152a (1,1-difluoroethane) has been identified as an alternative to R-134a. It is somewhat more efficient than R-134a and has a greenhouse warming potential of 120. However the flammability of R-152a is judged too high, for example to permit its safe use in mobile air conditioning systems. In particular it is believed that its lower flammable limit in air is too low, its flame speeds are too high, and its ignition energy is too low.


Thus there is a need to provide alternative refrigerants having improved properties such as low flammability. Fluorocarbon combustion chemistry is complex and unpredictable. It is not always the case that mixing a non-flammable fluorocarbon with a flammable fluorocarbon reduces the flammability of the fluid or reduces the range of flammable compositions in air. For example, the inventors have found that if non-flammable R-134a is mixed with flammable R-152a, the lower flammable limit of the mixture alters in a manner which is not predictable. The situation is rendered even more complex and less predictable if ternary or quaternary compositions are considered.


There is also a need to provide alternative refrigerants that may be used in existing devices such as refrigeration devices with little or no modification.


R-1234yf (2,3,3,3-tetrafluoropropene) has been identified as a candidate alternative refrigerant to replace R-134a in certain applications, notably the mobile air conditioning or heat pumping applications. Its GWP is about 4. R-1234yf is flammable but its flammability characteristics are generally regarded as acceptable for some applications including mobile air conditioning or heat pumping. In particular, when compared with R-152a, its lower flammable limit is higher, its minimum ignition energy is higher and the flame speed in air is significantly lower than that of R-152a.


The environmental impact of operating an air conditioning or refrigeration system, in terms of the emissions of greenhouse gases, should be considered with reference not only to the so-called “direct” GWP of the refrigerant, but also with reference to the so-called “indirect” emissions, meaning those emissions of carbon dioxide resulting from consumption of electricity or fuel to operate the system. Several metrics of this total GWP impact have been developed, including those known as Total Equivalent Warming Impact (TEWI) analysis, or Life-Cycle Carbon Production (LCCP) analysis. Both of these measures include estimation of the effect of refrigerant GWP and energy efficiency on overall warming impact. Emissions of carbon dioxide associated with manufacture of the refrigerant and system equipment should also be considered.


The energy efficiency and refrigeration capacity of R-1234yf have been found to be significantly lower than those of R-134a and in addition the fluid has been found to exhibit increased pressure drop in system pipework and heat exchangers. A consequence of this is that to use R-1234yf and achieve energy efficiency and cooling performance equivalent to R-134a, increased complexity of equipment and increased size of pipework is required, leading to an increase in indirect emissions associated with equipment. Furthermore, the production of R-1234yf is thought to be more complex and less efficient in its use of raw materials (fluorinated and chlorinated) than R-134a. Current projections of long term pricing for R-1234yf is in the range 10-20 times greater than R-134a. This price differential and the need for extra expenditure on hardware will limit the rate at which refrigerants are changed and hence limit the rate at which the overall environmental impact of refrigeration or air conditioning may be reduced. In summary, the adoption of R-1234yf to replace R-134a will consume more raw materials and result in more indirect emissions of greenhouse gases than does R-134a.


Some existing technologies designed for R-134a may not be able to accept even the reduced flammability of some heat transfer compositions (any composition having a GWP of less than 150 is believed to be flammable to some extent).


SUMMARY

A principal object of the present invention is therefore to provide a heat transfer composition which is usable in its own right or suitable as a replacement for existing refrigeration usages which should have a reduced GWP, yet have a capacity and energy efficiency (which may be conveniently expressed as the “Coefficient of Performance”) ideally within 10% of the values, for example of those attained using existing refrigerants (e.g. R-134a, R-152a, R-1234yf, R-22, R-410A, R-407A, R-407B, R-407C, R507 and R-404a), and preferably within less than 10% (e.g. about 5%) of these values. It is known in the art that differences of this order between fluids are usually resolvable by redesign of equipment and system operational features. The composition should also ideally have reduced toxicity and acceptable flammability.


The subject invention addresses the above deficiencies by the provision of a heat transfer composition comprising (i) a first component selected from trans-1,3,3,3-tetrafluoropropene (R-1234ze(E)), cis-1,3,3,3-tetrafluoropropene (R-1234ze(Z)) and mixtures thereof; (ii) carbon dioxide (CO2 or R-744); and (iii) a third component selected from difluoromethane (R-32), 1,1,1,2-tetrafluoroethane (R-134a), and mixtures thereof.


All of the chemicals herein described are commercially available. For example, the fluorochemicals may be obtained from Apollo Scientific (UK).


Typically, the compositions of the invention contain trans-1,3,3,3-tetrafluoropropene (R-1234ze(E)). The majority of the specific compositions described herein contain R-1234ze(E). It is to be understood, of course, that some or all of the R-1234ze(E) in such compositions can be replaced by R-1234ze(Z). The trans isomer is currently preferred, however.


Typically, the composition of the invention contain at least about 5% by weight R-1234ze(E), preferably at least about 15% by weight. In one embodiment, the compositions of the invention contain at least about 45% by weight R-1234ze(E), for example from about 50 to about 98% by weight.


The preferred amounts and choice of components for the invention are determined by a combination of properties:

    • (a) Flammability: non-flammable or weakly flammable compositions are preferred.
    • (b) Effective operating temperature of the refrigerant in an air conditioning system evaporator.
    • (c) Temperature “glide” of the mixture and its effect on heat exchanger performance.
    • (d) Critical temperature of the composition. This should be higher than the maximum expected condenser temperature.





BRIEF DESCRIPTION OF THE DRAWINGS


FIG. 1 is a graph of heating COP of CO2/R134a/R1234ze(E) mixtures as a function of CO2 content of mixture;



FIG. 2 is a graph of heating COP of CO2/R32/R1234ze(E) mixtures as a function of CO2 content of mixture; and



FIG. 3 is a graph of heating capacity of CO2/R32/R1234ze(E) mixtures as a function of CO2 content of mixture.





DETAILED DESCRIPTION

The effective operating temperature in an air conditioning cycle, especially automotive air conditioning, is limited by the need to avoid ice formation on the air-side surface of the refrigerant evaporator. Typically air conditioning systems must cool and dehumidify humid air; so liquid water will be formed on the air-side surface. Most evaporators (without exception for the automotive application) have finned surfaces with narrow fin spacing. If the evaporator is too cold then ice can be formed between the fins, restricting the flow of air over the surface and reducing overall performance by reducing the working area of the heat exchanger.


It is known for automotive air-conditioning applications (Modern Refrigeration and Air Conditioning by A D Althouse et al, 1988 edition, Chapter 27, which is incorporated herein by reference) that refrigerant evaporation temperatures of −2° C. or higher are preferred to ensure that the problem of ice formation is thereby avoided.


It is also known that non-azeotropic refrigerant mixtures exhibit temperature “glide” in evaporation or condensation. In other words, as the refrigerant is progressively vaporised or condensed at constant pressure, the temperature rises (in evaporation) or drops (in condensation), with the total temperature difference (inlet to outlet) being referred to as the temperature glide. The effect of glide on evaporation and condensation temperature must also be considered.


The critical temperature of a heat transfer composition should be higher than the maximum expected condenser temperature. This is because the cycle efficiency drops as critical temperature is approached. As this happens, the latent heat of the refrigerant is reduced and so more of the heat rejection in the condenser takes place by cooling gaseous refrigerant; this requires more area per unit heat transferred.


R-410A is commonly used in building and domestic heat pump systems and by way of illustration its critical temperature of about 71° C. is higher than the highest normal condensing temperature required to deliver useful warm air at about 50° C. The automotive duty requires air at about 50° C. so the critical temperature of the fluids of the invention should be higher than this if a conventional vapour compression cycle is to be utilised. Critical temperature is preferably at least 15K higher than the maximum air temperature.


In one aspect, the compositions of the invention have a critical temperature of greater than about 65° C., preferably greater than about 70° C.


The carbon dioxide content of the compositions of the invention is limited primarily by considerations (b) and/or (c) and/or (d) above. Conveniently, the compositions of the invention typically contain up to about 35% by weight R-744, preferably up to about 30% by weight.


In a preferred aspect, the compositions of the invention contain from about 4 to about 30% R-744 by weight, preferably from about 4 to about 28% by weight, or from about 8 to about 30% by weight, or from about 10 to about 30% by weight.


The content of the third component, which may include flammable refrigerants such as R-32, is selected so that even in the absence of the carbon dioxide element of the composition, the residual fluorocarbon mixture has a lower flammable limit in air at ambient temperature (e.g. 23° C.) (as determined in the ASHRAE-34 12 litre flask test apparatus) which is greater than 5% v/v, preferably greater than 6% v/v, most preferably such that the mixture is non-flammable. The issue of flammability is discussed further later in this specification.


Typically, the compositions of the invention contain up to about 60% by weight of the third component. Preferably, the compositions of the invention contain up to about 50% by weight of the third component. Conveniently, the compositions of the invention contain up to about 45% by weight of the third component. In one aspect, the compositions of the invention contain from about 1 to about 40% by weight of the third component.


In one embodiment, the compositions of the invention comprise from about 10 to about 95% R-1234ze(E) by weight, from about 2 to about 30% by weight R-744, and from about 3 to about 60% by weight of the third component.


As used herein, all % amounts mentioned in compositions herein, including in the claims, are by weight based on the total weight of the compositions, unless otherwise stated.


For the avoidance of doubt, it is to be understood that the stated upper and lower values for ranges of amounts of components in the compositions of the invention described herein may be interchanged in any way, provided that the resulting ranges fall within the broadest scope of the invention.


In one embodiment, the compositions of the invention consist essentially of (or consist of) the first component (e.g. R-1234ze(E)), R-744 and the third component.


By the term “consist essentially of”, we mean that the compositions of the invention contain substantially no other components, particularly no further (hydro)(fluoro)compounds (e.g. (hydro)(fluoro)alkanes or (hydro)(fluoro)alkenes) known to be used in heat transfer compositions. We include the term “consist of” within the meaning of “consist essentially of”.


For the avoidance of doubt, any of the compositions of the invention described herein, including those with specifically defined compounds and amounts of compounds or components, may consist essentially of (or consist of) the compounds or components defined in those compositions.


The third component is selected from R-32, R-134a and mixtures thereof.


In one aspect, the third component contains only one of the listed components. For example, the third component may contain only one of difluoromethane (R-32) or 1,1,1,2-tetrafluoroethane (R-134a) Thus, the compositions of the invention may be ternary blends of R-1234ze(E), R-744 and one of the listed third components (e.g. R-32 or R-134a).


However, mixtures of R-32 and R-134a can be used as the third component. R-134a typically is included to reduce the flammability of the equivalent composition that does not contain R-134a.


The invention contemplates compositions in which additional compounds are included in the third component. Examples of such compounds include 2,3,3,3-tetrafluoropropene (R-1234yf), 3,3,3-trifluoropropene (R1243zf), 1,1-difluoroethane (R-152a), fluoroethane (R-161), 1,1,1-trifluoropropane (R-263fb), 1,1,1,2,3-pentafluoropropane (R-245eb), propylene (R-1270), propane (R-290), n-butane (R-600), isobutane (R-600a), ammonia (R-717) and mixtures thereof.


Preferably, the compositions of the invention which contain R-134a are non-flammable at a test temperature of 60° C. using the ASHRAE-34 methodology. Advantageously, the mixtures of vapour that exist in equilibrium with the compositions of the invention at any temperature between about −20° C. and 60° C. are also non-flammable.


In one preferred embodiment, the third component comprises R-134a. The third component may consist essentially of (or consist of) R-134a.


Compositions of the invention which contain R-134a typically contain it in an amount of from about 2 to about 50% by weight, for example from about 5 to about 40% by weight.


Typical compositions of the invention containing R-134a comprise from about 20 to about 93% by weight R-1234ze(E), from about 2 to about 30% by weight R-744 and from about 5 to about 50% by weight R-134a.


A relatively low GWP composition containing R-134a comprises from about 60 to about 92% R-1234ze(E), from about 4 to about 30% by weight R-744 and from about 4 to about 10% by weight R-134a. A preferred such composition comprises from about 62 to about 86% R-1234ze(E), from about 10 to about 28% by weight R-744 and from about 4 to about 10% by weight R-134a.


A higher GWP composition containing R-134a comprises from about 20 to about 86% R-1234ze(E), from about 4 to about 30% by weight R-744 and from about 10 to about 50% by weight R-134a. A preferred such composition comprises from about 22 to about 80% R-1234ze(E), from about 10 to about 28% by weight R-744 and from about 10 to about 50% by weight R-134a.


In one embodiment, the third component comprises R-32. The third component may consist essentially of (or consist of) R-32.


Compositions of the invention which contain R-32 typically contain it in an amount of from about 2 to about 30% by weight, conveniently in an amount of from about 2 to about 25% by weight, for example from about 5 to about 20% by weight.


Typical compositions of the invention containing R-32 comprise from about 60 to about 91% by weight R-1234ze(E), from about 4 to about 30% by weight R-744 and from about 5 to about 30% by weight R-32.


A preferred composition comprises from about 58 to about 85% R-1234ze(E), from about 10 to about 28% by weight R-744 and from about 5 to about 30% by weight R-32.


Further advantageous compositions of the invention containing R-32 comprise from about 50 to about 88% by weight R-1234ze(E), from about 4 to about 30% by weight R-744 and from about 2 to about 20% by weight R-32.


In one embodiment, the third component comprises R-32 and R-134a. The third component may consist essentially of (or consist of) R-32 and R-134a.


Compositions of the invention containing R-32 and R-134a typically contain from about 5 to about 95% by weight R-1234ze(E), from about 4 to about 30% by weight R-744, from about 2 to about 30% by weight R-32 and from about 2 to about 50 by weight R-134a.


Preferred compositions comprise from about 5 to about 92% by weight R-1234ze(E), from about 4 to about 30% by weight R-744, from about 2 to about 25% by weight R-32 and from about 2 to about 40% by weight R-134a.


Advantageous compositions which have a relatively low GWP comprise from about 30 to about 81% by weight R-1234ze(E), from about 10 to about 30% by weight R-744, from about 5 to about 30% by weight R-32 and from about 4 to about 10 by weight R-134a. Preferably such compositions contain from about 37 to about 81% by weight R-1234ze(E), from about 10 to about 28% by weight R-744, from about 5 to about 25% by weight R-32 and from about 4 to about 10 by weight R-134a.


Yet further compositions of the invention containing R-32 and R-134a, and having a higher GWP, comprise from about 5 to about 75% by weight R-1234ze(E), from about 10 to about 30% by weight R-744, from about 5 to about 25% by weight R-32 and from about 10 to about 50 by weight R-134a. Preferred such compositions comprise from about 7 to about 75% by weight R-1234ze(E), from about 10 to about 28% by weight R-744, from about 5 to about 25% by weight R-32 and from about 10 to about 40 by weight R-134a.


Compositions according to the invention conveniently comprise substantially no R-1225 (pentafluoropropene), conveniently substantially no R-1225ye (1,2,3,3,3-pentafluoropropene) or R-1225zc (1,1,3,3,3-pentafluoropropene), which compounds may have associated toxicity issues.


By “substantially no”, we include the meaning that the compositions of the invention contain 0.5% by weight or less of the stated component, preferably 0.1% or less, based on the total weight of the composition.


Certain compositions of the invention may contain substantially no:

    • (i) 2,3,3,3-tetrafluoropropene (R-1234yf),
    • (ii) cis-1,3,3,3-tetrafluoropropene (R-1234ze(Z)), and/or
    • (iii) 3,3,3-trifluoropropene (R-1243zf).


The compositions of the invention have zero ozone depletion potential.


Typically, the compositions of the invention have a GWP that is less than 1300, preferably less than 1000, more preferably less than 800, 500, 400, 300 or 200, especially less than 150 or 100, even less than 50 in some cases. Unless otherwise stated, IPCC (Intergovernmental Panel on Climate Change) TAR (Third Assessment Report) values of GWP have been used herein.


Advantageously, the compositions are of reduced flammability hazard when compared to the third component(s) alone, e.g. R-32. Preferably, the compositions are of reduced flammability hazard when compared to R-1234yf.


In one aspect, the compositions have one or more of (a) a higher lower flammable limit; (b) a higher ignition energy; or (c) a lower flame velocity compared to the third component(s), such as R-32, or compared to R-1234yf. In a preferred embodiment, the compositions of the invention are non-flammable. Advantageously, the mixtures of vapour that exist in equilibrium with the compositions of the invention at any temperature between about −20° C. and 60° C. are also non-flammable.


Flammability may be determined in accordance with ASHRAE Standard 34 incorporating the ASTM Standard E-681 with test methodology as per Addendum 34p dated 2004, the entire content of which is incorporated herein by reference.


In some applications it may not be necessary for the formulation to be classed as non-flammable by the ASHRAE-34 methodology; it is possible to develop fluids whose flammability limits will be sufficiently reduced in air to render them safe for use in the application, for example if it is physically not possible to make a flammable mixture by leaking the refrigeration equipment charge into the surrounds.


R-1234ze(E) is non-flammable in air at 23° C., although it exhibits flammability at higher temperatures in humid air. We have determined by experimentation that mixtures of R-1234ze(E) with flammable fluorocarbons such as R-32, R-152a or R-161 will remain non-flammable in air at 23° C. if the “fluorine ratio” Rf of the mixture is greater than about 0.57, where Rf is defined per gram-mole of the overall refrigerant mixture as:






R
f=(gram-moles of fluorine)/(gram-moles fluorine+gram-moles hydrogen)


Thus for R-161, Rf=1/(1+5)=⅙ (0.167) and it is flammable, in contrast R-1234ze(E) has Rf= 4/6 (0.667) and it is non-flammable. We found by experiment that a 20% v/v mixture of R-161 in R-1234ze(E) was similarly non-flammable. The fluorine ratio of this non-flammable mixture is 0.2*(⅙)+0.8*( 4/6)=0.567.


The validity of this relationship between flammability and fluorine ratio of 0.57 or higher has thusfar been experimentally proven for HFC-32, HFC-152a and mixtures of HFC-32 with HFC-152a.


Takizawa et al, Reaction Stoichiometry for Combustion of Fluoroethane Blends, ASHRAE Transactions 112(2) 2006 (which is incorporated herein by reference), shows that there exists a near-linear relationship between this ratio and the flame speed of mixtures comprising R-152a, with increasing fluorine ratio resulting in lower flame speeds. The data in this reference teach that the fluorine ratio needs to be greater than about 0.65 for the flame speed to drop to zero, in other words, for the mixture to be non-flammable.


Similarly, Minor et al (Du Pont Patent Application WO2007/053697) provide teaching on the flammability of many hydrofluoroolefins, showing that such compounds could be expected to be non-flammable if the fluorine ratio is greater than about 0.7.


In view of this prior art teaching, it is unexpected that that mixtures of R-1234ze(E) with flammable fluorocarbons such as R-32 will remain non-flammable in air at 23° C. if the fluorine ratio Rf of the mixture is greater than about 0.57.


Furthermore, we identified that if the fluorine ratio is greater than about 0.46 then the composition can be expected to have a lower flammable limit in air of greater than 6% v/v at room temperature.


By producing low- or non-flammable R-744/third component/R-1234ze(E) blends containing unexpectedly low amounts of R-1234ze(E), the amounts of the third component, in particular, in such compositions are increased. This is believed to result in heat transfer compositions exhibiting increased cooling capacity and/or decreased pressure drop, compared to equivalent compositions containing higher amounts of (e.g. almost 100%) R-1234ze(E).


Thus, the compositions of the invention exhibit a completely unexpected combination of low-/non-flammability, low GWP and improved refrigeration performance properties. Some of these refrigeration performance properties are explained in more detail below.


Temperature glide, which can be thought of as the difference between bubble point and dew point temperatures of a zeotropic (non-azeotropic) mixture at constant pressure, is a characteristic of a refrigerant; if it is desired to replace a fluid with a mixture then it is often preferable to have similar or reduced glide in the alternative fluid. In an embodiment, the compositions of the invention are zeotropic.


Advantageously, the volumetric refrigeration capacity of the compositions of the invention is at least 85% of the existing refrigerant fluid it is replacing, preferably at least 90% or even at least 95%.


The compositions of the invention typically have a volumetric refrigeration capacity that is at least 90% of that of R-1234yf. Preferably, the compositions of the invention have a volumetric refrigeration capacity that is at least 95% of that of R-1234yf, for example from about 95% to about 120% of that of R-1234yf.


In one embodiment, the cycle efficiency (Coefficient of Performance, COP) of the compositions of the invention is within about 5% or even better than the existing refrigerant fluid it is replacing


Conveniently, the compressor discharge temperature of the compositions of the invention is within about 15K of the existing refrigerant fluid it is replacing, preferably about 10K or even about 5K.


The compositions of the invention preferably have energy efficiency at least 95% (preferably at least 98%) of R-134a under equivalent conditions, while having reduced or equivalent pressure drop characteristics and cooling capacity at 95% or higher of R-134a values. Advantageously the compositions have higher energy efficiency and lower pressure drop characteristics than R-134a under equivalent conditions. The compositions also advantageously have better energy efficiency and pressure drop characteristics than R-1234yf alone.


The heat transfer compositions of the invention are suitable for use in existing designs of equipment, and are compatible with all classes of lubricant currently used with established HFC refrigerants. They may be optionally stabilized or compatibilized with mineral oils by the use of appropriate additives.


Preferably, when used in heat transfer equipment, the composition of the invention is combined with a lubricant.


Conveniently, the lubricant is selected from the group consisting of mineral oil, silicone oil, polyalkyl benzenes (PABs), polyol esters (POEs), polyalkylene glycols (PAGs), polyalkylene glycol esters (PAG esters), polyvinyl ethers (PVEs), poly (alpha-olefins) and combinations thereof.


Advantageously, the lubricant further comprises a stabiliser.


Preferably, the stabiliser is selected from the group consisting of diene-based compounds, phosphates, phenol compounds and epoxides, and mixtures thereof.


Conveniently, the composition of the invention may be combined with a flame retardant.


Advantageously, the flame retardant is selected from the group consisting of tri-(2-chloroethyl)-phosphate, (chloropropyl) phosphate, tri-(2,3-dibromopropyl)-phosphate, tri-(1,3-dichloropropyl)-phosphate, diammonium phosphate, various halogenated aromatic compounds, antimony oxide, aluminium trihydrate, polyvinyl chloride, a fluorinated iodocarbon, a fluorinated bromocarbon, trifluoro iodomethane, perfluoroalkyl amines, bromo-fluoroalkyl amines and mixtures thereof.


Preferably, the heat transfer composition is a refrigerant composition.


In one embodiment, the invention provides a heat transfer device comprising a composition of the invention.


Preferably, the heat transfer device is a refrigeration device.


Conveniently, the heat transfer device is selected from the group consisting of automotive air conditioning systems, residential air conditioning systems, commercial air conditioning systems, residential refrigerator systems, residential freezer systems, commercial refrigerator systems, commercial freezer systems, chiller air conditioning systems, chiller refrigeration systems, and commercial or residential heat pump systems. Preferably, the heat transfer device is a refrigeration device or an air-conditioning system.


The compositions of the invention are particularly suitable for use in mobile air-conditioning applications, such as automotive air-conditioning systems (e.g. heat pump cycle for automotive air-conditioning).


Advantageously, the heat transfer device contains a centrifugal-type compressor.


The invention also provides the use of a composition of the invention in a heat transfer device as herein described.


According to a further aspect of the invention, there is provided a blowing agent comprising a composition of the invention.


According to another aspect of the invention, there is provided a foamable composition comprising one or more components capable of forming foam and a composition of the invention.


Preferably, the one or more components capable of forming foam are selected from polyurethanes, thermoplastic polymers and resins, such as polystyrene, and epoxy resins.


According to a further aspect of the invention, there is provided a foam obtainable from the foamable composition of the invention.


Preferably the foam comprises a composition of the invention.


According to another aspect of the invention, there is provided a sprayable composition comprising a material to be sprayed and a propellant comprising a composition of the invention.


According to a further aspect of the invention, there is provided a method for cooling an article which comprises condensing a composition of the invention and thereafter evaporating said composition in the vicinity of the article to be cooled.


According to another aspect of the invention, there is provided a method for heating an article which comprises condensing a composition of the invention in the vicinity of the article to be heated and thereafter evaporating said composition.


According to a further aspect of the invention, there is provided a method for extracting a substance from biomass comprising contacting the biomass with a solvent comprising a composition of the invention, and separating the substance from the solvent.


According to another aspect of the invention, there is provided a method of cleaning an article comprising contacting the article with a solvent comprising a composition of the invention.


According to a further aspect of the invention, there is provided a method for extracting a material from an aqueous solution comprising contacting the aqueous solution with a solvent comprising a composition of the invention, and separating the material from the solvent.


According to another aspect of the invention, there is provided a method for extracting a material from a particulate solid matrix comprising contacting the particulate solid matrix with a solvent comprising a composition of the invention, and separating the material from the solvent.


According to a further aspect of the invention, there is provided a mechanical power generation device containing a composition of the invention.


Preferably, the mechanical power generation device is adapted to use a Rankine Cycle or modification thereof to generate work from heat.


According to another aspect of the invention, there is provided a method of retrofitting a heat transfer device comprising the step of removing an existing heat transfer fluid, and introducing a composition of the invention. Preferably, the heat transfer device is a refrigeration device or (a static) air conditioning system. Advantageously, the method further comprises the step of obtaining an allocation of greenhouse gas (e.g. carbon dioxide) emission credit.


In accordance with the retrofitting method described above, an existing heat transfer fluid can be fully removed from the heat transfer device before introducing a composition of the invention. An existing heat transfer fluid can also be partially removed from a heat transfer device, followed by introducing a composition of the invention.


In another embodiment wherein the existing heat transfer fluid is R-134a, and the composition of the invention contains R134a, R-1234ze(E), R-744, the third component and any R-125 present (and optional components such as a lubricant, a stabiliser or an additional flame retardant), R-1234ze(E) and R-744, etc, can be added to the R-134a in the heat transfer device, thereby forming the compositions of the invention, and the heat transfer device of the invention, in situ. Some of the existing R-134a may be removed from the heat transfer device prior to adding the R-1234ze(E), R-744, etc, to facilitate providing the components of the compositions of the invention in the desired proportions.


Thus, the invention provides a method for preparing a composition and/or heat transfer device of the invention comprising introducing R-1234ze(E), R-744, the third component, any R-125 desired, and optional components such as a lubricant, a stabiliser or an additional flame retardant, into a heat transfer device containing an existing heat transfer fluid which is R-134a. Optionally, at least some of the R-134a is removed from the heat transfer device before introducing the R-1234ze(E), R-744, etc.


Of course, the compositions of the invention may also be prepared simply by mixing the R-1234ze(E), R-744, the third component, any R-125 desired (and optional components such as a lubricant, a stabiliser or an additional flame retardant) in the desired proportions. The compositions can then be added to a heat transfer device (or used in any other way as defined herein) that does not contain R-134a or any other existing heat transfer fluid, such as a device from which R-134a or any other existing heat transfer fluid have been removed.


In a further aspect of the invention, there is provided a method for reducing the environmental impact arising from operation of a product comprising an existing compound or composition, the method comprising replacing at least partially the existing compound or composition with a composition of the invention. Preferably, this method comprises the step of obtaining an allocation of greenhouse gas emission credit.


By environmental impact we include the generation and emission of greenhouse warming gases through operation of the product.


As mentioned above, this environmental impact can be considered as including not only those emissions of compounds or compositions having a significant environmental impact from leakage or other losses, but also including the emission of carbon dioxide arising from the energy consumed by the device over its working life. Such environmental impact may be quantified by the measure known as Total Equivalent Warming Impact (TEWI). This measure has been used in quantification of the environmental impact of certain stationary refrigeration and air conditioning equipment, including for example supermarket refrigeration systems (see, for example, http://en.wikipedia.org/wiki/Total equivalent warming impact).


The environmental impact may further be considered as including the emissions of greenhouse gases arising from the synthesis and manufacture of the compounds or compositions. In this case the manufacturing emissions are added to the energy consumption and direct loss effects to yield the measure known as Life-Cycle Carbon Production (LCCP, see for example http://www.sae.org/events/aars/presentations/2007papasavva.pdf). The use of LCCP is common in assessing environmental impact of automotive air conditioning systems.


Emission credit(s) are awarded for reducing pollutant emissions that contribute to global warming and may, for example, be banked, traded or sold. They are conventionally expressed in the equivalent amount of carbon dioxide. Thus if the emission of 1 kg of R-134a is avoided then an emission credit of 1×1300=1300 kg CO2 equivalent may be awarded.


In another embodiment of the invention, there is provided a method for generating greenhouse gas emission credit(s) comprising (i) replacing an existing compound or composition with a composition of the invention, wherein the composition of the invention has a lower GWP than the existing compound or composition; and (ii) obtaining greenhouse gas emission credit for said replacing step.


In a preferred embodiment, the use of the composition of the invention results in the equipment having a lower Total Equivalent Warming Impact, and/or a lower Life-Cycle Carbon Production than that which would be attained by use of the existing compound or composition.


These methods may be carried out on any suitable product, for example in the fields of air-conditioning, refrigeration (e.g. low and medium temperature refrigeration), heat transfer, blowing agents, aerosols or sprayable propellants, gaseous dielectrics, cryosurgery, veterinary procedures, dental procedures, fire extinguishing, flame suppression, solvents (e.g. carriers for flavorings and fragrances), cleaners, air horns, pellet guns, topical anesthetics, and expansion applications. Preferably, the field is air-conditioning or refrigeration.


Examples of suitable products include heat transfer devices, blowing agents, foamable compositions, sprayable compositions, solvents and mechanical power generation devices. In a preferred embodiment, the product is a heat transfer device, such as a refrigeration device or an air-conditioning unit.


The existing compound or composition has an environmental impact as measured by GWP and/or TEWI and/or LCCP that is higher than the composition of the invention which replaces it. The existing compound or composition may comprise a fluorocarbon compound, such as a perfluoro-, hydrofluoro-, chlorofluoro- or hydrochlorofluoro-carbon compound or it may comprise a fluorinated olefin


Preferably, the existing compound or composition is a heat transfer compound or composition such as a refrigerant. Examples of refrigerants that may be replaced include R-134a, R-152a, R-1234yf, R-410A, R-407A, R-407B, R-407C, R507, R-22 and R-404A. The compositions of the invention are particularly suited as replacements for R-134a, R-152a or R-1234yf, especially R-134a or R-1234yf.


Any amount of the existing compound or composition may be replaced so as to reduce the environmental impact. This may depend on the environmental impact of the existing compound or composition being replaced and the environmental impact of the replacement composition of the invention. Preferably, the existing compound or composition in the product is fully replaced by the composition of the invention.


The invention is illustrated by the following non-limiting examples.


EXAMPLES
Flammability

The flammability of certain compositions of the invention in air at atmospheric pressure and controlled humidity was studied in a flame tube test as follows.


The test vessel was an upright glass cylinder having a diameter of 2 inches. The ignition electrodes were placed 60 mm above the bottom of the cylinder. The cylinder was fitted with a pressure-release opening. The apparatus was shielded to restrict any explosion damage. A standing induction spark of 0.5 second duration was used as the ignition source.


The test was performed at 23 or 35° C. (see below). A known concentration of fuel in air was introduced into the glass cylinder. A spark was passed through the mixture and it was observed whether or not a flame detached itself from the ignition source and propagated independently. The gas concentration was increased in steps of 1% vol. until ignition occurred (if at all). The results are shown below (all compositions are v/v basis unless otherwise stated).















Fuel
Temperature (° C.)
Humidity
Resultsb







R134a/R1234ze(E) 10/90
23
50%RH/23° C.
Non flammable


CO2/R134a/R1234ze 10/10/80a
23
50%RH/23° C.
Non flammable


R134a/R1234yf 10/90
35
50%RH/23° C.
LFL 6% UFL 11%


R134a/R1234ze(E) 10/90
35
50%RH/23° C.
LFL 8% UFL 12%


CO2/R134a/R1234ze 10/10/80a
35
50%RH/23° C.
LFL 10% UFL 11%c






aThis corresponds to about 4% CO2, 10% R-134a and 86% R-1234ze(E) by weight.




bLFL = lower flammable limit and UFL = upper flammable limit




cIncomplete propagation







The ternary composition 4% CO2, 10% R-134a and 86% R-1234ze(E) by weight was shown to be non-flammable at 23° C. At 35° C., it was significantly less flammable than corresponding R134a/R1234yf and R134a/R1234ze(E) mixtures.


Modelled Performance Data
Generation of Accurate Physical Property Model

The physical properties of R-1234yf and R-1234ze(E) required to model refrigeration cycle performance, namely critical point, vapour pressure, liquid and vapour enthalpy, liquid and vapour density and heat capacities of vapour and liquid were accurately determined by experimental methods over the pressure range 0-200 bar and temperature range −40 to 200° C., and the resulting data used to generate Helmholtz free energy equation of state models of the Span-Wagner type for the fluid in the NIST REFPROP Version 8.0 software, which is more fully described in the user guide www.nist.gov/srd/PDFfiles/REFPROP8.PDF, and is incorporated herein by reference. The variation of ideal gas enthalpy of both fluids with temperature was estimated using molecular modelling software Hyperchem v7.5 (which is incorporated herein by reference) and the resulting ideal gas enthalpy function was used in the regression of the equation of state for these fluids. The predictions of this model for R1234yf and R1234ze(E) were compared to the predictions yielded by use of the standard files for R1234yf and R1234ze(E) included in REFPROP Version 9.0 (incorporated herein by reference). It was found that close agreement was obtained for each fluid's properties.


The vapour liquid equilibrium behaviour of R-1234ze(E) was studied in a series of binary pairs with carbon dioxide, R-32, R-125, R-134a, R-152a, R-161, propane and propylene over the temperature range −40 to +60° C., which encompasses the practical operating range of most refrigeration and air conditioning systems. The composition was varied over the full compositional space for each binary in the experimental programme, Mixture parameters for each binary pair were regressed to the experimentally obtained data and the parameters were also incorporated into the REFPROP software model. The academic literature was next searched for data on the vapour liquid equilibrium behaviour of carbon dioxide with the hydrofluorocarbons R-32, R-125, R-152a, R-161 and R-152a. The VLE data obtained from sources referenced in the article Applications of the simple multi-fluid model to correlations of the vapour-liquid equilibrium of refrigerant mixtures containing carbon dioxide, by R. Akasaka, Journal of Thermal Science and Technology, 159-168, 4, 1, 2009 (which is incorporated herein by reference) were then used to generate mixing parameters for the relevant binary mixtures and these were then also incorporated into the REFPROP model. The standard REFPROP mixing parameters for carbon dioxide with propane and propylene were also incorporated to this model.


The resulting software model was used to compare the performance of selected fluids of the invention with R-134a in a heat pumping cycle application.


Heat Pumping Cycle Comparison

In a first comparison the behaviour of the fluids was assessed for a simple vapour compression cycle with conditions typical of automotive heat pumping duty in low winter ambient temperatures. In this comparison pressure drop effects were included in the model by assignation of a representative expected pressure drop to the reference fluid (R-134a) followed by estimation of the equivalent pressure drop for the mixed refrigerant of the invention in the same equipment at the same heating capacity. The comparison was made on the basis of equal heat exchanger area for the reference fluid (R-134a) and for the mixed fluids of the invention. The methodology used for this model was derived using the assumptions of equal effective overall heat transfer coefficient for refrigerant condensation, refrigerant evaporation, refrigerant liquid subcooling and refrigerant vapour superheating processes to derive a so-called UA model for the process. The derivation of such a model for nonazeotropic refrigerant mixtures in heat pump cycles is more fully explained in the reference text Vapor Compression Heat Pumps with refrigerant mixtures by R Radermacher & Y Hwang (pub Taylor & Francis 2005) Chapter 3, which is incorporated herein by reference.


Briefly, the model starts with an initial estimate of the condensing and evaporating pressures for the refrigerant mixture and estimates the corresponding temperatures at the beginning and end of the condensation process in the condenser and the evaporation process in the evaporator. These temperatures are then used in conjunction with the specified changes in air temperatures over condenser and evaporator to estimate a required overall heat exchanger area for each of the condenser and evaporator. This is an iterative calculation: the condensing and evaporating pressures are adjusted to ensure that the overall heat exchanger areas are the same for reference fluid and for the mixed refrigerant.


For the comparison the worst case for heat pumping in automotive application was assumed with the following assumptions for air temperature and for R-134a cycle conditions.


Cycle Conditions
















Ambient air temperature on to condenser and evaporator
−15°
C.


Air temperature leaving evaporator:
−25°
C.


Air temperature leaving condenser (passenger air)
+45°
C.


R134a evaporating temperature
−30°
C.


R-134a condensing temperature
+50°
C.








Subcooling of refrigerant in condenser
1K


Superheating of refrigerant in evaporator
5K









Compressor suction temperature

C.








Compressor isentropic efficiency
66%









Passenger air heating load
2
kW


Pressure drop in evaporator for R-134a
0.03
bar


Pressure drop in condenser for R-134a
0.03
bar


Pressure drop in suction line for R-134a
0.03
bar









The model assumed countercurrent flow for each heat exchanger in its calculation of effective temperature differences for each of the heat transfer processes.


Condensing and evaporating temperatures for compositions was adjusted to give equivalent usage of heat exchange area as reference fluid. The following input parameters were used.














Parameter

Reference







Refrigerant

R134a


Mean condenser temperature
° C.
50


Mean evaporator temperature
° C.
−30


Condenser subcooling
K
1


Evaporator superheat
K
5


Suction diameter
mm
16.2


Heating capacity
kW
2


Evaporator pressure drop
bar
0.03


Suction line pressure drop
bar
0.03


Condenser pressure drop
bar
0.03


Compressor suction temperature
° C.
0


Isentropic efficiency

  66%


Evaporator air on
° C.
−15.00


Evaporator air off
° C.
−25.00


Condenser air on
° C.
−15.00


Condenser air off
° C.
45.00


Condenser area
100.0%
100.0%


Evaporator area
100.0%
100.0%









Using the above model, the performance data for the reference R-134a is shown below.
















COP (heating)

2.11


COP (heating) relative to Reference

100.0%


Volumetric heating capacity at suction
kJ/m3
879


Capacity relative to Reference

100.0%


Critical temperature
° C.
101.06


Critical pressure
bar
40.59


Condenser enthalpy change
kJ/kg
237.1


Pressure ratio

16.36


Refrigerant mass flow
kg/hr
30.4


Compressor discharge temperature
° C.
125.5


Evaporator inlet pressure
bar
0.86


Condenser inlet pressure
bar
13.2


Evaporator inlet temperature
° C.
−29.7


Evaporator dewpoint
° C.
−30.3


Evaporator exit gas temperature
° C.
−25.3


Evaporator mean temperature
° C.
−30.0


Evaporator glide (out-in)
K
−0.6


Compressor suction pressure
bar
0.81


Compressor discharge pressure
bar
13.2


Suction line pressure drop
Pa/m
292


Pressure drop relative to reference

100.0%


Condenser dew point
° C.
50.0


Condenser bubble point
° C.
50.0


Condenser exit liquid temperature
° C.
49.0


Condenser mean temperature
° C.
50.0


Condenser slide in-out
K
0.1









The generated performance data for selected compositions of the invention is set out in the following Tables. The tables show key parameters of the heat pump cycle, including operating pressures, volumetric heating capacity, energy efficiency (expressed as coefficient of performance for heating COP) compressor discharge temperature and pressure drops in pipework. The volumetric heating capacity of a refrigerant is a measure of the amount of heating which can be obtained for a given size of compressor operating at fixed speed. The coefficient of performance (COP) is the ratio of the amount of heat energy delivered in the condenser of the heat pump cycle to the amount of work consumed by the compressor.


The performance of R-134a is taken as the reference point for comparison of heating capacity, energy efficiency and pressure drop. This fluid is used as a reference for comparison of the ability of the fluids of the invention to be used in the heat pump mode of an automotive combined air conditioning and heat pump system.


It should be noted in passing that the utility of fluids of the invention is not limited to automotive systems. Indeed these fluids can be used in so-called stationary (residential or commercial) equipment. Currently the main fluids used in such stationary equipment are R-410A (having a GWP of 2100) or R22 (having a GWP of 1800 and an ozone depletion potential of 0.05). The use of the fluids of the invention in such stationary equipment offers the ability to realise similar utility but with fluids having no ozone depletion potential and significantly reduced GWP compared to R410A.


It is evident that fluids of the invention can provide improved energy efficiency compared to R-134a or R-410A. It is unexpectedly found that the addition of carbon dioxide to the refrigerants of the invention can increase the COP of the resulting cycle above that of R-134a, even in case where admixture of the other mixture components would result in a fluid having worse energy efficiency than R-134a.


It is further found for all the fluids of the invention that compositions up to about 30% w/w of CO2 can be used which yield refrigerant fluids whose critical temperature is about 70° C. or higher. This is particularly significant for stationary heat pumping applications where R-410A is currently used. The fundamental thermodynamic efficiency of a vapour compression process is affected by proximity of the critical temperature to the condensing temperature. R-410A has gained acceptance and can be considered an acceptable fluid for this application; its critical temperature is 71° C. It has unexpectedly been found that significant quantities of CO2 (critical temperature 31° C.) can be incorporated in fluids of the invention to yield mixtures having similar or higher critical temperature to R-410A. Preferred compositions of the invention therefore have critical temperatures are about 70° C. or higher.


The heating capacity of the preferred fluids of the invention typically exceeds that of R134a. It is thought that R-134a alone, operated in an automotive a/c and heat pump system, cannot provide all of the potential passenger air heating demand in heat pump mode. Therefore higher heating capacities than R-134a are preferred for potential use in an automotive a/c and heat pump application. The fluids of the invention offer the ability to optimise fluid capacity and energy efficiency for both air conditioning and cooling modes so as to provide an improved overall energy efficiency for both duties.


For reference, the heating capacity of R-410A in the same cycle conditions was estimated at about 290% of the R-134a value and the corresponding energy efficiency was found to be about 106% of the R-134a reference value.


It is evident by inspection of the tables that fluids of the invention have been discovered having comparable heating capacities and energy efficiencies to R-410A, allowing adaption of existing R-410A technology to use the fluids of the invention if so desired.


Some further benefits of the fluids of the invention are described in more detail below.


At equivalent cooling capacity the compositions of the invention offer reduced pressure drop compared to R-134a. This reduced pressure drop characteristic is believed to result in further improvement in energy efficiency (through reduction of pressure losses) in a real system. Pressure drop effects are of particular significance for automotive air conditioning and heat pump applications so these fluids offer particular advantage for this application.


The compositions containing CO2/R-134a/R-1234ze(E) are especially attractive since they have non-flammable liquid and vapour phases at 23° C. and selected compositions are also wholly non-flammable at 60° C.


The performance of fluids of the invention were compared to binary mixtures of CO2/R1234ze(E). For all the ternary and quaternary compositions of the invention apart from CO2/R1234yf/R1234ze(E) the energy efficiency of the ternary or quaternary mixtures was increased relative to the binary mixture having equivalent CO2 content. These mixtures therefore represent an improved solution relative to the CO2/R1234ze(E) binary refrigerant mixture, at least for CO2 content less than 30% w/w.









TABLE 1







Theoretical Performance Data of Selected R-744/R-134a/R-1234ze(E) blends containing 0-14% R-744 and 5% R-134









Composition CO2/R-134a/R-1234ze(E) % by weight
















0/5/95
2/5/93
4/5/91
6/5/89
8/5/87
10/5/85
12/5/83
14/5/81




















COP (heating)

2.00
2.06
2.10
2.14
2.16
2.18
2.20
2.21


COP (heating) relative to Reference

94.8%
97.7%
99.8%
101.4%
102.7%
103.6%
104.3%
104.9%


Volumetric heating capacity at suction
kJ/m3
634
715
799
886
976
1069
1166
1265


Capacity relative to Reference

72.1%
81.3%
90.9%
100.8%
111.1%
121.7%
132.7%
143.9%


Critical temperature
° C.
109.40
105.47
101.78
98.30
95.02
91.91
88.98
86.19


Critical pressure
bar
37.08
37.84
38.60
39.36
40.12
40.88
41.64
42.39


Condenser enthalpy change
kJ/kg
211.5
224.7
235.8
245.4
253.6
261.0
267.5
273.5


Pressure ratio

18.55
18.78
18.82
18.71
18.47
18.15
17.77
17.36


Refrigerant mass flow
kg/hr
34.0
32.0
30.5
29.3
28.4
27.6
26.9
26.3


Compressor discharge temperature
° C.
113.3
117.6
121.5
125.1
128.3
131.3
134.1
136.8


Evaporator inlet pressure
bar
0.67
0.71
0.76
0.82
0.89
0.97
1.05
1.14


Condenser inlet pressure
bar
10.9
12.1
13.3
14.5
15.7
16.9
18.0
19.2


Evaporator inlet temperature
° C.
−29.0
−29.7
−30.4
−31.1
−31.9
−32.7
−33.6
−34.5


Evaporator dewpoint
° C.
−30.2
−29.6
−29.0
−28.2
−27.4
−26.6
−25.8
−25.1


Evaporator exit gas temperature
° C.
−25.2
−24.6
−24.0
−23.2
−22.4
−21.6
−20.8
−20.1


Evaporator mean temperature
° C.
−29.6
−29.7
−29.7
−29.7
−29.7
−29.7
−29.7
−29.8


Evaporator glide (out-in)
K
−1.2
0.1
1.4
2.9
4.5
6.1
7.8
9.5


Compressor suction pressure
bar
0.59
0.64
0.71
0.77
0.85
0.93
1.01
1.10


Compressor discharge pressure
bar
10.9
12.1
13.3
14.5
15.7
16.9
18.0
19.2


Suction line pressure drop
Pa/m
447
378
327
286
253
226
204
185


Pressure drop relative to reference

152.9%
129.6%
111.8%
97.9%
86.6%
77.4%
69.7%
63.2%


Condenser dew point
° C.
53.1
55.0
56.5
57.8
58.8
59.6
60.2
60.5


Condenser bubble point
° C.
52.7
47.0
42.5
39.0
36.2
34.0
32.1
30.6


Condenser exit liquid temperature
° C.
51.7
46.0
41.5
38.0
35.2
33.0
31.1
29.6


Condenser mean temperature
° C.
52.9
51.0
49.5
48.4
47.5
46.8
46.1
45.6


Condenser glide (in-out)
K
0.4
7.9
14.0
18.8
22.6
25.7
28.1
29.9
















TABLE 2







Theoretical Performance Data of Selected R-744/R-134a/R-1234ze(E) blends containing 16-30% R-744 and 5% R-134a









Composition CO2/R-134a/R-1234ze(E) % by weight
















16/5/79
18/5/77
20/5/75
22/5/73
24/5/71
26/5/69
28/5/67
30/5/65




















COP (heating)

2.22
2.23
2.24
2.24
2.24
2.24
2.24
2.24


COP (heating) relative to Reference

105.4%
105.8%
106.0%
106.2%
106.3%
106.4%
106.4%
106.3%


Volumetric heating capacity at suction
kJ/m3
1366
1469
1575
1681
1789
1897
2007
2116


Capacity relative to Reference

155.5%
167.2%
179.2%
191.3%
203.6%
215.9%
228.4%
240.8%


Critical temperature
° C.
83.54
81.03
78.63
76.35
74.17
72.09
70.10
68.20


Critical pressure
bar
43.15
43.91
44.66
45.42
46.17
46.93
47.68
48.43


Condenser enthalpy change
kJ/kg
279.0
284.2
289.1
293.7
298.2
302.6
306.8
310.9


Pressure ratio

16.93
16.51
16.09
15.68
15.29
14.92
14.57
14.24


Refrigerant mass flow
kg/hr
25.8
25.3
24.9
24.5
24.1
23.8
23.5
23.2


Compressor discharge temperature
° C.
139.3
141.7
144.0
146.3
148.6
150.8
153.0
155.2


Evaporator inlet pressure
bar
1.23
1.32
1.42
1.53
1.63
1.74
1.85
1.97


Condenser inlet pressure
bar
20.3
21.4
22.5
23.6
24.6
25.7
26.7
27.7


Evaporator inlet temperature
° C.
−35.5
−36.5
−37.5
−38.6
−39.6
−40.6
−41.7
−42.6


Evaporator dewpoint
° C.
−24.4
−23.7
−23.1
−22.6
−22.1
−21.6
−21.3
−21.0


Evaporator exit gas temperature
° C.
−19.4
−18.7
−18.1
−17.6
−17.1
−16.6
−16.3
−16.0


Evaporator mean temperature
° C.
−29.9
−30.1
−30.3
−30.6
−30.8
−31.1
−31.5
−31.8


Evaporator glide (out-in)
K
11.1
12.8
14.4
16.0
17.5
19.0
20.4
21.7


Compressor suction pressure
bar
1.20
1.30
1.40
1.50
1.61
1.72
1.83
1.95


Compressor discharge pressure
bar
20.3
21.4
22.5
23.6
24.6
25.7
26.7
27.7


Suction line pressure drop
Pa/m
168
154
142
132
122
114
107
100


Pressure drop relative to reference

57.6%
52.8%
48.7%
45.1%
41.9%
39.0%
36.5%
34.3%


Condenser dew point
° C.
60.7
60.8
60.7
60.6
60.3
59.9
59.5
59.0


Condenser bubble point
° C.
29.3
28.3
27.4
26.6
25.9
25.4
24.9
24.4


Condenser exit liquid temperature
° C.
28.3
27.3
26.4
25.6
24.9
24.4
23.9
23.4


Condenser mean temperature
° C.
45.0
44.5
44.0
43.6
43.1
42.6
42.2
41.7


Condenser glide (in-out)
K
31.4
32.5
33.4
34.0
34.3
34.6
34.6
34.6
















TABLE 3







Theoretical Performance Data of Selected R-744/R-134a/R-1234ze(E) blends containing 0-14% R-744 and 10% R-134a









Composition CO2/R-134a/R-1234ze(E) % by weight
















0/10/90
2/10/88
4/10/86
6/10/84
8/10/82
10/10/80
12/10/78
14/10/76




















COP (heating)

2.01
2.07
2.11
2.14
2.17
2.19
2.20
2.21


COP (heating) relative to Reference

95.1%
97.9%
100.0%
101.6%
102.8%
103.7%
104.4%
105.0%


Volumetric heating capacity at suction
kJ/m3
652
734
819
906
998
1092
1190
1290


Capacity relative to Reference

74.2%
83.5%
93.2%
103.2%
113.6%
124.3%
135.4%
146.8%


Critical temperature
° C.
108.91
105.03
101.37
97.92
94.66
91.58
88.67
85.90


Critical pressure
bar
37.56
38.31
39.07
39.82
40.58
41.33
42.09
42.84


Condenser enthalpy change
kJ/kg
212.7
225.6
236.6
246.0
254.2
261.4
268.0
273.9


Pressure ratio

18.37
18.57
18.61
18.49
18.24
17.93
17.55
17.15


Refrigerant mass flow
kg/hr
33.9
31.9
30.4
29.3
28.3
27.5
26.9
26.3


Compressor discharge temperature
° C.
113.9
118.1
121.9
125.5
128.7
131.7
134.5
137.1


Evaporator inlet pressure
bar
0.68
0.73
0.78
0.84
0.91
0.99
1.07
1.16


Condenser inlet pressure
bar
11.1
12.3
13.5
14.7
15.9
17.1
18.2
19.4


Evaporator inlet temperature
° C.
−29.1
−29.8
−30.5
−31.2
−31.9
−32.8
−33.6
−34.5


Evaporator dewpoint
° C.
−30.1
−29.6
−28.9
−28.2
−27.4
−26.6
−25.8
−25.1


Evaporator exit gas temperature
° C.
−25.1
−24.6
−23.9
−23.2
−22.4
−21.6
−20.8
−20.1


Evaporator mean temperature
° C.
−29.6
−29.7
−29.7
−29.7
−29.7
−29.7
−29.7
−29.8


Evaporator glide (out-in)
K
−1.0
0.2
1.6
3.0
4.6
6.2
7.8
9.4


Compressor suction pressure
bar
0.61
0.66
0.73
0.80
0.87
0.95
1.04
1.13


Compressor discharge pressure
bar
11.1
12.3
13.5
14.7
15.9
17.1
18.2
19.4


Suction line pressure drop
Pa/m
432
367
318
279
247
221
199
181


Pressure drop relative to reference

147.9%
125.8%
108.8%
95.4%
84.6%
75.7%
68.2%
61.9%


Condenser dew point
° C.
53.0
54.8
56.3
57.6
58.5
59.3
59.8
60.1


Condenser bubble point
° C.
52.4
46.9
42.5
39.1
36.3
34.1
32.3
30.8


Condenser exit liquid temperature
° C.
51.4
45.9
41.5
38.1
35.3
33.1
31.3
29.8


Condenser mean temperature
° C.
52.7
50.9
49.4
48.3
47.4
46.7
46.0
45.5


Condenser glide (in-out)
K
0.6
7.9
13.8
18.5
22.2
25.2
27.5
29.3
















TABLE 4







Theoretical Performance Data of Selected R-744/R-134a/R-1234ze(E) blends containing 16-30% R-744 and 10% R-134a









Composition CO2/R-134a/R-1234ze(E) % by weight
















16/10/74
18/10/72
20/10/70
22/10/68
24/10/66
26/10/64
28/10/62
30/10/60




















COP (heating)

2.22
2.23
2.24
2.24
2.24
2.24
2.24
2.24


COP (heating) relative to Reference

105.5%
105.8%
106.1%
106.3%
106.4%
106.4%
106.4%
106.4%


Volumetric heating capacity at suction
kJ/m3
1393
1498
1604
1712
1822
1933
2044
2156


Capacity relative to Reference

158.5%
170.4%
182.6%
194.9%
207.4%
219.9%
232.6%
245.4%


Critical temperature
° C.
83.28
80.78
78.40
76.13
73.97
71.90
69.93
68.03


Critical pressure
bar
43.59
44.35
45.10
45.85
46.61
47.36
48.11
48.86


Condenser enthalpy change
kJ/kg
279.4
284.5
289.3
293.9
298.4
302.7
306.8
310.9


Pressure ratio

16.73
16.31
15.89
15.49
15.10
14.74
14.39
14.06


Refrigerant mass flow
kg/hr
25.8
25.3
24.9
24.5
24.1
23.8
23.5
23.2


Compressor discharge temperature
° C.
139.6
142.0
144.3
146.6
148.8
151.0
153.2
155.4


Evaporator inlet pressure
bar
1.25
1.35
1.45
1.56
1.67
1.78
1.89
2.01


Condenser inlet pressure
bar
20.5
21.6
22.7
23.8
24.9
25.9
27.0
28.0


Evaporator inlet temperature
° C.
−35.5
−36.5
−37.5
−38.5
−39.5
−40.5
−41.4
−42.4


Evaporator dewpoint
° C.
−24.4
−23.7
−23.2
−22.6
−22.1
−21.7
−21.4
−21.1


Evaporator exit gas temperature
° C.
−19.4
−18.7
−18.2
−17.6
−17.1
−16.7
−16.4
−16.1


Evaporator mean temperature
° C.
−29.9
−30.1
−30.3
−30.5
−30.8
−31.1
−31.4
−31.7


Evaporator glide (out-in)
K
11.1
12.7
14.3
15.8
17.3
18.8
20.1
21.3


Compressor suction pressure
bar
1.23
1.33
1.43
1.54
1.65
1.76
1.87
1.99


Compressor discharge pressure
bar
20.5
21.6
22.7
23.8
24.9
25.9
27.0
28.0


Suction line pressure drop
Pa/m
165
151
139
129
120
112
105
98


Pressure drop relative to reference

56.5%
51.8%
47.8%
44.2%
41.1%
38.3%
35.9%
33.7%


Condenser dew point
° C.
60.3
60.4
60.3
60.1
59.8
59.5
59.0
58.5


Condenser bubble point
° C.
29.5
28.5
27.6
26.8
26.2
25.6
25.1
24.7


Condenser exit liquid temperature
° C.
28.5
27.5
26.6
25.8
25.2
24.6
24.1
23.7


Condenser mean temperature
° C.
44.9
44.4
44.0
43.5
43.0
42.6
42.1
41.6


Condenser glide (in-out)
K
30.8
31.9
32.7
33.3
33.6
33.8
33.9
33.8
















TABLE 5







Theoretical Performance Data of Selected R-744/R-134a/R-1234ze(E) blends containing 0-14% R-744 and 15% R-134a









Composition CO2/R-134a/R-1234ze(E) % by weight
















0/15/85
2/15/83
4/15/81
6/15/79
8/15/77
10/15/75
12/15/73
14/15/71




















COP (heating)

2.01
2.07
2.11
2.14
2.17
2.19
2.20
2.22


COP (heating) relative to Reference

95.5%
98.2%
100.2%
101.7%
102.9%
103.8%
104.5%
105.1%


Volumetric heating capacity at suction
kJ/m3
670
753
838
927
1020
1115
1214
1315


Capacity relative to Reference

76.3%
85.7%
95.4%
105.5%
116.0%
126.9%
138.1%
149.7%


Critical temperature
° C.
108.44
104.58
100.96
97.54
94.31
91.26
88.36
85.62


Critical pressure
bar
38.00
38.75
39.50
40.25
41.00
41.76
42.51
43.26


Condenser enthalpy change
kJ/kg
213.8
226.6
237.4
246.7
254.8
262.0
268.5
274.3


Pressure ratio

18.19
18.38
18.40
18.28
18.03
17.72
17.35
16.95


Refrigerant mass flow
kg/hr
33.7
31.8
30.3
29.2
28.3
27.5
26.8
26.2


Compressor discharge temperature
° C.
114.4
118.6
122.4
125.9
129.1
132.1
134.9
137.5


Evaporator inlet pressure
bar
0.69
0.74
0.80
0.86
0.93
1.01
1.10
1.18


Condenser inlet pressure
bar
11.3
12.5
13.7
14.9
16.1
17.3
18.4
19.6


Evaporator inlet temperature
° C.
−29.2
−29.8
−30.5
−31.2
−32.0
−32.8
−33.6
−34.5


Evaporator dewpoint
° C.
−30.1
−29.5
−28.9
−28.1
−27.4
−26.6
−25.8
−25.1


Evaporator exit gas temperature
° C.
−25.1
−24.5
−23.9
−23.1
−22.4
−21.6
−20.8
−20.1


Evaporator mean temperature
° C.
−29.6
−29.7
−29.7
−29.7
−29.7
−29.7
−29.7
−29.8


Evaporator glide (out-in)
K
−0.9
0.3
1.6
3.1
4.6
6.2
7.8
9.4


Compressor suction pressure
bar
0.62
0.68
0.74
0.81
0.89
0.97
1.06
1.15


Compressor discharge pressure
bar
11.3
12.5
13.7
14.9
16.1
17.3
18.4
19.6


Suction line pressure drop
Pa/m
419
357
310
272
241
216
195
177


Pressure drop relative to reference

143.4%
122.3%
106.0%
93.1%
82.6%
74.0%
66.8%
60.6%


Condenser dew point
° C.
52.9
54.6
56.1
57.3
58.2
58.9
59.4
59.8


Condenser bubble point
° C.
52.2
46.8
42.5
39.2
36.4
34.3
32.5
31.0


Condenser exit liquid temperature
° C.
51.2
45.8
41.5
38.2
35.4
33.3
31.5
30.0


Condenser mean temperature
° C.
52.5
50.7
49.3
48.2
47.3
46.6
46.0
45.4


Condenser glide (in-out)
K
0.8
7.8
13.6
18.1
21.8
24.7
27.0
28.8
















TABLE 6







Theoretical Performance Data of Selected R-744/R-134a/R-1234ze(E) blends containing 16-30% R-744 and 15% R-134a









Composition CO2/R-134a/R-1234ze(E) % by weight
















16/15/69
18/15/67
20/15/65
22/15/63
24/15/61
26/15/59
28/15/57
30/15/55




















COP (heating)

2.22
2.23
2.24
2.24
2.24
2.25
2.24
2.24


COP (heating) relative to Reference

105.5%
105.9%
106.1%
106.3%
106.4%
106.5%
106.5%
106.4%


Volumetric heating capacity at suction
kJ/m3
1419
1525
1633
1743
1855
1967
2081
2196


Capacity relative to Reference

161.5%
173.6%
185.9%
198.4%
211.1%
223.9%
236.8%
249.9%


Critical temperature
° C.
83.01
80.53
78.17
75.92
73.77
71.71
69.75
67.87


Critical pressure
bar
44.01
44.76
45.52
46.27
47.02
47.77
48.52
49.27


Condenser enthalpy change
kJ/kg
279.8
284.9
289.7
294.2
298.6
302.8
306.9
310.9


Pressure ratio

16.54
16.12
15.71
15.31
14.93
14.56
14.21
13.88


Refrigerant mass flow
kg/hr
25.7
25.3
24.9
24.5
24.1
23.8
23.5
23.2


Compressor discharge temperature
° C.
140.0
142.3
144.6
146.9
149.1
151.3
153.4
155.5


Evaporator inlet pressure
bar
1.28
1.38
1.48
1.59
1.70
1.81
1.93
2.05


Condenser inlet pressure
bar
20.7
21.8
22.9
24.0
25.1
26.2
27.2
28.3


Evaporator inlet temperature
° C.
−35.4
−36.4
−37.4
−38.3
−39.3
−40.3
−41.2
−42.2


Evaporator dewpoint
° C.
−24.4
−23.8
−23.2
−22.7
−22.2
−21.8
−21.4
−21.1


Evaporator exit gas temperature
° C.
−19.4
−18.8
−18.2
−17.7
−17.2
−16.8
−16.4
−16.1


Evaporator mean temperature
° C.
−29.9
−30.1
−30.3
−30.5
−30.8
−31.0
−31.3
−31.6


Evaporator glide (out-in)
K
11.0
12.6
14.2
15.7
17.1
18.5
19.8
21.0


Compressor suction pressure
bar
1.25
1.35
1.46
1.57
1.68
1.80
1.91
2.04


Compressor discharge pressure
bar
20.7
21.8
22.9
24.0
25.1
26.2
27.2
28.3


Suction line pressure drop
Pa/m
162
148
137
127
118
110
103
97


Pressure drop relative to reference

55.4%
50.8%
46.9%
43.4%
40.3%
37.6%
35.2%
33.1%


Condenser dew point
° C.
59.9
60.0
59.9
59.7
59.4
59.0
58.6
58.1


Condenser bubble point
° C.
29.7
28.7
27.8
27.1
26.4
25.9
25.4
25.0


Condenser exit liquid temperature
° C.
28.7
27.7
26.8
26.1
25.4
24.9
24.4
24.0


Condenser mean temperature
° C.
44.8
44.3
43.9
43.4
42.9
42.5
42.0
41.6


Condenser glide (in-out)
K
30.2
31.3
32.1
32.6
33.0
33.2
33.2
33.1
















TABLE 7







Theoretical Performance Data of Selected R-744/R-134a/R-1234ze(E) blends containing 0-14% R-744 and 20% R-134a









Composition CO2/R-134a/R-1234ze(E) % by weight
















0/20/80
2/20/78
4/20/76
6/20/74
8/20/72
10/20/70
12/20/68
14/20/66




















COP (heating)

2.02
2.08
2.12
2.15
2.17
2.19
2.20
2.22


COP (heating) relative to Reference

95.8%
98.4%
100.4%
101.8%
103.0%
103.9%
104.6%
105.1%


Volumetric heating capacity at suction
kJ/m3
688
771
857
947
1041
1137
1237
1339


Capacity relative to Reference

78.3%
87.7%
97.6%
107.8%
118.4%
129.4%
140.7%
152.4%


Critical temperature
° C.
107.96
104.14
100.55
97.16
93.96
90.93
88.06
85.34


Critical pressure
bar
38.40
39.15
39.90
40.65
41.40
42.15
42.91
43.66


Condenser enthalpy change
kJ/kg
215.0
227.5
238.2
247.5
255.5
262.6
269.0
274.9


Pressure ratio

18.02
18.19
18.21
18.08
17.84
17.53
17.16
16.76


Refrigerant mass flow
kg/hr
33.5
31.6
30.2
29.1
28.2
27.4
26.8
26.2


Compressor discharge temperature
° C.
114.9
119.1
122.9
126.4
129.6
132.5
135.3
137.9


Evaporator inlet pressure
bar
0.71
0.76
0.81
0.88
0.95
1.03
1.12
1.21


Condenser inlet pressure
bar
11.5
12.7
13.9
15.1
16.3
17.5
18.6
19.8


Evaporator inlet temperature
° C.
−29.2
−29.9
−30.5
−31.3
−32.0
−32.8
−33.6
−34.5


Evaporator dewpoint
° C.
−30.0
−29.5
−28.8
−28.1
−27.4
−26.6
−25.9
−25.2


Evaporator exit gas temperature
° C.
−25.0
−24.5
−23.8
−23.1
−22.4
−21.6
−20.9
−20.2


Evaporator mean temperature
° C.
−29.6
−29.7
−29.7
−29.7
−29.7
−29.7
−29.7
−29.8


Evaporator glide (out-in)
K
−0.8
0.4
1.7
3.1
4.6
6.2
7.8
9.3


Compressor suction pressure
bar
0.64
0.70
0.76
0.83
0.91
1.00
1.08
1.18


Compressor discharge pressure
bar
11.5
12.7
13.9
15.1
16.3
17.5
18.6
19.8


Suction line pressure drop
Pa/m
406
348
302
266
236
212
191
174


Pressure drop relative to reference

139.1%
119.0%
103.4%
91.0%
80.8%
72.5%
65.4%
59.4%


Condenser dew point
° C.
52.8
54.5
55.9
57.0
57.9
58.6
59.1
59.4


Condenser bubble point
° C.
52.0
46.7
42.5
39.2
36.5
34.4
32.6
31.1


Condenser exit liquid temperature
° C.
51.0
45.7
41.5
38.2
35.5
33.4
31.6
30.1


Condenser mean temperature
° C.
52.4
50.6
49.2
48.1
47.2
46.5
45.9
45.3


Condenser glide (in-out)
K
0.8
7.7
13.3
17.8
21.4
24.2
26.5
28.2
















TABLE 8







Theoretical Performance Data of Selected R-744/R-134a/R-1234ze(E) blends containing 16-30% R-744 and 20% R-134a









Composition CO2/R-134a/R-1234ze(E) % by weight
















16/20/64
18/20/62
20/20/60
22/20/58
24/20/56
26/20/54
28/20/52
30/20/50




















COP (heating)

2.23
2.23
2.24
2.24
2.25
2.25
2.25
2.25


COP (heating) relative to Reference

105.6%
105.9%
106.2%
106.4%
106.5%
106.5%
106.5%
106.5%


Volumetric heating capacity at suction
kJ/m3
1445
1552
1662
1774
1887
2002
2117
2235


Capacity relative to Reference

164.4%
176.7%
189.2%
201.9%
214.8%
227.8%
241.0%
254.3%


Critical temperature
° C.
82.75
80.29
77.94
75.70
73.57
71.53
69.57
67.70


Critical pressure
bar
44.41
45.16
45.91
46.66
47.41
48.16
48.91
49.66


Condenser enthalpy change
kJ/kg
280.3
285.3
290.1
294.6
298.9
303.1
307.1
311.1


Pressure ratio

16.36
15.94
15.54
15.14
14.76
14.40
14.05
13.72


Refrigerant mass flow
kg/hr
25.7
25.2
24.8
24.4
24.1
23.8
23.4
23.1


Compressor discharge temperature
° C.
140.3
142.7
145.0
147.2
149.4
151.5
153.7
155.7


Evaporator inlet pressure
bar
1.31
1.41
1.51
1.62
1.73
1.85
1.97
2.09


Condenser inlet pressure
bar
20.9
22.0
23.1
24.2
25.3
26.4
27.5
28.5


Evaporator inlet temperature
° C.
−35.4
−36.3
−37.3
−38.2
−39.2
−40.1
−41.0
−41.9


Evaporator dewpoint
° C.
−24.5
−23.8
−23.3
−22.7
−22.3
−21.9
−21.5
−21.2


Evaporator exit gas temperature
° C.
−19.5
−18.8
−18.3
−17.7
−17.3
−16.9
−16.5
−16.2


Evaporator mean temperature
° C.
−29.9
−30.1
−30.3
−30.5
−30.7
−31.0
−31.3
−31.6


Evaporator glide (out-in)
K
10.9
12.5
14.0
15.5
16.9
18.3
19.5
20.7


Compressor suction pressure
bar
1.28
1.38
1.49
1.60
1.71
1.83
1.95
2.08


Compressor discharge pressure
bar
20.9
22.0
23.1
24.2
25.3
26.4
27.5
28.5


Suction line pressure drop
Pa/m
159
146
134
124
116
108
101
95


Pressure drop relative to reference

54.3%
49.9%
46.0%
42.6%
39.6%
37.0%
34.6%
32.5%


Condenser dew point
° C.
59.5
59.6
59.5
59.3
59.0
58.6
58.2
57.7


Condenser bubble point
° C.
29.9
28.9
28.0
27.3
26.7
26.1
25.6
25.2


Condenser exit liquid temperature
° C.
28.9
27.9
27.0
26.3
25.7
25.1
24.6
24.2


Condenser mean temperature
° C.
44.7
44.2
43.8
43.3
42.8
42.4
41.9
41.5


Condenser glide (in-out)
K
29.6
30.7
31.5
32.0
32.3
32.5
32.5
32.4
















TABLE 9







Theoretical Performance Data of Selected R-744/R-134a/R-1234ze(E) blends containing 0-14% R-744 and 30% R-134a









Composition CO2/R-134a/R-1234ze(E) % by weight
















0/30/70
2/30/68
4/30/66
6/30/64
8/30/62
10/30/60
12/30/58
14/30/56




















COP (heating)

2.03
2.08
2.12
2.15
2.18
2.19
2.21
2.22


COP (heating) relative to Reference

96.4%
98.9%
100.7%
102.1%
103.2%
104.1%
104.7%
105.3%


Volumetric heating capacity at suction
kJ/m3
721
806
894
985
1081
1179
1281
1387


Capacity relative to Reference

82.1%
91.7%
101.7%
112.1%
123.0%
134.2%
145.8%
157.8%


Critical temperature
° C.
107.03
103.28
99.75
96.42
93.27
90.29
87.47
84.78


Critical pressure
bar
39.11
39.86
40.61
41.37
42.12
42.87
43.62
44.37


Condenser enthalpy change
kJ/kg
217.3
229.6
240.1
249.1
257.0
264.1
270.4
276.1


Pressure ratio

17.70
17.85
17.86
17.73
17.49
17.18
16.82
16.43


Refrigerant mass flow
kg/hr
33.1
31.4
30.0
28.9
28.0
27.3
26.6
26.1


Compressor discharge temperature
° C.
116.0
120.2
123.9
127.4
130.5
133.5
136.2
138.8


Evaporator inlet pressure
bar
0.74
0.79
0.85
0.91
0.99
1.07
1.16
1.25


Condenser inlet pressure
bar
11.9
13.0
14.2
15.4
16.6
17.8
19.0
20.1


Evaporator inlet temperature
° C.
−29.3
−30.0
−30.6
−31.3
−32.0
−32.8
−33.6
−34.4


Evaporator dewpoint
° C.
−30.0
−29.5
−28.8
−28.1
−27.4
−26.7
−25.9
−25.2


Evaporator exit gas temperature
° C.
−25.0
−24.5
−23.8
−23.1
−22.4
−21.7
−20.9
−20.2


Evaporator mean temperature
° C.
−29.7
−29.7
−29.7
−29.7
−29.7
−29.7
−29.8
−29.8


Evaporator glide (out-in)
K
−0.7
0.5
1.8
3.2
4.6
6.1
7.6
9.2


Compressor suction pressure
bar
0.67
0.73
0.80
0.87
0.95
1.04
1.13
1.23


Compressor discharge pressure
bar
11.9
13.0
14.2
15.4
16.6
17.8
19.0
20.1


Suction line pressure drop
Pa/m
384
330
288
254
226
203
184
167


Pressure drop relative to reference

131.6%
113.1%
98.6%
87.0%
77.5%
69.6%
62.9%
57.2%


Condenser dew point
° C.
52.5
54.1
55.4
56.5
57.3
58.0
58.4
58.7


Condenser bubble point
° C.
51.6
46.6
42.5
39.3
36.7
34.6
32.9
31.4


Condenser exit liquid temperature
° C.
50.6
45.6
41.5
38.3
35.7
33.6
31.9
30.4


Condenser mean temperature
° C.
52.1
50.3
49.0
47.9
47.0
46.3
45.6
45.1


Condenser glide (in-out)
K
0.9
7.5
12.9
17.2
20.6
23.4
25.6
27.3
















TABLE 10







Theoretical Performance Data of Selected R-744/R-134a/R-1234ze(E) blends containing 16-30% R-744 and 30% R-134a









Composition CO2/R-134a/R-1234ze(E) % by weight
















16/30/54
18/30/52
20/30/50
22/30/48
24/30/46
26/30/44
28/30/42
30/30/40




















COP (heating)

2.23
2.24
2.24
2.25
2.25
2.25
2.25
2.25


COP (heating) relative to Reference

105.7%
106.0%
106.3%
106.5%
106.6%
106.7%
106.7%
106.6%


Volumetric heating capacity at suction
kJ/m3
1494
1605
1718
1833
1949
2068
2188
2309


Capacity relative to Reference

170.1%
182.7%
195.5%
208.6%
221.9%
235.3%
249.0%
262.8%


Critical temperature
° C.
82.23
79.80
77.49
75.28
73.17
71.16
69.23
67.38


Critical pressure
bar
45.12
45.88
46.63
47.38
48.13
48.88
49.63
50.38


Condenser enthalpy change
kJ/kg
281.5
286.4
291.1
295.5
299.8
303.8
307.8
311.6


Pressure ratio

16.03
15.63
15.23
14.84
14.46
14.10
13.75
13.42


Refrigerant mass flow
kg/hr
25.6
25.1
24.7
24.4
24.0
23.7
23.4
23.1


Compressor discharge temperature
° C.
141.2
143.5
145.8
148.0
150.1
152.2
154.2
156.3


Evaporator inlet pressure
bar
1.35
1.46
1.57
1.68
1.80
1.92
2.05
2.18


Condenser inlet pressure
bar
21.3
22.4
23.5
24.6
25.7
26.8
27.9
29.0


Evaporator inlet temperature
° C.
−35.3
−36.2
−37.1
−38.0
−38.9
−39.8
−40.7
−41.5


Evaporator dewpoint
° C.
−24.6
−24.0
−23.4
−22.9
−22.4
−22.0
−21.6
−21.3


Evaporator exit gas temperature
° C.
−19.6
−19.0
−18.4
−17.9
−17.4
−17.0
−16.6
−16.3


Evaporator mean temperature
° C.
−29.9
−30.1
−30.2
−30.4
−30.7
−30.9
−31.2
−31.4


Evaporator glide (out-in)
K
10.7
12.2
13.7
15.1
16.5
17.8
19.0
20.2


Compressor suction pressure
bar
1.33
1.43
1.55
1.66
1.78
1.90
2.03
2.16


Compressor discharge pressure
bar
21.3
22.4
23.5
24.6
25.7
26.8
27.9
29.0


Suction line pressure drop
Pa/m
153
140
130
120
112
104
98
92


Pressure drop relative to reference

52.3%
48.1%
44.4%
41.1%
38.3%
35.7%
33.4%
31.4%


Condenser dew point
° C.
58.8
58.8
58.7
58.5
58.2
57.9
57.4
56.9


Condenser bubble point
° C.
30.2
29.2
28.4
27.6
27.0
26.5
26.0
25.7


Condenser exit liquid temperature
° C.
29.2
28.2
27.4
26.6
26.0
25.5
25.0
24.7


Condenser mean temperature
° C.
44.5
44.0
43.6
43.1
42.6
42.2
41.7
41.3


Condenser glide (in-out)
K
28.6
29.6
30.4
30.9
31.2
31.4
31.4
31.3
















TABLE 11







Theoretical Performance Data of Selected R-744/R-134a/R-1234ze(E) blends containing 0-14% R-744 and 40% R-134a









Composition CO2/R-134a/R-1234ze(E) % by weight
















0/40/60
2/40/58
4/40/56
6/40/54
8/40/52
10/40/50
12/40/48
14/40/46




















COP (heating)

2.04
2.09
2.13
2.16
2.18
2.20
2.21
2.22


COP (heating) relative to Reference

96.9%
99.3%
101.1%
102.4%
103.4%
104.3%
104.9%
105.4%


Volumetric heating capacity at suction
kJ/m3
752
838
928
1021
1118
1220
1323
1431


Capacity relative to Reference

85.6%
95.4%
105.6%
116.2%
127.3%
138.8%
150.6%
162.8%


Critical temperature
° C.
106.12
102.44
98.97
95.70
92.60
89.66
86.88
84.24


Critical pressure
bar
39.69
40.45
41.21
41.96
42.72
43.48
44.23
44.99


Condenser enthalpy change
kJ/kg
219.7
231.7
242.1
251.0
258.9
265.8
272.1
277.8


Pressure ratio

17.41
17.56
17.56
17.42
17.19
16.88
16.53
16.15


Refrigerant mass flow
kg/hr
32.8
31.1
29.7
28.7
27.8
27.1
26.5
25.9


Compressor discharge temperature
° C.
117.2
121.3
125.1
128.5
131.6
134.5
137.2
139.8


Evaporator inlet pressure
bar
0.76
0.81
0.88
0.95
1.02
1.11
1.20
1.30


Condenser inlet pressure
bar
12.2
13.3
14.6
15.8
17.0
18.2
19.3
20.5


Evaporator inlet temperature
° C.
−29.4
−30.0
−30.6
−31.3
−32.0
−32.7
−33.5
−34.3


Evaporator dewpoint
° C.
−30.0
−29.5
−28.9
−28.2
−27.5
−26.7
−26.0
−25.3


Evaporator exit gas temperature
° C.
−25.0
−24.5
−23.9
−23.2
−22.5
−21.7
−21.0
−20.3


Evaporator mean temperature
° C.
−29.7
−29.7
−29.8
−29.7
−29.7
−29.7
−29.8
−29.8


Evaporator glide (out-in)
K
−0.6
0.5
1.8
3.1
4.6
6.0
7.5
9.0


Compressor suction pressure
bar
0.70
0.76
0.83
0.90
0.99
1.08
1.17
1.27


Compressor discharge pressure
bar
12.2
13.3
14.6
15.8
17.0
18.2
19.3
20.5


Suction line pressure drop
Pa/m
366
315
276
244
217
196
177
161


Pressure drop relative to reference

125.2%
108.0%
94.4%
83.5%
74.5%
66.9%
60.6%
55.2%


Condenser dew point
° C.
52.2
53.7
54.9
56.0
56.8
57.4
57.8
58.1


Condenser bubble point
° C.
51.4
46.4
42.5
39.3
36.8
34.7
33.0
31.6


Condenser exit liquid temperature
° C.
50.4
45.4
41.5
38.3
35.8
33.7
32.0
30.6


Condenser mean temperature
° C.
51.8
50.1
48.7
47.7
46.8
46.1
45.4
44.8


Condenser glide (in-out)
K
0.8
7.2
12.4
16.6
20.0
22.7
24.8
26.5
















TABLE 12







Theoretical Performance Data of Selected R-744/R-134a/R-1234ze(E) blends containing 16-30% R-744 and 40% R-134a









Composition CO2/R-134a/R-1234ze(E) % by weight
















16/40/44
18/40/42
20/40/40
22/40/38
24/40/36
26/40/34
28/40/32
30/40/30




















COP (heating)

2.23
2.24
2.24
2.25
2.25
2.25
2.25
2.25


COP (heating) relative to Reference

105.9%
106.2%
106.4%
106.6%
106.7%
106.8%
106.8%
106.8%


Volumetric heating capacity at suction
kJ/m3
1541
1654
1770
1888
2008
2130
2253
2379


Capacity relative to Reference

175.4%
188.3%
201.5%
214.9%
228.5%
242.4%
256.5%
270.7%


Critical temperature
° C.
81.72
79.33
77.05
74.87
72.78
70.79
68.89
67.06


Critical pressure
bar
45.74
46.50
47.26
48.01
48.77
49.52
50.27
51.03


Condenser enthalpy change
kJ/kg
283.0
287.9
292.5
296.9
301.0
305.0
308.8
312.5


Pressure ratio

15.76
15.36
14.97
14.58
14.21
13.85
13.50
13.17


Refrigerant mass flow
kg/hr
25.4
25.0
24.6
24.3
23.9
23.6
23.3
23.0


Compressor discharge temperature
° C.
142.2
144.5
146.7
148.8
150.9
153.0
155.0
157.0


Evaporator inlet pressure
bar
1.40
1.51
1.62
1.74
1.86
1.98
2.11
2.25


Condenser inlet pressure
bar
21.6
22.8
23.9
25.0
26.1
27.2
28.3
29.4


Evaporator inlet temperature
° C.
−35.2
−36.1
−36.9
−37.8
−38.7
−39.6
−40.4
−41.2


Evaporator dewpoint
° C.
−24.7
−24.1
−23.5
−23.0
−22.5
−22.1
−21.8
−21.5


Evaporator exit gas temperature
° C.
−19.7
−19.1
−18.5
−18.0
−17.5
−17.1
−16.8
−16.5


Evaporator mean temperature
° C.
−29.9
−30.1
−30.2
−30.4
−30.6
−30.8
−31.1
−31.3


Evaporator glide (out-in)
K
10.5
12.0
13.4
14.8
16.1
17.4
18.6
19.7


Compressor suction pressure
bar
1.37
1.48
1.60
1.72
1.84
1.97
2.10
2.23


Compressor discharge pressure
bar
21.6
22.8
23.9
25.0
26.1
27.2
28.3
29.4


Suction line pressure drop
Pa/m
148
136
125
116
108
101
95
89


Pressure drop relative to reference

50.5%
46.5%
42.9%
39.8%
37.0%
34.6%
32.4%
30.4%


Condenser dew point
° C.
58.2
58.2
58.1
57.9
57.6
57.2
56.8
56.3


Condenser bubble point
° C.
30.4
29.4
28.6
27.9
27.3
26.8
26.3
26.0


Condenser exit liquid temperature
° C.
29.4
28.4
27.6
26.9
26.3
25.8
25.3
25.0


Condenser mean temperature
° C.
44.3
43.8
43.3
42.9
42.4
42.0
41.6
41.1


Condenser glide (in-out)
K
27.8
28.8
29.5
30.0
30.3
30.4
30.4
30.3
















TABLE 13







Theoretical Performance Data of Selected R-744/R-134a/R-1234ze(E) blends containing 0-14% R-744 and 50% R-134a









Composition CO2/R-134a/R-1234ze(E) % by weight
















0/50/50
2/50/48
4/50/46
6/50/44
8/50/42
10/50/40
12/50/38
14/50/36




















COP (heating)

2.05
2.10
2.14
2.17
2.19
2.20
2.22
2.23


COP (heating) relative to Reference

97.5%
99.7%
101.4%
102.7%
103.7%
104.5%
105.1%
105.6%


Volumetric heating capacity at suction
kJ/m3
780
868
959
1054
1153
1256
1362
1472


Capacity relative to Reference

88.8%
98.7%
109.1%
120.0%
131.2%
143.0%
155.0%
167.5%


Critical temperature
° C.
105.23
101.62
98.21
94.99
91.94
89.05
86.31
83.70


Critical pressure
bar
40.15
40.91
41.68
42.45
43.21
43.98
44.74
45.51


Condenser enthalpy change
kJ/kg
222.2
234.1
244.4
253.2
261.0
267.9
274.1
279.7


Pressure ratio

17.16
17.30
17.30
17.17
16.94
16.64
16.30
15.92


Refrigerant mass flow
kg/hr
32.4
30.8
29.5
28.4
27.6
26.9
26.3
25.7


Compressor discharge temperature
° C.
118.4
122.5
126.3
129.7
132.8
135.7
138.4
140.9


Evaporator inlet pressure
bar
0.78
0.84
0.90
0.97
1.05
1.14
1.23
1.33


Condenser inlet pressure
bar
12.4
13.6
14.8
16.1
17.3
18.5
19.6
20.8


Evaporator inlet temperature
° C.
−29.5
−30.1
−30.7
−31.3
−32.0
−32.7
−33.5
−34.3


Evaporator dewpoint
° C.
−30.0
−29.5
−28.9
−28.2
−27.5
−26.8
−26.1
−25.4


Evaporator exit gas temperature
° C.
−25.0
−24.5
−23.9
−23.2
−22.5
−21.8
−21.1
−20.4


Evaporator mean temperature
° C.
−29.7
−29.8
−29.8
−29.8
−29.8
−29.8
−29.8
−29.9


Evaporator glide (out-in)
K
−0.6
0.5
1.8
3.1
4.5
5.9
7.4
8.9


Compressor suction pressure
bar
0.72
0.79
0.86
0.93
1.02
1.11
1.21
1.31


Compressor discharge pressure
bar
12.4
13.6
14.8
16.1
17.3
18.5
19.6
20.8


Suction line pressure drop
Pa/m
349
302
265
235
210
189
171
156


Pressure drop relative to reference

119.7%
103.5%
90.7%
80.3%
71.8%
64.6%
58.6%
53.4%


Condenser dew point
° C.
51.8
53.2
54.5
55.5
56.3
56.9
57.3
57.5


Condenser bubble point
° C.
51.1
46.3
42.4
39.3
36.8
34.8
33.1
31.7


Condenser exit liquid temperature
° C.
50.1
45.3
41.4
38.3
35.8
33.8
32.1
30.7


Condenser mean temperature
° C.
51.5
49.8
48.5
47.4
46.5
45.8
45.2
44.6


Condenser glide (in-out)
K
0.7
6.9
12.1
16.2
19.5
22.1
24.2
25.9
















TABLE 14







Theoretical Performance Data of Selected R-744/R-134a/R-1234ze(E) blends containing 16-30% R-744 and 50% R-134a









Composition CO2/R-134a/R-1234ze(E) % by weight
















16/50/34
18/50/32
20/50/32
22/50/28
24/50/26
26/50/24
28/50/22
30/50/20




















COP (heating)

2.24
2.24
2.25
2.25
2.25
2.26
2.26
2.26


COP (heating) relative to Reference

106.1%
106.4%
106.6%
106.8%
106.9%
107.0%
107.0%
107.0%


Volumetric heating capacity at suction
kJ/m3
1585
1700
1818
1939
2061
2186
2312
2441


Capacity relative to Reference

180.3%
193.5%
206.9%
220.7%
234.6%
248.8%
263.2%
277.8%


Critical temperature
° C.
81.22
78.86
76.61
74.46
72.40
70.44
68.55
66.75


Critical pressure
bar
46.27
47.03
47.80
48.56
49.32
50.08
50.84
51.60


Condenser enthalpy change
kJ/kg
284.9
289.7
294.3
298.6
302.7
306.6
310.4
314.0


Pressure ratio

15.53
15.14
14.75
14.37
14.00
13.64
13.30
12.97


Refrigerant mass flow
kg/hr
25.3
24.9
24.5
24.1
23.8
23.5
23.2
22.9


Compressor discharge temperature
° C.
143.3
145.6
147.7
149.9
151.9
153.9
155.9
157.9


Evaporator inlet pressure
bar
1.44
1.55
1.67
1.79
1.91
2.04
2.17
2.31


Condenser inlet pressure
bar
22.0
23.1
24.3
25.4
26.5
27.6
28.7
29.8


Evaporator inlet temperature
° C.
−35.1
−36.0
−36.8
−37.7
−38.5
−39.4
−40.2
−41.0


Evaporator dewpoint
° C.
−24.8
−24.2
−23.6
−23.1
−22.6
−22.2
−21.9
−21.6


Evaporator exit gas temperature
° C.
−19.8
−19.2
−18.6
−18.1
−17.6
−17.2
−16.9
−16.6


Evaporator mean temperature
° C.
−29.9
−30.1
−30.2
−30.4
−30.6
−30.8
−31.0
−31.3


Evaporator glide (out-in)
K
10.3
11.8
13.2
14.6
15.9
17.2
18.3
19.4


Compressor suction pressure
bar
1.41
1.53
1.64
1.77
1.89
2.02
2.16
2.30


Compressor discharge pressure
bar
22.0
23.1
24.3
25.4
26.5
27.6
28.7
29.8


Suction line pressure drop
Pa/m
143
131
121
113
105
98
92
86


Pressure drop relative to reference

48.9%
45.0%
41.6%
38.6%
35.9%
33.6%
31.4%
29.5%


Condenser dew point
° C.
57.7
57.7
57.5
57.3
57.0
56.7
56.2
55.8


Condenser bubble point
° C.
30.5
29.5
28.7
28.0
27.4
26.9
26.5
26.2


Condenser exit liquid temperature
° C.
29.5
28.5
27.7
27.0
26.4
25.9
25.5
25.2


Condenser mean temperature
° C.
44.1
43.6
43.1
42.7
42.2
41.8
41.4
41.0


Condenser glide (in-out)
K
27.1
28.1
28.8
29.3
29.6
29.7
29.7
29.6
















TABLE 15







Theoretical Performance Data of Selected R-744/R-32/R-1234ze(E) blends containing 0-14% R-744 and 5% R-32









Composition CO2/R-32/R-1234ze(E) % by weight
















0/5/95
2/5/93
4/5/91
6/5/89
8/5/87
10/5/85
12/5/83
14/5/81




















COP (heating)

2.07
2.11
2.15
2.17
2.19
2.21
2.22
2.23


COP (heating) relative to Reference

98.0%
100.2%
101.8%
103.1%
104.0%
104.8%
105.4%
105.9%


Volumetric heating capacity at suction
kJ/m3
729
813
900
990
1083
1179
1278
1379


Capacity relative to Reference

83.0%
92.5%
102.4%
112.7%
123.3%
134.2%
145.4%
156.9%


Critical temperature
° C.
106.60
103.13
99.78
96.58
93.54
90.65
87.91
85.29


Critical pressure
bar
39.06
39.91
40.71
41.47
42.23
42.98
43.73
44.48


Condenser enthalpy change
kJ/kg
226.5
237.7
247.3
255.7
263.2
269.9
276.1
281.7


Pressure ratio

17.96
17.98
17.89
17.68
17.40
17.07
16.71
16.33


Refrigerant mass flow
kg/hr
31.8
30.3
29.1
28.2
27.4
26.7
26.1
25.6


Compressor discharge temperature
° C.
118.1
121.9
125.4
128.6
131.6
134.4
137.1
139.6


Evaporator inlet pressure
bar
0.73
0.78
0.84
0.91
0.99
1.07
1.15
1.25


Condenser inlet pressure
bar
12.0
13.1
14.2
15.4
16.5
17.7
18.8
19.9


Evaporator inlet temperature
° C.
−29.9
−30.5
−31.3
−32.1
−32.9
−33.7
−34.6
−35.6


Evaporator dewpoint
° C.
−29.4
−28.8
−28.1
−27.3
−26.5
−25.8
−25.1
−24.4


Evaporator exit gas temperature
° C.
−24.4
−23.8
−23.1
−22.3
−21.5
−20.8
−20.1
−19.4


Evaporator mean temperature
° C.
−29.6
−29.7
−29.7
−29.7
−29.7
−29.8
−29.9
−30.0


Evaporator glide (out-in)
K
0.4
1.8
3.2
4.8
6.3
8.0
9.6
11.2


Compressor suction pressure
bar
0.67
0.73
0.80
0.87
0.95
1.03
1.12
1.22


Compressor discharge pressure
bar
12.0
13.1
14.2
15.4
16.5
17.7
18.8
19.9


Suction line pressure drop
Pa/m
368
319
280
248
222
200
181
166


Pressure drop relative to reference

126.2%
109.2%
95.8%
84.9%
75.9%
68.4%
62.1%
56.7%


Condenser dew point
° C.
53.8
55.3
56.6
57.6
58.3
58.9
59.3
59.5


Condenser bubble point
° C.
48.6
44.2
40.6
37.8
35.4
33.5
31.9
30.5


Condenser exit liquid temperature
° C.
47.6
43.2
39.6
36.8
34.4
32.5
30.9
29.5


Condenser mean temperature
° C.
51.2
49.7
48.6
47.7
46.9
46.2
45.6
45.0


Condenser glide (in-out)
K
5.2
11.1
15.9
19.8
22.9
25.4
27.4
29.0
















TABLE 16







Theoretical Performance Data of Selected R-744/R-32/R-1234ze(E) blends containing 16-30% R-744 and 5% R-32









Composition CO2/R-32/R-1234ze(E) % by weight
















16/5/79
18/5/77
20/5/75
22/5/73
24/5/71
26/5/69
28/5/67
30/5/65




















COP (heating)

2.24
2.25
2.25
2.25
2.25
2.25
2.25
2.25


COP (heating) relative to Reference

106.3%
106.6%
106.8%
106.9%
106.9%
106.9%
106.9%
106.8%


Volumetric heating capacity at suction
kJ/m3
1482
1586
1692
1799
1907
2015
2125
2236


Capacity relative to Reference

168.6%
180.5%
192.5%
204.7%
217.0%
229.4%
241.8%
254.4%


Critical temperature
° C.
82.80
80.43
78.16
75.99
73.92
71.94
70.04
68.22


Critical pressure
bar
45.22
45.96
46.71
47.45
48.19
48.93
49.66
50.40


Condenser enthalpy change
kJ/kg
287.1
292.1
296.9
301.5
306.0
310.3
314.5
318.6


Pressure ratio

15.95
15.57
15.21
14.86
14.52
14.20
13.89
13.59


Refrigerant mass flow
kg/hr
25.1
24.6
24.2
23.9
23.5
23.2
22.9
22.6


Compressor discharge temperature
° C.
142.1
144.5
146.8
149.1
151.3
153.6
155.8
158.0


Evaporator inlet pressure
bar
1.34
1.44
1.54
1.65
1.75
1.86
1.98
2.09


Condenser inlet pressure
bar
21.0
22.0
23.1
24.2
25.2
26.2
27.2
28.2


Evaporator inlet temperature
° C.
−36.5
−37.5
−38.5
−39.5
−40.4
−41.4
−42.3
−43.1


Evaporator dewpoint
° C.
−23.7
−23.2
−22.6
−22.2
−21.8
−21.4
−21.1
−20.9


Evaporator exit gas temperature
° C.
−18.7
−18.2
−17.6
−17.2
−16.8
−16.4
−16.1
−15.9


Evaporator mean temperature
° C.
−30.1
−30.3
−30.6
−30.8
−31.1
−31.4
−31.7
−32.0


Evaporator glide (out-in)
K
12.8
14.4
15.9
17.3
18.7
20.0
21.1
22.2


Compressor suction pressure
bar
1.31
1.42
1.52
1.63
1.73
1.85
1.96
2.08


Compressor discharge pressure
bar
21.0
22.0
23.1
24.2
25.2
26.2
27.2
28.2


Suction line pressure drop
Pa/m
152
140
130
121
113
105
99
93


Pressure drop relative to reference

52.0%
48.0%
44.4%
41.3%
38.5%
36.1%
33.9%
31.9%


Condenser dew point
° C.
59.6
59.6
59.5
59.3
59.0
58.6
58.1
57.6


Condenser bubble point
° C.
29.4
28.4
27.6
26.9
26.3
25.7
25.3
24.9


Condenser exit liquid temperature
° C.
28.4
27.4
26.6
25.9
25.3
24.7
24.3
23.9


Condenser mean temperature
° C.
44.5
44.0
43.5
43.1
42.6
42.1
41.7
41.2


Condenser glide (in-out)
K
30.2
31.2
31.9
32.4
32.7
32.8
32.9
32.8
















TABLE 17







Theoretical Performance Data of Selected R-744/R-32/R-1234ze(E) blends containing 0-14% R-744 and 10% R-32









Composition CO2/R-32/R-1234ze(E) % by weight
















0/10/90
2/10/88
4/10/86
6/10/84
8/10/82
10/10/80
12/10/78
14/10/76




















COP (heating)

2.12
2.16
2.18
2.20
2.22
2.23
2.24
2.25


COP (heating) relative to Reference

100.6%
102.3%
103.5%
104.5%
105.3%
106.0%
106.4%
106.8%


Volumetric heating capacity at suction
kJ/m3
847
934
1024
1118
1215
1314
1415
1518


Capacity relative to Reference

96.3%
106.3%
116.6%
127.3%
138.2%
149.5%
161.0%
172.8%


Critical temperature
° C.
103.66
100.50
97.45
94.53
91.74
89.08
86.53
84.10


Critical pressure
bar
41.28
42.13
42.93
43.70
44.47
45.22
45.97
46.71


Condenser enthalpy change
kJ/kg
240.3
249.9
258.3
265.9
272.8
279.1
284.9
290.4


Pressure ratio

17.03
16.94
16.77
16.52
16.25
15.93
15.61
15.27


Refrigerant mass flow
kg/hr
30.0
28.8
27.9
27.1
26.4
25.8
25.3
24.8


Compressor discharge temperature
° C.
122.7
126.1
129.3
132.3
135.2
137.8
140.4
142.9


Evaporator inlet pressure
bar
0.82
0.88
0.95
1.03
1.11
1.20
1.29
1.38


Condenser inlet pressure
bar
13.1
14.2
15.3
16.4
17.5
18.6
19.7
20.8


Evaporator inlet temperature
° C.
−30.7
−31.4
−32.2
−33.0
−33.8
−34.7
−35.5
−36.4


Evaporator dewpoint
° C.
−28.6
−27.9
−27.2
−26.5
−25.8
−25.1
−24.5
−23.9


Evaporator exit gas temperature
° C.
−23.6
−22.9
−22.2
−21.5
−20.8
−20.1
−19.5
−18.9


Evaporator mean temperature
° C.
−29.7
−29.7
−29.7
−29.7
−29.8
−29.9
−30.0
−30.2


Evaporator glide (out-in)
K
2.1
3.5
5.0
6.5
8.0
9.6
11.1
12.5


Compressor suction pressure
bar
0.77
0.84
0.91
0.99
1.08
1.17
1.26
1.36


Compressor discharge pressure
bar
13.1
14.2
15.3
16.4
17.5
18.6
19.7
20.8


Suction line pressure drop
Pa/m
304
267
238
213
193
175
160
147


Pressure drop relative to reference

104.0%
91.6%
81.4%
73.0%
65.9%
59.9%
54.8%
50.3%


Condenser dew point
° C.
53.9
55.0
56.0
56.8
57.3
57.7
58.0
58.1


Condenser bubble point
° C.
45.9
42.3
39.4
37.0
35.1
33.4
32.0
30.8


Condenser exit liquid temperature
° C.
44.9
41.3
38.4
36.0
34.1
32.4
31.0
29.8


Condenser mean temperature
° C.
49.9
48.7
47.7
46.9
46.2
45.6
45.0
44.4


Condenser glide (in-out)
K
8.0
12.7
16.6
19.7
22.3
24.3
26.0
27.3
















TABLE 18







Theoretical Performance Data of Selected R-744/R-32/R-1234ze(E) blends containing 16-30% R-744 and 10% R-32









Composition CO2/R-32/R-1234ze(E) % by weight
















16/10/74
18/10/72
20/10/70
22/10/68
24/10/66
26/10/64
28/10/62
30/10/60




















COP (heating)

2.26
2.26
2.27
2.27
2.27
2.27
2.26
2.26


COP (heating) relative to Reference

107.1%
107.3%
107.4%
107.5%
107.5%
107.5%
107.4%
107.3%


Volumetric heating capacity at suction
kJ/m3
1623
1730
1838
1947
2057
2169
2283
2397


Capacity relative to Reference

184.7%
196.9%
209.1%
221.6%
234.1%
246.8%
259.8%
272.8%


Critical temperature
° C.
81.78
79.56
77.44
75.40
73.45
71.58
69.78
68.05


Critical pressure
bar
47.46
48.20
48.93
49.67
50.41
51.14
51.88
52.61


Condenser enthalpy change
kJ/kg
295.5
300.4
305.1
309.6
314.0
318.2
322.3
326.2


Pressure ratio

14.94
14.62
14.30
13.99
13.69
13.40
13.12
12.85


Refrigerant mass flow
kg/hr
24.4
24.0
23.6
23.3
22.9
22.6
22.3
22.1


Compressor discharge temperature
° C.
145.3
147.6
149.9
152.1
154.4
156.6
158.7
160.8


Evaporator inlet pressure
bar
1.48
1.59
1.69
1.80
1.91
2.03
2.15
2.27


Condenser inlet pressure
bar
21.8
22.9
23.9
24.9
26.0
27.0
28.0
29.0


Evaporator inlet temperature
° C.
−37.3
−38.2
−39.1
−39.9
−40.8
−41.5
−42.3
−43.0


Evaporator dewpoint
° C.
−23.3
−22.9
−22.4
−22.0
−21.7
−21.4
−21.1
−20.9


Evaporator exit gas temperature
° C.
−18.3
−17.9
−17.4
−17.0
−16.7
−16.4
−16.1
−15.9


Evaporator mean temperature
° C.
−30.3
−30.5
−30.7
−31.0
−31.2
−31.5
−31.7
−31.9


Evaporator glide (out-in)
K
14.0
15.4
16.7
17.9
19.1
20.1
21.1
22.0


Compressor suction pressure
bar
1.46
1.56
1.67
1.78
1.90
2.01
2.13
2.26


Compressor discharge pressure
bar
21.8
22.9
23.9
24.9
26.0
27.0
28.0
29.0


Suction line pressure drop
Pa/m
136
126
117
109
102
96
90
85


Pressure drop relative to reference

46.4%
43.1%
40.1%
37.4%
35.0%
32.9%
31.0%
29.2%


Condenser dew point
° C.
58.1
58.0
57.8
57.6
57.2
56.8
56.3
55.8


Condenser bubble point
° C.
29.7
28.9
28.1
27.4
26.9
26.4
25.9
25.6


Condenser exit liquid temperature
° C.
28.7
27.9
27.1
26.4
25.9
25.4
24.9
24.6


Condenser mean temperature
° C.
43.9
43.4
43.0
42.5
42.0
41.6
41.1
40.7


Condenser glide (in-out)
K
28.4
29.1
29.7
30.1
30.3
30.4
30.4
30.3
















TABLE 19







Theoretical Performance Data of Selected R-744/R-32/R-1234ze(E) blends containing 0-14% R-744 and 15% R-32









Composition CO2/R-32/R-1234ze(E) % by weight
















0/15/85
2/15/83
4/15/81
6/15/79
8/15/77
10/15/75
12/15/73
14/15/71




















COP (heating)

2.17
2.19
2.21
2.23
2.24
2.25
2.26
2.27


COP (heating) relative to Reference

102.7%
104.0%
105.0%
105.8%
106.4%
106.9%
107.3%
107.6%


Volumetric heating capacity at suction
kJ/m3
965
1056
1150
1247
1346
1447
1551
1656


Capacity relative to Reference

109.9%
120.2%
130.9%
141.9%
153.2%
164.7%
176.5%
188.5%


Critical temperature
° C.
101.02
98.12
95.32
92.63
90.05
87.59
85.23
82.97


Critical pressure
bar
43.26
44.09
44.90
45.68
46.45
47.21
47.96
48.71


Condenser enthalpy change
kJ/kg
252.5
261.1
268.8
275.8
282.2
288.2
293.8
299.1


Pressure ratio

16.11
15.97
15.76
15.52
15.25
14.97
14.68
14.38


Refrigerant mass flow
kg/hr
28.5
27.6
26.8
26.1
25.5
25.0
24.5
24.1


Compressor discharge temperature
° C.
126.9
130.1
133.1
135.9
138.6
141.2
143.7
146.2


Evaporator inlet pressure
bar
0.92
0.99
1.07
1.15
1.24
1.33
1.42
1.52


Condenser inlet pressure
bar
14.1
15.2
16.3
17.3
18.4
19.5
20.5
21.6


Evaporator inlet temperature
° C.
−31.6
−32.3
−33.0
−33.8
−34.6
−35.4
−36.2
−37.0


Evaporator dewpoint
° C.
−27.9
−27.2
−26.5
−25.9
−25.2
−24.6
−24.1
−23.6


Evaporator exit gas temperature
° C.
−22.9
−22.2
−21.5
−20.9
−20.2
−19.6
−19.1
−18.6


Evaporator mean temperature
° C.
−29.7
−29.7
−29.8
−29.8
−29.9
−30.0
−30.2
−30.3


Evaporator glide (out-in)
K
3.7
5.1
6.5
7.9
9.4
10.7
12.1
13.4


Compressor suction pressure
bar
0.88
0.95
1.03
1.12
1.21
1.30
1.40
1.50


Compressor discharge pressure
bar
14.1
15.2
16.3
17.3
18.4
19.5
20.5
21.6


Suction line pressure drop
Pa/m
257
229
206
186
169
155
143
132


Pressure drop relative to reference

87.9%
78.4%
70.4%
63.7%
58.0%
53.1%
48.8%
45.1%


Condenser dew point
° C.
53.6
54.5
55.2
55.8
56.2
56.5
56.6
56.6


Condenser bubble point
° C.
44.1
41.1
38.7
36.6
34.9
33.4
32.1
31.1


Condenser exit liquid temperature
° C.
43.1
40.1
37.7
35.6
33.9
32.4
31.1
30.1


Condenser mean temperature
° C.
48.8
47.8
47.0
46.2
45.5
44.9
44.4
43.9


Condenser glide (in-out)
K
9.5
13.4
16.5
19.1
21.3
23.0
24.5
25.6
















TABLE 20







Theoretical Performance Data of Selected R-744/R-32/R-1234ze(E) blends containing 16-30% R-744 and 15% R-32









Composition CO2/R-32/R-1234ze(E) % by weight
















16/15/69
18/15/67
20/15/65
22/15/63
24/15/61
26/15/59
28/15/57
30/15/55




















COP (heating)

2.27
2.28
2.28
2.28
2.28
2.28
2.28
2.27


COP (heating) relative to Reference

107.8%
107.9%
108.0%
108.1%
108.0%
108.0%
107.9%
107.8%


Volumetric heating capacity at suction
kJ/m3
1763
1872
1983
2095
2209
2324
2442
2562


Capacity relative to Reference

200.7%
213.1%
225.6%
238.4%
251.4%
264.5%
277.9%
291.5%


Critical temperature
° C.
80.80
78.72
76.73
74.82
72.98
71.21
69.51
67.88


Critical pressure
bar
49.46
50.20
50.94
51.68
52.42
53.16
53.90
54.63


Condenser enthalpy change
kJ/kg
304.1
308.9
313.4
317.8
322.0
326.1
330.0
333.8


Pressure ratio

14.09
13.80
13.52
13.23
12.96
12.70
12.44
12.19


Refrigerant mass flow
kg/hr
23.7
23.3
23.0
22.7
22.4
22.1
21.8
21.6


Compressor discharge temperature
° C.
148.5
150.8
153.1
155.2
157.4
159.5
161.6
163.6


Evaporator inlet pressure
bar
1.63
1.73
1.84
1.96
2.08
2.20
2.32
2.45


Condenser inlet pressure
bar
22.6
23.6
24.7
25.7
26.7
27.7
28.7
29.7


Evaporator inlet temperature
° C.
−37.8
−38.6
−39.3
−40.1
−40.7
−41.4
−42.0
−42.5


Evaporator dewpoint
° C.
−23.1
−22.7
−22.3
−22.0
−21.7
−21.5
−21.3
−21.1


Evaporator exit gas temperature
° C.
−18.1
−17.7
−17.3
−17.0
−16.7
−16.5
−16.3
−16.1


Evaporator mean temperature
° C.
−30.5
−30.6
−30.8
−31.0
−31.2
−31.4
−31.6
−31.8


Evaporator glide (out-in)
K
14.7
15.9
17.0
18.0
19.0
19.9
20.7
21.4


Compressor suction pressure
bar
1.61
1.71
1.83
1.94
2.06
2.18
2.31
2.44


Compressor discharge pressure
bar
22.6
23.6
24.7
25.7
26.7
27.7
28.7
29.7


Suction line pressure drop
Pa/m
122
114
106
100
93
88
83
78


Pressure drop relative to reference

41.9%
39.0%
36.4%
34.1%
32.0%
30.1%
28.4%
26.9%


Condenser dew point
° C.
56.6
56.4
56.2
55.9
55.5
55.1
54.6
54.1


Condenser bubble point
° C.
30.1
29.3
28.6
28.0
27.5
27.0
26.6
26.3


Condenser exit liquid temperature
° C.
29.1
28.3
27.6
27.0
26.5
26.0
25.6
25.3


Condenser mean temperature
° C.
43.4
42.9
42.4
41.9
41.5
41.1
40.6
40.2


Condenser glide (in-out)
K
26.5
27.1
27.6
27.9
28.1
28.1
28.0
27.9
















TABLE 21







Theoretical Performance Data of Selected R-744/R-32/R-1234ze(E) blends containing 0-14% R-744 and 20% R-32









Composition CO2/R-32/R-1234ze(E) % by weight
















0/20/80
2/20/78
4/20/76
6/20/74
8/20/72
10/20/70
12/20/68
14/20/66




















COP (heating)

2.20
2.22
2.24
2.25
2.26
2.27
2.28
2.28


COP (heating) relative to Reference

104.4%
105.4%
106.2%
106.8%
107.3%
107.7%
108.0%
108.2%


Volumetric heating capacity at suction
kJ/m3
1085
1179
1275
1375
1476
1580
1685
1793


Capacity relative to Reference

123.5%
134.1%
145.1%
156.4%
168.0%
179.8%
191.8%
204.1%


Critical temperature
° C.
98.64
95.95
93.36
90.88
88.49
86.20
84.00
81.89


Critical pressure
bar
45.03
45.86
46.66
47.44
48.22
48.98
49.75
50.50


Condenser enthalpy change
kJ/kg
263.9
271.7
278.9
285.5
291.6
297.4
302.8
307.9


Pressure ratio

15.25
15.09
14.88
14.65
14.40
14.15
13.88
13.62


Refrigerant mass flow
kg/hr
27.3
26.5
25.8
25.2
24.7
24.2
23.8
23.4


Compressor discharge temperature
° C.
130.9
134.0
136.8
139.6
142.2
144.7
147.1
149.5


Evaporator inlet pressure
bar
1.03
1.10
1.18
1.27
1.36
1.46
1.56
1.66


Condenser inlet pressure
bar
15.1
16.1
17.2
18.2
19.3
20.3
21.3
22.4


Evaporator inlet temperature
° C.
−32.3
−33.0
−33.7
−34.4
−35.2
−35.9
−36.6
−37.3


Evaporator dewpoint
° C.
−27.2
−26.6
−26.0
−25.4
−24.9
−24.4
−23.9
−23.5


Evaporator exit gas temperature
° C.
−22.2
−21.6
−21.0
−20.4
−19.9
−19.4
−18.9
−18.5


Evaporator mean temperature
° C.
−29.8
−29.8
−29.9
−29.9
−30.0
−30.1
−30.3
−30.4


Evaporator glide (out-in)
K
5.1
6.4
7.7
9.0
10.3
11.5
12.7
13.9


Compressor suction pressure
bar
0.99
1.07
1.15
1.24
1.34
1.43
1.54
1.64


Compressor discharge pressure
bar
15.1
16.1
17.2
18.2
19.3
20.3
21.3
22.4


Suction line pressure drop
Pa/m
221
199
180
164
151
139
128
119


Pressure drop relative to reference

75.6%
68.1%
61.7%
56.3%
51.6%
47.5%
43.9%
40.8%


Condenser dew point
° C.
53.0
53.7
54.3
54.7
55.0
55.2
55.2
55.2


Condenser bubble point
° C.
42.9
40.3
38.2
36.4
34.8
33.5
32.4
31.4


Condenser exit liquid temperature
° C.
41.9
39.3
37.2
35.4
33.8
32.5
31.4
30.4


Condenser mean temperature
° C.
47.9
47.0
46.2
45.5
44.9
44.3
43.8
43.3


Condenser glide (in-out)
K
10.2
13.4
16.1
18.3
20.1
21.6
22.9
23.8
















TABLE 22







Theoretical Performance Data of Selected R-744/R-32/R-1234ze(E) blends containing 16-30% R-744 and 20% R-32









Composition CO2/R-32/R-1234ze(E) % by weight
















16/20/64
18/20/62
20/20/60
22/20/58
24/20/56
26/20/54
28/20/52
30/20/50




















COP (heating)

2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.28


COP (heating) relative to Reference

108.4%
108.5%
108.5%
108.6%
108.5%
108.5%
108.4%
108.3%


Volumetric heating capacity at suction
kJ/m3
1903
2014
2127
2243
2360
2481
2603
2729


Capacity relative to Reference

216.5%
229.2%
242.1%
255.2%
268.6%
282.3%
296.3%
310.6%


Critical temperature
° C.
79.87
77.92
76.05
74.25
72.52
70.86
69.25
67.70


Critical pressure
bar
51.26
52.01
52.76
53.51
54.25
55.00
55.75
56.49


Condenser enthalpy change
kJ/kg
312.7
317.4
321.8
326.1
330.1
334.0
337.8
341.3


Pressure ratio

13.36
13.09
12.84
12.58
12.33
12.08
11.84
11.60


Refrigerant mass flow
kg/hr
23.0
22.7
22.4
22.1
21.8
21.6
21.3
21.1


Compressor discharge temperature
° C.
151.8
154.0
156.2
158.4
160.4
162.5
164.5
166.4


Evaporator inlet pressure
bar
1.77
1.88
2.00
2.12
2.24
2.37
2.50
2.64


Condenser inlet pressure
bar
23.4
24.4
25.4
26.4
27.4
28.4
29.5
30.5


Evaporator inlet temperature
° C.
−38.0
−38.7
−39.3
−39.9
−40.5
−41.0
−41.4
−41.8


Evaporator dewpoint
° C.
−23.1
−22.7
−22.4
−22.1
−21.9
−21.7
−21.5
−21.3


Evaporator exit gas temperature
° C.
−18.1
−17.7
−17.4
−17.1
−16.9
−16.7
−16.5
−16.3


Evaporator mean temperature
° C.
−30.5
−30.7
−30.9
−31.0
−31.2
−31.3
−31.5
−31.6


Evaporator glide (out-in)
K
14.9
16.0
16.9
17.8
18.6
19.3
19.9
20.5


Compressor suction pressure
bar
1.75
1.86
1.98
2.10
2.23
2.35
2.49
2.63


Compressor discharge pressure
bar
23.4
24.4
25.4
26.4
27.4
28.4
29.5
30.5


Suction line pressure drop
Pa/m
111
104
97
91
86
81
77
72


Pressure drop relative to reference

38.0%
35.5%
33.2%
31.2%
29.4%
27.7%
26.2%
24.8%


Condenser dew point
° C.
55.1
54.9
54.6
54.3
53.9
53.5
53.0
52.5


Condenser bubble point
° C.
30.5
29.8
29.1
28.5
28.0
27.6
27.3
27.0


Condenser exit liquid temperature
° C.
29.5
28.8
28.1
27.5
27.0
26.6
26.3
26.0


Condenser mean temperature
° C.
42.8
42.3
41.9
41.4
41.0
40.6
40.2
39.8


Condenser glide (in-out)
K
24.6
25.1
25.5
25.8
25.9
25.9
25.8
25.6
















TABLE 23







Theoretical Performance Data of Selected R-744/R-32/R-1234ze(E) blends containing 0-14% R-744 and 25% R-32









Composition CO2/R-32/R-1234ze(E) % by weight
















0/25/75
2/25/73
4/25/71
6/25/69
8/25/67
10/25/65
12/25/63
14/25/61




















COP (heating)

2.23
2.25
2.26
2.27
2.28
2.29
2.29
2.29


COP (heating) relative to Reference

105.7%
106.5%
107.2%
107.7%
108.1%
108.4%
108.6%
108.8%


Volumetric heating capacity at suction
kJ/m3
1205
1301
1399
1500
1604
1710
1818
1928


Capacity relative to Reference

137.1%
148.0%
159.2%
170.8%
182.5%
194.6%
206.9%
219.4%


Critical temperature
° C.
96.47
93.97
91.57
89.26
87.04
84.91
82.86
80.89


Critical pressure
bar
46.62
47.44
48.24
49.03
49.81
50.59
51.36
52.13


Condenser enthalpy change
kJ/kg
274.8
282.1
288.9
295.2
301.1
306.6
311.8
316.8


Pressure ratio

14.48
14.31
14.12
13.91
13.68
13.45
13.21
12.96


Refrigerant mass flow
kg/hr
26.2
25.5
24.9
24.4
23.9
23.5
23.1
22.7


Compressor discharge temperature
° C.
134.9
137.8
140.5
143.2
145.7
148.2
150.6
152.9


Evaporator inlet pressure
bar
1.14
1.22
1.30
1.39
1.49
1.59
1.69
1.80


Condenser inlet pressure
bar
16.0
17.0
18.0
19.0
20.1
21.1
22.1
23.1


Evaporator inlet temperature
° C.
−32.9
−33.6
−34.2
−34.9
−35.5
−36.2
−36.8
−37.4


Evaporator dewpoint
° C.
−26.8
−26.2
−25.7
−25.2
−24.7
−24.3
−23.9
−23.5


Evaporator exit gas temperature
° C.
−21.8
−21.2
−20.7
−20.2
−19.7
−19.3
−18.9
−18.5


Evaporator mean temperature
° C.
−29.8
−29.9
−30.0
−30.0
−30.1
−30.2
−30.3
−30.4


Evaporator glide (out-in)
K
6.1
7.3
8.5
9.7
10.8
11.9
12.9
13.9


Compressor suction pressure
bar
1.10
1.19
1.28
1.37
1.47
1.57
1.67
1.78


Compressor discharge pressure
bar
16.0
17.0
18.0
19.0
20.1
21.1
22.1
23.1


Suction line pressure drop
Pa/m
193
175
160
147
135
125
116
108


Pressure drop relative to reference

66.1%
60.0%
54.8%
50.3%
46.4%
42.9%
39.8%
37.1%


Condenser dew point
° C.
52.3
52.8
53.2
53.5
53.7
53.8
53.8
53.8


Condenser bubble point
° C.
42.0
39.8
37.9
36.3
34.9
33.7
32.6
31.7


Condenser exit liquid temperature
° C.
41.0
38.8
36.9
35.3
33.9
32.7
31.6
30.7


Condenser mean temperature
° C.
47.2
46.3
45.6
44.9
44.3
43.8
43.2
42.7


Condenser glide (in-out)
K
10.3
13.0
15.3
17.3
18.9
20.2
21.2
22.1
















TABLE 24







Theoretical Performance Data of Selected R-744/R-32/R-1234ze(E) blends containing 16-30% R-744 and 25% R-32









Composition CO2/R-32/R-1234ze(E) % by weight
















16/25/59
18/25/57
20/25/55
22/25/53
24/25/51
26/25/49
28/25/47
30/25/45




















COP (heating)

2.30
2.30
2.30
2.30
2.30
2.30
2.30
2.29


COP (heating) relative to Reference

108.9%
109.0%
109.0%
109.0%
109.0%
108.9%
108.9%
108.8%


Volumetric heating capacity at suction
kJ/m3
2040
2155
2272
2391
2513
2638
2766
2898


Capacity relative to Reference

232.2%
245.2%
258.5%
272.1%
286.0%
300.3%
314.8%
329.8%


Critical temperature
° C.
78.99
77.17
75.41
73.72
72.08
70.51
68.99
67.53


Critical pressure
bar
52.89
53.65
54.41
55.17
55.93
56.69
57.45
58.20


Condenser enthalpy change
kJ/kg
321.5
326.0
330.3
334.4
338.3
342.0
345.5
348.9


Pressure ratio

12.72
12.48
12.24
12.00
11.76
11.53
11.29
11.06


Refrigerant mass flow
kg/hr
22.4
22.1
21.8
21.5
21.3
21.1
20.8
20.6


Compressor discharge temperature
° C.
155.1
157.3
159.4
161.5
163.5
165.4
167.3
169.1


Evaporator inlet pressure
bar
1.91
2.03
2.15
2.28
2.41
2.54
2.68
2.83


Condenser inlet pressure
bar
24.1
25.1
26.1
27.1
28.1
29.1
30.2
31.2


Evaporator inlet temperature
° C.
−38.0
−38.5
−39.1
−39.6
−40.0
−40.4
−40.8
−41.1


Evaporator dewpoint
° C.
−23.1
−22.8
−22.6
−22.3
−22.1
−21.9
−21.8
−21.7


Evaporator exit gas temperature
° C.
−18.1
−17.8
−17.6
−17.3
−17.1
−16.9
−16.8
−16.7


Evaporator mean temperature
° C.
−30.6
−30.7
−30.8
−30.9
−31.1
−31.2
−31.3
−31.4


Evaporator glide (out-in)
K
14.8
15.7
16.5
17.2
17.9
18.5
19.0
19.4


Compressor suction pressure
bar
1.90
2.01
2.14
2.26
2.39
2.53
2.67
2.82


Compressor discharge pressure
bar
24.1
25.1
26.1
27.1
28.1
29.1
30.2
31.2


Suction line pressure drop
Pa/m
101
95
89
84
79
75
71
67


Pressure drop relative to reference

34.7%
32.5%
30.5%
28.7%
27.1%
25.6%
24.2%
23.0%


Condenser dew point
° C.
53.6
53.4
53.1
52.8
52.4
52.0
51.5
51.0


Condenser bubble point
° C.
30.9
30.2
29.6
29.1
28.6
28.2
27.9
27.6


Condenser exit liquid temperature
° C.
29.9
29.2
28.6
28.1
27.6
27.2
26.9
26.6


Condenser mean temperature
° C.
42.3
41.8
41.4
40.9
40.5
40.1
39.7
39.3


Condenser glide (in-out)
K
22.7
23.2
23.5
23.7
23.8
23.7
23.6
23.4
















TABLE 25







Theoretical Performance Data of Selected R-744/R-32/R-1234ze(E) blends containing 0-14% R-744 and 30% R-32









Composition CO2/R-32/R-1234ze(E) % by weight
















0/30/70
2/30/68
4/30/66
6/30/64
8/30/62
10/30/60
12/30/58
14/30/56




















COP (heating)

2.25
2.27
2.28
2.29
2.29
2.30
2.30
2.30


COP (heating) relative to Reference

106.8%
107.5%
108.0%
108.4%
108.7%
109.0%
109.2%
109.3%


Volumetric heating capacity at suction
kJ/m3
1323
1421
1522
1625
1730
1838
1949
2062


Capacity relative to Reference

150.5%
161.7%
173.2%
184.9%
196.9%
209.2%
221.8%
234.7%


Critical temperature
° C.
94.49
92.17
89.93
87.77
85.70
83.71
81.79
79.95


Critical pressure
bar
48.05
48.86
49.66
50.46
51.25
52.03
52.82
53.60


Condenser enthalpy change
kJ/kg
285.4
292.4
298.9
304.9
310.6
315.9
321.0
325.8


Pressure ratio

13.81
13.64
13.46
13.26
13.05
12.84
12.61
12.39


Refrigerant mass flow
kg/hr
25.2
24.6
24.1
23.6
23.2
22.8
22.4
22.1


Compressor discharge temperature
° C.
138.8
141.6
144.3
146.8
149.3
151.7
154.1
156.3


Evaporator inlet pressure
bar
1.25
1.33
1.42
1.52
1.62
1.72
1.83
1.94


Condenser inlet pressure
bar
16.8
17.8
18.8
19.8
20.8
21.8
22.8
23.8


Evaporator inlet temperature
° C.
−33.3
−33.9
−34.5
−35.1
−35.7
−36.2
−36.8
−37.3


Evaporator dewpoint
° C.
−26.5
−26.0
−25.6
−25.1
−24.7
−24.3
−24.0
−23.6


Evaporator exit gas temperature
° C.
−21.5
−21.0
−20.6
−20.1
−19.7
−19.3
−19.0
−18.6


Evaporator mean temperature
° C.
−29.9
−30.0
−30.0
−30.1
−30.2
−30.3
−30.4
−30.5


Evaporator glide (out-in)
K
6.8
7.9
9.0
10.0
11.0
11.9
12.8
13.7


Compressor suction pressure
bar
1.22
1.30
1.40
1.49
1.59
1.70
1.81
1.92


Compressor discharge pressure
bar
16.8
17.8
18.8
19.8
20.8
21.8
22.8
23.8


Suction line pressure drop
Pa/m
171
156
144
132
123
114
106
99


Pressure drop relative to reference

58.5%
53.5%
49.1%
45.3%
42.0%
39.0%
36.4%
34.0%


Condenser dew point
° C.
51.4
51.8
52.2
52.4
52.5
52.5
52.5
52.4


Condenser bubble point
° C.
41.4
39.4
37.7
36.3
35.0
33.9
32.9
32.0


Condenser exit liquid temperature
° C.
40.4
38.4
36.7
35.3
34.0
32.9
31.9
31.0


Condenser mean temperature
° C.
46.4
45.6
44.9
44.3
43.7
43.2
42.7
42.2


Condenser glide (in-out)
K
10.0
12.4
14.4
16.1
17.5
18.7
19.6
20.4
















TABLE 26







Theoretical Performance Data of Selected R-744/R-32/R-1234ze(E) blends containing 16-30% R-744 and 30% R-32









Composition CO2/R-32/R-1234ze(E) % by weight
















16/30/54
18/30/52
20/3/50
22/30/48
24/30/46
26/30/44
28/30/42
30/30/40




















COP (heating)

2.31
2.31
2.31
2.31
2.31
2.31
2.31
2.30


COP (heating) relative to Reference

109.4%
109.4%
109.5%
109.5%
109.4%
109.4%
109.4%
109.3%


Volumetric heating capacity at suction
kJ/m3
2177
2296
2416
2540
2667
2797
2931
3068


Capacity relative to Reference

247.8%
261.3%
275.0%
289.1%
303.5%
318.3%
333.5%
349.2%


Critical temperature
° C.
78.17
76.45
74.80
73.21
71.67
70.18
68.75
67.36


Critical pressure
bar
54.37
55.15
55.92
56.70
57.47
58.24
59.01
59.78


Condenser enthalpy change
kJ/kg
330.3
334.7
338.8
342.7
346.4
350.0
353.3
356.5


Pressure ratio

12.16
11.93
11.70
11.48
11.25
11.03
10.80
10.58


Refrigerant mass flow
kg/hr
21.8
21.5
21.3
21.0
20.8
20.6
20.4
20.2


Compressor discharge temperature
° C.
158.5
160.6
162.6
164.6
166.5
168.3
170.1
171.7


Evaporator inlet pressure
bar
2.06
2.18
2.31
2.44
2.57
2.72
2.87
3.02


Condenser inlet pressure
bar
24.8
25.8
26.8
27.8
28.8
29.8
30.8
31.9


Evaporator inlet temperature
° C.
−37.8
−38.2
−38.7
−39.1
−39.4
−39.7
−40.0
−40.2


Evaporator dewpoint
° C.
−23.3
−23.1
−22.8
−22.6
−22.4
−22.3
−22.2
−22.1


Evaporator exit gas temperature
° C.
−18.3
−18.1
−17.8
−17.6
−17.4
−17.3
−17.2
−17.1


Evaporator mean temperature
° C.
−30.6
−30.7
−30.8
−30.8
−30.9
−31.0
−31.1
−31.1


Evaporator glide (out-in)
K
14.4
15.2
15.8
16.4
17.0
17.4
17.8
18.2


Compressor suction pressure
bar
2.04
2.16
2.29
2.42
2.56
2.71
2.86
3.01


Compressor discharge pressure
bar
24.8
25.8
26.8
27.8
28.8
29.8
30.8
31.9


Suction line pressure drop
Pa/m
93
87
82
78
73
69
66
62


Pressure drop relative to reference

31.9%
29.9%
28.2%
26.6%
25.1%
23.7%
22.5%
21.3%


Condenser dew point
° C.
52.2
52.0
51.7
51.3
51.0
50.5
50.1
49.6


Condenser bubble point
° C.
31.3
30.6
30.1
29.6
29.2
28.8
28.5
28.3


Condenser exit liquid temperature
° C.
30.3
29.6
29.1
28.6
28.2
27.8
27.5
27.3


Condenser mean temperature
° C.
41.7
41.3
40.9
40.5
40.1
39.7
39.3
38.9


Condenser glide (in-out)
K
20.9
21.3
21.6
21.7
21.8
21.7
21.6
21.3
















TABLE 27







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-


1234ze(E) blends containing 0-14% R-744, 5% R-32 and 5% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















0/5/5/90
2/5/5/88
4/5/5/86
6/5/5/84
8/5/5/82
10/5/5/80
12/5/5/78
14/5/5/76




















COP (heating)

2.07
2.12
2.15
2.18
2.20
2.21
2.22
2.23


COP (heating) relative to Reference

98.2%
100.3%
101.9%
103.2%
104.1%
104.9%
105.5%
106.0%


Volumetric heating capacity at suction
kJ/m3
748
833
920
1012
1106
1203
1302
1405


Capacity relative to Reference

85.2%
94.8%
104.7%
115.1%
125.8%
136.9%
148.2%
159.8%


Critical temperature
° C.
106.20
102.70
99.37
96.19
93.18
90.31
87.59
84.99


Critical pressure
bar
39.52
40.32
41.10
41.86
42.62
43.37
44.11
44.86


Condenser enthalpy change
kJ/kg
227.4
238.4
247.9
256.2
263.7
270.3
276.5
282.1


Pressure ratio

17.76
17.77
17.68
17.47
17.19
16.87
16.51
16.14


Refrigerant mass flow
kg/hr
31.7
30.2
29.0
28.1
27.3
26.6
26.0
25.5


Compressor discharge temperature
° C.
118.5
122.3
125.8
129.0
132.0
134.8
137.5
140.0


Evaporator inlet pressure
bar
0.75
0.80
0.86
0.93
1.01
1.09
1.18
1.27


Condenser inlet pressure
bar
12.1
13.3
14.4
15.6
16.7
17.9
19.0
20.1


Evaporator inlet temperature
° C.
−29.9
−30.6
−31.3
−32.1
−32.9
−33.7
−34.6
−35.5


Evaporator dewpoint
° C.
−29.4
−28.7
−28.0
−27.3
−26.5
−25.8
−25.1
−24.4


Evaporator exit gas temperature
° C.
−24.4
−23.7
−23.0
−22.3
−21.5
−20.8
−20.1
−19.4


Evaporator mean temperature
° C.
−29.6
−29.7
−29.7
−29.7
−29.7
−29.8
−29.9
−30.0


Evaporator glide (out-in)
K
0.5
1.9
3.3
4.8
6.3
7.9
9.5
11.1


Compressor suction pressure
bar
0.68
0.75
0.82
0.89
0.97
1.06
1.15
1.24


Compressor discharge pressure
bar
12.1
13.3
14.4
15.6
16.7
17.9
19.0
20.1


Suction line pressure drop
Pa/m
358
311
273
242
217
196
178
162


Pressure drop relative to reference

122.7%
106.4%
93.5%
83.0%
74.3%
67.0%
60.9%
55.6%


Condenser dew point
° C.
53.6
55.1
56.3
57.2
58.0
58.5
58.9
59.1


Condenser bubble point
° C.
48.6
44.2
40.7
37.9
35.6
33.7
32.1
30.8


Condenser exit liquid temperature
° C.
47.6
43.2
39.7
36.9
34.6
32.7
31.1
29.8


Condenser mean temperature
° C.
51.1
49.7
48.5
47.6
46.8
46.1
45.5
44.9


Condenser glide (in-out)
K
5.0
10.8
15.5
19.3
22.4
24.9
26.8
28.4
















TABLE 28







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 5% R-32 and 5% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















16/5/5/74
18/5/5/72
20/5/5/70
22/5/5/68
24/5/5/66
26/5/5/64
28/5/5/62
30/5/5/60




















COP (heating)

2.24
2.25
2.25
2.25
2.26
2.26
2.25
2.25


COP (heating) relative to Reference

106.3%
106.6%
106.8%
106.9%
107.0%
107.0%
106.9%
106.8%


Volumetric heating capacity at suction
kJ/m3
1509
1615
1722
1831
1941
2052
2164
2277


Capacity relative to Reference

171.7%
183.7%
196.0%
208.4%
220.9%
233.5%
246.2%
259.1%


Critical temperature
° C.
82.52
80.17
77.92
75.76
73.71
71.74
69.85
68.04


Critical pressure
bar
45.60
46.34
47.08
47.82
48.56
49.30
50.04
50.78


Condenser enthalpy change
kJ/kg
287.4
292.4
297.2
301.7
306.1
310.4
314.5
318.5


Pressure ratio

15.77
15.40
15.03
14.68
14.35
14.02
13.72
13.42


Refrigerant mass flow
kg/hr
25.1
24.6
24.2
23.9
23.5
23.2
22.9
22.6


Compressor discharge temperature
° C.
142.4
144.8
147.1
149.3
151.6
153.8
155.9
158.1


Evaporator inlet pressure
bar
1.37
1.47
1.57
1.68
1.79
1.90
2.02
2.14


Condenser inlet pressure
bar
21.2
22.2
23.3
24.4
25.4
26.5
27.5
28.5


Evaporator inlet temperature
° C.
−36.5
−37.4
−38.4
−39.3
−40.2
−41.1
−42.0
−42.8


Evaporator dewpoint
° C.
−23.8
−23.2
−22.7
−22.3
−21.9
−21.5
−21.2
−21.0


Evaporator exit gas temperature
° C.
−18.8
−18.2
−17.7
−17.3
−16.9
−16.5
−16.2
−16.0


Evaporator mean temperature
° C.
−30.1
−30.3
−30.5
−30.8
−31.0
−31.3
−31.6
−31.9


Evaporator glide (out-in)
K
12.7
14.2
15.6
17.0
18.4
19.6
20.8
21.8


Compressor suction pressure
bar
1.34
1.45
1.55
1.66
1.77
1.89
2.00
2.12


Compressor discharge pressure
bar
21.2
22.2
23.3
24.4
25.4
26.5
27.5
28.5


Suction line pressure drop
Pa/m
149
137
127
118
111
103
97
91


Pressure drop relative to reference

51.0%
47.1%
43.6%
40.5%
37.8%
35.4%
33.3%
31.3%


Condenser dew point
° C.
59.2
59.2
59.0
58.8
58.5
58.1
57.7
57.2


Condenser bubble point
° C.
29.6
28.7
27.9
27.1
26.5
26.0
25.5
25.2


Condenser exit liquid temperature
° C.
28.6
27.7
26.9
26.1
25.5
25.0
24.5
24.2


Condenser mean temperature
° C.
44.4
43.9
43.5
43.0
42.5
42.1
41.6
41.2


Condenser glide (in-out)
K
29.6
30.5
31.2
31.7
32.0
32.1
32.1
32.0
















TABLE 29







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 0-14% R-744, 5% R-32 and 10% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















0/5/10/85
2/5/10/83
4/5/10/81
6/5/10/79
8/5/10/77
10/5/10/75
12/5/10/73
14/5/10/71




















COP (heating)

2.08
2.12
2.15
2.18
2.20
2.21
2.23
2.24


COP (heating) relative to Reference

98.5%
100.5%
102.0%
103.3%
104.2%
105.0%
105.5%
106.0%


Volumetric heating capacity at suction
kJ/m3
766
852
940
1032
1127
1226
1326
1430


Capacity relative to Reference

87.2%
96.9%
107.0%
117.5%
128.3%
139.5%
151.0%
162.7%


Critical temperature
° C.
105.78
102.29
98.97
95.82
92.83
89.99
87.28
84.71


Critical pressure
bar
39.92
40.71
41.48
42.23
42.99
43.73
44.48
45.22


Condenser enthalpy change
kJ/kg
228.3
239.1
248.6
256.8
264.2
270.9
276.9
282.5


Pressure ratio

17.57
17.58
17.48
17.27
17.00
16.68
16.33
15.97


Refrigerant mass flow
kg/hr
31.5
30.1
29.0
28.0
27.3
26.6
26.0
25.5


Compressor discharge temperature
° C.
119.0
122.7
126.2
129.4
132.4
135.2
137.8
140.3


Evaporator inlet pressure
bar
0.76
0.82
0.88
0.95
1.03
1.11
1.20
1.30


Condenser inlet pressure
bar
12.3
13.5
14.6
15.8
16.9
18.0
19.2
20.3


Evaporator inlet temperature
° C.
−30.0
−30.6
−31.4
−32.1
−32.9
−33.7
−34.6
−35.5


Evaporator dewpoint
° C.
−29.4
−28.7
−28.0
−27.3
−26.6
−25.8
−25.1
−24.5


Evaporator exit gas temperature
° C.
−24.4
−23.7
−23.0
−22.3
−21.6
−20.8
−20.1
−19.5


Evaporator mean temperature
° C.
−29.7
−29.7
−29.7
−29.7
−29.7
−29.8
−29.9
−30.0


Evaporator glide (out-in)
K
0.6
1.9
3.3
4.8
6.3
7.9
9.4
11.0


Compressor suction pressure
bar
0.70
0.77
0.84
0.91
0.99
1.08
1.17
1.27


Compressor discharge pressure
bar
12.3
13.5
14.6
15.8
16.9
18.0
19.2
20.3


Suction line pressure drop
Pa/m
349
303
267
237
212
192
174
159


Pressure drop relative to reference

119.4%
103.8%
91.3%
81.1%
72.7%
65.7%
59.7%
54.5%


Condenser dew point
° C.
53.4
54.8
56.0
56.9
57.6
58.2
58.5
58.7


Condenser bubble point
° C.
48.6
44.3
40.8
38.0
35.7
33.9
32.3
31.0


Condenser exit liquid temperature
° C.
47.6
43.3
39.8
37.0
34.7
32.9
31.3
30.0


Condenser mean temperature
° C.
51.0
49.6
48.4
47.5
46.7
46.0
45.4
44.8


Condenser glide (in-out)
K
4.9
10.5
15.2
18.9
21.9
24.3
26.2
27.8
















TABLE 30







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 5% R-32 and 10% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















16/5/10/69
18/5/10/67
20/5/10/65
22/5/10/63
24/5/10/61
26/5/10/59
28/5/10/57
30/5/10/55




















COP (heating)

2.24
2.25
2.25
2.26
2.26
2.26
2.26
2.25


COP (heating) relative to Reference

106.4%
106.7%
106.8%
107.0%
107.0%
107.0%
107.0%
106.9%


Volumetric heating capacity at suction
kJ/m3
1535
1643
1752
1862
1974
2088
2202
2318


Capacity relative to Reference

174.7%
187.0%
199.4%
212.0%
224.7%
237.6%
250.6%
263.8%


Critical temperature
° C.
82.25
79.91
77.68
75.54
73.50
71.55
69.67
67.87


Critical pressure
bar
45.96
46.71
47.45
48.19
48.93
49.67
50.40
51.14


Condenser enthalpy change
kJ/kg
287.8
292.8
297.5
302.0
306.3
310.5
314.6
318.5


Pressure ratio

15.60
15.23
14.87
14.52
14.18
13.86
13.55
13.25


Refrigerant mass flow
kg/hr
25.0
24.6
24.2
23.8
23.5
23.2
22.9
22.6


Compressor discharge temperature
° C.
142.8
145.1
147.4
149.6
151.8
154.0
156.1
158.2


Evaporator inlet pressure
bar
1.40
1.50
1.60
1.71
1.83
1.94
2.06
2.19


Condenser inlet pressure
bar
21.4
22.5
23.5
24.6
25.6
26.7
27.7
28.8


Evaporator inlet temperature
° C.
−36.4
−37.3
−38.2
−39.1
−40.0
−40.9
−41.7
−42.5


Evaporator dewpoint
° C.
−23.9
−23.3
−22.8
−22.4
−22.0
−21.6
−21.3
−21.1


Evaporator exit gas temperature
° C.
−18.9
−18.3
−17.8
−17.4
−17.0
−16.6
−16.3
−16.1


Evaporator mean temperature
° C.
−30.1
−30.3
−30.5
−30.7
−31.0
−31.2
−31.5
−31.8


Evaporator glide (out-in)
K
12.5
14.0
15.4
16.8
18.1
19.3
20.4
21.4


Compressor suction pressure
bar
1.37
1.47
1.58
1.69
1.81
1.93
2.05
2.17


Compressor discharge pressure
bar
21.4
22.5
23.5
24.6
25.6
26.7
27.7
28.8


Suction line pressure drop
Pa/m
146
135
125
116
109
102
95
90


Pressure drop relative to reference

50.1%
46.2%
42.8%
39.8%
37.2%
34.8%
32.7%
30.7%


Condenser dew point
° C.
58.8
58.8
58.6
58.4
58.1
57.7
57.2
56.7


Condenser bubble point
° C.
29.9
28.9
28.1
27.4
26.8
26.3
25.8
25.4


Condenser exit liquid temperature
° C.
28.9
27.9
27.1
26.4
25.8
25.3
24.8
24.4


Condenser mean temperature
° C.
44.3
43.8
43.4
42.9
42.4
42.0
41.5
41.1


Condenser glide (in-out)
K
29.0
29.9
30.5
31.0
31.3
31.4
31.4
31.3
















TABLE 31







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 0-14% R-744, 5% R-32 and 20% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















0/5/20/75
2/5/20/73
4/5/20/71
6/5/20/69
8/5/20/67
10/5/20/65
12/5/20/63
14/5/20/61




















COP (heating)

2.08
2.13
2.16
2.18
2.20
2.22
2.23
2.24


COP (heating) relative to Reference

98.9%
100.8%
102.3%
103.5%
104.4%
105.1%
105.7%
106.1%


Volumetric heating capacity at suction
kJ/m3
801
888
978
1072
1170
1270
1373
1479


Capacity relative to Reference

91.2%
101.1%
111.3%
122.0%
133.1%
144.5%
156.2%
168.3%


Critical temperature
° C.
104.94
101.49
98.21
95.11
92.16
89.36
86.70
84.16


Critical pressure
bar
40.64
41.40
42.16
42.91
43.66
44.41
45.15
45.90


Condenser enthalpy change
kJ/kg
230.1
240.7
250.0
258.2
265.5
272.1
278.1
283.6


Pressure ratio

17.21
17.22
17.12
16.93
16.65
16.35
16.00
15.65


Refrigerant mass flow
kg/hr
31.3
29.9
28.8
27.9
27.1
26.5
25.9
25.4


Compressor discharge temperature
° C.
120.0
123.7
127.1
130.3
133.3
136.1
138.7
141.2


Evaporator inlet pressure
bar
0.79
0.85
0.92
0.99
1.07
1.16
1.25
1.35


Condenser inlet pressure
bar
12.7
13.8
14.9
16.1
17.3
18.4
19.5
20.6


Evaporator inlet temperature
° C.
−30.0
−30.7
−31.4
−32.1
−32.8
−33.6
−34.5
−35.3


Evaporator dewpoint
° C.
−29.3
−28.7
−28.1
−27.3
−26.6
−25.9
−25.3
−24.6


Evaporator exit gas temperature
° C.
−24.3
−23.7
−23.1
−22.3
−21.6
−20.9
−20.3
−19.6


Evaporator mean temperature
° C.
−29.7
−29.7
−29.7
−29.7
−29.7
−29.8
−29.9
−30.0


Evaporator glide (out-in)
K
0.7
2.0
3.3
4.7
6.2
7.7
9.2
10.7


Compressor suction pressure
bar
0.74
0.80
0.87
0.95
1.04
1.13
1.22
1.32


Compressor discharge pressure
bar
12.7
13.8
14.9
16.1
17.3
18.4
19.5
20.6


Suction line pressure drop
Pa/m
332
289
255
227
204
185
168
154


Pressure drop relative to reference

113.6%
99.0%
87.4%
77.8%
69.9%
63.2%
57.5%
52.6%


Condenser dew point
° C.
53.0
54.3
55.4
56.3
57.0
57.5
57.8
58.0


Condenser bubble point
° C.
48.5
44.4
41.0
38.3
36.0
34.2
32.6
31.3


Condenser exit liquid temperature
° C.
47.5
43.4
40.0
37.3
35.0
33.2
31.6
30.3


Condenser mean temperature
° C.
50.8
49.3
48.2
47.3
46.5
45.8
45.2
44.7


Condenser glide (in-out)
K
4.5
9.9
14.4
18.0
20.9
23.3
25.2
26.7
















TABLE 32







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 5% R-32 and 20% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















16/5/20/59
18/5/20/57
20/5/20/55
22/5/20/53
24/5/20/51
26/5/20/49
28/5/20/47
30/5/20/45




















COP (heating)

2.24
2.25
2.25
2.26
2.26
2.26
2.26
2.26


COP (heating) relative to Reference

106.5%
106.7%
106.9%
107.1%
107.1%
107.2%
107.1%
107.1%


Volumetric heating capacity at suction
kJ/m3
1587
1697
1810
1924
2040
2158
2277
2398


Capacity relative to Reference

180.6%
193.2%
206.0%
219.0%
232.2%
245.6%
259.1%
272.9%


Critical temperature
° C.
81.74
79.43
77.23
75.12
73.11
71.18
69.32
67.55


Critical pressure
bar
46.64
47.38
48.12
48.86
49.61
50.35
51.09
51.83


Condenser enthalpy change
kJ/kg
288.8
293.7
298.3
302.7
307.0
311.0
315.0
318.8


Pressure ratio

15.28
14.92
14.57
14.22
13.89
13.56
13.25
12.95


Refrigerant mass flow
kg/hr
24.9
24.5
24.1
23.8
23.5
23.1
22.9
22.6


Compressor discharge temperature
° C.
143.6
145.9
148.1
150.3
152.4
154.5
156.6
158.6


Evaporator inlet pressure
bar
1.45
1.55
1.66
1.78
1.90
2.02
2.14
2.27


Condenser inlet pressure
bar
21.7
22.8
23.9
25.0
26.1
27.1
28.2
29.2


Evaporator inlet temperature
° C.
−36.2
−37.0
−37.9
−38.8
−39.6
−40.4
−41.2
−41.9


Evaporator dewpoint
° C.
−24.0
−23.5
−23.0
−22.5
−22.1
−21.8
−21.5
−21.2


Evaporator exit gas temperature
° C.
−19.0
−18.5
−18.0
−17.5
−17.1
−16.8
−16.5
−16.2


Evaporator mean temperature
° C.
−30.1
−30.3
−30.4
−30.6
−30.9
−31.1
−31.3
−31.6


Evaporator glide (out-in)
K
12.1
13.5
14.9
16.2
17.4
18.6
19.7
20.7


Compressor suction pressure
bar
1.42
1.53
1.64
1.76
1.88
2.00
2.13
2.26


Compressor discharge pressure
bar
21.7
22.8
23.9
25.0
26.1
27.1
28.2
29.2


Suction line pressure drop
Pa/m
141
130
121
112
105
98
92
87


Pressure drop relative to reference

48.3%
44.6%
41.4%
38.5%
35.9%
33.6%
31.6%
29.7%


Condenser dew point
° C.
58.0
58.0
57.8
57.6
57.3
56.9
56.4
55.9


Condenser bubble point
° C.
30.2
29.3
28.5
27.8
27.2
26.7
26.3
25.9


Condenser exit liquid temperature
° C.
29.2
28.3
27.5
26.8
26.2
25.7
25.3
24.9


Condenser mean temperature
° C.
44.1
43.6
43.2
42.7
42.3
41.8
41.4
40.9


Condenser glide (in-out)
K
27.8
28.7
29.4
29.8
30.1
30.2
30.2
30.0
















TABLE 33







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 0-14% R-744, 5% R-32 and 30% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















0/5/30/65
2/5/30/63
4/5/30/61
6/5/30/59
8/5/30/57
10/2/30/55
12/5/30/53
14/5/30/51




















COP (heating)

2.09
2.13
2.16
2.19
2.20
2.22
2.23
2.24


COP (heating) relative to Reference

99.2%
101.1%
102.5%
103.7%
104.5%
105.2%
105.8%
106.2%


Volumetric heating capacity at suction
kJ/m3
833
922
1014
1109
1209
1311
1417
1525


Capacity relative to Reference

94.9%
104.9%
115.4%
126.3%
137.6%
149.2%
161.2%
173.6%


Critical temperature
° C.
104.11
100.71
97.48
94.43
91.52
88.76
86.14
83.64


Critical pressure
bar
41.22
41.98
42.74
43.49
44.24
44.99
45.74
46.49


Condenser enthalpy change
kJ/kg
232.0
242.5
251.7
259.9
267.1
273.6
279.5
285.0


Pressure ratio

16.90
16.91
16.81
16.63
16.36
16.06
15.72
15.37


Refrigerant mass flow
kg/hr
31.0
29.7
28.6
27.7
27.0
26.3
25.8
25.3


Compressor discharge temperature
° C.
121.0
124.7
128.2
131.3
134.3
137.0
139.6
142.1


Evaporator inlet pressure
bar
0.82
0.88
0.95
1.03
1.11
1.20
1.29
1.39


Condenser inlet pressure
bar
13.0
14.1
15.3
16.4
17.6
18.7
19.9
21.0


Evaporator inlet temperature
° C.
−30.1
−30.7
−31.4
−32.1
−32.8
−33.5
−34.3
−35.1


Evaporator dewpoint
° C.
−29.4
−28.8
−28.1
−27.4
−26.7
−26.1
−25.4
−24.8


Evaporator exit gas temperature
° C.
−24.4
−23.8
−23.1
−22.4
−21.7
−21.1
−20.4
−19.8


Evaporator mean temperature
° C.
−29.7
−29.7
−29.7
−29.7
−29.8
−29.8
−29.9
−30.0


Evaporator glide (out-in)
K
0.7
1.9
3.2
4.6
6.0
7.5
8.9
10.4


Compressor suction pressure
bar
0.77
0.83
0.91
0.99
1.07
1.17
1.26
1.37


Compressor discharge pressure
bar
13.0
14.1
15.3
16.4
17.6
18.7
19.9
21.0


Suction line pressure drop
Pa/m
317
277
245
219
197
178
162
148


Pressure drop relative to reference

108.5%
94.9%
83.9%
74.8%
67.3%
60.9%
55.5%
50.8%


Condenser dew point
° C.
52.6
53.8
54.9
55.7
56.3
56.8
57.1
57.3


Condenser bubble point
° C.
48.5
44.4
41.1
38.4
36.2
34.4
32.9
31.6


Condenser exit liquid temperature
° C.
47.5
43.4
40.1
37.4
35.2
33.4
31.9
30.6


Condenser mean temperature
° C.
50.5
49.1
48.0
47.1
46.3
45.6
45.0
44.4


Condenser glide (in-out)
K
4.1
9.4
13.7
17.3
20.1
22.4
24.3
25.7
















TABLE 34







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 5% R-32 and 30% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















16/5/30/49
18/5/30/47
20/5/30/45
22/5/30/43
24/5/30/41
26/5/30/39
28/5/30/37
30/5/30/35




















COP (heating)

2.25
2.25
2.26
2.26
2.26
2.26
2.26
2.26


COP (heating) relative to Reference

106.6%
106.9%
107.1%
107.2%
107.3%
107.3%
107.3%
107.3%


Volumetric heating capacity at suction
kJ/m3
1636
1749
1865
1983
2102
2224
2347
2473


Capacity relative to Reference

186.2%
199.1%
212.3%
225.6%
239.3%
253.1%
267.1%
281.4%


Critical temperature
° C.
81.25
78.98
76.80
74.72
72.73
70.82
68.99
67.24


Critical pressure
bar
47.24
47.98
48.73
49.47
50.22
50.96
51.71
52.45


Condenser enthalpy change
kJ/kg
290.1
294.9
299.5
303.8
308.0
311.9
315.7
319.4


Pressure ratio

15.02
14.66
14.31
13.96
13.63
13.30
12.99
12.69


Refrigerant mass flow
kg/hr
24.8
24.4
24.0
23.7
23.4
23.1
22.8
22.5


Compressor discharge temperature
° C.
144.5
146.7
148.9
151.1
153.1
155.2
157.2
159.2


Evaporator inlet pressure
bar
1.50
1.61
1.72
1.84
1.96
2.09
2.22
2.35


Condenser inlet pressure
bar
22.1
23.2
24.3
25.4
26.5
27.6
28.6
29.7


Evaporator inlet temperature
° C.
−36.0
−36.8
−37.6
−38.4
−39.2
−40.0
−40.7
−41.4


Evaporator dewpoint
° C.
−24.2
−23.7
−23.2
−22.7
−22.3
−22.0
−21.7
−21.4


Evaporator exit gas temperature
° C.
−19.2
−18.7
−18.2
−17.7
−17.3
−17.0
−16.7
−16.4


Evaporator mean temperature
° C.
−30.1
−30.2
−30.4
−30.6
−30.8
−31.0
−31.2
−31.4


Evaporator glide (out-in)
K
11.8
13.1
14.4
15.7
16.9
18.0
19.1
20.0


Compressor suction pressure
bar
1.47
1.58
1.70
1.82
1.94
2.07
2.20
2.34


Compressor discharge pressure
bar
22.1
23.2
24.3
25.4
26.5
27.6
28.6
29.7


Suction line pressure drop
Pa/m
136
126
117
109
102
95
89
84


Pressure drop relative to reference

46.7%
43.2%
40.0%
37.2%
34.8%
32.6%
30.6%
28.8%


Condenser dew point
° C.
57.4
57.3
57.1
56.9
56.6
56.2
55.8
55.2


Condenser bubble point
° C.
30.5
29.6
28.8
28.1
27.6
27.1
26.7
26.3


Condenser exit liquid temperature
° C.
29.5
28.6
27.8
27.1
26.6
26.1
25.7
25.3


Condenser mean temperature
° C.
43.9
43.4
43.0
42.5
42.1
41.6
41.2
40.8


Condenser glide (in-out)
K
26.9
27.7
28.3
28.8
29.0
29.1
29.1
28.9
















TABLE 35







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 0-14% R-744, 5% R-32 and 40% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















0/5/40/55
2/5/40/53
4/5/40/51
6/5/40/49
8/5/40/47
10/5/40/45
12/5/40/43
14/5/40/41




















COP (heating)

2.10
2.14
2.17
2.19
2.21
2.22
2.23
2.24


COP (heating) relative to Reference

99.6%
101.4%
102.8%
103.9%
104.7%
105.4%
106.0%
106.4%


Volumetric heating capacity at suction
kJ/m3
863
953
1047
1144
1245
1350
1457
1568


Capacity relative to Reference

98.2%
108.5%
119.1%
130.2%
141.7%
153.7%
165.9%
178.5%


Critical temperature
° C.
103.30
99.95
96.78
93.77
90.91
88.19
85.60
83.14


Critical pressure
bar
41.67
42.44
43.21
43.97
44.73
45.49
46.24
47.00


Condenser enthalpy change
kJ/kg
234.1
244.6
253.7
261.8
269.0
275.4
281.3
286.8


Pressure ratio

16.63
16.64
16.55
16.37
16.11
15.81
15.49
15.14


Refrigerant mass flow
kg/hr
30.8
29.4
28.4
27.5
26.8
26.1
25.6
25.1


Compressor discharge temperature
° C.
122.1
125.8
129.3
132.5
135.4
138.1
140.7
143.1


Evaporator inlet pressure
bar
0.85
0.91
0.98
1.06
1.14
1.23
1.33
1.43


Condenser inlet pressure
bar
13.2
14.4
15.5
16.7
17.9
19.0
20.2
21.3


Evaporator inlet temperature
° C.
−30.1
−30.7
−31.3
−32.0
−32.7
−33.4
−34.2
−35.0


Evaporator dewpoint
° C.
−29.4
−28.9
−28.2
−27.6
−26.9
−26.2
−25.5
−24.9


Evaporator exit gas temperature
° C.
−24.4
−23.9
−23.2
−22.6
−21.9
−21.2
−20.5
−19.9


Evaporator mean temperature
° C.
−29.8
−29.8
−29.8
−29.8
−29.8
−29.8
−29.9
−30.0


Evaporator glide (out-in)
K
0.7
1.8
3.1
4.5
5.8
7.2
8.6
10.0


Compressor suction pressure
bar
0.79
0.86
0.94
1.02
1.11
1.20
1.30
1.41


Compressor discharge pressure
bar
13.2
14.4
15.5
16.7
17.9
19.0
20.2
21.3


Suction line pressure drop
Pa/m
304
266
236
211
190
172
157
144


Pressure drop relative to reference

104.0%
91.2%
80.8%
72.2%
65.0%
58.9%
53.7%
49.2%


Condenser dew point
° C.
52.1
53.3
54.3
55.1
55.8
56.2
56.5
56.7


Condenser bubble point
° C.
48.5
44.5
41.2
38.5
36.4
34.5
33.0
31.8


Condenser exit liquid temperature
° C.
47.5
43.5
40.2
37.5
35.4
33.5
32.0
30.8


Condenser mean temperature
° C.
50.3
48.9
47.8
46.8
46.1
45.4
44.8
44.2


Condenser glide (in-out)
K
3.6
8.8
13.1
16.6
19.4
21.7
23.5
24.9
















TABLE 36







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 5% R-32 and 40% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















16/5/40/39
18/5/40/37
20/5/40/35
22/5/40/33
24/5/40/31
26/5/40/29
28/5/40/27
30/5/40/25




















COP (heating)

2.25
2.26
2.26
2.26
2.27
2.27
2.27
2.27


COP (heating) relative to Reference

106.7%
107.0%
107.2%
107.3%
107.4%
107.5%
107.5%
107.4%


Volumetric heating capacity at suction
kJ/m3
1682
1798
1916
2037
2160
2284
2411
2540


Capacity relative to Reference

191.4%
204.6%
218.1%
231.8%
245.8%
260.0%
274.4%
289.1%


Critical temperature
° C.
80.79
78.54
76.39
74.34
72.38
70.49
68.68
66.95


Critical pressure
bar
47.75
48.51
49.26
50.01
50.76
51.51
52.26
53.01


Condenser enthalpy change
kJ/kg
291.8
296.6
301.0
305.3
309.4
313.2
317.0
320.6


Pressure ratio

14.79
14.44
14.09
13.74
13.41
13.09
12.78
12.48


Refrigerant mass flow
kg/hr
24.7
24.3
23.9
23.6
23.3
23.0
22.7
22.5


Compressor discharge temperature
° C.
145.5
147.7
149.9
152.0
154.0
156.0
158.0
159.9


Evaporator inlet pressure
bar
1.54
1.65
1.77
1.89
2.02
2.15
2.29
2.43


Condenser inlet pressure
bar
22.4
23.6
24.7
25.8
26.9
27.9
29.0
30.1


Evaporator inlet temperature
° C.
−35.8
−36.6
−37.4
−38.2
−38.9
−39.7
−40.4
−41.1


Evaporator dewpoint
° C.
−24.4
−23.8
−23.3
−22.9
−22.5
−22.1
−21.8
−21.6


Evaporator exit gas temperature
° C.
−19.4
−18.8
−18.3
−17.9
−17.5
−17.1
−16.8
−16.6


Evaporator mean temperature
° C.
−30.1
−30.2
−30.4
−30.5
−30.7
−30.9
−31.1
−31.3


Evaporator glide (out-in)
K
11.4
12.8
14.1
15.3
16.5
17.6
18.6
19.5


Compressor suction pressure
bar
1.52
1.63
1.75
1.87
2.00
2.13
2.27
2.41


Compressor discharge pressure
bar
22.4
23.6
24.7
25.8
26.9
27.9
29.0
30.1


Suction line pressure drop
Pa/m
132
122
113
106
99
92
87
82


Pressure drop relative to reference

45.3%
41.8%
38.8%
36.1%
33.7%
31.6%
29.7%
27.9%


Condenser dew point
° C.
56.7
56.7
56.5
56.3
56.0
55.6
55.2
54.7


Condenser bubble point
° C.
30.7
29.8
29.0
28.3
27.8
27.3
26.9
26.6


Condenser exit liquid temperature
° C.
29.7
28.8
28.0
27.3
26.8
26.3
25.9
25.6


Condenser mean temperature
° C.
43.7
43.2
42.8
42.3
41.9
41.5
41.0
40.6


Condenser glide (in-out)
K
26.1
26.9
27.5
28.0
28.2
28.3
28.3
28.1
















TABLE 37







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 0-14% R-744, 5% R-32 and 50% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















0/5/50/45
2/5/50/43
4/5/50/41
6/5/50/39
8/5/50/37
10/5/50/35
12/5/50/33
14/5/50/31




















COP (heating)

2.11
2.15
2.17
2.20
2.21
2.23
2.24
2.25


COP (heating) relative to Reference

100.0%
101.7%
103.1%
104.1%
105.0%
105.6%
106.2%
106.6%


Volumetric heating capacity at suction
kJ/m3
890
981
1076
1176
1278
1385
1495
1607


Capacity relative to Reference

101.3%
111.7%
122.5%
133.8%
145.5%
157.6%
170.1%
182.9%


Critical temperature
° C.
102.50
99.21
96.09
93.13
90.31
87.63
85.09
82.66


Critical pressure
bar
42.02
42.80
43.58
44.35
45.12
45.89
46.66
47.43


Condenser enthalpy change
kJ/kg
236.4
246.8
256.0
264.0
271.2
277.6
283.5
288.9


Pressure ratio

16.40
16.42
16.33
16.15
15.91
15.61
15.30
14.95


Refrigerant mass flow
kg/hr
30.5
29.2
28.1
27.3
26.6
25.9
25.4
24.9


Compressor discharge temperature
° C.
123.3
127.1
130.5
133.7
136.6
139.3
141.9
144.3


Evaporator inlet pressure
bar
0.87
0.93
1.01
1.08
1.17
1.26
1.36
1.47


Condenser inlet pressure
bar
13.4
14.6
15.8
17.0
18.1
19.3
20.5
21.6


Evaporator inlet temperature
° C.
−30.1
−30.7
−31.3
−32.0
−32.6
−33.3
−34.1
−34.9


Evaporator dewpoint
° C.
−29.5
−29.0
−28.3
−27.7
−27.0
−26.3
−25.7
−25.1


Evaporator exit gas temperature
° C.
−24.5
−24.0
−23.3
−22.7
−22.0
−21.3
−20.7
−20.1


Evaporator mean temperature
° C.
−29.8
−29.8
−29.8
−29.8
−29.8
−29.8
−29.9
−30.0


Evaporator glide (out-in)
K
0.6
1.7
3.0
4.3
5.6
7.0
8.4
9.8


Compressor suction pressure
bar
0.82
0.89
0.97
1.05
1.14
1.24
1.34
1.44


Compressor discharge pressure
bar
13.4
14.6
15.8
17.0
18.1
19.3
20.5
21.6


Suction line pressure drop
Pa/m
293
257
228
204
184
167
152
139


Pressure drop relative to reference

100.2%
87.9%
78.0%
69.8%
62.9%
57.0%
52.0%
47.7%


Condenser dew point
° C.
51.6
52.8
53.8
54.6
55.3
55.7
56.0
56.2


Condenser bubble point
° C.
48.5
44.5
41.2
38.6
36.4
34.6
33.1
31.8


Condenser exit liquid temperature
° C.
47.5
43.5
40.2
37.6
35.4
33.6
32.1
30.8


Condenser mean temperature
° C.
50.0
48.6
47.5
46.6
45.8
45.1
44.5
44.0


Condenser glide (in-out)
K
3.2
8.3
12.6
16.1
18.9
21.1
22.9
24.4
















TABLE 38







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 5% R-32 and 50% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















16/5/50/29
18/5/50/27
20/5/50/25
22/5/50/23
24/5/50/21
26/5/50/19
28/5/50/17
30/5/50/15




















COP (heating)

2.25
2.26
2.26
2.27
2.27
2.27
2.27
2.27


COP (heating) relative to Reference

106.9%
107.2%
107.4%
107.5%
107.6%
107.7%
107.7%
107.6%


Volumetric heating capacity at suction
kJ/m3
1723
1841
1962
2085
2211
2338
2467
2599


Capacity relative to Reference

196.1%
209.6%
223.3%
237.3%
251.6%
266.1%
280.8%
295.8%


Critical temperature
° C.
80.34
78.12
76.00
73.98
72.04
70.17
68.39
66.67


Critical pressure
bar
48.19
48.96
49.72
50.48
51.24
52.00
52.76
53.52


Condenser enthalpy change
kJ/kg
293.9
298.6
303.0
307.2
311.2
315.1
318.7
322.3


Pressure ratio

14.61
14.26
13.91
13.57
13.24
12.93
12.62
12.32


Refrigerant mass flow
kg/hr
24.5
24.1
23.8
23.4
23.1
22.9
22.6
22.3


Compressor discharge temperature
° C.
146.6
148.9
151.0
153.1
155.1
157.1
159.0
160.9


Evaporator inlet pressure
bar
1.58
1.69
1.81
1.94
2.07
2.20
2.34
2.48


Condenser inlet pressure
bar
22.7
23.9
25.0
26.1
27.2
28.3
29.4
30.4


Evaporator inlet temperature
° C.
−35.6
−36.4
−37.2
−38.0
−38.8
−39.5
−40.2
−40.9


Evaporator dewpoint
° C.
−24.5
−23.9
−23.4
−23.0
−22.6
−22.2
−21.9
−21.6


Evaporator exit gas temperature
° C.
−19.5
−18.9
−18.4
−18.0
−17.6
−17.2
−16.9
−16.6


Evaporator mean temperature
° C.
−30.1
−30.2
−30.3
−30.5
−30.7
−30.9
−31.1
−31.3


Evaporator glide (out-in)
K
11.2
12.5
13.8
15.0
16.2
17.3
18.3
19.2


Compressor suction pressure
bar
1.56
1.67
1.80
1.92
2.05
2.19
2.33
2.47


Compressor discharge pressure
bar
22.7
23.9
25.0
26.1
27.2
28.3
29.4
30.4


Suction line pressure drop
Pa/m
128
119
110
103
96
90
84
79


Pressure drop relative to reference

43.9%
40.6%
37.7%
35.1%
32.8%
30.7%
28.9%
27.2%


Condenser dew point
° C.
56.2
56.2
56.0
55.8
55.5
55.1
54.7
54.2


Condenser bubble point
° C.
30.8
29.9
29.1
28.4
27.9
27.4
27.0
26.7


Condenser exit liquid temperature
° C.
29.8
28.9
28.1
27.4
26.9
26.4
26.0
25.7


Condenser mean temperature
° C.
43.5
43.0
42.6
42.1
41.7
41.3
40.9
40.4


Condenser glide (in-out)
K
25.5
26.3
26.9
27.4
27.6
27.7
27.7
27.5
















TABLE 39







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 0-14% R-744, 10% R-32 and 5% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















0/10/5/85
2/10/5/83
4/10/5/81
6/10/5/79
8/10/5/77
10/10/5/75
12/10/5/73
14/10/5/71




















COP (heating)

2.13
2.16
2.18
2.21
2.22
2.23
2.25
2.25


COP (heating) relative to Reference

100.8%
102.4%
103.6%
104.6%
105.4%
106.0%
106.5%
106.9%


Volumetric heating capacity at suction
kJ/m3
865
953
1044
1139
1237
1337
1439
1544


Capacity relative to Reference

98.4%
108.5%
118.9%
129.7%
140.7%
152.1%
163.8%
175.7%


Critical temperature
° C.
103.31
100.13
97.08
94.18
91.40
88.76
86.23
83.82


Critical pressure
bar
41.66
42.48
43.26
44.03
44.79
45.54
46.28
47.03


Condenser enthalpy change
kJ/kg
240.9
250.5
258.9
266.5
273.3
279.6
285.4
290.8


Pressure ratio

16.85
16.76
16.59
16.35
16.07
15.77
15.44
15.12


Refrigerant mass flow
kg/hr
29.9
28.7
27.8
27.0
26.3
25.8
25.2
24.8


Compressor discharge temperature
° C.
123.1
126.5
129.7
132.7
135.6
138.2
140.8
143.2


Evaporator inlet pressure
bar
0.84
0.90
0.97
1.05
1.13
1.22
1.31
1.41


Condenser inlet pressure
bar
13.2
14.3
15.5
16.6
17.7
18.8
19.9
20.9


Evaporator inlet temperature
° C.
−30.8
−31.5
−32.2
−33.0
−33.8
−34.6
−35.4
−36.3


Evaporator dewpoint
° C.
−28.6
−27.9
−27.2
−26.5
−25.8
−25.2
−24.6
−24.0


Evaporator exit gas temperature
° C.
−23.6
−22.9
−22.2
−21.5
−20.8
−20.2
−19.6
−19.0


Evaporator mean temperature
° C.
−29.7
−29.7
−29.7
−29.7
−29.8
−29.9
−30.0
−30.1


Evaporator glide (out-in)
K
2.2
3.5
5.0
6.4
7.9
9.4
10.9
12.3


Compressor suction pressure
bar
0.79
0.86
0.93
1.01
1.10
1.19
1.29
1.39


Compressor discharge pressure
bar
13.2
14.3
15.5
16.6
17.7
18.8
19.9
20.9


Suction line pressure drop
Pa/m
297
262
233
209
189
172
157
144


Pressure drop relative to reference

101.6%
89.6%
79.7%
71.5%
64.7%
58.8%
53.8%
49.4%


Condenser dew point
° C.
53.6
54.7
55.7
56.4
56.9
57.3
57.6
57.7


Condenser bubble point
° C.
46.0
42.5
39.6
37.2
35.2
33.6
32.2
31.0


Condenser exit liquid temperature
° C.
45.0
41.5
38.6
36.2
34.2
32.6
31.2
30.0


Condenser mean temperature
° C.
49.8
48.6
47.6
46.8
46.1
45.5
44.9
44.3


Condenser glide (in-out)
K
7.7
12.3
16.1
19.2
21.7
23.7
25.4
26.7
















TABLE 40







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 10% R-32 and 5% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















16/10/5/69
18/10/5/67
20/10/5/65
22/10/5/63
24/10/5/61
26/10/5/59
28/10/5/57
30/10/5/55




















COP (heating)

2.26
2.26
2.27
2.27
2.27
2.27
2.27
2.26


COP (heating) relative to Reference

107.1%
107.3%
107.5%
107.5%
107.6%
107.5%
107.5%
107.4%


Volumetric heating capacity y at suction
kJ/m3
1650
1758
1868
1979
2092
2206
2323
2440


Capacity relative to Reference

187.8%
200.1%
212.6%
225.3%
238.1%
251.1%
264.3%
277.7%


Critical temperature
° C.
81.51
79.31
77.20
75.17
73.24
71.38
69.59
67.88


Critical pressure
bar
47.77
48.51
49.25
49.99
50.72
51.46
52.19
52.93


Condenser enthalpy change
kJ/kg
295.9
300.8
305.4
309.9
314.1
318.3
322.3
326.1


Pressure ratio

14.79
14.46
14.14
13.84
13.54
13.25
12.96
12.69


Refrigerant mass flow
kg/hr
24.3
23.9
23.6
23.2
22.9
22.6
22.3
22.1


Compressor discharge temperature
° C.
145.6
147.9
150.2
152.4
154.6
156.7
158.8
160.9


Evaporator inlet pressure
bar
1.51
1.62
1.72
1.84
1.95
2.07
2.19
2.32


Condenser inlet pressure
bar
22.0
23.1
24.1
25.1
26.2
27.2
28.2
29.3


Evaporator inlet temperature
° C.
−37.2
−38.0
−38.9
−39.7
−40.5
−41.2
−41.9
−42.6


Evaporator dewpoint
° C.
−23.4
−23.0
−22.5
−22.1
−21.8
−21.5
−21.3
−21.0


Evaporator exit gas temperature
° C.
−18.4
−18.0
−17.5
−17.1
−16.8
−16.5
−16.3
−16.0


Evaporator mean temperature
° C.
−30.3
−30.5
−30.7
−30.9
−31.1
−31.4
−31.6
−31.8


Evaporator glide (out-in)
K
13.7
15.1
16.3
17.5
18.7
19.7
20.7
21.5


Compressor suction pressure
bar
1.49
1.59
1.70
1.82
1.93
2.05
2.18
2.30


Compressor discharge pressure
bar
22.0
23.1
24.1
25.1
26.2
27.2
28.2
29.3


Suction line pressure drop
Pa/m
133
124
115
107
101
94
89
84


Pressure drop relative to reference

45.6%
42.3%
39.4%
36.8%
34.4%
32.3%
30.4%
28.7%


Condenser dew point
° C.
57.7
57.6
57.4
57.1
56.8
56.4
55.9
55.4


Condenser bubble point
° C.
30.0
29.1
28.3
27.7
27.1
26.6
26.2
25.9


Condenser exit liquid temperature
° C.
29.0
28.1
27.3
26.7
26.1
25.6
25.2
24.9


Condenser mean temperature
° C.
43.8
43.3
42.9
42.4
42.0
41.5
41.1
40.6


Condenser glide (in-out)
K
27.7
28.5
29.1
29.4
29.7
29.7
29.7
29.5
















TABLE 41







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 0-14% R-744, 10% R-32 and 10% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















0/10/10/80
2/10/10/78
4/10/10/76
6/10/10/74
8/10/10/72
10/10/10/70
12/10/10/68
14/10/10/66




















COP (heating)

2.13
2.16
2.19
2.21
2.22
2.24
2.25
2.25


COP (heating) relative to Reference

100.9%
102.5%
103.7%
104.7%
105.4%
106.0%
106.5%
106.9%


Volumetric heating capacity at suction
kJ/m3
883
972
1064
1160
1258
1359
1463
1569


Capacity relative to Reference

100.5%
110.6%
121.1%
132.0%
143.2%
154.7%
166.5%
178.6%


Critical temperature
° C.
102.94
99.76
96.73
93.84
91.08
88.45
85.94
83.55


Critical pressure
bar
42.01
42.80
43.57
44.34
45.09
45.84
46.59
47.33


Condenser enthalpy change
kJ/kg
241.7
251.1
259.6
267.1
273.9
280.1
285.9
291.3


Pressure ratio

16.67
16.58
16.42
16.18
15.91
15.61
15.29
14.97


Refrigerant mass flow
kg/hr
29.8
28.7
27.7
27.0
26.3
25.7
25.2
24.7


Compressor discharge temperature
° C.
123.6
127.0
130.2
133.2
136.0
138.6
141.2
143.6


Evaporator inlet pressure
bar
0.85
0.92
0.99
1.07
1.15
1.24
1.34
1.44


Condenser inlet pressure
bar
13.4
14.5
15.6
16.7
17.8
18.9
20.0
21.1


Evaporator inlet temperature
° C.
−30.8
−31.5
−32.2
−32.9
−33.7
−34.5
−35.3
−36.2


Evaporator dewpoint
° C.
−28.6
−28.0
−27.3
−26.6
−25.9
−25.3
−24.7
−24.1


Evaporator exit gas temperature
° C.
−23.6
−23.0
−22.3
−21.6
−20.9
−20.3
−19.7
−19.1


Evaporator mean temperature
° C.
−29.7
−29.7
−29.7
−29.8
−29.8
−29.9
−30.0
−30.1


Evaporator glide (out-in)
K
2.2
3.5
4.9
6.3
7.8
9.2
10.7
12.1


Compressor suction pressure
bar
0.80
0.87
0.95
1.03
1.12
1.21
1.31
1.41


Compressor discharge pressure
bar
13.4
14.5
15.6
16.7
17.8
18.9
20.0
21.1


Suction line pressure drop
Pa/m
290
256
228
205
185
169
154
142


Pressure drop relative to reference

99.3%
87.7%
78.1%
70.1%
63.4%
57.7%
52.8%
48.6%


Condenser dew point
° C.
53.4
54.4
55.3
56.0
56.6
57.0
57.2
57.3


Condenser bubble point
° C.
46.1
42.6
39.7
37.4
35.4
33.8
32.4
31.2


Condenser exit liquid temperature
° C.
45.1
41.6
38.7
36.4
34.4
32.8
31.4
30.2


Condenser mean temperature
° C.
49.7
48.5
47.5
46.7
46.0
45.4
44.8
44.2


Condenser glide (in-out)
K
7.3
11.9
15.6
18.7
21.2
23.2
24.8
26.1
















TABLE 42







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 10% R-32 and 10% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















16/10/
18/10/
20/10/
22/10/
24/10/
26/10/
28/10/
30/10/



10/64
10/62
10/60
10/58
10/56
10/54
10/52
10/50




















COP (heating)

2.26
2.26
2.27
2.27
2.27
2.27
2.27
2.27


COP (heating) relative to Reference

107.2%
107.4%
107.5%
107.6%
107.6%
107.6%
107.6%
107.5%


Volumetric heating capacity at suction
kJ/m3
1677
1787
1898
2011
2126
2243
2362
2483


Capacity relative to Reference

190.8%
203.3%
216.0%
228.9%
242.0%
255.3%
268.8%
282.5%


Critical temperature
° C.
81.26
79.07
76.97
74.96
73.03
71.19
69.41
67.71


Critical pressure
bar
48.07
48.81
49.55
50.29
51.03
51.76
52.50
53.23


Condenser enthalpy change
kJ/kg
296.3
301.2
305.8
310.2
314.4
318.5
322.4
326.2


Pressure ratio

14.64
14.32
14.00
13.69
13.39
13.10
12.81
12.54


Refrigerant mass flow
kg/hr
24.3
23.9
23.5
23.2
22.9
22.6
22.3
22.1


Compressor discharge temperature
° C.
146.0
148.3
150.5
152.7
154.9
157.0
159.0
161.1


Evaporator inlet pressure
bar
1.54
1.64
1.76
1.87
1.99
2.11
2.24
2.37


Condenser inlet pressure
bar
22.2
23.3
24.3
25.4
26.4
27.4
28.5
29.5


Evaporator inlet temperature
° C.
−37.0
−37.8
−38.6
−39.4
−40.2
−40.9
−41.6
−42.2


Evaporator dewpoint
° C.
−23.6
−23.1
−22.6
−22.3
−21.9
−21.6
−21.4
−21.2


Evaporator exit gas temperature
° C.
−18.6
−18.1
−17.6
−17.3
−16.9
−16.6
−16.4
−16.2


Evaporator mean temperature
° C.
−30.3
−30.5
−30.6
−30.8
−31.1
−31.3
−31.5
−31.7


Evaporator glide (out-in)
K
13.5
14.8
16.0
17.2
18.3
19.3
20.2
21.1


Compressor suction pressure
bar
1.52
1.62
1.74
1.85
1.97
2.09
2.22
2.35


Compressor discharge pressure
bar
22.2
23.3
24.3
25.4
26.4
27.4
28.5
29.5


Suction line pressure drop
Pa/m
131
122
113
106
99
93
87
82


Pressure drop relative to reference

44.9%
41.6%
38.7%
36.1%
33.8%
31.8%
29.9%
28.2%


Condenser dew point
° C.
57.3
57.2
57.0
56.7
56.4
56.0
55.5
55.0


Condenser bubble point
° C.
30.2
29.3
28.6
27.9
27.4
26.9
26.5
26.1


Condenser exit liquid temperature
° C.
29.2
28.3
27.6
26.9
26.4
25.9
25.5
25.1


Condenser mean temperature
° C.
43.7
43.3
42.8
42.3
41.9
41.4
41.0
40.6


Condenser glide (in-out)
K
27.1
27.9
28.4
28.8
29.0
29.1
29.0
28.9
















TABLE 43







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 0-14% R-744, 10% R-32


and 20% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















0/10/20/70
2/10/20/68
4/10/20/66
6/10/20/64
8/10/20/62
10/10/20/60
12/10/20/58
14/10/20/56




















COP (heating)

2.13
2.17
2.19
2.21
2.23
2.24
2.25
2.26


COP (heating) relative to Reference

101.2%
102.7%
103.9%
104.8%
105.6%
106.2%
106.6%
107.0%


Volumetric heating capacity at suction
kJ/m3
917
1007
1101
1198
1299
1403
1509
1617


Capacity relative to Reference

104.3%
114.6%
125.3%
136.4%
147.9%
159.7%
171.7%
184.1%


Critical temperature
° C.
102.20
99.05
96.05
93.19
90.47
87.87
85.40
83.03


Critical pressure
bar
42.60
43.37
44.14
44.89
45.65
46.39
47.14
47.89


Condenser enthalpy change
kJ/kg
243.2
252.7
261.0
268.5
275.2
281.4
287.1
292.5


Pressure ratio

16.35
16.27
16.12
15.89
15.62
15.33
15.02
14.70


Refrigerant mass flow
kg/hr
29.6
28.5
27.6
26.8
26.2
25.6
25.1
24.6


Compressor discharge temperature
° C.
124.5
127.9
131.1
134.1
136.9
139.5
142.1
144.5


Evaporator inlet pressure
bar
0.89
0.95
1.03
1.11
1.19
1.29
1.38
1.48


Condenser inlet pressure
bar
13.7
14.8
15.9
17.0
18.2
19.3
20.4
21.5


Evaporator inlet temperature
° C.
−30.8
−31.4
−32.1
−32.8
−33.6
−34.3
−35.1
−35.9


Evaporator dewpoint
° C.
−28.7
−28.0
−27.4
−26.7
−26.1
−25.4
−24.8
−24.3


Evaporator exit gas temperature
° C.
−23.7
−23.0
−22.4
−21.7
−21.1
−20.4
−19.8
−19.3


Evaporator mean temperature
° C.
−29.7
−29.7
−29.8
−29.8
−29.8
−29.9
−30.0
−30.1


Evaporator glide (out-in)
K
2.1
3.4
4.7
6.1
7.5
8.9
10.3
11.6


Compressor suction pressure
bar
0.84
0.91
0.99
1.07
1.16
1.26
1.36
1.46


Compressor discharge pressure
bar
13.7
14.8
15.9
17.0
18.2
19.3
20.4
21.5


Suction line pressure drop
Pa/m
278
246
220
197
179
163
149
137


Pressure drop relative to reference

95.2%
84.2%
75.2%
67.6%
61.2%
55.8%
51.1%
47.0%


Condenser dew point
° C.
52.8
53.9
54.7
55.4
55.9
56.2
56.5
56.6


Condenser bubble point
° C.
46.2
42.8
40.0
37.7
35.7
34.1
32.7
31.5


Condenser exit liquid temperature
° C.
45.2
41.8
39.0
36.7
34.7
33.1
31.7
30.5


Condenser mean temperature
° C.
49.5
48.3
47.4
46.5
45.8
45.2
44.6
44.1


Condenser glide (in-out)
K
6.6
11.0
14.7
17.7
20.2
22.2
23.8
25.0
















TABLE 44







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 10% R-32


and 20% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















16/10/20/54
18/10/20/52
20/10/20/50
22/10/20/48
24/10/20/46
26/10/20/44
28/10/20/42
30/10/20/40




















COP (heating)

2.26
2.27
2.27
2.27
2.27
2.27
2.27
2.27


COP (heating) relative

107.3%
107.5%
107.6%
107.7%
107.7%
107.7%
107.7%
107.7%


to Reference


Volumetric heating
kJ/m3
1728
1841
1956
2073
2193
2314
2438
2563


capacity at suction


Capacity relative to

196.7%
209.5%
222.6%
236.0%
249.5%
263.3%
277.4%
291.7%


Reference


Critical temperature
° C.
80.77
78.61
76.54
74.56
72.66
70.83
69.08
67.39


Critical pressure
bar
48.63
49.37
50.12
50.86
51.60
52.34
53.08
53.82


Condenser enthalpy change
kJ/kg
297.5
302.2
306.7
311.0
315.1
319.1
322.9
326.5


Pressure ratio

14.38
14.06
13.74
13.43
13.13
12.84
12.55
12.27


Refrigerant mass flow
kg/hr
24.2
23.8
23.5
23.2
22.8
22.6
22.3
22.1


Compressor discharge
° C.
146.8
149.1
151.3
153.4
155.5
157.5
159.5
161.5


temperature


Evaporator inlet pressure
bar
1.59
1.70
1.82
1.94
2.06
2.19
2.32
2.46


Condenser inlet pressure
bar
22.6
23.6
24.7
25.8
26.8
27.9
28.9
30.0


Evaporator inlet
° C.
−36.7
−37.5
−38.2
−39.0
−39.7
−40.4
−41.0
−41.6


temperature


Evaporator dewpoint
° C.
−23.8
−23.3
−22.9
−22.5
−22.1
−21.9
−21.6
−21.4


Evaporator exit
° C.
−18.8
−18.3
−17.9
−17.5
−17.1
−16.9
−16.6
−16.4


gas temperature


Evaporator mean
° C.
−30.2
−30.4
−30.6
−30.7
−30.9
−31.1
−31.3
−31.5


temperature


Evaporator glide (out-in)
K
12.9
14.2
15.4
16.5
17.6
18.5
19.4
20.2


Compressor suction
bar
1.57
1.68
1.80
1.92
2.04
2.17
2.30
2.44


pressure


Compressor discharge
bar
22.6
23.6
24.7
25.8
26.8
27.9
28.9
30.0


pressure


Suction line pressure drop
Pa/m
127
118
109
102
96
90
85
80


Pressure drop relative

43.4%
40.3%
37.5%
35.0%
32.8%
30.8%
28.9%
27.3%


to reference


Condenser dew point
° C.
56.6
56.4
56.3
56.0
55.6
55.2
54.8
54.3


Condenser bubble point
° C.
30.5
29.7
28.9
28.3
27.8
27.3
26.9
26.6


Condenser exit
° C.
29.5
28.7
27.9
27.3
26.8
26.3
25.9
25.6


liquid temperature


Condenser mean
° C.
43.5
43.1
42.6
42.1
41.7
41.3
40.8
40.4


temperature


Condenser glide (in-out)
K
26.0
26.8
27.3
27.7
27.9
27.9
27.9
27.7
















TABLE 45







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 0-14% R-744, 10% R-32 and


30% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















0/10/30/60
2/10/30/58
4/10/30/56
6/10/30/54
8/10/30/52
10/10/30/50
12/10/30/48
14/10/30/46




















COP (heating)

2.14
2.17
2.19
2.21
2.23
2.24
2.25
2.26


COP (heating) relative to Reference

101.5%
102.9%
104.1%
105.0%
105.7%
106.3%
106.7%
107.1%


Volumetric heating capacity at
kJ/m3
948
1040
1135
1234
1337
1443
1551
1662


suction


Capacity relative to Reference

107.8%
118.3%
129.2%
140.5%
152.2%
164.2%
176.5%
189.2%


Critical temperature
° C.
101.47
98.35
95.39
92.57
89.89
87.33
84.88
82.55


Critical pressure
bar
43.07
43.84
44.60
45.36
46.12
46.87
47.63
48.38


Condenser enthalpy change
kJ/kg
245.0
254.4
262.7
270.2
276.9
283.0
288.7
294.0


Pressure ratio

16.08
16.00
15.85
15.64
15.38
15.09
14.79
14.47


Refrigerant mass flow
kg/hr
29.4
28.3
27.4
26.6
26.0
25.4
24.9
24.5


Compressor discharge temperature
° C.
125.6
129.0
132.2
135.2
137.9
140.6
143.1
145.5


Evaporator inlet pressure
bar
0.91
0.98
1.06
1.14
1.23
1.32
1.42
1.53


Condenser inlet pressure
bar
14.0
15.1
16.2
17.3
18.5
19.6
20.7
21.8


Evaporator inlet temperature
° C.
−30.8
−31.4
−32.0
−32.7
−33.4
−34.1
−34.9
−35.6


Evaporator dewpoint
° C.
−28.8
−28.2
−27.5
−26.9
−26.3
−25.6
−25.0
−24.5


Evaporator exit gas temperature
° C.
−23.8
−23.2
−22.5
−21.9
−21.3
−20.6
−20.0
−19.5


Evaporator mean temperature
° C.
−29.8
−29.8
−29.8
−29.8
−29.8
−29.9
−30.0
−30.1


Evaporator glide (out-in)
K
2.0
3.2
4.5
5.8
7.2
8.5
9.8
11.2


Compressor suction pressure
bar
0.87
0.94
1.02
1.11
1.20
1.30
1.40
1.51


Compressor discharge pressure
bar
14.0
15.1
16.2
17.3
18.5
19.6
20.7
21.8


Suction line pressure drop
Pa/m
267
237
212
191
173
158
144
133


Pressure drop relative to reference

91.6%
81.1%
72.5%
65.3%
59.2%
54.0%
49.5%
45.5%


Condenser dew point
° C.
52.3
53.3
54.1
54.8
55.3
55.6
55.8
55.9


Condenser bubble point
° C.
46.4
43.0
40.2
37.9
35.9
34.3
33.0
31.8


Condenser exit liquid temperature
° C.
45.4
42.0
39.2
36.9
34.9
33.3
32.0
30.8


Condenser mean temperature
° C.
49.3
48.1
47.2
46.3
45.6
45.0
44.4
43.8


Condenser glide (in-out)
K
5.9
10.3
13.9
16.9
19.3
21.3
22.9
24.1
















TABLE 46







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 10% R-32


and 30% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight




















24/
26/
28/
30/



16/10/30/44
18/10/30/42
20/10/30/40
22/10/30/38
10/30/36
10/30/34
10/30/32
10/30/30




















COP (heating)

2.26
2.27
2.27
2.27
2.27
2.28
2.27
2.27


COP (heating) relative to Reference

107.4%
107.6%
107.7%
107.8%
107.9%
107.9%
107.9%
107.8%


Volumetric heating capacity at
kJ/m3
1776
1892
2011
2131
2254
2379
2507
2637


suction


Capacity relative to Reference

202.1%
215.4%
228.8%
242.6%
256.5%
270.8%
285.3%
300.1%


Critical temperature
° C.
80.32
78.19
76.15
74.19
72.31
70.50
68.77
67.11


Critical pressure
bar
49.13
49.88
50.62
51.37
52.12
52.87
53.61
54.36


Condenser enthalpy change
kJ/kg
298.9
303.6
308.0
312.2
316.3
320.1
323.8
327.3


Pressure ratio

14.15
13.83
13.52
13.21
12.91
12.61
12.33
12.05


Refrigerant mass flow
kg/hr
24.1
23.7
23.4
23.1
22.8
22.5
22.2
22.0


Compressor discharge temperature
° C.
147.8
150.0
152.1
154.2
156.3
158.2
160.2
162.1


Evaporator inlet pressure
bar
1.64
1.75
1.87
1.99
2.12
2.26
2.39
2.54


Condenser inlet pressure
bar
22.9
24.0
25.0
26.1
27.2
28.3
29.3
30.4


Evaporator inlet temperature
° C.
−36.4
−37.1
−37.9
−38.6
−39.3
−39.9
−40.5
−41.1


Evaporator dewpoint
° C.
−24.0
−23.5
−23.1
−22.7
−22.4
−22.1
−21.8
−21.6


Evaporator exit gas temperature
° C.
−19.0
−18.5
−18.1
−17.7
−17.4
−17.1
−16.8
−16.6


Evaporator mean temperature
° C.
−30.2
−30.3
−30.5
−30.6
−30.8
−31.0
−31.2
−31.3


Evaporator glide (out-in)
K
12.4
13.6
14.8
15.9
16.9
17.9
18.8
19.5


Compressor suction pressure
bar
1.62
1.73
1.85
1.98
2.11
2.24
2.38
2.52


Compressor discharge pressure
bar
22.9
24.0
25.0
26.1
27.2
28.3
29.3
30.4


Suction line pressure drop
Pa/m
123
114
106
99
93
87
82
77


Pressure drop relative to reference

42.1%
39.0%
36.3%
33.9%
31.8%
29.8%
28.1%
26.5%


Condenser dew point
° C.
55.9
55.8
55.6
55.3
55.0
54.6
54.2
53.7


Condenser bubble point
° C.
30.8
29.9
29.2
28.6
28.1
27.6
27.2
26.9


Condenser exit liquid temperature
° C.
29.8
28.9
28.2
27.6
27.1
26.6
26.2
25.9


Condenser mean temperature
° C.
43.3
42.9
42.4
42.0
41.5
41.1
40.7
40.3


Condenser glide (in-out)
K
25.1
25.8
26.4
26.7
26.9
27.0
26.9
26.8
















TABLE 47







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 0-14% R-744, 10% R-32 and


40% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















0/10/40/50
2/10/40/48
4/10/40/46
6/10/40/44
8/10/40/42
10/10/40/40
12/10/40/38
14/10/40/36




















COP (heating)

2.14
2.17
2.20
2.22
2.23
2.24
2.25
2.26


COP (heating) relative to Reference

101.7%
103.2%
104.3%
105.1%
105.9%
106.4%
106.9%
107.2%


Volumetric heating capacity at suction
kJ/m3
976
1069
1167
1267
1372
1480
1591
1704


Capacity relative to Reference

111.1%
121.7%
132.8%
144.2%
156.1%
168.4%
181.1%
193.9%


Critical temperature
° C.
100.75
97.68
94.76
91.98
89.33
86.81
84.40
82.10


Critical pressure
bar
43.42
44.20
44.97
45.74
46.51
47.27
48.04
48.80


Condenser enthalpy change
kJ/kg
247.0
256.4
264.8
272.2
278.9
285.0
290.6
295.9


Pressure ratio

15.84
15.77
15.63
15.43
15.18
14.89
14.59
14.28


Refrigerant mass flow
kg/hr
29.1
28.1
27.2
26.5
25.8
25.3
24.8
24.3


Compressor discharge temperature
° C.
126.7
130.1
133.3
136.3
139.1
141.7
144.2
146.6


Evaporator inlet pressure
bar
0.94
1.01
1.09
1.17
1.26
1.36
1.46
1.57


Condenser inlet pressure
bar
14.2
15.3
16.4
17.6
18.7
19.8
21.0
22.1


Evaporator inlet temperature
° C.
−30.7
−31.3
−31.9
−32.6
−33.3
−34.0
−34.7
−35.4


Evaporator dewpoint
° C.
−28.9
−28.3
−27.7
−27.1
−26.4
−25.8
−25.2
−24.7


Evaporator exit gas temperature
° C.
−23.9
−23.3
−22.7
−22.1
−21.4
−20.8
−20.2
−19.7


Evaporator mean temperature
° C.
−29.8
−29.8
−29.8
−29.8
−29.9
−29.9
−30.0
−30.1


Evaporator glide (out-in)
K
1.8
3.0
4.2
5.5
6.9
8.2
9.5
10.8


Compressor suction pressure
bar
0.90
0.97
1.05
1.14
1.23
1.33
1.44
1.55


Compressor discharge pressure
bar
14.2
15.3
16.4
17.6
18.7
19.8
21.0
22.1


Suction line pressure drop
Pa/m
258
229
205
185
168
153
140
129


Pressure drop relative to reference

88.4%
78.4%
70.2%
63.3%
57.4%
52.3%
48.0%
44.2%


Condenser dew point
° C.
51.7
52.7
53.5
54.2
54.7
55.0
55.2
55.3


Condenser bubble point
° C.
46.5
43.1
40.3
38.0
36.1
34.5
33.1
31.9


Condenser exit liquid temperature
° C.
45.5
42.1
39.3
37.0
35.1
33.5
32.1
30.9


Condenser mean temperature
° C.
49.1
47.9
46.9
46.1
45.4
44.7
44.2
43.6


Condenser glide (in-out)
K
5.3
9.6
13.2
16.2
18.6
20.6
22.1
23.4
















TABLE 48







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 10% R-32


and 40% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight




















24/
26/
28/
30/



16/10/40/34
18/10/40/32
20/10/40/30
22/10/40/28
10/40/26
10/40/24
10/40/22
10/40/20




















COP (heating)

2.27
2.27
2.27
2.28
2.28
2.28
2.28
2.28


COP (heating) relative to Reference

107.5%
107.7%
107.9%
108.0%
108.1%
108.1%
108.1%
108.0%


Volumetric heating capacity at
kJ/m3
1820
1939
2060
2184
2309
2437
2569
2701


suction


Capacity relative to Reference

207.2%
220.7%
234.5%
248.5%
262.8%
277.4%
292.3%
307.4%


Critical temperature
° C.
79.90
77.79
75.77
73.84
71.98
70.20
68.49
66.84


Critical pressure
bar
49.56
50.32
51.07
51.83
52.59
53.34
54.10
54.85


Condenser enthalpy change
kJ/kg
300.8
305.4
309.8
313.9
317.9
321.6
325.2
328.7


Pressure ratio

13.97
13.65
13.34
13.03
12.73
12.44
12.15
11.87


Refrigerant mass flow
kg/hr
23.9
23.6
23.2
22.9
22.7
22.4
22.1
21.9


Compressor discharge temperature
° C.
148.8
151.0
153.1
155.2
157.2
159.2
161.0
162.9


Evaporator inlet pressure
bar
1.68
1.80
1.92
2.05
2.18
2.31
2.46
2.60


Condenser inlet pressure
bar
23.2
24.3
25.4
26.5
27.5
28.6
29.7
30.8


Evaporator inlet temperature
° C.
−36.2
−36.9
−37.6
−38.3
−39.0
−39.6
−40.2
−40.8


Evaporator dewpoint
° C.
−24.2
−23.7
−23.3
−22.9
−22.5
−22.2
−21.9
−21.7


Evaporator exit gas temperature
° C.
−19.2
−18.7
−18.3
−17.9
−17.5
−17.2
−16.9
−16.7


Evaporator mean temperature
° C.
−30.2
−30.3
−30.4
−30.6
−30.8
−30.9
−31.1
−31.2


Evaporator glide (out-in)
K
12.0
13.2
14.3
15.4
16.5
17.4
18.3
19.1


Compressor suction pressure
bar
1.66
1.78
1.90
2.03
2.16
2.30
2.44
2.59


Compressor discharge pressure
bar
23.2
24.3
25.4
26.5
27.5
28.6
29.7
30.8


Suction line pressure drop
Pa/m
119
111
103
96
90
85
80
75


Pressure drop relative to reference

40.9%
37.9%
35.3%
33.0%
30.9%
29.0%
27.3%
25.8%


Condenser dew point
° C.
55.3
55.2
55.1
54.8
54.5
54.1
53.6
53.2


Condenser bubble point
° C.
31.0
30.1
29.4
28.8
28.3
27.8
27.4
27.1


Condenser exit liquid temperature
° C.
30.0
29.1
28.4
27.8
27.3
26.8
26.4
26.1


Condenser mean temperature
° C.
43.1
42.7
42.2
41.8
41.4
40.9
40.5
40.1


Condenser glide (in-out)
K
24.4
25.1
25.7
26.0
26.2
26.3
26.2
26.1
















TABLE 49







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 0-14% R-744, 10% R-32 and


50% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















0/10/50/40
2/10/50/38
4/10/50/36
6/10/50/34
8/10/50/32
10/10/50/30
12/10/50/28
14/10/50/26




















COP (heating)

2.15
2.18
2.20
2.22
2.24
2.25
2.26
2.26


COP (heating) relative to Reference

102.0%
103.4%
104.5%
105.4%
106.1%
106.6%
107.1%
107.4%


Volumetric heating capacity at suction
kJ/m3
1001
1096
1195
1297
1403
1513
1626
1741


Capacity relative to Reference

113.9%
124.7%
136.0%
147.6%
159.7%
172.2%
185.0%
198.1%


Critical temperature
° C.
100.04
97.02
94.14
91.41
88.80
86.31
83.94
81.67


Critical pressure
bar
43.67
44.47
45.25
46.04
46.82
47.60
48.37
49.15


Condenser enthalpy change
kJ/kg
249.3
258.7
267.1
274.5
281.2
287.3
293.0
298.2


Pressure ratio

15.64
15.58
15.45
15.26
15.01
14.74
14.44
14.13


Refrigerant mass flow
kg/hr
28.9
27.8
27.0
26.2
25.6
25.1
24.6
24.1


Compressor discharge temperature
° C.
127.9
131.4
134.6
137.6
140.4
143.0
145.4
147.8


Evaporator inlet pressure
bar
0.96
1.03
1.11
1.20
1.29
1.39
1.49
1.60


Condenser inlet pressure
bar
14.4
15.5
16.6
17.8
18.9
20.1
21.2
22.3


Evaporator inlet temperature
° C.
−30.7
−31.3
−31.9
−32.5
−33.2
−33.9
−34.6
−35.3


Evaporator dewpoint
° C.
−29.0
−28.5
−27.8
−27.2
−26.6
−26.0
−25.4
−24.8


Evaporator exit gas temperature
° C.
−24.0
−23.5
−22.8
−22.2
−21.6
−21.0
−20.4
−19.8


Evaporator mean temperature
° C.
−29.9
−29.9
−29.9
−29.9
−29.9
−29.9
−30.0
−30.1


Evaporator glide (out-in)
K
1.6
2.8
4.0
5.3
6.6
7.9
9.2
10.4


Compressor suction pressure
bar
0.92
0.99
1.08
1.17
1.26
1.36
1.47
1.58


Compressor discharge pressure
bar
14.4
15.5
16.6
17.8
18.9
20.1
21.2
22.3


Suction line pressure drop
Pa/m
250
222
199
179
163
149
136
126


Pressure drop relative to reference

85.6%
76.0%
68.1%
61.4%
55.8%
50.9%
46.7%
43.0%


Condenser dew point
° C.
51.2
52.2
53.0
53.7
54.2
54.5
54.8
54.9


Condenser bubble point
° C.
46.6
43.2
40.4
38.1
36.1
34.5
33.1
32.0


Condenser exit liquid temperature
° C.
45.6
42.2
39.4
37.1
35.1
33.5
32.1
31.0


Condenser mean temperature
° C.
48.9
47.7
46.7
45.9
45.2
44.5
43.9
43.4


Condenser glide (in-out)
K
4.7
9.0
12.7
15.6
18.1
20.0
21.6
22.9
















TABLE 50







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 10% R-32


and 50% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight




















24/
26/
28/
30/



16/10/50/24
18/10/50/22
20/10/50/20
22/10/50/18
10/50/16
10/50/14
10/50/12
10/50/10




















COP (heating)

2.27
2.28
2.28
2.28
2.28
2.28
2.28
2.28


COP (heating) relative to Reference

107.7%
107.9%
108.1%
108.2%
108.2%
108.3%
108.3%
108.2%


Volumetric heating capacity at
kJ/m3
1859
1980
2103
2229
2357
2487
2620
2755


suction


Capacity relative to Reference

211.6%
225.4%
239.4%
253.7%
268.2%
283.1%
298.2%
313.5%


Critical temperature
° C.
79.50
77.42
75.43
73.52
71.69
69.93
68.24
66.61


Critical pressure
bar
49.92
50.69
51.46
52.23
53.00
53.77
54.53
55.30


Condenser enthalpy change
kJ/kg
303.0
307.6
311.9
316.0
320.0
323.7
327.3
330.7


Pressure ratio

13.82
13.50
13.19
12.89
12.59
12.31
12.02
11.75


Refrigerant mass flow
kg/hr
23.8
23.4
23.1
22.8
22.5
22.2
22.0
21.8


Compressor discharge temperature
° C.
150.1
152.2
154.3
156.4
158.3
160.3
162.1
164.0


Evaporator inlet pressure
bar
1.72
1.84
1.96
2.09
2.22
2.36
2.51
2.66


Condenser inlet pressure
bar
23.4
24.5
25.6
26.7
27.8
28.9
30.0
31.1


Evaporator inlet temperature
° C.
−36.0
−36.7
−37.4
−38.1
−38.8
−39.4
−40.0
−40.6


Evaporator dewpoint
° C.
−24.3
−23.8
−23.4
−23.0
−22.6
−22.3
−22.0
−21.8


Evaporator exit gas temperature
° C.
−19.3
−18.8
−18.4
−18.0
−17.6
−17.3
−17.0
−16.8


Evaporator mean temperature
° C.
−30.2
−30.3
−30.4
−30.6
−30.7
−30.9
−31.0
−31.2


Evaporator glide (out-in)
K
11.7
12.9
14.0
15.1
16.2
17.1
18.0
18.8


Compressor suction pressure
bar
1.70
1.82
1.94
2.07
2.21
2.35
2.49
2.64


Compressor discharge pressure
bar
23.4
24.5
25.6
26.7
27.8
28.9
30.0
31.1


Suction line pressure drop
Pa/m
116
108
101
94
88
83
78
73


Pressure drop relative to reference

39.8%
36.9%
34.4%
32.2%
30.1%
28.3%
26.7%
25.2%


Condenser dew point
° C.
54.9
54.8
54.6
54.4
54.0
53.7
53.2
52.8


Condenser bubble point
° C.
31.0
30.2
29.4
28.8
28.3
27.9
27.5
27.2


Condenser exit liquid temperature
° C.
30.0
29.2
28.4
27.8
27.3
26.9
26.5
26.2


Condenser mean temperature
° C.
42.9
42.5
42.0
41.6
41.2
40.8
40.4
40.0


Condenser glide (in-out)
K
23.9
24.6
25.2
25.5
25.7
25.8
25.8
25.6
















TABLE 51







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 0-14% R-744, 15% R-32 and


5% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















0/15/5/80
2/15/5/78
4/15/5/76
6/15/5/74
8/15/5/72
10/15/5/70
12/15/5/68
14/15/5/66




















COP (heating)

2.17
2.19
2.21
2.23
2.24
2.26
2.26
2.27


COP (heating) relative to Reference

102.8%
104.0%
105.0%
105.8%
106.5%
107.0%
107.3%
107.6%


Volumetric heating capacity at suction
kJ/m3
983
1075
1170
1267
1368
1471
1575
1682


Capacity relative to Reference

111.9%
122.3%
133.1%
144.2%
155.7%
167.4%
179.2%
191.4%


Critical temperature
° C.
100.70
97.79
94.99
92.31
89.74
87.29
84.94
82.70


Critical pressure
bar
43.58
44.39
45.17
45.95
46.71
47.47
48.22
48.97


Condenser enthalpy change
kJ/kg
253.1
261.7
269.4
276.4
282.8
288.7
294.3
299.5


Pressure ratio

15.94
15.80
15.61
15.37
15.11
14.82
14.54
14.25


Refrigerant mass flow
kg/hr
28.4
27.5
26.7
26.1
25.5
24.9
24.5
24.0


Compressor discharge temperature
° C.
127.4
130.5
133.5
136.4
139.1
141.6
144.1
146.5


Evaporator inlet pressure
bar
0.94
1.01
1.09
1.17
1.26
1.35
1.45
1.55


Condenser inlet pressure
bar
14.3
15.3
16.4
17.5
18.6
19.6
20.7
21.8


Evaporator inlet temperature
° C.
−31.5
−32.2
−33.0
−33.7
−34.5
−35.3
−36.0
−36.8


Evaporator dewpoint
° C.
−27.9
−27.2
−26.6
−26.0
−25.3
−24.8
−24.2
−23.7


Evaporator exit gas temperature
° C.
−22.9
−22.2
−21.6
−21.0
−20.3
−19.8
−19.2
−18.7


Evaporator mean temperature
° C.
−29.7
−29.7
−29.8
−29.8
−29.9
−30.0
−30.1
−30.3


Evaporator glide (out-in)
K
3.7
5.0
6.4
7.8
9.1
10.5
11.8
13.1


Compressor suction pressure
bar
0.89
0.97
1.05
1.14
1.23
1.32
1.42
1.53


Compressor discharge pressure
bar
14.3
15.3
16.4
17.5
18.6
19.6
20.7
21.8


Suction line pressure drop
Pa/m
251
224
202
183
166
152
140
130


Pressure drop relative to reference

86.1%
76.8%
69.1%
62.6%
57.0%
52.2%
48.0%
44.4%


Condenser dew point
° C.
53.3
54.2
54.9
55.4
55.8
56.1
56.2
56.2


Condenser bubble point
° C.
44.2
41.3
38.9
36.8
35.1
33.6
32.4
31.3


Condenser exit liquid temperature
° C.
43.2
40.3
37.9
35.8
34.1
32.6
31.4
30.3


Condenser mean temperature
° C.
48.8
47.7
46.9
46.1
45.4
44.8
44.3
43.8


Condenser glide (in-out)
K
9.0
12.8
16.0
18.6
20.7
22.5
23.9
25.0
















TABLE 52







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 15% R-32


and 5% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















16/15/5/64
18/15/5/62
20/15/5/60
22/15/5/58
24/15/5/56
26/15/5/54
28/15/5/52
30/15/5/50




















COP (heating)

2.27
2.28
2.28
2.28
2.28
2.28
2.28
2.28


COP (heating) relative to Reference

107.8%
108.0%
108.1%
108.1%
108.1%
108.1%
108.0%
107.9%


Volumetric heating capacity at suction
kJ/m3
1790
1901
2014
2128
2244
2362
2483
2606


Capacity relative to Reference

203.8%
216.4%
229.2%
242.2%
255.4%
268.9%
282.6%
296.5%


Critical temperature
° C.
80.54
78.48
76.50
74.60
72.77
71.02
69.33
67.70


Critical pressure
bar
49.71
50.46
51.20
51.94
52.68
53.42
54.16
54.90


Condenser enthalpy change
kJ/kg
304.5
309.2
313.7
318.1
322.2
326.2
330.1
333.8


Pressure ratio

13.96
13.67
13.38
13.10
12.83
12.56
12.30
12.05


Refrigerant mass flow
kg/hr
23.6
23.3
22.9
22.6
22.3
22.1
21.8
21.6


Compressor discharge temperature
° C.
148.9
151.1
153.3
155.5
157.6
159.7
161.7
163.7


Evaporator inlet pressure
bar
1.65
1.76
1.88
1.99
2.11
2.24
2.37
2.50


Condenser inlet pressure
bar
22.8
23.8
24.9
25.9
26.9
27.9
29.0
30.0


Evaporator inlet temperature
° C.
−37.6
−38.3
−39.1
−39.8
−40.4
−41.0
−41.6
−42.1


Evaporator dewpoint
° C.
−23.3
−22.8
−22.5
−22.1
−21.9
−21.6
−21.4
−21.2


Evaporator exit gas temperature
° C.
−18.3
−17.8
−17.5
−17.1
−16.9
−16.6
−16.4
−16.2


Evaporator mean temperature
° C.
−30.4
−30.6
−30.8
−30.9
−31.1
−31.3
−31.5
−31.7


Evaporator glide (out-in)
K
14.3
15.5
16.6
17.6
18.5
19.4
20.2
20.9


Compressor suction pressure
bar
1.63
1.74
1.86
1.98
2.10
2.22
2.35
2.49


Compressor discharge pressure
bar
22.8
23.8
24.9
25.9
26.9
27.9
29.0
30.0


Suction line pressure drop
Pa/m
120
112
105
98
92
87
82
77


Pressure drop relative to reference

41.2%
38.3%
35.8%
33.5%
31.5%
29.6%
28.0%
26.4%


Condenser dew point
° C.
56.2
56.0
55.8
55.5
55.1
54.7
54.3
53.7


Condenser bubble point
° C.
30.3
29.5
28.8
28.2
27.7
27.3
26.9
26.5


Condenser exit liquid temperature
° C.
29.3
28.5
27.8
27.2
26.7
26.3
25.9
25.5


Condenser mean temperature
° C.
43.3
42.8
42.3
41.9
41.4
41.0
40.6
40.1


Condenser glide (in-out)
K
25.8
26.5
27.0
27.3
27.4
27.5
27.4
27.2
















TABLE 53







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 0-14% R-744, 15% R-32


and 10% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















0/15/10/75
2/15/10/73
4/15/10/71
6/15/10/69
8/15/10/67
10/15/10/65
12/15/10/63
14/15/10/61




















COP (heating)

2.17
2.20
2.22
2.23
2.25
2.26
2.26
2.27


COP (heating) relative to Reference

102.9%
104.1%
105.1%
105.9%
106.5%
107.0%
107.4%
107.7%


Volumetric heating capacity at suction
kJ/m3
1001
1093
1188
1287
1389
1493
1599
1707


Capacity relative to Reference

113.9%
124.4%
135.2%
146.5%
158.0%
169.9%
182.0%
194.3%


Critical temperature
° C.
100.38
97.46
94.67
92.00
89.45
87.01
84.68
82.44


Critical pressure
bar
43.87
44.66
45.43
46.20
46.96
47.71
48.47
49.22


Condenser enthalpy change
kJ/kg
253.8
262.3
270.0
277.0
283.4
289.3
294.9
300.1


Pressure ratio

15.79
15.65
15.47
15.24
14.97
14.70
14.41
14.12


Refrigerant mass flow
kg/hr
28.4
27.4
26.7
26.0
25.4
24.9
24.4
24.0


Compressor discharge temperature
° C.
127.8
131.0
134.0
136.8
139.5
142.1
144.5
146.9


Evaporator inlet pressure
bar
0.95
1.03
1.10
1.19
1.28
1.37
1.47
1.57


Condenser inlet pressure
bar
14.4
15.5
16.6
17.6
18.7
19.8
20.9
21.9


Evaporator inlet temperature
° C.
−31.5
−32.2
−32.9
−33.6
−34.4
−35.1
−35.9
−36.6


Evaporator dewpoint
° C.
−28.0
−27.3
−26.7
−26.1
−25.5
−24.9
−24.3
−23.8


Evaporator exit gas temperature
° C.
−23.0
−22.3
−21.7
−21.1
−20.5
−19.9
−19.3
−18.8


Evaporator mean temperature
° C.
−29.7
−29.8
−29.8
−29.8
−29.9
−30.0
−30.1
−30.2


Evaporator glide (out-in)
K
3.6
4.9
6.2
7.6
8.9
10.2
11.5
12.8


Compressor suction pressure
bar
0.91
0.99
1.07
1.16
1.25
1.35
1.45
1.55


Compressor discharge pressure
bar
14.4
15.5
16.6
17.6
18.7
19.8
20.9
21.9


Suction line pressure drop
Pa/m
247
220
198
180
164
150
138
128


Pressure drop relative to reference

84.5%
75.4%
67.9%
61.5%
56.0%
51.3%
47.2%
43.7%


Condenser dew point
° C.
53.0
53.8
54.5
55.0
55.4
55.7
55.8
55.9


Condenser bubble point
° C.
44.4
41.5
39.0
37.0
35.3
33.8
32.5
31.5


Condenser exit liquid temperature
° C.
43.4
40.5
38.0
36.0
34.3
32.8
31.5
30.5


Condenser mean temperature
° C.
48.7
47.6
46.8
46.0
45.4
44.7
44.2
43.7


Condenser glide (in-out)
K
8.6
12.3
15.5
18.0
20.2
21.9
23.3
24.4
















TABLE 54







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 15% R-32


and 10% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight




















24/
26/
28/
30/



16/15/10/59
18/15/10/57
20/15/10/55
22/15/10/53
15/10/51
15/10/49
15/10/47
15/10/45




















COP (heating)

2.27
2.28
2.28
2.28
2.28
2.28
2.28
2.28


COP (heating) relative to Reference

107.9%
108.0%
108.1%
108.2%
108.2%
108.1%
108.1%
108.0%


Volumetric heating capacity at
kJ/m3
1817
1930
2044
2161
2279
2400
2523
2648


suction


Capacity relative to Reference

206.8%
219.6%
232.7%
245.9%
259.4%
273.1%
287.1%
301.4%


Critical temperature
° C.
80.30
78.25
76.28
74.40
72.58
70.84
69.16
67.54


Critical pressure
bar
49.96
50.71
51.45
52.19
52.94
53.68
54.42
55.16


Condenser enthalpy change
kJ/kg
305.0
309.7
314.1
318.4
322.5
326.4
330.2
333.8


Pressure ratio

13.83
13.54
13.25
12.97
12.70
12.43
12.17
11.91


Refrigerant mass flow
kg/hr
23.6
23.3
22.9
22.6
22.3
22.1
21.8
21.6


Compressor discharge temperature
° C.
149.3
151.5
153.7
155.8
157.9
159.9
161.9
163.9


Evaporator inlet pressure
bar
1.68
1.79
1.91
2.03
2.15
2.28
2.41
2.55


Condenser inlet pressure
bar
23.0
24.0
25.1
26.1
27.1
28.2
29.2
30.2


Evaporator inlet temperature
° C.
−37.4
−38.1
−38.8
−39.5
−40.1
−40.7
−41.2
−41.7


Evaporator dewpoint
° C.
−23.4
−23.0
−22.6
−22.3
−22.0
−21.7
−21.5
−21.4


Evaporator exit gas temperature
° C.
−18.4
−18.0
−17.6
−17.3
−17.0
−16.7
−16.5
−16.4


Evaporator mean temperature
° C.
−30.4
−30.5
−30.7
−30.9
−31.1
−31.2
−31.4
−31.5


Evaporator glide (out-in)
K
14.0
15.1
16.2
17.2
18.1
18.9
19.7
20.4


Compressor suction pressure
bar
1.66
1.77
1.89
2.01
2.14
2.27
2.40
2.54


Compressor discharge pressure
bar
23.0
24.0
25.1
26.1
27.1
28.2
29.2
30.2


Suction line pressure drop
Pa/m
118
110
103
96
90
85
80
76


Pressure drop relative to reference

40.5%
37.7%
35.2%
33.0%
31.0%
29.2%
27.5%
26.0%


Condenser dew point
° C.
55.8
55.6
55.4
55.1
54.8
54.3
53.9
53.4


Condenser bubble point
° C.
30.5
29.7
29.0
28.4
27.9
27.5
27.1
26.8


Condenser exit liquid temperature
° C.
29.5
28.7
28.0
27.4
26.9
26.5
26.1
25.8


Condenser mean temperature
° C.
43.2
42.7
42.2
41.8
41.3
40.9
40.5
40.1


Condenser glide (in-out)
K
25.3
25.9
26.4
26.7
26.8
26.9
26.8
26.6
















TABLE 55







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 0-14% R-744, 15% R-32 and


20% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















0/15/20/65
2/15/20/63
4/15/20/61
6/15/20/59
8/15/20/57
10/15/20/55
12/15/20/53
14/15/20/51




















COP (heating)

2.17
2.20
2.22
2.23
2.25
2.26
2.27
2.27


COP (heating) relative to Reference

103.1%
104.3%
105.2%
106.0%
106.6%
107.1%
107.4%
107.7%


Volumetric heating capacity at suction
kJ/m3
1033
1127
1224
1325
1428
1534
1643
1755


Capacity relative to Reference

117.6%
128.3%
139.3%
150.7%
162.5%
174.6%
187.0%
199.7%


Critical temperature
° C.
99.72
96.82
94.05
91.41
88.89
86.48
84.18
81.97


Critical pressure
bar
44.35
45.12
45.89
46.65
47.41
48.17
48.92
49.67


Condenser enthalpy change
kJ/kg
255.3
263.9
271.6
278.5
284.9
290.8
296.3
301.4


Pressure ratio

15.52
15.39
15.22
14.99
14.74
14.46
14.18
13.89


Refrigerant mass flow
kg/hr
28.2
27.3
26.5
25.9
25.3
24.8
24.3
23.9


Compressor discharge temperature
° C.
128.8
132.0
135.0
137.8
140.5
143.0
145.5
147.8


Evaporator inlet pressure
bar
0.99
1.06
1.14
1.23
1.32
1.41
1.52
1.62


Condenser inlet pressure
bar
14.7
15.7
16.8
17.9
19.0
20.1
21.2
22.2


Evaporator inlet temperature
° C.
−31.4
−32.1
−32.8
−33.4
−34.1
−34.8
−35.6
−36.3


Evaporator dewpoint
° C.
−28.1
−27.5
−26.9
−26.3
−25.7
−25.1
−24.6
−24.1


Evaporator exit gas temperature
° C.
−23.1
−22.5
−21.9
−21.3
−20.7
−20.1
−19.6
−19.1


Evaporator mean temperature
° C.
−29.8
−29.8
−29.8
−29.9
−29.9
−30.0
−30.1
−30.2


Evaporator glide (out-in)
K
3.3
4.6
5.9
7.2
8.4
9.7
11.0
12.2


Compressor suction pressure
bar
0.94
1.02
1.11
1.20
1.29
1.39
1.49
1.60


Compressor discharge pressure
bar
14.7
15.7
16.8
17.9
19.0
20.1
21.2
22.2


Suction line pressure drop
Pa/m
238
213
192
174
158
145
134
124


Pressure drop relative to reference

81.4%
72.8%
65.6%
59.5%
54.3%
49.7%
45.8%
42.3%


Condenser dew point
° C.
52.4
53.2
53.8
54.4
54.7
55.0
55.1
55.2


Condenser bubble point
° C.
44.7
41.8
39.3
37.3
35.6
34.1
32.9
31.8


Condenser exit liquid temperature
° C.
43.7
40.8
38.3
36.3
34.6
33.1
31.9
30.8


Condenser mean temperature
° C.
48.5
47.5
46.6
45.8
45.2
44.6
44.0
43.5


Condenser glide (in-out)
K
7.7
11.4
14.5
17.1
19.2
20.9
22.3
23.4
















TABLE 56







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 15% R-32


and 20% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight





















26/
28/
30/



16/15/20/49
18/15/20/47
20/15/20/45
22/15/20/43
24/15/20/41
15/20/39
15/20/37
15/20/35




















COP (heating)

2.28
2.28
2.28
2.28
2.28
2.28
2.28
2.28


COP (heating) relative to

108.0%
108.1%
108.2%
108.3%
108.3%
108.3%
108.3%
108.2%


Reference


Volumetric heating capacity at
kJ/m3
1868
1984
2102
2222
2345
2470
2598
2729


suction


Capacity relative to Reference

212.6%
225.8%
239.2%
252.9%
266.9%
281.1%
295.7%
310.5%


Critical temperature
° C.
79.86
77.83
75.88
74.02
72.22
70.50
68.84
67.24


Critical pressure
bar
50.42
51.17
51.92
52.67
53.42
54.16
54.91
55.65


Condenser enthalpy change
kJ/kg
306.2
310.8
315.2
319.4
323.4
327.2
330.8
334.3


Pressure ratio

13.60
13.31
13.02
12.74
12.47
12.20
11.93
11.67


Refrigerant mass flow
kg/hr
23.5
23.2
22.8
22.5
22.3
22.0
21.8
21.5


Compressor discharge
° C.
150.1
152.3
154.4
156.5
158.5
160.5
162.4
164.3


temperature


Evaporator inlet pressure
bar
1.73
1.85
1.97
2.09
2.22
2.36
2.49
2.64


Condenser inlet pressure
bar
23.3
24.4
25.4
26.5
27.5
28.6
29.6
30.7


Evaporator inlet temperature
° C.
−37.0
−37.7
−38.3
−39.0
−39.6
−40.1
−40.6
−41.1


Evaporator dewpoint
° C.
−23.7
−23.2
−22.9
−22.5
−22.3
−22.0
−21.8
−21.6


Evaporator exit gas temperature
° C.
−18.7
−18.2
−17.9
−17.5
−17.3
−17.0
−16.8
−16.6


Evaporator mean temperature
° C.
−30.3
−30.5
−30.6
−30.8
−30.9
−31.1
−31.2
−31.3


Evaporator glide (out-in)
K
13.3
14.4
15.5
16.4
17.3
18.1
18.9
19.5


Compressor suction pressure
bar
1.71
1.83
1.95
2.08
2.21
2.34
2.48
2.63


Compressor discharge pressure
bar
23.3
24.4
25.4
26.5
27.5
28.6
29.6
30.7


Suction line pressure drop
Pa/m
115
107
100
93
88
83
78
74


Pressure drop relative to reference

39.3%
36.6%
34.2%
32.0%
30.0%
28.3%
26.7%
25.2%


Condenser dew point
° C.
55.1
54.9
54.7
54.4
54.1
53.7
53.2
52.7


Condenser bubble point
° C.
30.9
30.1
29.4
28.8
28.3
27.9
27.5
27.2


Condenser exit liquid temperature
° C.
29.9
29.1
28.4
27.8
27.3
26.9
26.5
26.2


Condenser mean temperature
° C.
43.0
42.5
42.1
41.6
41.2
40.8
40.4
40.0


Condenser glide (in-out)
K
24.2
24.9
25.3
25.6
25.8
25.8
25.7
25.5
















TABLE 57







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 0-14% R-744, 15% R-32 and


30% R-134a









Composition CO2/R-321R-134a/R-1234ze(E) % by weight
















0/15/30/55
2/15/30/53
4/15/30/51
6/15/30/49
8/15/30/47
10/15/30/45
12/15/30/43
14/15/30/41




















COP (heating)

2.18
2.20
2.22
2.24
2.25
2.26
2.27
2.27


COP (heating) relative to Reference

103.2%
104.4%
105.3%
106.1%
106.7%
107.2%
107.5%
107.8%


Volumetric heating capacity at suction
kJ/m3
1063
1158
1257
1359
1465
1573
1685
1799


Capacity relative to Reference

120.9%
131.8%
143.1%
154.7%
166.7%
179.0%
191.7%
204.7%


Critical temperature
° C.
99.07
96.20
93.47
90.86
88.37
85.99
83.71
81.53


Critical pressure
bar
44.72
45.49
46.26
47.03
47.79
48.55
49.31
50.07


Condenser enthalpy change
kJ/kg
257.1
265.7
273.4
280.3
286.7
292.5
298.0
303.1


Pressure ratio

15.28
15.17
15.00
14.79
14.54
14.27
13.99
13.70


Refrigerant mass flow
kg/hr
28.0
27.1
26.3
25.7
25.1
24.6
24.2
23.8


Compressor discharge temperature
° C.
129.9
133.1
136.1
138.9
141.6
144.1
146.5
148.9


Evaporator inlet pressure
bar
1.01
1.09
1.17
1.26
1.35
1.45
1.56
1.67


Condenser inlet pressure
bar
14.9
16.0
17.1
18.2
19.3
20.4
21.5
22.5


Evaporator inlet temperature
° C.
−31.3
−32.0
−32.6
−33.3
−33.9
−34.6
−35.3
−36.0


Evaporator dewpoint
° C.
−28.3
−27.7
−27.1
−26.5
−25.9
−25.4
−24.8
−24.4


Evaporator exit gas temperature
° C.
−23.3
−22.7
−22.1
−21.5
−20.9
−20.4
−19.8
−19.4


Evaporator mean temperature
° C.
−29.8
−29.8
−29.8
−29.9
−29.9
−30.0
−30.1
−30.2


Evaporator glide (out-in)
K
3.1
4.3
5.5
6.7
8.0
9.2
10.4
11.6


Compressor suction pressure
bar
0.97
1.05
1.14
1.23
1.33
1.43
1.53
1.65


Compressor discharge pressure
bar
14.9
16.0
17.1
18.2
19.3
20.4
21.5
22.5


Suction line pressure drop
Pa/m
230
206
186
169
154
141
130
120


Pressure drop relative to reference

78.8%
70.5%
63.6%
57.7%
52.7%
48.3%
44.5%
41.1%


Condenser dew point
° C.
51.8
52.6
53.2
53.7
54.1
54.4
54.5
54.5


Condenser bubble point
° C.
44.9
42.0
39.6
37.5
35.8
34.3
33.1
32.0


Condenser exit liquid temperature
° C.
43.9
41.0
38.6
36.5
34.8
33.3
32.1
31.0


Condenser mean temperature
° C.
48.3
47.3
46.4
45.6
45.0
44.3
43.8
43.3


Condenser glide (in-out)
K
6.9
10.6
13.7
16.2
18.3
20.0
21.4
22.5
















TABLE 58







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 15% R-32 and 30% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















16/15/
18/15/
20/15/
22/15/
24/15/
26/15/
28/15/
30/15/



30/39
30/37
30/35
30/33
30/31
30/29
30/27
30/25




















COP (heating)

2.28
2.28
2.28
2.29
2.29
2.29
2.29
2.29


COP (heating) relative to Reference

108.1%
108.2%
108.4%
108.4%
108.5%
108.5%
108.4%
108.4%


Volumetric heating capacity at suction
kJ/m3
1915
2034
2155
2279
2405
2534
2665
2800


Capacity relative to Reference

218.0%
231.5%
245.3%
259.4%
273.7%
288.4%
303.3%
318.6%


Critical temperature
° C.
79.44
77.44
75.52
73.68
71.90
70.20
68.56
66.98


Critical pressure
bar
50.83
51.59
52.34
53.10
53.85
54.61
55.36
56.12


Condenser enthalpy change
kJ/kg
307.9
312.4
316.7
320.8
324.7
328.4
332.0
335.4


Pressure ratio

13.41
13.12
12.83
12.55
12.28
12.01
11.74
11.49


Refrigerant mass flow
kg/hr
23.4
23.0
22.7
22.4
22.2
21.9
21.7
21.5


Compressor discharge temperature
° C.
151.1
153.3
155.4
157.4
159.4
161.3
163.2
165.0


Evaporator inlet pressure
bar
1.78
1.90
2.02
2.15
2.28
2.42
2.57
2.72


Condenser inlet pressure
bar
23.6
24.7
25.8
26.8
27.9
28.9
30.0
31.0


Evaporator inlet temperature
° C.
−36.6
−37.3
−37.9
−38.5
−39.1
−39.7
−40.2
−40.6


Evaporator dewpoint
° C.
−23.9
−23.5
−23.1
−22.8
−22.5
−22.2
−22.0
−21.8


Evaporator exit gas temperature
° C.
−18.9
−18.5
−18.1
−17.8
−17.5
−17.2
−17.0
−16.8


Evaporator mean temperature
° C.
−30.3
−30.4
−30.5
−30.7
−30.8
−30.9
−31.1
−31.2


Evaporator glide (out-in)
K
12.7
13.8
14.8
15.8
16.7
17.5
18.2
18.8


Compressor suction pressure
bar
1.76
1.88
2.01
2.14
2.27
2.41
2.55
2.70


Compressor discharge pressure
bar
23.6
24.7
25.8
26.8
27.9
28.9
30.0
31.0


Suction line pressure drop
Pa/m
112
104
97
91
85
80
76
72


Pressure drop relative to reference

38.2%
35.6%
33.2%
31.1%
29.2%
27.5%
25.9%
24.5%


Condenser dew point
° C.
54.5
54.3
54.1
53.8
53.5
53.1
52.7
52.2


Condenser bubble point
° C.
31.1
30.3
29.6
29.1
28.6
28.1
27.8
27.5


Condenser exit liquid temperature
° C.
30.1
29.3
28.6
28.1
27.6
27.1
26.8
26.5


Condenser mean temperature
° C.
42.8
42.3
41.9
41.4
41.0
40.6
40.2
39.8


Condenser glide (in-out)
K
23.4
24.0
24.5
24.8
25.0
25.0
24.9
24.7
















TABLE 59







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 0-14% R-744, 15% R-32 and 40% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















0/15/40/45
2/15/40/43
4/15/40/41
6/15/40/39
8/15/40/37
10/15/40/35
12/15/40/33
14/15/40/31




















COP (heating)

2.18
2.21
2.22
2.24
2.25
2.26
2.27
2.28


COP (heating) relative to Reference

103.4%
104.6%
105.5%
106.2%
106.8%
107.3%
107.7%
108.0%


Volumetric heating capacity at suction
kJ/m3
1089
1186
1286
1390
1498
1608
1722
1838


Capacity relative to Reference

124.0%
135.0%
146.4%
158.2%
170.4%
183.0%
196.0%
209.2%


Critical temperature
° C.
98.43
95.60
92.90
90.33
87.87
85.52
83.27
81.12


Critical pressure
bar
44.98
45.76
46.54
47.32
48.10
48.87
49.64
50.41


Condenser enthalpy change
kJ/kg
259.2
267.8
275.5
282.5
288.8
294.7
300.1
305.1


Pressure ratio

15.09
14.98
14.82
14.61
14.37
14.11
13.83
13.54


Refrigerant mass flow
kg/hr
27.8
26.9
26.1
25.5
24.9
24.4
24.0
23.6


Compressor discharge temperature
° C.
131.0
134.2
137.3
140.1
142.8
145.3
147.7
150.0


Evaporator inlet pressure
bar
1.04
1.11
1.20
1.29
1.38
1.48
1.59
1.70


Condenser inlet pressure
bar
15.1
16.2
17.3
18.4
19.5
20.6
21.7
22.8


Evaporator inlet temperature
° C.
−31.3
−31.8
−32.5
−33.1
−33.7
−34.4
−35.0
−35.7


Evaporator dewpoint
° C.
−28.5
−27.9
−27.3
−26.7
−26.1
−25.6
−25.1
−24.6


Evaporator exit gas temperature
° C.
−23.5
−22.9
−22.3
−21.7
−21.1
−20.6
−20.1
−19.6


Evaporator mean temperature
° C.
−29.9
−29.9
−29.9
−29.9
−29.9
−30.0
−30.1
−30.1


Evaporator glide (out-in)
K
2.8
4.0
5.1
6.4
7.6
8.8
10.0
11.1


Compressor suction pressure
bar
1.00
1.08
1.17
1.26
1.36
1.46
1.57
1.68


Compressor discharge pressure
bar
15.1
16.2
17.3
18.4
19.5
20.6
21.7
22.8


Suction line pressure drop
Pa/m
223
200
180
164
150
137
126
117


Pressure drop relative to reference

76.4%
68.5%
61.8%
56.1%
51.2%
47.0%
43.3%
40.0%


Condenser dew point
° C.
51.2
52.0
52.7
53.2
53.6
53.8
54.0
54.0


Condenser bubble point
° C.
45.0
42.1
39.7
37.6
35.9
34.4
33.2
32.1


Condenser exit liquid temperature
° C.
44.0
41.1
38.7
36.6
34.9
33.4
32.2
31.1


Condenser mean temperature
° C.
48.1
47.1
46.2
45.4
44.7
44.1
43.6
43.1


Condenser glide (in-out)
K
6.1
9.9
13.0
15.5
17.7
19.4
20.8
21.9
















TABLE 60







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 15% R-32 and 40% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















16/15/
18/15/
20/15/
22/15/
24/15/
26/15/
28/15/
30/15/



40/29
40/27
40/25
40/23
40/21
40/19
40/17
40/15




















COP (heating)

2.28
2.29
2.29
2.29
2.29
2.29
2.29
2.29


COP (heating) relative to Reference

108.2%
108.4%
108.5%
108.6%
108.6%
108.7%
108.6%
108.6%


Volumetric heating capacity at suction
kJ/m3
1957
2078
2202
2329
2457
2589
2723
2859


Capacity relative to Reference

222.7%
236.5%
250.6%
265.0%
279.7%
294.6%
309.9%
325.4%


Critical temperature
° C.
79.06
77.08
75.19
73.36
71.61
69.93
68.31
66.75


Critical pressure
bar
51.18
51.95
52.72
53.48
54.25
55.02
55.78
56.54


Condenser enthalpy change
kJ/kg
309.9
314.4
318.6
322.6
326.5
330.2
333.7
337.1


Pressure ratio

13.26
12.97
12.68
12.40
12.13
11.86
11.60
11.35


Refrigerant mass flow
kg/hr
23.2
22.9
22.6
22.3
22.1
21.8
21.6
21.4


Compressor discharge temperature
° C.
152.2
154.4
156.4
158.4
160.4
162.3
164.1
165.9


Evaporator inlet pressure
bar
1.82
1.94
2.07
2.20
2.34
2.48
2.62
2.78


Condenser inlet pressure
bar
23.9
25.0
26.0
27.1
28.2
29.2
30.3
31.4


Evaporator inlet temperature
° C.
−36.4
−37.0
−37.6
−38.3
−38.8
−39.4
−39.9
−40.3


Evaporator dewpoint
° C.
−24.1
−23.7
−23.3
−23.0
−22.6
−22.4
−22.1
−21.9


Evaporator exit gas temperature
° C.
−19.1
−18.7
−18.3
−18.0
−17.6
−17.4
−17.1
−16.9


Evaporator mean temperature
° C.
−30.2
−30.3
−30.5
−30.6
−30.7
−30.9
−31.0
−31.1


Evaporator glide (out-in)
K
12.3
13.3
14.3
15.3
16.2
17.0
17.7
18.4


Compressor suction pressure
bar
1.80
1.92
2.05
2.19
2.32
2.46
2.61
2.76


Compressor discharge pressure
bar
23.9
25.0
26.0
27.1
28.2
29.2
30.3
31.4


Suction line pressure drop
Pa/m
109
101
95
89
83
78
74
70


Pressure drop relative to reference

37.2%
34.6%
32.4%
30.3%
28.5%
26.8%
25.3%
23.9%


Condenser dew point
° C.
54.0
53.8
53.6
53.4
53.0
52.7
52.2
51.8


Condenser bubble point
° C.
31.2
30.4
29.8
29.2
28.7
28.3
27.9
27.6


Condenser exit liquid temperature
° C.
30.2
29.4
28.8
28.2
27.7
27.3
26.9
26.6


Condenser mean temperature
° C.
42.6
42.1
41.7
41.3
40.9
40.5
40.1
39.7


Condenser glide (in-out)
K
22.8
23.4
23.9
24.2
24.4
24.4
24.3
24.1
















TABLE 61







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 0-14% R-744, 20% R-32 and 5% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















0/20/5/75
2/20/5/73
4/20/5/71
6/20/5/69
8/20/5/67
10/20/5/65
12/20/5/63
14/20/5/61




















COP (heating)

2.20
2.22
2.24
2.25
2.26
2.27
2.28
2.28


COP (heating) relative to Reference

104.4%
105.4%
106.2%
106.8%
107.3%
107.7%
108.0%
108.3%


Volumetric heating capacity at suction
kJ/m3
1103
1197
1294
1394
1497
1602
1709
1818


Capacity relative to Reference

125.5%
136.2%
147.3%
158.7%
170.4%
182.3%
194.5%
206.9%


Critical temperature
° C.
98.35
95.65
93.07
90.59
88.21
85.93
83.74
81.64


Critical pressure
bar
45.29
46.10
46.88
47.66
48.43
49.20
49.96
50.71


Condenser enthalpy change
kJ/kg
264.5
272.4
279.5
286.1
292.2
298.0
303.3
308.4


Pressure ratio

15.11
14.95
14.76
14.53
14.29
14.03
13.77
13.50


Refrigerant mass flow
kg/hr
27.2
26.4
25.8
25.2
24.6
24.2
23.7
23.3


Compressor discharge temperature
° C.
131.4
134.4
137.3
140.0
142.6
145.1
147.5
149.9


Evaporator inlet pressure
bar
1.04
1.12
1.20
1.29
1.38
1.48
1.58
1.69


Condenser inlet pressure
bar
15.2
16.3
17.3
18.4
19.4
20.5
21.5
22.5


Evaporator inlet temperature
° C.
−32.2
−32.9
−33.6
−34.3
−35.0
−35.7
−36.4
−37.1


Evaporator dewpoint
° C.
−27.3
−26.7
−26.2
−25.6
−25.0
−24.5
−24.1
−23.6


Evaporator exit gas temperature
° C.
−22.3
−21.7
−21.2
−20.6
−20.0
−19.5
−19.1
−18.6


Evaporator mean temperature
° C.
−29.8
−29.8
−29.9
−29.9
−30.0
−30.1
−30.2
−30.4


Evaporator glide (out-in)
K
4.9
6.2
7.5
8.7
10.0
11.2
12.3
13.5


Compressor suction pressure
bar
1.01
1.09
1.17
1.26
1.36
1.46
1.56
1.67


Compressor discharge pressure
bar
15.2
16.3
17.3
18.4
19.4
20.5
21.5
22.5


Suction line pressure drop
Pa/m
217
196
177
162
148
137
126
117


Pressure drop relative to reference

74.3%
67.0%
60.7%
55.4%
50.8%
46.8%
43.3%
40.2%


Condenser dew point
° C.
52.7
53.4
53.9
54.3
54.6
54.8
54.8
54.8


Condenser bubble point
° C.
43.0
40.5
38.4
36.6
35.0
33.7
32.6
31.6


Condenser exit liquid temperature
° C.
42.0
39.5
37.4
35.6
34.0
32.7
31.6
30.6


Condenser mean temperature
° C.
47.9
46.9
46.2
45.5
44.8
44.2
43.7
43.2


Condenser glide (in-out)
K
9.6
12.8
15.5
17.7
19.6
21.1
22.3
23.2
















TABLE 62







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 20% R-32 and 5% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















16/20/5/59
18/20/5/57
20/20/5/55
22/20/5/53
24/20/5/51
26/20/5/49
28/20/5/47
30/20/5/45




















COP (heating)

2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29


COP (heating) relative to Reference

108.4%
108.5%
108.6%
108.6%
108.6%
108.6%
108.5%
108.4%


Volumetric heating capacity at suction
kJ/m3
1930
2043
2159
2276
2396
2519
2645
2773


Capacity relative to Reference

219.6%
232.5%
245.7%
259.1%
272.7%
286.7%
301.0%
315.6%


Critical temperature
° C.
79.63
77.69
75.84
74.05
72.33
70.67
69.07
67.53


Critical pressure
bar
51.47
52.22
52.97
53.72
54.47
55.22
55.96
56.71


Condenser enthalpy change
kJ/kg
313.2
317.8
322.2
326.4
330.4
334.2
337.9
341.4


Pressure ratio

13.24
12.98
12.72
12.46
12.21
11.96
11.71
11.47


Refrigerant mass flow
kg/hr
23.0
22.7
22.3
22.1
21.8
21.5
21.3
21.1


Compressor discharge temperature
° C.
152.2
154.4
156.5
158.6
160.7
162.7
164.6
166.5


Evaporator inlet pressure
bar
1.80
1.91
2.03
2.15
2.28
2.41
2.55
2.69


Condenser inlet pressure
bar
23.6
24.6
25.6
26.6
27.6
28.7
29.7
30.7


Evaporator inlet temperature
° C.
−37.8
−38.4
−39.0
−39.6
−40.1
−40.6
−41.1
−41.4


Evaporator dewpoint
° C.
−23.2
−22.9
−22.6
−22.3
−22.0
−21.8
−21.6
−21.5


Evaporator exit gas temperature
° C.
−18.2
−17.9
−17.6
−17.3
−17.0
−16.8
−16.6
−16.5


Evaporator mean temperature
° C.
−30.5
−30.6
−30.8
−30.9
−31.1
−31.2
−31.3
−31.5


Evaporator glide (out-in)
K
14.5
15.5
16.5
17.3
18.1
18.8
19.4
20.0


Compressor suction pressure
bar
1.78
1.89
2.01
2.14
2.26
2.40
2.53
2.68


Compressor discharge pressure
bar
23.6
24.6
25.6
26.6
27.6
28.7
29.7
30.7


Suction line pressure drop
Pa/m
109
102
96
90
85
80
75
71


Pressure drop relative to reference

37.4%
34.9%
32.7%
30.7%
28.9%
27.3%
25.8%
24.4%


Condenser dew point
° C.
54.7
54.5
54.3
53.9
53.6
53.1
52.7
52.2


Condenser bubble point
° C.
30.7
30.0
29.3
28.8
28.3
27.9
27.5
27.2


Condenser exit liquid temperature
° C.
29.7
29.0
28.3
27.8
27.3
26.9
26.5
26.2


Condenser mean temperature
° C.
42.7
42.2
41.8
41.3
40.9
40.5
40.1
39.7


Condenser glide (in-out)
K
24.0
24.5
24.9
25.2
25.3
25.3
25.2
25.0
















TABLE 63







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 0-14% R-744, 20% R-32 and 10% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















0/20/10/70
2/20/10/68
4/20/10/66
6/20/10/64
8/20/10/64
10/20/10/60
12/20/10/58
14/20/10/56




















COP (heating)

2.20
2.22
2.24
2.25
2.26
2.27
2.28
2.28


COP (heating) relative to Reference

104.5%
105.5%
106.2%
106.9%
107.4%
107.8%
108.1%
108.3%


Volumetric heating capacity at suction
kJ/m3
1119
1214
1312
1413
1517
1624
1732
1843


Capacity relative to Reference

127.4%
138.2%
149.3%
160.9%
172.7%
184.8%
197.1%
209.7%


Critical temperature
° C.
98.06
95.36
92.78
90.31
87.94
85.67
83.49
81.41


Critical pressure
bar
45.53
46.31
47.09
47.87
48.63
49.40
50.16
50.91


Condenser enthalpy change
kJ/kg
265.2
273.1
280.3
286.8
292.9
298.6
304.0
309.0


Pressure ratio

14.98
14.83
14.64
14.42
14.17
13.92
13.66
13.39


Refrigerant mass flow
kg/hr
27.1
26.4
25.7
25.1
24.6
24.1
23.7
23.3


Compressor discharge temperature
° C.
131.9
134.9
137.8
140.5
143.1
145.6
148.0
150.3


Evaporator inlet pressure
bar
1.06
1.14
1.22
1.31
1.40
1.50
1.61
1.71


Condenser inlet pressure
bar
15.3
16.4
17.4
18.5
19.5
20.6
21.6
22.7


Evaporator inlet temperature
° C.
−32.2
−32.8
−33.5
−34.2
−34.8
−35.5
−36.2
−36.9


Evaporator dewpoint
° C.
−27.4
−26.9
−26.3
−25.7
−25.2
−24.7
−24.2
−23.8


Evaporator exit gas temperature
° C.
−22.4
−21.9
−21.3
−20.7
−20.2
−19.7
−19.2
−18.8


Evaporator mean temperature
° C.
−29.8
−29.8
−29.9
−29.9
−30.0
−30.1
−30.2
−30.3


Evaporator glide (out-in)
K
4.7
6.0
7.2
8.4
9.7
10.8
12.0
13.1


Compressor suction pressure
bar
1.02
1.10
1.19
1.28
1.38
1.48
1.58
1.69


Compressor discharge pressure
bar
15.3
16.4
17.4
18.5
19.5
20.6
21.6
22.7


Suction line pressure drop
Pa/m
213
192
175
159
146
135
124
116


Pressure drop relative to reference

73.1%
65.9%
59.8%
54.5%
50.0%
46.1%
42.6%
39.6%


Condenser dew point
° C.
52.4
53.0
53.6
54.0
54.2
54.4
54.5
54.4


Condenser bubble point
° C.
43.2
40.7
38.6
36.8
35.2
33.9
32.7
31.8


Condenser exit liquid temperature
° C.
42.2
39.7
37.6
35.8
34.2
32.9
31.7
30.8


Condenser mean temperature
° C.
47.8
46.9
46.1
45.4
44.7
44.1
43.6
43.1


Condenser glide (in-out)
K
9.1
12.3
15.0
17.2
19.0
20.5
21.7
22.7
















TABLE 64







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 20% R-32 and 10% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















16/20/
18/20/
20/20/
22/20/
24/20/
26/20/
28/20/
30/20/



10/54
10/52
10/50
10/48
10/46
10/44
10/42
10/40




















COP (heating)

2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29


COP (heating) relative to Reference

108.5%
108.6%
108.6%
108.7%
108.7%
108.6%
108.6%
108.5%


Volumetric heating capacity at suction
kJ/m3
1956
2071
2189
2309
2431
2556
2684
2816


Capacity relative to Reference

222.6%
235.7%
249.1%
262.8%
276.7%
290.9%
305.5%
320.4%


Critical temperature
° C.
79.40
77.48
75.63
73.85
72.14
70.50
68.91
67.38


Critical pressure
bar
51.67
52.42
53.17
53.93
54.68
55.43
56.18
56.93


Condenser enthalpy change
kJ/kg
313.8
318.3
322.6
326.8
330.7
334.5
338.1
341.5


Pressure ratio

13.13
12.87
12.60
12.35
12.09
11.84
11.59
11.35


Refrigerant mass flow
kg/hr
22.9
22.6
22.3
22.0
21.8
21.5
21.3
21.1


Compressor discharge temperature
° C.
152.6
154.8
156.9
159.0
161.0
162.9
164.8
166.6


Evaporator inlet pressure
bar
1.83
1.94
2.06
2.19
2.32
2.45
2.59
2.74


Condenser inlet pressure
bar
23.7
24.8
25.8
26.8
27.8
28.9
29.9
30.9


Evaporator inlet temperature
° C.
−37.5
−38.1
−38.7
−39.3
−39.8
−40.3
−40.7
−41.1


Evaporator dewpoint
° C.
−23.4
−23.0
−22.7
−22.4
−22.2
−22.0
−21.8
−21.6


Evaporator exit gas temperature
° C.
−18.4
−18.0
−17.7
−17.4
−17.2
−17.0
−16.8
−16.6


Evaporator mean temperature
° C.
−30.4
−30.6
−30.7
−30.9
−31.0
−31.1
−31.2
−31.4


Evaporator glide (out-in)
K
14.1
15.1
16.0
16.9
17.6
18.3
18.9
19.5


Compressor suction pressure
bar
1.81
1.92
2.05
2.17
2.30
2.44
2.58
2.73


Compressor discharge pressure
bar
23.7
24.8
25.8
26.8
27.8
28.9
29.9
30.9


Suction line pressure drop
Pa/m
108
101
94
88
83
78
74
70


Pressure drop relative to reference

36.9%
34.4%
32.2%
30.3%
28.5%
26.9%
25.4%
24.0%


Condenser dew point
° C.
54.3
54.1
53.9
53.6
53.2
52.8
52.3
51.8


Condenser bubble point
° C.
30.9
30.2
29.5
29.0
28.5
28.1
27.7
27.4


Condenser exit liquid temperature
° C.
29.9
29.2
28.5
28.0
27.5
27.1
26.7
26.4


Condenser mean temperature
° C.
42.6
42.2
41.7
41.3
40.9
40.4
40.0
39.6


Condenser glide (in-out)
K
23.4
24.0
24.4
24.6
24.7
24.7
24.6
24.4
















TABLE 65







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 0-14% R-744, 20% R-32 and 20% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















0/20/20/60
2/20/20/58
4/20/20/56
6/20/20/54
8/20/20/52
10/20/20/50
12/20/20/48
14/20/20/46




















COP (heating)

2.20
2.23
2.24
2.25
2.27
2.27
2.28
2.29


COP (heating) relative to Reference

104.6%
105.5%
106.3%
106.9%
107.4%
107.8%
108.1%
108.4%


Volumetric heating capacity at suction
kJ/m3
1150
1247
1347
1449
1556
1664
1776
1890


Capacity relative to Reference

130.9%
141.9%
153.3%
165.0%
177.0%
189.4%
202.1%
215.1%


Critical temperature
° C.
97.47
94.79
92.23
89.78
87.43
85.19
83.03
80.97


Critical pressure
bar
45.91
46.68
47.46
48.23
48.99
49.76
50.52
51.28


Condenser enthalpy change
kJ/kg
266.8
274.7
281.9
288.5
294.5
300.2
305.5
310.5


Pressure ratio

14.75
14.61
14.42
14.21
13.98
13.72
13.46
13.20


Refrigerant mass flow
kg/hr
27.0
26.2
25.5
25.0
24.4
24.0
23.6
23.2


Compressor discharge temperature
° C.
132.9
135.9
138.8
141.5
144.1
146.6
149.0
151.3


Evaporator inlet pressure
bar
1.09
1.17
1.25
1.35
1.44
1.54
1.65
1.76


Condenser inlet pressure
bar
15.6
16.6
17.7
18.7
19.8
20.9
21.9
23.0


Evaporator inlet temperature
° C.
−32.0
−32.6
−33.2
−33.9
−34.5
−35.2
−35.8
−36.4


Evaporator dewpoint
° C.
−27.7
−27.1
−26.5
−26.0
−25.5
−25.0
−24.5
−24.1


Evaporator exit gas temperature
° C.
−22.7
−22.1
−21.5
−21.0
−20.5
−20.0
−19.5
−19.1


Evaporator mean temperature
° C.
−29.8
−29.9
−29.9
−29.9
−30.0
−30.1
−30.2
−30.3


Evaporator glide (out-in)
K
4.3
5.5
6.7
7.9
9.1
10.2
11.3
12.4


Compressor suction pressure
bar
1.05
1.14
1.23
1.32
1.42
1.52
1.63
1.74


Compressor discharge pressure
bar
15.6
16.6
17.7
18.7
19.8
20.9
21.9
23.0


Suction line pressure drop
Pa/m
207
187
169
155
142
131
121
112


Pressure drop relative to reference

70.8%
63.9%
58.0%
53.0%
48.6%
44.8%
41.4%
38.5%


Condenser dew point
° C.
51.7
52.4
52.9
53.3
53.6
53.7
53.8
53.8


Condenser bubble point
° C.
43.5
41.0
38.9
37.1
35.5
34.2
33.0
32.0


Condenser exit liquid temperature
° C.
42.5
40.0
37.9
36.1
34.5
33.2
32.0
31.0


Condenser mean temperature
° C.
47.6
46.7
45.9
45.2
44.5
44.0
43.4
42.9


Condenser glide (in-out)
K
8.2
11.3
14.0
16.2
18.1
19.6
20.8
21.7
















TABLE 66







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 20% R-32 and 20% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















16/20/
18/20/
20/20/
22/20/
24/20/
26/20/
28/20/
30/20/



20/44
20/42
20/40
20/38
20/38
20/34
20/32
20/30




















COP (heating)

2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29


COP (heating) relative to Reference

108.6%
108.7%
108.8%
108.8%
108.8%
108.8%
108.8%
108.7%


Volumetric heating capacity at suction
kJ/m3
2006
2125
2246
2370
2496
2626
2758
2894


Capacity relative to Reference

228.3%
241.8%
255.6%
269.7%
284.1%
298.8%
313.9%
329.3%


Critical temperature
° C.
78.99
77.09
75.26
73.50
71.81
70.18
68.61
67.10


Critical pressure
bar
52.04
52.80
53.56
54.32
55.07
55.83
56.59
57.34


Condenser enthalpy change
kJ/kg
315.2
319.6
323.8
327.9
331.7
335.4
338.9
342.2


Pressure ratio

12.93
12.67
12.41
12.15
11.89
11.64
11.39
11.14


Refrigerant mass flow
kg/hr
22.8
22.5
22.2
22.0
21.7
21.5
21.2
21.0


Compressor discharge temperature
° C.
153.5
155.6
157.7
159.7
161.6
163.5
165.4
167.1


Evaporator inlet pressure
bar
1.88
2.00
2.12
2.25
2.39
2.53
2.67
2.82


Condenser inlet pressure
bar
24.0
25.1
26.1
27.2
28.2
29.2
30.3
31.3


Evaporator inlet temperature
° C.
−37.1
−37.6
−38.2
−38.8
−39.3
−39.7
−40.1
−40.5


Evaporator dewpoint
° C.
−23.7
−23.3
−23.0
−22.7
−22.5
−22.2
−22.0
−21.9


Evaporator exit gas temperature
° C.
−18.7
−18.3
−18.0
−17.7
−17.5
−17.2
−17.0
−16.9


Evaporator mean temperature
° C.
−30.4
−30.5
−30.6
−30.7
−30.9
−31.0
−31.1
−31.2


Evaporator glide (out-in)
K
13.4
14.3
15.2
16.0
16.8
17.5
18.1
18.6


Compressor suction pressure
bar
1.86
1.98
2.11
2.24
2.37
2.51
2.66
2.81


Compressor discharge pressure
bar
24.0
25.1
26.1
27.2
28.2
29.2
30.3
31.3


Suction line pressure drop
Pa/m
105
98
92
86
81
76
72
68


Pressure drop relative to reference

35.8%
33.5%
31.3%
29.4%
27.7%
26.1%
24.7%
23.3%


Condenser dew point
° C.
53.7
53.5
53.3
53.0
52.6
52.2
51.8
51.3


Condenser bubble point
° C.
31.2
30.5
29.8
29.3
28.8
28.4
28.1
27.8


Condenser exit liquid temperature
° C.
30.2
29.5
28.8
28.3
27.8
27.4
27.1
26.8


Condenser mean temperature
° C.
42.4
42.0
41.5
41.1
40.7
40.3
39.9
39.5


Condenser glide (in-out)
K
22.5
23.0
23.4
23.7
23.8
23.8
23.7
23.5
















TABLE 67







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 0-14% R-744, 20% R-32 and 30% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















0/20/30/50
2/20/30/48
4/20/30/46
6/20/30/44
8/20/30/42
10/20/30/40
12/20/30/38
14/20/30/36




















COP (heating)

2.21
2.23
2.24
2.26
2.27
2.28
2.28
2.29


COP (heating) relative to Reference

104.7%
105.7%
106.4%
107.0%
107.5%
107.9%
108.3%
108.5%


Volumetric heating capacity at suction
kJ/m3
1178
1276
1378
1482
1590
1702
1815
1932


Capacity relative to Reference

134.1%
145.2%
156.8%
168.7%
181.0%
193.6%
206.6%
219.9%


Critical temperature
° C.
96.89
94.24
91.70
89.28
86.96
84.74
82.61
80.57


Critical pressure
bar
46.18
46.96
47.74
48.51
49.29
50.06
50.83
51.60


Condenser enthalpy change
kJ/kg
268.7
276.6
283.8
290.4
296.5
302.1
307.4
312.3


Pressure ratio

14.56
14.42
14.24
14.04
13.81
13.56
13.30
13.04


Refrigerant mass flow
kg/hr
26.8
26.0
25.4
24.8
24.3
23.8
23.4
23.1


Compressor discharge temperature
° C.
134.0
137.1
139.9
142.7
145.3
147.7
150.1
152.3


Evaporator inlet pressure
bar
1.12
1.20
1.28
1.38
1.48
1.58
1.69
1.80


Condenser inlet pressure
bar
15.8
16.8
17.9
19.0
20.0
21.1
22.2
23.2


Evaporator inlet temperature
° C.
−31.8
−32.4
−33.0
−33.6
−34.3
−34.9
−35.5
−36.1


Evaporator dewpoint
° C.
−27.9
−27.4
−26.8
−26.3
−25.7
−25.2
−24.8
−24.3


Evaporator exit gas temperature
° C.
−22.9
−22.4
−21.8
−21.3
−20.7
−20.2
−19.8
−19.3


Evaporator mean temperature
° C.
−29.9
−29.9
−29.9
−30.0
−30.0
−30.1
−30.1
−30.2


Evaporator glide (out-in)
K
3.9
5.1
6.2
7.4
8.5
9.6
10.7
11.8


Compressor suction pressure
bar
1.08
1.17
1.26
1.35
1.45
1.56
1.67
1.78


Compressor discharge pressure
bar
15.8
16.8
17.9
19.0
20.0
21.1
22.2
23.2


Suction line pressure drop
Pa/m
201
181
165
151
138
127
118
109


Pressure drop relative to reference

68.8%
62.1%
56.4%
51.5%
47.3%
43.6%
40.3%
37.4%


Condenser dew point
° C.
51.1
51.7
52.3
52.7
53.0
53.1
53.2
53.2


Condenser bubble point
° C.
43.8
41.2
39.1
37.3
35.7
34.4
33.2
32.2


Condenser exit liquid temperature
° C.
42.8
40.2
38.1
36.3
34.7
33.4
32.2
31.2


Condenser mean temperature
° C.
47.4
46.5
45.7
45.0
44.3
43.8
43.2
42.7


Condenser glide (in-out)
K
7.3
10.5
13.2
15.4
17.3
18.8
20.0
21.0
















TABLE 68







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 20% R-32 and 30% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















16/20/
18/20/
20/20/
22/20/
24/20/
26/20/
28/20/
30/20/



30/34
20/32
30/30
30/28
30/26
30/24
30/22
30/20




















COP (heating)

2.29
2.29
2.30
2.30
2.30
2.30
2.30
2.30


COP (heating) relative to Reference

108.7%
108.8%
108.9%
109.0%
109.0%
109.0%
109.0%
108.9%


Volumetric heating capacity at suction
kJ/m3
2051
2173
2297
2424
2554
2686
2822
2961


Capacity relative to Reference

233.4%
247.3%
261.4%
275.9%
290.7%
305.7%
321.2%
336.9%


Critical temperature
° C.
78.61
76.73
74.93
73.19
71.52
69.91
68.36
66.86


Critical pressure
bar
52.37
53.14
53.91
54.67
55.44
56.21
56.97
57.74


Condenser enthalpy change
kJ/kg
316.9
321.3
325.5
329.5
333.2
336.8
340.3
343.5


Pressure ratio

12.77
12.51
12.24
11.98
11.73
11.48
11.23
10.99


Refrigerant mass flow
kg/hr
22.7
22.4
22.1
21.9
21.6
21.4
21.2
21.0


Compressor discharge temperature
° C.
154.5
156.6
158.6
160.6
162.5
164.4
166.2
167.9


Evaporator inlet pressure
bar
1.92
2.04
2.17
2.31
2.45
2.59
2.74
2.89


Condenser inlet pressure
bar
24.3
25.4
26.4
27.5
28.5
29.6
30.6
31.7


Evaporator inlet temperature
° C.
−36.7
−37.3
−37.8
−38.3
−38.8
−39.3
−39.7
−40.1


Evaporator dewpoint
° C.
−23.9
−23.6
−23.2
−22.9
−22.7
−22.5
−22.3
−22.1


Evaporator exit gas temperature
° C.
−18.9
−18.6
−18.2
−17.9
−17.7
−17.5
−17.3
−17.1


Evaporator mean temperature
° C.
−30.3
−30.4
−30.5
−30.6
−30.8
−30.9
−31.0
−31.1


Evaporator glide (out-in)
K
12.8
13.7
14.6
15.4
16.2
16.8
17.4
18.0


Compressor suction pressure
bar
1.90
2.03
2.16
2.29
2.43
2.58
2.73
2.88


Compressor discharge pressure
bar
24.3
25.4
26.4
27.5
28.5
29.6
30.6
31.7


Suction line pressure drop
Pa/m
102
95
89
84
79
74
70
66


Pressure drop relative to reference

34.9%
32.6%
30.5%
28.7%
27.0%
25.4%
24.0%
22.7%


Condenser dew point
° C.
53.1
53.0
52.7
52.4
52.1
51.7
51.3
50.8


Condenser bubble point
° C.
31.4
30.7
30.0
29.5
29.0
28.6
28.3
28.0


Condenser exit liquid temperature
° C.
30.4
29.7
29.0
28.5
28.0
27.6
27.3
27.0


Condenser mean temperature
° C.
42.3
41.8
41.4
41.0
40.6
40.2
39.8
39.4


Condenser glide (in-out)
K
21.7
22.3
22.7
23.0
23.1
23.1
23.0
22.8
















TABLE 69







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 0-14% R-744, 20% R-32 and 40% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















0/20/40/40
2/20/40/38
4/20/40/36
6/20/40/34
8/20/40/32
10/20/40/30
12/20/40/28
14/20/40/26




















COP (heating)

2.21
2.23
2.24
2.26
2.27
2.28
2.28
2.29


COP (heating) relative to Reference

104.9%
105.7%
106.4%
107.0%
107.5%
107.9%
108.3%
108.5%


Volumetric heating capacity at suction
kJ/m3
1202
1276
1378
1482
1590
1702
1815
1932


Capacity relative to Reference

136.8%
145.2%
156.8%
168.7%
181.0%
193.6%
206.6%
219.9%


Critical temperature
° C.
96.33
94.24
91.70
89.28
86.96
84.74
82.61
80.57


Critical pressure
bar
46.37
46.96
47.74
48.51
49.29
50.06
50.83
51.60


Condenser enthalpy change
kJ/kg
270.8
276.6
283.8
290.4
296.5
302.1
307.4
312.3


Pressure ratio

14.39
14.42
14.24
14.04
13.81
13.56
13.30
13.04


Refrigerant mass flow
kg/hr
26.6
26.0
25.4
24.8
24.3
23.8
23.4
23.1


Compressor discharge temperature
° C.
135.2
137.1
139.9
142.7
145.3
147.7
150.1
152.3


Evaporator inlet pressure
bar
1.14
1.20
1.28
1.38
1.48
1.58
1.69
1.80


Condenser inlet pressure
bar
15.9
16.8
17.9
19.0
20.0
21.1
22.2
23.2


Evaporator inlet temperature
° C.
−31.7
−32.4
−33.0
−33.6
−34.3
−34.9
−35.5
−36.1


Evaporator dewpoint
° C.
−28.1
−27.4
−26.8
−26.3
−25.7
−25.2
−24.8
−24.3


Evaporator exit gas temperature
° C.
−23.1
−22.4
−21.8
−21.3
−20.7
−20.2
−19.8
−19.3


Evaporator mean temperature
° C.
−29.9
−29.9
−29.9
−30.0
−30.0
−30.1
−30.1
−30.2


Evaporator glide (out-in)
K
3.6
5.1
6.2
7.4
8.5
9.6
10.7
11.8


Compressor suction pressure
bar
1.11
1.17
1.26
1.35
1.45
1.56
1.67
1.78


Compressor discharge pressure
bar
15.9
16.8
17.9
19.0
20.0
21.1
22.2
23.2


Suction line pressure drop
Pa/m
196
181
165
151
138
127
118
109


Pressure drop relative to reference

67.0%
62.1%
56.4%
51.5%
47.3%
43.6%
40.3%
37.4%


Condenser dew point
° C.
50.5
51.7
52.3
52.7
53.0
53.1
53.2
53.2


Condenser bubble point
° C.
44.0
41.3
39.1
37.3
35.7
34.4
33.2
32.2


Condenser exit liquid temperature
° C.
43.0
40.3
38.1
36.3
34.7
33.4
32.2
31.2


Condenser mean temperature
° C.
47.2
46.5
45.7
45.0
44.3
43.8
43.2
42.7


Condenser glide (in-out)
K
6.5
10.5
13.2
15.4
17.3
18.8
20.0
21.0
















TABLE 70







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 20% R-32 and 40% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















16/20/
18/20/
20/20/
22/20/
24/20/
26/20/
28/20/
30/20/



40/24
40/22
40/20
40/18
40/16
40/14
40/12
40/10




















COP (heating)

2.29
2.29
2.30
2.30
2.30
2.30
2.30
2.30


COP (heating) relative to Reference

108.7%
108.8%
108.9%
109.0%
109.0%
109.0%
109.0%
108.9%


Volumetric heating capacity at suction
kJ/m3
2051
2173
2297
2424
2554
2686
2822
2961


Capacity relative to Reference

233.4%
247.3%
261.4%
275.9%
290.7%
305.7%
321.2%
336.9%


Critical temperature
° C.
78.61
76.73
74.93
73.19
71.52
69.91
68.36
66.86


Critical pressure
bar
52.37
53.14
53.91
54.67
55.44
56.21
56.97
57.74


Condenser enthalpy change
kJ/kg
316.9
321.3
325.5
329.5
333.2
336.8
340.3
343.5


Pressure ratio

12.77
12.51
12.24
11.98
11.73
11.48
11.23
10.99


Refrigerant mass flow
kg/hr
22.7
22.4
22.1
21.9
21.6
21.4
21.2
21.0


Compressor discharge temperature
° C.
154.5
156.6
158.6
160.6
162.5
164.4
166.2
167.9


Evaporator inlet pressure
bar
1.92
2.04
2.17
2.31
2.45
2.59
2.74
2.89


Condenser inlet pressure
bar
24.3
25.4
26.4
27.5
28.5
29.6
30.6
31.7


Evaporator inlet temperature
° C.
−36.7
−37.3
−37.8
−38.3
−38.8
−39.3
−39.7
−40.1


Evaporator dewpoint
° C.
−23.9
−23.6
−23.2
−22.9
−22.7
−22.5
−22.3
−22.1


Evaporator exit gas temperature
° C.
−18.9
−18.6
−18.2
−17.9
−17.7
−17.5
−17.3
−17.1


Evaporator mean temperature
° C.
−30.3
−30.4
−30.5
−30.6
−30.8
−30.9
−31.0
−31.1


Evaporator glide (out-in)
K
12.8
13.7
14.6
15.4
16.2
16.8
17.4
18.0


Compressor suction pressure
bar
1.90
2.03
2.16
2.29
2.43
2.58
2.73
2.88


Compressor discharge pressure
bar
24.3
25.4
26.4
27.5
28.5
29.6
30.6
31.7


Suction line pressure drop
Pa/m
102
95
89
84
79
74
70
66


Pressure drop relative to reference

34.9%
32.6%
30.5%
28.7%
27.0%
25.4%
24.0%
22.7%


Condenser dew point
° C.
53.1
53.0
52.7
52.4
52.1
51.7
51.3
50.8


Condenser bubble point
° C.
31.4
30.7
30.0
29.5
29.0
28.6
28.3
28.0


Condenser exit liquid temperature
° C.
30.4
29.7
29.0
28.5
28.0
27.6
27.3
27.0


Condenser mean temperature
° C.
42.3
41.8
41.4
41.0
40.6
40.2
39.8
39.4


Condenser glide (in-out)
K
21.7
22.3
22.7
23.0
23.1
23.1
23.0
22.8
















TABLE 71







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 0-14% R-744, 25% R-32 and 5% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















0/25/5/70
2/25/5/68
4/25/5/66
6/25/5/64
8/25/5/62
10/25/5/60
12/25/5/58
14/25/5/56




















COP (heating)

2.23
2.25
2.26
2.27
2.28
2.29
2.29
2.29


COP (heating) relative to Reference

105.7%
106.5%
107.2%
107.7%
108.1%
108.4%
108.7%
108.8%


Volumetric heating capacity at suction
kJ/m3
1221
1318
1418
1520
1624
1732
1841
1953


Capacity relative to Reference

139.0%
150.0%
161.3%
172.9%
184.9%
197.1%
209.5%
222.3%


Critical temperature
° C.
96.21
93.71
91.30
89.00
86.78
84.66
82.62
80.65


Critical pressure
bar
46.83
47.63
48.42
49.20
49.98
50.75
51.52
52.29


Condenser enthalpy change
kJ/kg
275.4
282.8
289.6
295.9
301.8
307.3
312.5
317.4


Pressure ratio

14.37
14.20
14.01
13.80
13.58
13.34
13.10
12.86


Refrigerant mass flow
kg/hr
26.1
25.5
24.9
24.3
23.9
23.4
23.0
22.7


Compressor discharge temperature
° C.
135.4
138.2
141.0
143.7
146.2
148.7
151.0
153.3


Evaporator inlet pressure
bar
1.15
1.23
1.32
1.41
1.51
1.61
1.72
1.83


Condenser inlet pressure
bar
16.1
17.1
18.1
19.2
20.2
21.2
22.2
23.3


Evaporator inlet temperature
° C.
−32.8
−33.4
−34.0
−34.7
−35.3
−35.9
−36.5
−37.1


Evaporator dewpoint
° C.
−26.9
−26.4
−25.9
−25.4
−24.9
−24.5
−24.0
−23.7


Evaporator exit gas temperature
° C.
−21.9
−21.4
−20.9
−20.4
−19.9
−19.5
−19.0
−18.7


Evaporator mean temperature
° C.
−29.9
−29.9
−30.0
−30.0
−30.1
−30.2
−30.3
−30.4


Evaporator glide (out-in)
K
5.9
7.0
8.2
9.3
10.4
11.5
12.5
13.5


Compressor suction pressure
bar
1.12
1.20
1.29
1.39
1.49
1.59
1.70
1.81


Compressor discharge pressure
bar
16.1
17.1
18.1
19.2
20.2
21.2
22.2
23.3


Suction line pressure drop
Pa/m
190
173
158
145
133
124
115
107


Pressure drop relative to reference

65.1%
59.1%
54.0%
49.6%
45.7%
42.3%
39.3%
36.6%


Condenser dew point
° C.
51.9
52.5
52.9
53.2
53.4
53.5
53.5
53.4


Condenser bubble point
° C.
42.2
40.0
38.1
36.5
35.1
33.9
32.8
31.9


Condenser exit liquid temperature
° C.
41.2
39.0
37.1
35.5
34.1
32.9
31.8
30.9


Condenser mean temperature
° C.
47.1
46.2
45.5
44.8
44.2
43.7
43.1
42.6


Condenser glide (in-out)
K
9.7
12.5
14.8
16.7
18.3
19.6
20.7
21.5
















TABLE 72







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 25% R-32 and 5% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















16/25/5/54
18/25/5/52
20/25/5/50
22/25/5/48
24/25/5/46
26/25/5/44
28/25/5/42
30/25/5/40




















COP (heating)

2.30
2.30
2.30
2.30
2.30
2.30
2.30
2.30


COP (heating) relative to Reference

109.0%
109.0%
109.1%
109.1%
109.1%
109.0%
109.0%
108.9%


Volumetric heating capacity at suction
kJ/m3
2067
2184
2303
2425
2549
2677
2808
2942


Capacity relative to Reference

235.3%
248.6%
262.1%
276.0%
290.1%
304.6%
319.5%
334.8%


Critical temperature
° C.
78.77
76.95
75.20
73.52
71.90
70.33
68.83
67.37


Critical pressure
bar
53.05
53.82
54.58
55.34
56.10
56.86
57.62
58.38


Condenser enthalpy change
kJ/kg
322.0
326.5
330.7
334.7
338.6
342.2
345.7
349.0


Pressure ratio

12.62
12.37
12.13
11.89
11.65
11.41
11.18
10.95


Refrigerant mass flow
kg/hr
22.4
22.1
21.8
21.5
21.3
21.0
20.8
20.6


Compressor discharge temperature
° C.
155.5
157.7
159.7
161.8
163.7
165.6
167.4
169.2


Evaporator inlet pressure
bar
1.94
2.06
2.18
2.31
2.45
2.58
2.73
2.88


Condenser inlet pressure
bar
24.3
25.3
26.3
27.3
28.3
29.4
30.4
31.4


Evaporator inlet temperature
° C.
−37.7
−38.2
−38.8
−39.2
−39.7
−40.0
−40.4
−40.7


Evaporator dewpoint
° C.
−23.3
−23.0
−22.7
−22.5
−22.3
−22.1
−22.0
−21.8


Evaporator exit gas temperature
° C.
−18.3
−18.0
−17.7
−17.5
−17.3
−17.1
−17.0
−16.8


Evaporator mean temperature
° C.
−30.5
−30.6
−30.7
−30.9
−31.0
−31.1
−31.2
−31.3


Evaporator glide (out-in)
K
14.4
15.2
16.0
16.7
17.4
17.9
18.4
18.9


Compressor suction pressure
bar
1.92
2.04
2.17
2.30
2.43
2.57
2.72
2.87


Compressor discharge pressure
bar
24.3
25.3
26.3
27.3
28.3
29.4
30.4
31.4


Suction line pressure drop
Pa/m
100
94
88
83
78
74
70
66


Pressure drop relative to reference

34.2%
32.0%
30.1%
28.3%
26.7%
25.2%
23.9%
22.6%


Condenser dew point
° C.
53.3
53.0
52.8
52.4
52.1
51.7
51.2
50.7


Condenser bubble point
° C.
31.1
30.4
29.8
29.3
28.8
28.5
28.1
27.9


Condenser exit liquid temperature
° C.
30.1
29.4
28.8
28.3
27.8
27.5
27.1
26.9


Condenser mean temperature
° C.
42.2
41.7
41.3
40.9
40.5
40.1
39.7
39.3


Condenser glide (in-out)
K
22.2
22.6
23.0
23.2
23.2
23.2
23.1
22.8
















TABLE 73







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 0-14% R-744, 25% R-32 and 10% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















0/25/10/65
2/25/10/63
4/25/10/61
6/25/10/59
8/25/10/57
10/25/10/55
12/25/10/53
14/25/10/51




















COP (heating)

2.23
2.25
2.26
2.27
2.28
2.29
2.29
2.30


COP (heating) relative to Reference

105.8%
106.6%
107.2%
107.7%
108.1%
108.4%
108.7%
108.9%


Volumetric heating capacity at suction
kJ/m3
1237
1335
1435
1538
1644
1753
1864
1977


Capacity relative to Reference

140.8%
151.9%
163.3%
175.0%
187.1%
199.5%
212.1%
225.1%


Critical temperature
° C.
95.95
93.44
91.04
88.74
86.54
84.42
82.39
80.44


Critical pressure
bar
47.01
47.80
48.58
49.36
50.14
50.91
51.68
52.45


Condenser enthalpy change
kJ/kg
276.2
283.6
290.4
296.7
302.5
308.0
313.2
318.0


Pressure ratio

14.26
14.10
13.91
13.71
13.48
13.25
13.01
12.77


Refrigerant mass flow
kg/hr
26.1
25.4
24.8
24.3
23.8
23.4
23.0
22.6


Compressor discharge temperature
° C.
135.9
138.8
141.5
144.2
146.7
149.1
151.5
153.7


Evaporator inlet pressure
bar
1.17
1.25
1.34
1.43
1.53
1.63
1.74
1.85


Condenser inlet pressure
bar
16.2
17.2
18.3
19.3
20.3
21.4
22.4
23.4


Evaporator inlet temperature
° C.
−32.7
−33.3
−33.9
−34.5
−35.1
−35.7
−36.3
−36.9


Evaporator dewpoint
° C.
−27.1
−26.5
−26.0
−25.5
−25.1
−24.6
−24.2
−23.8


Evaporator exit gas temperature
° C.
−22.1
−21.5
−21.0
−20.5
−20.1
−19.6
−19.2
−18.8


Evaporator mean temperature
° C.
−29.9
−29.9
−30.0
−30.0
−30.1
−30.2
−30.3
−30.4


Evaporator glide (out-in)
K
5.6
6.7
7.9
9.0
10.0
11.1
12.1
13.0


Compressor suction pressure
bar
1.14
1.22
1.31
1.41
1.51
1.61
1.72
1.83


Compressor discharge pressure
bar
16.2
17.2
18.3
19.3
20.3
21.4
22.4
23.4


Suction line pressure drop
Pa/m
187
170
155
143
132
122
113
105


Pressure drop relative to reference

64.1%
58.3%
53.2%
48.9%
45.1%
41.7%
38.7%
36.1%


Condenser dew point
° C.
51.6
52.1
52.5
52.8
53.0
53.1
53.1
53.1


Condenser bubble point
° C.
42.4
40.2
38.3
36.6
35.2
34.0
33.0
32.1


Condenser exit liquid temperature
° C.
41.4
39.2
37.3
35.6
34.2
33.0
32.0
31.1


Condenser mean temperature
° C.
47.0
46.1
45.4
44.7
44.1
43.6
43.0
42.6


Condenser glide (in-out)
K
9.2
11.9
14.2
16.2
17.8
19.1
20.2
21.0
















TABLE 74







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 25% R-32 and 10% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















16/25/
18/25/
20/25/
22/25/
24/25/
26/25/
28/25/
30/25/



10/49
10/47
10/45
10/43
10/41
10/39
10/37
10/35




















COP (heating)

2.30
2.30
2.30
2.30
2.30
2.30
2.30
2.30


COP (heating) relative to Reference

109.0%
109.1%
109.1%
109.2%
109.2%
109.1%
109.1%
109.0%


Volumetric heating capacity at suction
kJ/m3
2093
2212
2333
2457
2584
2714
2847
2983


Capacity relative to Reference

238.3%
251.7%
265.5%
279.6%
294.1%
308.8%
324.0%
339.5%


Critical temperature
° C.
78.56
76.75
75.02
73.34
71.73
70.17
68.67
67.22


Critical pressure
bar
53.21
53.98
54.74
55.51
56.27
57.03
57.80
58.56


Condenser enthalpy change
kJ/kg
322.6
327.0
331.2
335.2
339.0
342.6
346.0
349.2


Pressure ratio

12.52
12.28
12.03
11.79
11.55
11.31
11.08
10.84


Refrigerant mass flow
kg/hr
22.3
22.0
21.7
21.5
21.2
21.0
20.8
20.6


Compressor discharge temperature
° C.
155.9
158.0
160.1
162.1
164.0
165.9
167.7
169.4


Evaporator inlet pressure
bar
1.97
2.09
2.22
2.35
2.48
2.62
2.77
2.93


Condenser inlet pressure
bar
24.4
25.5
26.5
27.5
28.5
29.5
30.6
31.6


Evaporator inlet temperature
° C.
−37.4
−38.0
−38.5
−38.9
−39.3
−39.7
−40.1
−40.3


Evaporator dewpoint
° C.
−23.5
−23.2
−22.9
−22.7
−22.4
−22.3
−22.1
−22.0


Evaporator exit gas temperature
° C.
−18.5
−18.2
−17.9
−17.7
−17.4
−17.3
−17.1
−17.0


Evaporator mean temperature
° C.
−30.5
−30.6
−30.7
−30.8
−30.9
−31.0
−31.1
−31.2


Evaporator glide (out-in)
K
13.9
14.8
15.6
16.3
16.9
17.5
18.0
18.4


Compressor suction pressure
bar
1.95
2.07
2.20
2.33
2.47
2.61
2.76
2.91


Compressor discharge pressure
bar
24.4
25.5
26.5
27.5
28.5
29.5
30.6
31.6


Suction line pressure drop
Pa/m
98
92
87
82
77
73
69
65


Pressure drop relative to reference

33.7%
31.6%
29.7%
27.9%
26.3%
24.9%
23.5%
22.3%


Condenser dew point
° C.
52.9
52.7
52.4
52.1
51.8
51.3
50.9
50.4


Condenser bubble point
° C.
31.3
30.6
30.0
29.5
29.0
28.6
28.3
28.1


Condenser exit liquid temperature
° C.
30.3
29.6
29.0
28.5
28.0
27.6
27.3
27.1


Condenser mean temperature
° C.
42.1
41.6
41.2
40.8
40.4
40.0
39.6
39.2


Condenser glide (in-out)
K
21.7
22.1
22.5
22.7
22.7
22.7
22.6
22.4
















TABLE 75







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 0-14% R-744, 25% R-32 and 20% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















0/25/20/55
2/25/20/53
4/25/20/51
6/25/20/49
8/25/20/47
10/25/20/45
12/25/20/43
14/25/20/41




















COP (heating)

2.23
2.25
2.26
2.27
2.28
2.29
2.29
2.30


COP (heating) relative to Reference

105.8%
106.6%
107.3%
107.8%
108.2%
108.5%
108.8%
109.0%


Volumetric heating capacity at suction
kJ/m3
1266
1365
1468
1573
1681
1792
1906
2023


Capacity relative to Reference

144.1%
155.4%
167.0%
179.0%
191.3%
204.0%
217.0%
230.2%


Critical temperature
° C.
95.42
92.93
90.55
88.26
86.08
83.98
81.97
80.04


Critical pressure
bar
47.30
48.08
48.86
49.64
50.41
51.19
51.96
52.74


Condenser enthalpy change
kJ/kg
277.9
285.3
292.1
298.4
304.2
309.7
314.8
319.6


Pressure ratio

14.07
13.91
13.73
13.53
13.32
13.08
12.84
12.60


Refrigerant mass flow
kg/hr
25.9
25.2
24.6
24.1
23.7
23.2
22.9
22.5


Compressor discharge temperature
° C.
136.9
139.8
142.6
145.2
147.8
150.2
152.5
154.7


Evaporator inlet pressure
bar
1.20
1.28
1.37
1.47
1.57
1.67
1.78
1.90


Condenser inlet pressure
bar
16.4
17.4
18.5
19.5
20.6
21.6
22.6
23.7


Evaporator inlet temperature
° C.
−32.4
−33.0
−33.6
−34.2
−34.8
−35.3
−35.9
−36.4


Evaporator dewpoint
° C.
−27.4
−26.9
−26.3
−25.9
−25.4
−25.0
−24.5
−24.2


Evaporator exit gas temperature
° C.
−22.4
−21.9
−21.3
−20.9
−20.4
−20.0
−19.5
−19.2


Evaporator mean temperature
° C.
−29.9
−29.9
−30.0
−30.0
−30.1
−30.1
−30.2
−30.3


Evaporator glide (out-in)
K
5.1
6.2
7.2
8.3
9.4
10.4
11.3
12.3


Compressor suction pressure
bar
1.16
1.25
1.34
1.44
1.54
1.65
1.76
1.88


Compressor discharge pressure
bar
16.4
17.4
18.5
19.5
20.6
21.6
22.6
23.7


Suction line pressure drop
Pa/m
182
166
151
139
128
119
110
103


Pressure drop relative to reference

62.4%
56.7%
51.8%
47.6%
43.9%
40.6%
37.7%
35.1%


Condenser dew point
° C.
50.9
51.4
51.9
52.2
52.4
52.5
52.5
52.5


Condenser bubble point
° C.
42.7
40.5
38.6
36.9
35.5
34.3
33.2
32.3


Condenser exit liquid temperature
° C.
41.7
39.5
37.6
35.9
34.5
33.3
32.2
31.3


Condenser mean temperature
° C.
46.8
46.0
45.2
44.5
43.9
43.4
42.9
42.4


Condenser glide (in-out)
K
8.2
11.0
13.3
15.2
16.9
18.2
19.3
20.1
















TABLE 76







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 25% R-32 and 20% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















16/25/
18/25/
20/25/
22/25/
24/25/
26/25/
28/25/
30/25/



20/39
20/37
20/35
20/33
20/31
20/29
20/27
20/25




















COP (heating)

2.30
2.30
2.30
2.30
2.31
2.30
2.30
2.30


COP (heating) relative to Reference

109.1%
109.2%
109.3%
109.3%
109.3%
109.3%
109.3%
109.2%


Volumetric heating capacity at suction
kJ/m3
2142
2264
2389
2516
2647
2780
2917
3058


Capacity relative to Reference

243.8%
257.7%
271.9%
286.4%
301.2%
316.4%
332.0%
348.0%


Critical temperature
° C.
78.18
76.39
74.67
73.02
71.42
69.88
68.40
66.96


Critical pressure
bar
53.51
54.28
55.05
55.82
56.59
57.36
58.13
58.90


Condenser enthalpy change
kJ/kg
324.2
328.5
332.6
336.5
340.2
343.7
347.0
350.2


Pressure ratio

12.35
12.10
11.86
11.62
11.37
11.14
10.90
10.67


Refrigerant mass flow
kg/hr
22.2
21.9
21.6
21.4
21.2
20.9
20.7
20.6


Compressor discharge temperature
° C.
156.9
158.9
160.9
162.9
164.7
166.6
168.3
170.0


Evaporator inlet pressure
bar
2.02
2.14
2.27
2.41
2.55
2.70
2.85
3.01


Condenser inlet pressure
bar
24.7
25.8
26.8
27.8
28.9
29.9
30.9
32.0


Evaporator inlet temperature
° C.
−37.0
−37.5
−38.0
−38.4
−38.8
−39.2
−39.5
−39.8


Evaporator dewpoint
° C.
−23.8
−23.5
−23.2
−23.0
−22.7
−22.5
−22.4
−22.2


Evaporator exit gas temperature
° C.
−18.8
−18.5
−18.2
−18.0
−17.7
−17.5
−17.4
−17.2


Evaporator mean temperature
° C.
−30.4
−30.5
−30.6
−30.7
−30.8
−30.9
−30.9
−31.0


Evaporator glide (out-in)
K
13.2
14.0
14.8
15.5
16.1
16.7
17.1
17.6


Compressor suction pressure
bar
2.00
2.13
2.26
2.40
2.54
2.68
2.84
3.00


Compressor discharge pressure
bar
24.7
25.8
26.8
27.8
28.9
29.9
30.9
32.0


Suction line pressure drop
Pa/m
96
90
84
79
75
71
67
63


Pressure drop relative to reference

32.8%
30.8%
28.9%
27.2%
25.6%
24.2%
22.9%
21.7%


Condenser dew point
° C.
52.3
52.1
51.9
51.6
51.2
50.8
50.4
49.9


Condenser bubble point
° C.
31.5
30.8
30.2
29.7
29.3
28.9
28.6
28.3


Condenser exit liquid temperature
° C.
30.5
29.8
29.2
28.7
28.3
27.9
27.6
27.3


Condenser mean temperature
° C.
41.9
41.5
41.1
40.6
40.3
39.9
39.5
39.1


Condenser glide (in-out)
K
20.8
21.3
21.6
21.8
21.9
21.9
21.8
21.6
















TABLE 77







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 0-14% R-744, 25% R-32 and 30% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















0/25/30/45
2/25/30/43
4/25/30/41
6/25/30/39
8/25/30/37
10/25/30/35
12/25/30/33
14/25/30/31




















COP (heating)

2.23
2.25
2.26
2.27
2.28
2.29
2.30
2.30


COP (heating) relative to Reference

105.9%
106.7%
107.4%
107.9%
108.3%
108.6%
108.9%
109.1%


Volumetric heating capacity at suction
kJ/m3
1292
1393
1497
1604
1714
1828
1944
2063


Capacity relative to Reference

147.0%
158.5%
170.3%
182.6%
195.1%
208.0%
221.2%
234.8%


Critical temperature
° C.
94.91
92.44
90.08
87.82
85.65
83.58
81.59
79.68


Critical pressure
bar
47.50
48.28
49.07
49.85
50.63
51.42
52.20
52.98


Condenser enthalpy change
kJ/kg
279.9
287.3
294.2
300.5
306.3
311.8
316.8
321.6


Pressure ratio

13.91
13.76
13.59
13.39
13.18
12.94
12.71
12.46


Refrigerant mass flow
kg/hr
25.7
25.1
24.5
24.0
23.5
23.1
22.7
22.4


Compressor discharge temperature
° C.
138.1
141.0
143.8
146.4
149.0
151.3
153.6
155.8


Evaporator inlet pressure
bar
1.22
1.31
1.40
1.50
1.60
1.71
1.82
1.94


Condenser inlet pressure
bar
16.6
17.6
18.7
19.7
20.8
21.8
22.9
23.9


Evaporator inlet temperature
° C.
−32.2
−32.8
−33.3
−33.9
−34.4
−35.0
−35.6
−36.1


Evaporator dewpoint
° C.
−27.7
−27.1
−26.6
−26.2
−25.7
−25.2
−24.8
−24.4


Evaporator exit gas temperature
° C.
−22.7
−22.1
−21.6
−21.2
−20.7
−20.2
−19.8
−19.4


Evaporator mean temperature
° C.
−29.9
−30.0
−30.0
−30.0
−30.1
−30.1
−30.2
−30.3


Evaporator glide (out-in)
K
4.6
5.6
6.7
7.7
8.8
9.8
10.7
11.7


Compressor suction pressure
bar
1.19
1.28
1.37
1.47
1.58
1.69
1.80
1.92


Compressor discharge pressure
bar
16.6
17.6
18.7
19.7
20.8
21.8
22.9
23.9


Suction line pressure drop
Pa/m
178
162
148
136
125
116
108
100


Pressure drop relative to reference

60.8%
55.3%
50.5%
46.4%
42.8%
39.6%
36.8%
34.3%


Condenser dew point
° C.
50.3
50.8
51.3
51.6
51.8
51.9
52.0
51.9


Condenser bubble point
° C.
43.0
40.7
38.8
37.1
35.7
34.4
33.4
32.5


Condenser exit liquid temperature
° C.
42.0
39.7
37.8
36.1
34.7
33.4
32.4
31.5


Condenser mean temperature
° C.
46.6
45.8
45.0
44.4
43.7
43.2
42.7
42.2


Condenser glide (in-out)
K
7.3
10.1
12.5
14.5
16.1
17.5
18.6
19.5
















TABLE 78







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 25% R-32 and 30% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















16/25/
18/25/
20/25/
22/25/
24/25/
26/25/
28/25/
30/25/



30/29
30/27
30/25
30/23
30/21
30/19
30/17
30/15




















COP (heating)

2.30
2.31
2.31
2.31
2.31
2.31
2.31
2.31


COP (heating) relative to Reference

109.2%
109.4%
109.4%
109.5%
109.5%
109.5%
109.5%
109.4%


Volumetric heating capacity at suction
kJ/m3
2185
2310
2437
2567
2700
2837
2976
3119


Capacity relative to Reference

248.7%
262.9%
277.4%
292.2%
307.3%
322.8%
338.7%
354.9%


Critical temperature
° C.
77.84
76.07
74.37
72.73
71.15
69.63
68.16
66.75


Critical pressure
bar
53.77
54.55
55.33
56.11
56.89
57.67
58.45
59.24


Condenser enthalpy change
kJ/kg
326.1
330.4
334.4
338.3
341.9
345.4
348.7
351.9


Pressure ratio

12.21
11.97
11.72
11.48
11.24
11.01
10.77
10.54


Refrigerant mass flow
kg/hr
22.1
21.8
21.5
21.3
21.1
20.8
20.6
20.5


Compressor discharge temperature
° C.
157.9
160.0
162.0
163.9
165.7
167.5
169.2
170.9


Evaporator inlet pressure
bar
2.06
2.19
2.32
2.46
2.60
2.75
2.91
3.07


Condenser inlet pressure
bar
25.0
26.0
27.0
28.1
29.1
30.2
31.2
32.3


Evaporator inlet temperature
° C.
−36.6
−37.1
−37.6
−38.0
−38.4
−38.8
−39.2
−39.5


Evaporator dewpoint
° C.
−24.1
−23.7
−23.5
−23.2
−23.0
−22.7
−22.6
−22.4


Evaporator exit gas temperature
° C.
−19.1
−18.7
−18.5
−18.2
−18.0
−17.7
−17.6
−17.4


Evaporator mean temperature
° C.
−30.3
−30.4
−30.5
−30.6
−30.7
−30.8
−30.9
−30.9


Evaporator glide (out-in)
K
12.5
13.4
14.1
14.8
15.5
16.1
16.6
17.0


Compressor suction pressure
bar
2.04
2.17
2.31
2.45
2.59
2.74
2.90
3.06


Compressor discharge pressure
bar
25.0
26.0
27.0
28.1
29.1
30.2
31.2
32.3


Suction line pressure drop
Pa/m
94
88
82
78
73
69
65
62


Pressure drop relative to reference

32.0%
30.0%
28.2%
26.5%
25.0%
23.6%
22.4%
21.2%


Condenser dew point
° C.
51.8
51.6
51.4
51.1
50.8
50.4
50.0
49.5


Condenser bubble point
° C.
31.7
31.0
30.4
29.9
29.4
29.1
28.7
28.5


Condenser exit liquid temperature
° C.
30.7
30.0
29.4
28.9
28.4
28.1
27.7
27.5


Condenser mean temperature
° C.
41.7
41.3
40.9
40.5
40.1
39.7
39.4
39.0


Condenser glide (in-out)
K
20.2
20.7
21.0
21.2
21.3
21.3
21.2
21.0
















TABLE 79







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 0-14% R-744, 25% R-32 and 40% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















0/25/40/35
2/25/40/33
4/25/40/31
6/25/40/29
8/25/40/27
10/25/40/25
12/25/40/23
14/25/40/21




















COP (heating)

2.24
2.25
2.27
2.28
2.29
2.29
2.30
2.30


COP (heating) relative to Reference

106.1%
106.9%
107.5%
108.0%
108.4%
108.8%
109.0%
109.2%


Volumetric heating capacity at suction
kJ/m3
1314
1416
1522
1631
1742
1858
1976
2097


Capacity relative to Reference

149.5%
161.2%
173.2%
185.6%
198.3%
211.4%
224.9%
238.7%


Critical temperature
° C.
94.41
91.96
89.63
87.40
85.26
83.21
81.24
79.35


Critical pressure
bar
47.61
48.41
49.20
50.00
50.80
51.60
52.40
53.19


Condenser enthalpy change
kJ/kg
282.2
289.7
296.6
302.9
308.8
314.2
319.3
324.0


Pressure ratio

13.77
13.63
13.47
13.27
13.07
12.84
12.60
12.36


Refrigerant mass flow
kg/hr
25.5
24.9
24.3
23.8
23.3
22.9
22.6
22.2


Compressor discharge temperature
° C.
139.4
142.3
145.1
147.7
150.3
152.6
154.9
157.1


Evaporator inlet pressure
bar
1.24
1.33
1.42
1.52
1.62
1.73
1.85
1.97


Condenser inlet pressure
bar
16.7
17.7
18.8
19.9
20.9
22.0
23.0
24.1


Evaporator inlet temperature
° C.
−32.1
−32.6
−33.1
−33.7
−34.2
−34.8
−35.3
−35.8


Evaporator dewpoint
° C.
−27.9
−27.4
−26.9
−26.4
−25.9
−25.5
−25.1
−24.7


Evaporator exit gas temperature
° C.
−22.9
−22.4
−21.9
−21.4
−20.9
−20.5
−20.1
−19.7


Evaporator mean temperature
° C.
−30.0
−30.0
−30.0
−30.0
−30.1
−30.1
−30.2
−30.2


Evaporator glide (out-in)
K
4.1
5.2
6.2
7.2
8.3
9.3
10.2
11.2


Compressor suction pressure
bar
1.21
1.30
1.40
1.50
1.60
1.71
1.83
1.95


Compressor discharge pressure
bar
16.7
17.7
18.8
19.9
20.9
22.0
23.0
24.1


Suction line pressure drop
Pa/m
174
158
144
133
122
113
105
98


Pressure drop relative to reference

59.4%
54.0%
49.4%
45.4%
41.9%
38.8%
36.0%
33.6%


Condenser dew point
° C.
49.8
50.3
50.8
51.1
51.3
51.5
51.5
51.5


Condenser bubble point
° C.
43.2
40.9
38.9
37.2
35.8
34.5
33.4
32.5


Condenser exit liquid temperature
° C.
42.2
39.9
37.9
36.2
34.8
33.5
32.4
31.5


Condenser mean temperature
° C.
46.5
45.6
44.8
44.2
43.5
43.0
42.5
42.0


Condenser glide (in-out)
K
6.6
9.5
11.9
13.9
15.6
17.0
18.1
19.0
















TABLE 80







Theoretical Performance Data of Selected R-744/R-32/R-134a/R-1234ze(E) blends containing 16-30% R-744, 25% R-32 and 40% R-134a









Composition CO2/R-32/R-134a/R-1234ze(E) % by weight
















16/25/
28/25/
20/25/
22/25/
24/25/
26/25/
28/25/
30/25/



40/19
40/17
40/15
40/13
40/11
40/9
40/7
40/5




















COP (heating)

2.31
2.31
2.31
2.31
2.31
2.31
2.31
2.31


COP (heating) relative to Reference

109.4%
109.5%
109.6%
109.7%
109.7%
109.7%
109.7%
109.6%


Volumetric heating capacity at suction
kJ/m3
2221
2348
2477
2609
2743
2881
3021
3165


Capacity relative to Reference

252.8%
267.2%
281.9%
296.9%
312.2%
327.9%
343.8%
360.2%


Critical temperature
° C.
77.54
75.79
74.11
72.49
70.93
69.43
67.98
66.57


Critical pressure
bar
53.99
54.79
55.58
56.38
57.17
57.97
58.76
59.56


Condenser enthalpy change
kJ/kg
328.5
332.8
336.8
340.7
344.3
347.8
351.1
354.2


Pressure ratio

12.12
11.87
11.63
11.39
11.15
10.92
10.69
10.47


Refrigerant mass flow
kg/hr
21.9
21.6
21.4
21.1
20.9
20.7
20.5
20.3


Compressor discharge temperature
° C.
159.2
161.2
163.2
165.1
166.9
168.7
170.4
172.1


Evaporator inlet pressure
bar
2.09
2.22
2.36
2.50
2.64
2.79
2.95
3.11


Condenser inlet pressure
bar
25.2
26.2
27.3
28.3
29.3
30.4
31.4
32.5


Evaporator inlet temperature
° C.
−36.4
−36.9
−37.3
−37.8
−38.2
−38.6
−39.0
−39.3


Evaporator dewpoint
° C.
−24.3
−23.9
−23.6
−23.3
−23.1
−22.9
−22.7
−22.5


Evaporator exit gas temperature
° C.
−19.3
−18.9
−18.6
−18.3
−18.1
−17.9
−17.7
−17.5


Evaporator mean temperature
° C.
−30.3
−30.4
−30.5
−30.6
−30.7
−30.8
−30.8
−30.9


Evaporator glide (out-in)
K
12.1
12.9
13.7
14.5
15.1
15.8
16.3
16.8


Compressor suction pressure
bar
2.08
2.21
2.34
2.48
2.63
2.78
2.94
3.10


Compressor discharge pressure
bar
25.2
26.2
27.3
28.3
29.3
30.4
31.4
32.5


Suction line pressure drop
Pa/m
92
86
81
76
72
68
64
61


Pressure drop relative to reference

31.4%
29.4%
27.6%
26.0%
24.5%
23.2%
21.9%
20.8%


Condenser dew point
° C.
51.4
51.3
51.0
50.8
50.4
50.1
49.7
49.2


Condenser bubble point
° C.
31.7
31.0
30.4
29.9
29.4
29.1
28.7
28.5


Condenser exit liquid temperature
° C.
30.7
30.0
29.4
28.9
28.4
28.1
27.7
27.5


Condenser mean temperature
° C.
41.6
41.1
40.7
40.3
39.9
39.6
39.2
38.9


Condenser glide (in-out)
K
19.7
20.3
20.6
20.9
21.0
21.0
20.9
20.8
















TABLE 81







Theoretical Performance Data of Selected R-744/R-1234ze(E) blends containing 0-14% R-744









Composition CO2/R-1234ze(E) % by weight
















0/100
2/98
4/96
6/94
8/92
10/90
12/88
14/86




















COP (heating)

1.99
2.05
2.10
2.14
2.16
2.18
2.20
2.21


COP (heating) relative to Reference

94.4%
97.4%
99.6%
101.3%
102.5%
103.5%
104.3%
104.9%


Volumetric heating capacity at suction
kJ/m3
615
695
778
864
953
1046
1141
1239


Capacity relative to Reference

70.0%
79.1%
88.6%
98.3%
108.5%
119.0%
129.8%
141.0%


Critical temperature
° C.
109.89
105.93
102.20
98.69
95.38
92.25
89.29
86.48


Critical pressure
bar
36.57
37.34
38.10
38.87
39.63
40.40
41.16
41.92


Condenser enthalpy change
kJ/kg
210.2
223.7
235.1
244.8
253.2
260.5
267.2
273.2


Pressure ratio

18.75
18.99
19.05
18.95
18.71
18.39
18.00
17.58


Refrigerant mass flow
kg/hr
34.2
32.2
30.6
29.4
28.4
27.6
27.0
26.4


Compressor discharge temperature
° C.
112.8
117.1
121.1
124.7
127.9
131.0
133.8
136.5


Evaporator inlet pressure
bar
0.65
0.69
0.74
0.80
0.87
0.95
1.03
1.11


Condenser inlet pressure
bar
10.7
11.9
13.1
14.3
15.5
16.7
17.8
19.0


Evaporator inlet temperature
° C.
−28.9
−29.6
−30.3
−31.1
−31.9
−32.7
−33.6
−34.5


Evaporator dewpoint
° C.
−30.3
−29.7
−29.0
−28.3
−27.5
−26.6
−25.8
−25.1


Evaporator exit gas temperature
° C.
−25.3
−24.7
−24.0
−23.3
−22.5
−21.6
−20.8
−20.1


Evaporator mean temperature
° C.
−29.6
−29.7
−29.7
−29.7
−29.7
−29.7
−29.7
−29.8


Evaporator glide (out-in)
K
−1.3
−0.1
1.3
2.8
4.4
6.0
7.7
9.4


Compressor suction pressure
bar
0.57
0.63
0.69
0.75
0.83
0.91
0.99
1.08


Compressor discharge pressure
bar
10.7
11.9
13.1
14.3
15.5
16.7
17.8
19.0


Suction line pressure drop
Pa/m
462
390
336
294
259
231
208
189


Pressure drop relative to reference

158.3%
133.6%
115.0%
100.5%
88.8%
79.2%
71.3%
64.6%


Condenser dew point
° C.
53.1
55.1
56.7
58.1
59.2
60.0
60.5
60.9


Condenser bubble point
° C.
53.0
47.1
42.6
38.9
36.1
33.8
31.9
30.4


Condenser exit liquid temperature
° C.
52.0
46.1
41.6
37.9
35.1
32.8
30.9
29.4


Condenser mean temperature
° C.
53.1
51.1
49.7
48.5
47.6
46.9
46.2
45.7


Condenser glide (in-out)
K
0.1
7.9
14.2
19.1
23.1
26.2
28.6
30.6
















TABLE 82







Theoretical Performance Data of Selected R-744/R-1234ze(E) blends containing 16-30% R-744









Composition CO2/R-1234ze(E) % by weight
















16/84
18/82
20/80
22/78
24/76
26/74
28/72
30/70




















COP (heating)

2.22
2.23
2.23
2.24
2.24
2.24
2.24
2.24


COP (heating) relative to Reference

105.4%
105.7%
106.0%
106.2%
106.3%
106.3%
106.3%
106.2%


Volumetric heating capacity at suction
kJ/m3
1339
1441
1545
1650
1756
1862
1969
2076


Capacity relative to Reference

152.4%
164.0%
175.8%
187.7%
199.8%
211.9%
224.1%
236.3%


Critical temperature
° C.
83.81
81.28
78.87
76.57
74.38
72.28
70.28
68.37


Critical pressure
bar
42.68
43.44
44.20
44.96
45.72
46.47
47.23
47.98


Condenser enthalpy change
kJ/kg
278.7
283.9
288.9
293.6
298.1
302.5
306.8
311.0


Pressure ratio

17.15
16.72
16.29
15.88
15.49
15.12
14.77
14.44


Refrigerant mass flow
kg/hr
25.8
25.4
24.9
24.5
24.2
23.8
23.5
23.1


Compressor discharge temperature
° C.
139.0
141.4
143.8
146.1
148.4
150.6
152.9
155.1


Evaporator inlet pressure
bar
1.20
1.29
1.39
1.49
1.60
1.70
1.81
1.92


Condenser inlet pressure
bar
20.1
21.2
22.3
23.3
24.4
25.4
26.5
27.5


Evaporator inlet temperature
° C.
−35.5
−36.5
−37.6
−38.7
−39.7
−40.8
−41.9
−42.9


Evaporator dewpoint
° C.
−24.4
−23.7
−23.1
−22.5
−22.0
−21.6
−21.2
−20.9


Evaporator exit gas temperature
° C.
−19.4
−18.7
−18.1
−17.5
−17.0
−16.6
−16.2
−15.9


Evaporator mean temperature
° C.
−29.9
−30.1
−30.3
−30.6
−30.9
−31.2
−31.5
−31.9


Evaporator glide (out-in)
K
11.2
12.9
14.5
16.2
17.7
19.2
20.7
22.0


Compressor suction pressure
bar
1.17
1.27
1.37
1.47
1.57
1.68
1.79
1.90


Compressor discharge pressure
bar
20.1
21.2
22.3
23.3
24.4
25.4
26.5
27.5


Suction line pressure drop
Pa/m
172
157
145
134
125
116
109
102


Pressure drop relative to reference

58.8%
53.9%
49.7%
45.9%
42.7%
39.8%
37.2%
35.0%


Condenser dew point
° C.
61.2
61.2
61.2
61.0
60.8
60.4
60.0
59.5


Condenser bubble point
° C.
29.1
28.0
27.1
26.3
25.7
25.1
24.6
24.1


Condenser exit liquid temperature
° C.
28.1
27.0
26.1
25.3
24.7
24.1
23.6
23.1


Condenser mean temperature
° C.
45.1
44.6
44.1
43.7
43.2
42.7
42.3
41.8


Condenser glide (in-out)
K
32.1
33.2
34.1
34.7
35.1
35.3
35.4
35.3









Further Performance Data

The performance of a composition containing 6% by weight CO2, 10% by weight R-134a and 84% by weight R-1234ze(E) was tested in an automotive air conditioning system suitable for use with R-134a. This composition is denoted “Blend” in the results shown below.


The test conditions used were as described in SAE Standard J2765, which is incorporated herein by reference. These conditions are summarised below.

    • Ambient air condition 35° C. and 40% relative humidity (RH)
    • Air off temperature from evaporator controlled to 3° C.
    • Compressor displacement variable 0-175 cc per stroke
    • Conventional R-134a expansion valve was replaced with an electronic expansion valve to allow for ease of superheat adjustment
    • System used without internal heat exchanger and with equivalent superheat at evaporator exit for all fluids


The results are shown below, in which I, L, M and H refer to idle, low, medium and high speed, and wherein 35 and 45 refer to the ambient temperature in ° C.























Relative to










Measured cooling capacity (kW)
R-134a












Test point
R134a
Blend
Blend







I35
4.67
4.5
96%



L35
5.86
5.66
97%



M35
6.43
6.18
96%



H35
6.65
6.5
98%



I45
3.81
3.64
96%



L45
4.76
4.61
97%



M45
5.2
5.05
97%



H45
5.41
5.33
99%







Measured Energy
(expressed

COP relative



Efficiency
as COP)

to R-134a



Test point
R134a
Blend
Blend







I35
2.87
2.62
91%



L35
1.98
1.89
95%



M35
1.79
1.7
95%



H35
1.4
1.36
97%



I45
2.3
2.18
95%



L45
1.64
1.62
99%



M45
1.48
1.45
98%



H45
1.18
1.16
98%










The Blend composition of the invention represents a good match of capacity and efficiency for R-134a in an R-134a air-conditioning system across a range of conditions.


Lubricant Miscibility Data

The miscibility of a composition of the invention containing about 6% by weight CO2, about 10% by weight R-134a and about 84% by weight R-1234ze(E) (referred to below as Blend) was tested with the polyalkylene glycol (PAG) lubricant YN12 and the polyol ester (POE) lubricant 32H. The results of these experiments were compared to the miscibility of pure R-1234yf with the same lubricants. The results are shown below.


Miscibility Results for Blend

with 32H













Temperature
Lubricant Concentration wt %













deg C.
4
7
10
20
30
50
















−20
miscible
miscible
miscible
miscible
miscible
miscible


−10
miscible
miscible
miscible
miscible
miscible
miscible


0
miscible
miscible
miscible
miscible
miscible
miscible


10
miscible
miscible
miscible
miscible
miscible
miscible


20
miscible
miscible
miscible
miscible
miscible
miscible


30
miscible
miscible
miscible
miscible
miscible
miscible


40
miscible
miscible
miscible
miscible
miscible
miscible


50
miscible
miscible
miscible
miscible
miscible
miscible


60
miscible
miscible
miscible
miscible
miscible
miscible


70
miscible
miscible
miscible
miscible
miscible
miscible


80
miscible
miscible
miscible
miscible
miscible
miscible









Miscibility Results for 1234yf with 32H













Temperature
Lubricant Concentration wt %













deg C.
4
7
10
20
30
50
















−20
miscible
miscible
miscible
miscible
miscible
miscible


−10
miscible
miscible
miscible
miscible
miscible
miscible


0
miscible
miscible
miscible
miscible
miscible
miscible


10
slightly
slightly
miscible
miscible
miscible
miscible



opaque
opaque


20
slightly
slightly
miscible
miscible
miscible
miscible



opaque
opaque


30
slightly
slightly
miscible
miscible
miscible
miscible



opaque
opaque


40
slightly
slightly
miscible
miscible
miscible
miscible



opaque
opaque


50
slightly
slightly
miscible
miscible
slightly
slightly



opaque
opaque


opaque
opaque


60
slightly
slightly
miscible
miscible
slightly
slightly



opaque
opaque


opaque
opaque


70
slightly
slightly
miscible
miscible
slightly
slightly



opaque
opaque


opaque
opaque


80
Miscible
slightly
miscible
Opaque 2
Opaque 2
Opaque




opaque

layers
layers










Miscibility Results for Blend with YN12













Temp
Lubricant Concentration wt %













deg C.
4
7
10
20
30
50
















−20
Opaque
Opaque
Opaque
Opaque
Opaque
Opaque


−10
Opaque
Opaque
Opaque
Opaque
slightly
slightly







opaque
opaque


0
Opaque
Opaque
slightly
slightly
slightly
slightly





opaque
opaque
opaque
opaque


10
Opaque
Opaque
slightly
slightly
slightly
slightly





opaque
opaque
opaque
opaque


20
Opaque
Opaque
slightly
slightly
slightly
slightly





opaque
opaque
opaque
opaque


30
slightly
Opaque
slightly
slightly
slightly
slightly



opaque

opaque
opaque
opaque
opaque


40
slightly
slightly
slightly
slightly
slightly
slightly



opaque
opaque
opaque
opaque
opaque
opaque


50
very
very
slightly
slightly
slightly
slightly



Slighty
Slighty
opaque
opaque
opaque
opaque



opaque
opaque


60
very
very
slightly
slightly
slightly
slightly



Slighty
Slighty
opaque
opaque
opaque
opaque



opaque
opaque


70
very
very
2 layers
2 layers
2 layers
slightly



Slighty
Slighty



opaque



opaque
opaque


80
2 layers
2 layers
2 layers
2 layers
2 layers
2 layers










Miscibility Results for 1234yf with


YN12













Temperature
Lubricant Concentration wt %













deg C.
4
7
10
20
30
50
















−20
opaque
opaque
2 layers
opaque
2 layers
2 layers


−10
slightly
slightly
2 layers
opaque
2 layers
2 layers



opaque
opaque


0
slightly
opaque
2 layers
opaque
opaque
opaque



opaque


10
slightly
opaque
2 layers
2 layers
2 layers
2 layers



opaque

opaque
opaque
opaque
opaque


20
opaque
slightly
2 layers
2 layers
2 layers
2 layers




opaque 2
opaque

opaque
opaque




layers


30
opaque
opaque
2 layers
2 layers
2 layers
2 layers





opaque

opaque
opaque


40
clear 2
clear 2
2 layers
2 layers
2 layers
2 layers



layers
layers
clear

clear
clear


50
clear 2
clear 2
2 layers
2 layers
2 layers
2 layers



layers
layers
clear

clear
clear


60
clear 2
clear 2
2 layers
2 layers
2 layers
2 layers



layers
layers
clear

clear
clear


70
clear 2
clear 2
2 layers
2 layers
2 layers
2 layers



layers
layers
clear

clear
clear


80
clear 2
clear 2
2 layers
2 layers
2 layers
2 layers



layers
layers
clear

clear
clear









The miscibility of further compositions of the invention were tested with the polyalkylene glycol (PAG) lubricant YN12. The lubricant was present in a concentration of 4% w/w. This concentration is representative of the typical oil concentration present in an air conditioning system. The results of these experiments were compared to the miscibility of pure R-1234yf. The results are shown below.















Temperature/° C.













0
10
20
30
40
















R-1234yf
opaque
opaque
opaque
very
opaque


(comparative)



opaque


CO2/R-134a/
slightly
slightly
slightly
very
slightly


R-1234ze
opaque
opaque
opaque
slightly
opaque


(15/10/75



opaque


% by weight)


CO2/R-134a/
opaque
slightly
very
ok


R-1234ze

opaque
slightly


(25/10/65


opaque


% by weight)


CO2/R-32/
opaque
slightly
very
ok


R-1234ze

opaque
slightly


(4/7/89


opaque


% by weight)









The results show that the compositions of the invention have improved miscibility with lubricants compared to the pure fluid R-1234yf.


In summary, the invention provides new compositions that exhibit a surprising combination of advantageous properties including good refrigeration performance, low flammability, low GWP, and/or miscibility with lubricants compared to existing refrigerants such as R-134a and the proposed refrigerant R-1234yf.


The invention is defined by the following claims.

Claims
  • 1. A heat transfer composition comprising: (i) a first component selected from trans-1,3,3,3-tetrafluoropropene (R-1234ze(E)), cis-1,3,3,3-tetrafluoropropene (R-1234ze(Z)) and mixtures thereof;(ii) carbon dioxide (R-744); and(iii) a third component selected from difluoromethane (R-32), 1,1,1,2-tetrafluoroethane (R-134a) and mixtures thereof.
  • 2. A composition according to claim 1 wherein the first component comprises R-1234ze(E).
  • 3. A composition according to claim 1 or 2 comprising at least about 15% by weight R-1234ze(E).
  • 4. A composition according to any of the preceding claims comprising up to about 35% by weight R-744, preferably about 30% by weight R-744.
  • 5. A composition according to claim 4 comprising from about 4 to about 30% R-744 by weight, preferably from about 4 to about 28% by weight, or from about 8 to about 30% by weight, or from about 10 to about 30% by weight.
  • 6. A composition according to any of the preceding claims comprising up to about 60% by weight of the third component, preferably up to about 50% by weight.
  • 7. A composition according to any of the preceding claims comprising from about 10 to about 95% R-1234ze(E) by weight, from about 2 to about 30% by weight R-744, and from about 3 to about 60% by weight of the third component.
  • 8. A composition according to any of the preceding claims which has a critical temperature of greater than about 65° C., preferably greater than about 70° C.
  • 9. A composition according to any of the preceding claims wherein the third component comprises R-134a, preferably from about 2 to about 50% R-134a.
  • 10. A composition according to any of the preceding claims comprising from about 20 to about 94% by weight R-1234ze(E), from about 2 to about 30% by weight R-744 and from about 4 to about 50% by weight R-134a.
  • 11. A composition according to claim 10 comprising from about 60 to about 92% R-1234ze(E), from about 4 to about 30% by weight R-744 and from about 4 to about 10% by weight R-134a, preferably comprising from about 62 to about 86% R-1234ze(E), from about 10 to about 28% by weight R-744 and from about 4 to about 10% by weight R-134a.
  • 12. A composition according to claim 10 comprising from about 20 to about 86% R-1234ze(E), from about 4 to about 30% by weight R-744 and from about 10 to about 50% by weight R-134a, preferably comprising from about 22 to about 80% R-1234ze(E), from about 10 to about 28% by weight R-744 and from about 10 to about 50% by weight R-134a.
  • 13. A composition according to any of claims 1 to 8 wherein the third component comprises R-32, preferably from about 2 to about 30% by weight R-32.
  • 14. A composition according to claim 13 comprising from about 60 to about 91% by weight R-1234ze(E), from about 4 to about 30% by weight R-744 and from about 5 to about 30% by weight R-32, preferably comprising from about 58 to about 85% R-1234ze(E), from about 10 to about 28% by weight R-744 and from about 5 to about 30% by weight R-32.
  • 15. A composition according to claim 13 comprising from about 50 to about 88% by weight R-1234ze(E), from about 4 to about 30% by weight R-744 and from about 2 to about 20% by weight R-32.
  • 16. A composition according to any of claims 1 to 8 wherein the third component comprises R-134a and R-32.
  • 17. A composition according to claim 16 comprising from about 5 to about 95% by weight R-1234ze(E), from about 4 to about 30% by weight R-744, from about 2 to about 30% by weight R-32 and from about 2 to about 50 by weight R-134a, preferably comprising from about 5 to about 92% by weight R-1234ze(E), from about 4 to about 30% by weight R-744, from about 2 to about 25% by weight R-32 and from about 2 to about 40% by weight R-134a.
  • 18. A composition according to claim 17 comprising from about 30 to about 81% by weight R-1234ze(E), from about 10 to about 30% by weight R-744, from about 5 to about 30% by weight R-32 and from about 4 to about 10 by weight R-134a, preferably comprising from about 37 to about 81% by weight R-1234ze(E), from about 10 to about 28% by weight R-744, from about 5 to about 25% by weight R-32 and from about 4 to about 10 by weight R-134a.
  • 19. A composition according to claim 17 comprising from about 5 to about 75% by weight R-1234ze(E), from about 10 to about 30% by weight R-744, from about 5 to about 25% by weight R-32 and from about 10 to about 50 by weight R-134a, preferably comprising from about 7 to about 75% by weight R-1234ze(E), from about 10 to about 28% by weight R-744, from about 5 to about 25% by weight R-32 and from about 10 to about 40 by weight R-134a.
  • 20. A composition according to any of the preceding claims consisting essentially of R-1234ze(E), R-744 and the third component.
  • 21. A composition according to any of claims 1 to 19, further comprising pentafluoroethane (R-125).
  • 22. A composition consisting essentially of from about 4 to about 34% by weight carbon dioxide (R-744) and from about 66 to about 96% by weight trans-1,3,3,3-tetrafluoropropene (R-1234ze(E)).
  • 23. A composition according to claim 21 consisting essentially of from about 4 to about 30% by weight R-744 and from about 70 to about 96% by weight R-1234ze(E).
  • 24. A composition according to claim 22 consisting essentially of from about 6 to about 30% by weight R-744 and from about 70 to about 94% by weight R-1234ze(E).
  • 25. A composition according to any of claims 22 to 24 which has a critical temperature of greater than about 70° C.
  • 26. A composition according to any of the preceding claims, wherein the composition has a GWP of less than 1000, preferably less than 150.
  • 27. A composition according to any of the preceding claims, wherein the composition has a volumetric refrigeration capacity within about 15%, preferably within about 10% of the existing refrigerant that it is intended to replace.
  • 28. A composition according to any of the preceding claims, wherein the composition is less flammable than R-32 alone or R-1234yf alone.
  • 29. A composition according to claim 28 wherein the composition has: (a) a higher flammable limit;(b) a higher ignition energy; and/or(c) a lower flame velocity
  • 30. A composition according to any of the preceding claims which has a fluorine ratio (F/(F+H)) of from about 0.42 to about 0.7, preferably from about 0.44 to about 0.67.
  • 31. A composition according to any of the preceding claims which is non-flammable.
  • 32. A composition according to any of the preceding claims, wherein the composition has a cycle efficiency within about 5% of the existing refrigerant that it is intended to replace.
  • 33. A composition according to any of the preceding claims, wherein the composition has a compressor discharge temperature within about 15K, preferably within about 10K, of the existing refrigerant that it is intended to replace.
  • 34. A composition comprising a lubricant and a composition according to any of the preceding claims.
  • 35. A composition according to claim 34, wherein the lubricant is selected from mineral oil, silicone oil, polyalkyl benzenes (PABs), polyol esters (POEs), polyalkylene glycols (PAGs), polyalkylene glycol esters (PAG esters), polyvinyl ethers (PVEs), poly (alpha-olefins) and combinations thereof.
  • 36. A composition according to claim 34 or 35 further comprising a stabiliser.
  • 37. A composition according to claim 36, wherein the stabiliser is selected from diene-based compounds, phosphates, phenol compounds and epoxides, and mixtures thereof.
  • 38. A composition comprising a flame retardant and a composition according to any of the preceding claims.
  • 39. A composition according to claim 38, wherein the flame retardant is selected from the group consisting of tri-(2-chloroethyl)-phosphate, (chloropropyl) phosphate, tri-(2,3-dibromopropyl)-phosphate, tri-(1,3-dichloropropyl)-phosphate, diammonium phosphate, various halogenated aromatic compounds, antimony oxide, aluminium trihydrate, polyvinyl chloride, a fluorinated iodocarbon, a fluorinated bromocarbon, trifluoro iodomethane, perfluoroalkyl amines, bromo-fluoroalkyl amines and mixtures thereof.
  • 40. A composition according to any of the preceding claims which is a refrigerant composition.
  • 41. A heat transfer device containing a composition as defined in any one of claims 1 to 40.
  • 42. Use of a composition defined in any of claims 1 to 40 in a heat transfer device.
  • 43. A heat transfer device according to claim 41 or 42 which is a refrigeration device.
  • 44. A heat transfer device according to claim 43 which is selected from group consisting of automotive air conditioning systems, residential air conditioning systems, commercial air conditioning systems, residential refrigerator systems, residential freezer systems, commercial refrigerator systems, commercial freezer systems, chiller air conditioning systems, chiller refrigeration systems, and commercial or residential heat pump systems, preferably wherein the heat transfer device is an automobile air-conditioning system.
  • 45. A heat transfer device according to claim 43 or 44 which contains a compressor.
  • 46. A blowing agent comprising a composition as defined in any of claims 1 to 40.
  • 47. A foamable composition comprising one or more components capable of forming foam and a composition as defined in any of claims 1 to 40, wherein the one or more components capable of forming foam are selected from polyurethanes, thermoplastic polymers and resins, such as polystyrene, and epoxy resins, and mixtures thereof.
  • 48. A foam obtainable from the foamable composition as defined in claim 47.
  • 49. A foam according to claim 48 comprising a composition as defined in any one of claims 1 to 41.
  • 50. A sprayable composition comprising material to be sprayed and a propellant comprising a composition as defined in any of claims 1 to 40.
  • 51. A method for cooling an article which comprises condensing a composition defined in any of claims 1 to 40 and thereafter evaporating the composition in the vicinity of the article to be cooled.
  • 52. A method for heating an article which comprises condensing a composition as defined in any one of claims 1 to 40 in the vicinity of the article to be heated and thereafter evaporating the composition.
  • 53. A method for extracting a substance from biomass comprising contacting biomass with a solvent comprising a composition as defined in any of claims 1 to 40, and separating the substance from the solvent.
  • 54. A method of cleaning an article comprising contacting the article with a solvent comprising a composition as defined in any of claims 1 to 40.
  • 55. A method of extracting a material from an aqueous solution comprising contacting the aqueous solution with a solvent comprising a composition as defined in any of claims 1 to 40, and separating the substance from the solvent.
  • 56. A method for extracting a material from a particulate solid matrix comprising contacting the particulate solid matrix with a solvent comprising a composition as defined in any of claims 1 to 40, and separating the material from the solvent.
  • 57. A mechanical power generation device containing a composition as defined in any of claims 1 to 40.
  • 58. A mechanical power generating device according to claim 57 which is adapted to use a Rankine Cycle or modification thereof to generate work from heat.
  • 59. A method of retrofitting a heat transfer device comprising the step of removing an existing heat transfer fluid, and introducing a composition as defined in any one of claims 1 to 40.
  • 60. A method of claim 59 wherein the heat transfer device is a refrigeration device.
  • 61. A method according to claim 60 wherein the heat transfer device is an air conditioning system.
  • 62. A method for reducing the environmental impact arising from the operation of a product comprising an existing compound or composition, the method comprising replacing at least partially the existing compound or composition with a composition as defined in any one of claims 1 to 40.
  • 63. A method for preparing a composition as defined in any of claims 1 to 40, and/or a heat transfer device as defined in any of claims 41 or 43 to 45, which composition or heat transfer device contains R-134a, the method comprising introducing R-1234ze(E), R-744, the third component, and optionally R-125, a lubricant, a stabiliser and/or a flame retardant, into a heat transfer device containing an existing heat transfer fluid which is R-134a.
  • 64. A method according to claim 63 comprising the step of removing at least some of the existing R-134a from the heat transfer device before introducing the R-1234ze(E), R-744, the third component, and optionally the R-125, the lubricant, the stabiliser and/or the flame retardant.
  • 65. A method for generating greenhouse gas emission credit comprising (i) replacing an existing compound or composition with a composition as defined in any one of claims 1 to 40, wherein the composition as defined in any one of claims 1 to 40 has a lower GWP than the existing compound or composition; and (ii) obtaining greenhouse gas emission credit for said replacing step.
  • 66. A method of claim 65 wherein the use of the composition of the invention results in a lower Total Equivalent Warming Impact, and/or a lower Life-Cycle Carbon Production than is attained by use of the existing compound or composition.
  • 67. A method of claim 65 or 66 carried out on a product from the fields of air-conditioning, refrigeration, heat transfer, blowing agents, aerosols or sprayable propellants, gaseous dielectrics, cryosurgery, veterinary procedures, dental procedures, fire extinguishing, flame suppression, solvents, cleaners, air horns, pellet guns, topical anesthetics, and expansion applications.
  • 68. A method according to claim 62 or 67 wherein the product is selected from a heat transfer device, a blowing agent, a foamable composition, a sprayable composition, a solvent or a mechanical power generation device.
  • 69. A method according to claim 68 wherein the product is a heat transfer device.
  • 70. A method according to any one of claims 60 or 63 to 67 wherein the existing compound or composition is a heat transfer composition.
  • 71. A method according to claim 70 wherein the heat transfer composition is a refrigerant selected from R-134a, R-1234yf, R-152a, R-404A, R-410A, R-507, R-407A, R-407B, R-407D, R-407E and R-407F.
  • 72. Any novel heat transfer composition substantially as hereinbefore described, optionally with reference to the examples.
Priority Claims (4)
Number Date Country Kind
1008438.2 May 2010 GB national
1010057.6 Jun 2010 GB national
1020624.1 Dec 2010 GB national
1102556.6 Feb 2011 GB national
CROSS-REFERENCE TO RELATED APPLICATIONS

This application is a continuation of U.S. application Ser. No. 13/698,817, filed Nov. 19, 2012, which is the U.S. National Phase under 35 U.S.C. §371 of International Application No. PCT/GB2011/000772, filed May 20, 2011, designating the United States and published in English on Nov. 24, 2011, as WO 2011/144909, which claims priority to United Kingdom Application No. 1008438.2, filed May 20, 2010, United Kingdom Application No. 1010057.6, filed Jun. 16, 2010, United Kingdom Application No. 1020624.1, filed Dec. 6, 2010, and United Kingdom Application No. 1102556.6, filed Feb. 14, 2011, each of which is incorporated by reference in its entirety.

Continuations (1)
Number Date Country
Parent 13698817 Jan 2013 US
Child 15091242 US