The invention relates to refrigeration. More particularly, the invention relates to beverage coolers.
As a natural and environmentally benign refrigerant, CO2 (R-744) is attracting significant attention. In most air-conditioning operating ranges, CO2 systems operate in transcritical mode.
The major difference between transcritical and conventional operation is that heat rejection in the gas cooler is in the supercritical region because the critical temperature for CO2 is 87.8° F. Consequently, pressure is not solely dependent on temperature and this opens additional control and optimization issues for system operation.
For a fixed gas cooler discharge temperature, as the high side pressure is increased, the exit enthalpy of the refrigerant decreases, yielding a higher differential enthalpy through the gas cooler. The capacity of the gas cooler is a function of the mass flowrate of refrigerant and the enthalpy difference across the gas cooler. For a beverage cooler, the evaporator may be essentially at the cooler interior temperature. It is typically desired to maintain this temperature in a very narrow range regardless of external condition. For example, it may be desired to maintain the interior very close to 37° F. This temperature essentially fixes the steady state compressor suction pressure.
For a fixed compressor suction pressure, as the high side pressure increases, the amount of energy used by the compressor increases, and the volumetric efficiency of the compressor decreases. When the volumetric efficiency of the compressor decreases, the flowrate through the system decreases. The balance of these two counteracting effects is typically an increase in gas cooler capacity as the high side pressure is increased. However, above a certain pressure the amount of capacity increase becomes very small. Because the expansion device is usually isenthalpic, the evaporator capacity will also typically increase as the high side pressure increases.
The energy efficiency of a vapor compression system, the Coefficient of Performance (COP), is usually expressed as a ratio of the system capacity to the energy consumed. Because an increase in pressure typically produces both a higher capacity and a higher energy consumption, the balance between the two will dictate the overall COP. Therefore, there is typically an optimal pressure which yields the highest possible performance.
An electronic expansion valve is usually used as the device 26 to control the high side pressure to optimize the COP of the CO2 vapor compression system. An electronic expansion valve typically comprises a stepper motor attached to a needle valve to vary the effective valve opening or flow capacity to a large number of possible positions (typically over one hundred). This provides good control of the high side pressure over a large range of operating conditions. The opening of the valve is electronically controlled by a controller 50 to match the actual high side pressure to the desired set point. This pressure control strategy involves a fairly high cost valve, a sophisticated controller 50, and a sensor 52 for measuring the high side pressure. This equipment adds a significant amount of cost to the CO2 vapor compression system, causing the CO2 vapor compression system to be less attractive compared to an HFC system.
It is possible to use a fixed expansion device in a transcritical vapor compression system, but this approach has limitations which may cause a loss of performance or functionality. During steady state operation, a fixed expansion device (e.g., a fixed orifice or capillary tube) can work well to regulate the system high side pressure to a near optimum pressure. During pulldown, when the system is started and the evaporation temperature and pressure can be very high, the flowrate through a fixed speed and displacement compressor can become relatively high. This high flowrate can cause the high side pressure to exceed a safe limit.
An expensive expansion device may be eliminated in favor of a less expensive pressure regulator in a CO2 vapor compression system such as is used in a bottle cooler or small-capacity air conditioner, refrigerator, or other system. The potential for overpressurization may be reduced by using an inexpensive, multi-step fixed expansion device based on one or more solenoid valves.
The details of one or more embodiments of the invention are set forth in the accompanying drawings and the description below. Other features, objects, and advantages of the invention will be apparent from the description and drawings, and from the claims.
Like reference numbers and designations in the various drawings indicate like elements.
The current invention relates to high-side pressure optimization for a CO2 vapor compression system. For HVAC & R products which do not have broad operating envelopes, the optimal high side pressures for all operating conditions do not vary much. Therefore, a fixed expansion device (e.g., an orifice or capillary tube) can be used to regulate the high side pressure to a preset constant value for all steady state operating conditions of the CO2 vapor compression system. The preset value should be determined such that the CO2 vapor compression system can achieve the best overall Coefficient of Performance (COP) for the entire operating envelope. Using a fixed expansion device can significantly reduce the cost of the pressure control components in a CO2 vapor compression system.
For pulldown conditions, the compressor flowrate will be significantly higher than during steady state conditions. The high-side pressure should be optimized such that the pulldown cooling capacity of the CO2 vapor compression system can be maximized, but the flow through the pressure regulator does not exceed the flow through the compressor (so that the system pressure becomes too great). This optimal high-side pressure for maximizing capacity is usually higher than the optimal high-side pressure for maximizing the overall COP. However, because the compressor flowrate is much higher during pulldown conditions than during steady state conditions, the expansion device may be configured to have a larger flow capacity during pulldown conditions. A simple multi-position expansion device may provide this. There are a number of ways through which this can be achieved through the use of solenoid valves to enable a two or more position pressure control system.
The following examples reflect modifications of the basic system of
During steady state operating conditions, when the compressor flowrate is relatively low, the solenoid valve 70 is kept fully closed. During pulldown conditions, the compressor flowrate is relatively high. In order to avoid overpressurization during pulldown, the solenoid valve 70 is opened, allowing flow through the second fixed expansion device 72. The combination of both expansion devices 68 and 72 regulates the high-side pressure to avoid overpressurization while still delivering good system performance.
In operation, a pulldown condition may be detected by means of one or more temperature sensors 75 and pressure sensor 74 coupled to a controller 76 coupled to control the solenoid valve 70. The controller 76 may also be coupled to the compressor and/or fan(s) to control their respective operation. For ease of illustration, the sensor and controller are not illustrated in the following examples although they may be present.
A variety of sensor and/or user inputs may be used to control the solenoid valve(s). Direct measurement of the high-side pressure may be made by the sensor 74. When this pressure exceeds one or more associated thresholds, the controller 76 may cause the valve(s) to assume an associated relatively free-flow condition. Alternatively or in addition to high-side pressure measurement would be sensor 74, input may be received from an air temperature sensor. The exemplary sensor 75 may be positioned to be exposed to air in or from the cooler interior (e.g., to the flow 36 upstream of the evaporator 28). The sensor 75 may form part of a control thermostat. Accordingly, use of such a sensor alone may permit cost savings through the elimination of the pressure sensor 52 or 74.
For fixed speed and displacement compressor, the flow through the system is a direct function of the density of the refrigerant entering the compressor and, to a lesser extent, the pressure ratio of the compressor. The inlet density is a direct function of the saturation temperature and superheat of the refrigerant. These, in turn, are direct functions of the air temperature, system size, and charge. For a simple system, these parameters may be determined in the design stage as a function of air temperature flowing through the evaporator. A correlation can be produced which matches the evaporator air temperature to the refrigerant inlet density. In operation, the solenoid valve(s) would remain in the open position until the output of the evaporator temperature sensor 75 drops below a predetermined value. When this happens, the solenoid valve or one of the solenoid valves is closed. This can be repeated for systems having multiple solenoid valves further reducing the effective expansion orifice area as the temperature drops so as to maintain a mere optimal pressure in the high pressure portion of the system.
If a high-side pressure is directly measured (e.g., by the sensor 74) a different correlation may be used. The optimal high-side pressure may be known as a function of evaporator temperature and, optionally, the ambient temperature. The solenoid valve or valves may be actuated to maintain the pressure within certain limits.
The exemplary cassette 202 draws the air flow 34 through a front grille in the base 224 and discharges the air flow 34 from a rear of the base. The cassette may be extractable through the base front by removing or opening the grille. The exemplary cassette drives the air flow 36 on a recirculating flow path through the interior 206 via the rear duct 210 and top duct 218.
One or more embodiments of the present invention have been described. Nevertheless, it will be understood that various modifications may be made without departing from the spirit and scope of the invention. For example, when implemented as a remanufacturing of an existing system or reengineering of an existing system configuration, details of the existing configuration may influence details of the implementation. Accordingly, other embodiments are within the scope of the following claims.
Benefit is claimed of U.S. patent application Ser. No. 60/663,960, filed Mar. 18, 2005, and entitled “High Side Pressure Regulation for Transcritical Vapor Compression System”, the disclosure of which is incorporated by reference herein as if set forth at length.
Filing Document | Filing Date | Country | Kind | 371c Date |
---|---|---|---|---|
PCT/US05/47528 | 12/30/2005 | WO | 00 | 9/14/2007 |
Number | Date | Country | |
---|---|---|---|
60663960 | Mar 2005 | US |