This invention relates to direct current-to-direct current converters (DC/DC) and, in particular, to methods, systems, apparatus and devices for a high efficiency and high power density wide input range front end DC/DC converter for use in distributed power systems and server power supplies.
Range winding topology activates to increase the transformer turn-ratio for hold up time when the input DC voltage drops to certain value, so the converter is only required to be designed for narrow range input and it operates with large duty cycle with easy soft switching in the primary side resulting in good efficiency. At the same time range winding topology needs small current rating components because only certain hold up time, such as 20 ms, is its operation. However, transient problems occur during range winding activation because of the nonlinearity of range winding topology performance and the limitation of the close-loop bandwidth.
Conventional secondary side post regulators (SSPR) control the pulse width to regulate the tight output voltage and the primary side switches operate at 0.5 duty cycle, resulting in very easy conditions for soft switching in the primary side. But post regulators introduce extra conduction loss in the secondary side. Also post regulators cannot reduce the voltage stress across the secondary side rectifiers in wide range input DC/DC converter because the converter is required to be designed in the lowest DC input voltage and operates in the highest DC input voltage, so the efficiency resulting from the use of a conventional post regulator is poor.
In medium power rating converters, a half bridge converter is attractive because of its simplicity and low transformer turn-ratio. In wide range input DC/DC converters, conventional half bridge does not achieve zero voltage switching (ZVS) in the primary side because of small duty cycle operation. Asymmetrical half bridge converter and duty cycle shifting (DCS) control can achieve ZVS under certain conditions, but it does not provide ZVS in full range loads. In wide range input conditions, the efficiency of the half bridge converter is low. The best efficiency of isolated converters such as half bridge, full bridge and push pull topologies, exist in the conditions of approximately 0.5 duty cycle in the primary side, there is still the problem of regulating the output voltage.
Generally, wide range input DC/DC converters are designed at the minimum input voltage Vin min and always operates at the maximum input voltage Vin max with a small duty cycle, which makes very difficult to achieve soft switching in the primary side switch while achieving higher voltage stresses in the secondary rectifier that have large conduction and switching losses, so that the resulting converter has low efficiency.
In
In
The schematic diagram of
In
A primary objective of the invention is to provide methods, systems, apparatus and devices for a high efficiency and high power density wide range input isolated dc-dc converter.
A secondary objective of the invention is to provide methods, systems, apparatus and devices to provide a parallel post regulator having a smaller conduction loss than conventional post regulators for use in wide range input isolated DC/DC converter resulting in high efficiency.
A third objective of the invention is to provide methods, systems, apparatus and devices for a wide input range front end DC/DC converter for use in distributed power systems and server power supplies which require a hold up time to provide output voltage within regulation after input AC line dropout at full load conditions.
A fourth objective of the invention is to provide methods, systems, apparatus and devices to provide a DC/DC converter that reduces voltage stresses across main rectifiers, has a smaller conduction losses compared with conventional post regulators and the requirement of input and output filters is significantly reduced due to the filtered waveforms produced.
A fifth objective of the invention is to provide methods, systems, apparatus and devices to provide a DC/DC converter that has small current stresses components of parallel post regulator resulting in high efficiency and high power density.
A first preferred embodiment of the invention provides a wide high efficiency range input DC/DC converter. The DC/DC converter includes a voltage source for providing a direct input voltage and an input rectifier circuit for converting the direct input voltage to a primary rectified voltage, wherein the primary side switches operate with a duty cycle to achieve zero voltage switching. The secondary side includes a main rectifier circuit connected across the secondary winding of a transformer provide a load current to a load and includes a parallel post regulator connected in parallel with the main rectifier for providing a supplemental load current when the main rectifier is in an off state to regulate the output power. The DC/DC converter provides a high efficiency and high power density wide input range front end DC/DC converter for use in distributed power systems and server power supplies.
A second embodiment provides a method for DC/DC conversion comprising the steps of converting a direct input voltage to a primary rectified voltage, switching a secondary main rectifier to an on state to provide an output current to a load, switching the secondary main regulator to an off state and switching a parallel post regulator to an on state when the secondary main regulator is switched to an off state during to provide a supplemental load current to the load to provide a high efficiency and high power density wide range input isolated DC/DC converter.
Further objects and advantages of this invention will be apparent from the following detailed description of preferred embodiments which are illustrated schematically in the accompanying drawings.
a is a schematic diagram of an example of a prior art secondary side post regulators.
b is a schematic diagram of a second example of a prior art secondary side post regulators.
c is a schematic diagram of a third example of a prior art secondary side post regulators.
d is a schematic diagram of range winding topology.
a is a schematic diagram of an operation of the parallel post regulator between time t0 and approximately t1 as shown in
b is a schematic diagram of another operation of the parallel post regulator between time t1 and approximately t2 as shown in
c is a schematic diagram of operation of the parallel post between time t2 and approximately t3 as shown in
a shows a control method for the parallel post regulator with a first switching frequency.
b shows another control method for the parallel post regulator with a second switching frequency.
Before explaining the disclosed embodiments of the present invention in detail it is to be understood that the invention is not limited in its application to the details of the particular arrangements shown since the invention is capable of other embodiments. Also, the terminology used herein is for the purpose of description and not of limitation.
The following is a list of the reference numbers used in the drawings and the detailed specification to identify components:
The apparatus, methods, systems and devices of the present invention provide a topology which delivers most of the needed power to a load with approximately 0.5 duty cycle in primary side with part of power delivered by a novel parallel post regulator to regulate the output voltage using secondary side control. The novel parallel post regulator has a smaller conduction loss than conventional post regulators to achieve high efficiency. The apparatus, methods, systems and device of the present invention provide a high efficiency and high power density wide range input isolated dc-dc converter. Wide input range front end DC/DC converters are widely used in the distributed power systems (DPS) and server power supplies which require a hold up time to provide output voltage within regulation after input AC line dropout at full load conditions.
The rectified voltage Vo1 in the parallel post regulator 30 doubles the output voltage of main rectifier 20 because of the two secondary windings 32 and 34 in the parallel post regulator 30. The current through rectifiers D3 and D4 is the average current of parallel post regulator 30, which is the product of the duty cycle of parallel post regulator 30 and the output current. At the same time, parallel post regulator 30 utilizes main rectifiers D1 and D2 of half bridge converter 20 as its freewheeling diodes. The switching frequency of the parallel post regulator 30 is independent of the switching frequency of the primary half bridge converter 10. The key waveforms corresponding to the parallel post regulator 30 are shown in
As shown by the waveforms in
Referring to the transformer primary current waveform 400 in
At time interval t1, parallel post regulator 30 turns off and the secondary inductor current transfers from switch Q3 to rectifier D1, after that, rectifier D1 conducts all the load current during time between t1 and approximately t2 as shown in
At the time t2, switch Q1 turns off as shown by waveform 101 and the energy stored in the transformer primary leakage inductor starts to charge the parasitic capacitors of switches Q1 and Q2 until the body diode DQ2 of Q2 begins conducting as shown by waveform 102, thus switch Q2 achieves zero-voltage-switching during the dead time td 103 shown in drive signal waveform 100. At the same time, both diodes D1 and D2 in the secondary side main rectifier 20 conduct together to free-wheel inductor current during which time the voltage 601 across switch Q3 is approximately the one secondary windings voltage Vs as shown in
From the volt-second balance in filter inductor Lf, the DC voltage conversion ratio in continuous conduction mode is obtained from
Vo=(Vin/2n)(1+D)
According to the above equation, the parallel post regulator can be designed for the highest DC input voltage with small duty cycle D to regulate the tight voltage so that the unregulated output voltage can be very close to output voltage by large turn ratio transformer and the rest of the voltage is compensated by the parallel post regulator. Large turn ratio transformer reduces the current rating in the primary side resulting in reduced conduction loss and reduces the voltage stresses on the main rectifier resulting in low conduction loss in secondary side. When input DC voltage drops, the duty cycle D of parallel post regulator increases to regulate output voltage.
a and 10b show two different control methods with different switching frequency and trailing edge modulation in the parallel post regulator. The waveforms in
The parallel post regulator utilizes the main rectifiers D1 and D2 as its freewheeling diodes so that it simplifies the circuit and improves efficiency. Also, in the main rectifiers a smaller current through rectifiers D3 and D4 cause smaller conduction loss in primary and secondary side, so that the parallel post regulator efficiency η2 is higher than prior art post regulators. η1 is the efficiency of unregulated output voltage in the half bridge converter operating in 0.5 duty cycle with main rectifiers. The total efficiency of half bridge and the parallel post regulator is obtained according to
η=(η1η2)/((1−D)η2+Dη1.
While the invention has been described, disclosed, illustrated and shown in various terms of certain embodiments or modifications which it has presumed in practice, the scope of the invention is not intended to be, nor should it be deemed to be, limited thereby and such other modifications or embodiments as may be suggested by the teachings herein are particularly reserved especially as they fall within the breadth and scope of the claims here appended.
Number | Name | Date | Kind |
---|---|---|---|
6130828 | Rozman | Oct 2000 | A |
6178098 | He et al. | Jan 2001 | B1 |
6449175 | Cuadra et al. | Sep 2002 | B1 |
6469914 | Hwang et al. | Oct 2002 | B1 |