Before any embodiments of the invention are explained in detail, it is to be understood that the invention is not limited in its application to the details of construction and the arrangement of components set forth in the following description or illustrated in the following drawings. The invention is capable of other embodiments and of being practiced or of being carried out in various ways. Also, it is to be understood that the phraseology and terminology used herein is for the purpose of description and should not be regarded as limiting. The use of “including,” “comprising,” or “having” and variations thereof herein is meant to encompass the items listed thereafter and equivalents thereof as well as additional items. Unless specified or limited otherwise, the terms “mounted,” “connected,” “supported,” and “coupled” and variations thereof are used broadly and encompass both direct and indirect mountings, connections, supports, and couplings. Further, “connected” and “coupled” are not restricted to physical or mechanical connections or couplings.
Referring again to
In addition, the elevated step 30 supports a divider 60 that divides the space between the bottom of the tank 35, skirt 50, and the base pan 15 into a combustion chamber 65 (above the divider 60) and plenum 70 (below the divider 60).
A cold water inlet tube 75 and a hot water outlet tube 80 extend through a top wall of the water tank 35. A flue 85 extends through the tank 35, and water in the tank 35 surrounds the flue 85. The flue 85 includes an inlet end 90 and an outlet end 95.
The combustion chamber 65 and plenum 70 space is substantially air-tightly sealed, except for the air inlet opening 27 and inlet end 90 of the flue 85, and seals 105 between the skirt 50 and the tank 35 and base pan 15 assist in sealing the space. The seals 105 may be, for example and without limitation, fiberglass material or a high-temperature caulk material. A radiation shield 110 sits on the divider 60 within the sealed combustion chamber 65 and reflects radiant heat up toward the tank 35.
A flame arrester 115 is affixed in a sealed condition across an opening 120 in the divider 60 such that all air flowing from the plenum 70 into the combustion chamber 65 should flow through the flame arrester 115. The air inlet 27, air plenum 70, and opening 120 in the divider 60 together define an air intake for the combustion chamber 65, and all air flowing into the combustion chamber 65 through the opening (see arrows in
With reference again to
A main burner 155 in the combustion chamber 65 burns a mixture of fuel and air to create the products of combustion that flow up through the flue 85 to heat the water in the tank 35. The main burner 155 receives fuel through a gas manifold tube 160 that extends in a sealed condition through an access door 165 mounted in a sealed condition over an access opening in the skirt 50.
The construction shown (illustrated in
The gas valve/thermostat 170 provides a flow of fuel to the pilot burner 185 to maintain a standing pilot burner flame, and this construction is therefore generally referred to as a “continuous pilot ignition” system. The spark igniter 195 is used to initiate flame on the pilot burner 185 without having to reach into the combustion chamber with a match. A spark is generated by the spark igniter 195 in response to pushing a button on the gas valve/thermostat 170. The thermocouple 190 provides feedback to the gas valve/thermostat 170 as to the presence of flame at the pilot burner 185. More specifically, the gas valve/thermostat 170 includes an interrupter valve or some other means for selectively shutting off fuel flow to the pilot burner 185 and main burner 155. The interrupter valve is biased toward a closed position. The interrupter valve is held open by a voltage arising in the thermocouple 190 in response to the tip of the thermocouple 190 being heated by the pilot burner flame. If the pilot burner 185 loses its flame, the thermocouple 190 will cool down and not provide the voltage to the interrupter valve, and the interrupter valve will close and shut off fuel flow to the pilot burner 185 and main burner 155.
The gas valve/thermostat 170 permits fuel to flow to the main burner 155 in response to a water temperature sensor (e.g., the water temperature probe 180) indicating that the water temperature in the water tank 35 has fallen below a selected temperature. When fuel flows to the main burner 155, it is mixed with air and the mixture is ignited when it contacts the pilot burner flame. Once the water temperature sensor indicates that the water has reached the desired temperature, the gas valve/thermostat 170 shuts off fuel flow to the main burner 155, and the water heater 10 is in “standby mode” until the water temperature again drops to the point where the gas valve/thermostat 170 should again provide fuel to the main burner 155.
The secondary safety circuit 200 includes a low-voltage pulse actuated valve 210, at least one sensor 215, and a power source 220. The power source shown in
Once closed, the low-voltage pulse actuated valve 210 remains closed until it is opened manually by pressing a reset button while, at the same time, applying a voltage pulse of opposite polarity and substantially the same magnitude as the pulse used to close the valve 210. The pulse can be provided by an external battery or other suitable power source. In some constructions, the means for application of the pulse (e.g., terminals) for resetting the valve 210 can be hidden and require a qualified serviceman to reset the valve 210. Requiring a serviceman to reset the valve 210 can ensure that the safety condition which caused the valve 210 to close is repaired before the water heater is put back into service. Because the low-voltage pulse actuated valve 210 is a normally open valve, it requires no energy to remain open during normal operation.
In the construction shown in
When the low-voltage pulse actuated valve 210 receives a low-voltage pulse, it closes shutting off the supply of gas through pilot gas line 225 to the pilot burner 185. Shutting off the supply of gas to the pilot burner 185 results in the pilot burner flame extinguishing. Once the pilot burner flame extinguishes, the thermocouple 190 will cool and stop providing voltage to the interrupter valve. When the voltage provided by the thermocouple 190 to the interrupter valve drops below a threshold, the interrupter valve will close and fuel flow will be shut off to the main burner 155 and to the pilot burner 185. The thermocouple 220, of the secondary safety circuit 200, also cools and the voltage provided to the secondary safety circuit 200 drops. The loss of voltage has no impact on the secondary safety circuit 200 because the low-voltage pulse actuated valve 210 remains closed until it is manually reset.
The low-voltage pulse actuated valve 210 can have a first node 235 coupled to an electrical common 240 of the secondary safety circuit 200. The low-voltage pulse actuated valve 210 can also have a second node 245. The second node 245 can be coupled to an output 250 of the at least one comparator 230. When a voltage differential between the first node 235 and the second node 245 of the low-voltage pulse actuated valve 210 exceeds a threshold, the low-voltage pulse actuated valve 210 closes. When the low-voltage actuated valve 210 closes, it interrupts the flow of fuel in a pilot gas line 225, and extinguishes the pilot burner flame as discussed above. Once the safety condition that resulted in closing the low-voltage actuated valve 210 is corrected, the low-voltage actuated valve 210 is manually reset, as described above, to open the valve 210. In some embodiments, the valve 210 can reopen automatically when the safety condition is corrected and not require manual resetting.
The thermocouple 220 can have a negative node 255 coupled to common 240 of the secondary safety circuit 200 and a positive node 260 coupled to an input 265 of the at least one comparator 230. The thermocouple 220 produces a direct current voltage between its negative node 255 and its positive node 260 that is proportional to a temperature of the thermocouple 220.
The at least one sensor 215 can be self powered (sensors 215A and 215B) or can require an external power source (sensor 215C). The at least one sensor 215 has an output 270 which is coupled to a gate input 275 of the at least one comparator 230. When the voltage at the gate input 275 is below a threshold, the comparator 230 functions as an open switch preventing current applied to the input 265 from passing through to the output 250. When the voltage at the gate input 275 is above the threshold, the comparator 230 functions as a closed switch allowing current applied to the input 265 to pass through to the output 250.
The at least one sensor 215 can have a common node 280 coupled to the common 240 of the second safety circuit 200. If the sensor 215 requires an external power source (sensor 215C), the sensor 215 can have a power input node 285. The power input node 285 can be coupled to the positive node 260 of the thermocouple 220 (as shown in
When the sensor 215 detects a safety condition, the sensor 215 can provide a signal of the safety condition in the form of a voltage at its output 270. The sensor 215 can be configured as a switch such that, when the sensor 215 detects its condition, it outputs a voltage and when it does not detect its condition it outputs no voltage. The sensor 215 can also be configured as a sensor that outputs a voltage proportional to a severity of the condition it detects (e.g., a CO sensor that outputs an increasing voltage as a concentration of CO increases). The sensor 215 is configured such that when the sensor 215 detects a condition (or the severity of the condition exceeds a predetermined threshold), the sensor 215 provides a voltage to the gate input 275 of the comparator 230 sufficient to close the circuit and apply the voltage from the thermocouple 220 to the low-voltage actuated valve 210 and close the low-voltage actuated valve 210.
In some embodiments, the at least one sensor 215 includes a plurality of sensors wired in series such that all the sensors wired in series should detect one or more safety conditions before the secondary safety circuit 200 closes the low-voltage actuated valve 210.
In some embodiments, the low-voltage actuated valve 210 can be installed in a main the main gas line 175 and can interrupt fuel flow to the entire water heater 10 when a safety condition is detected.
In some constructions, a pulse actuated valve can be used which requires a relatively high voltage pulse (e.g., 24 Vdc) to close. A power source to provide the pulse can include a step-down transformer and a rectifier circuit powered by a 120 Vac line voltage.
While the secondary safety circuit has been described in relation to a water heater, the secondary safety circuit has application in any gas-fired device including a furnace, a stove, and a boiler. Further, the secondary safety circuit is not limited to gas-fired devices incorporating a pilot burner and associated safety circuit. Instead the secondary safety circuit can be power by a battery or external power source and can interrupt the main flow of fuel to the device. In addition, the secondary safety circuit can be used in any device in which a flow of fuel is required, including propane (e.g., barbeque grills) and gasoline (e.g., automobiles).
Thus, the invention provides, among other things, a secondary safety circuit for devices requiring a fuel supply. Various features and advantages of the invention are set forth in the following claims.