Embodiments of the subject matter disclosed herein generally relate to a system and method for cooling or heating an input air stream, and more particularly, to a hybrid air-conditioning system that combines cooling coils and indirect evaporative technology for decoupled sensible and latent heat removal.
Energy consumption for air conditioning has been increasing exponentially due to population growth and increase of living standard. From 2000 to 2015, the energy consumption for air conditioning has increased from 3.6 EJ to 7 EJ, representing about 15% of peak electricity demand worldwide. In the Gulf Cooperation Council (GCC) countries, the cooling demand is more than 36 million Rton, and it consumes 50-70% of the peak electricity generation. Consequently, a significant portion of natural energy resources (oil and gas) produced in these countries are consumed for cooling. To tackle the challenges of global energy shortage, it is critical to reduce energy consumption of air conditioning systems
The demand for cooling is usually addressed by mechanical-vapor-compression (MVC) chillers. The energy consumption of these chillers has been measured to be around 0.85+0.03 kW/Rton. In the GCC countries, the energy consumption for chillers is over 3 times as compared to that of other regions. This is attributed to the severe weather conditions, i.e., hot and humid conditions. To remove the moisture from the air to be cooled, the evaporator's temperature (5-12° C.) has to be lower than the dew point temperature of the supplied air. Meanwhile, the condenser temperature is very high (larger than 45° C.) due to the high heat rejection temperature. As a result of the high thermal lift between the evaporator and the condenser, the energy consumption of the MVC chillers is significant for humid and hot environments.
To improve the energy efficiency of the cooling units, decoupling of sensible and latent loads has been proposed, where the latent load is associated with the humidity removal and the sensible load is associated with the heating of the dry air. Traditionally, the moisture is first removed from the incoming air stream using a dehumidifier (latent load), after which the hot and dry air is cooled (sensible load) to the desired temperature. The sensible cooling of the dry air is usually achieved using an indirect evaporative cooler (IEC), which uses the evaporative potential of the dry air as the driving force for cooling and consumes little energy. A well-designed IEC can achieve a COP (coefficient-of-performance) of more than 20 when the air is dry. Therefore, the overall COP of the air conditioning system is dependent on the performance of the dehumidifier.
Existing dehumidification technologies include liquid and solid desiccant systems. Most of these systems have a COP of less than 1 due to a lack of heat recovery. Recently, it was proposed a desiccant coated heat pump, which adds desiccant coating on the heat exchangers of conventional chillers. This system achieved a COP larger than 6. However, operation of the system is complex. It requires cyclic switching between dehumidification and regeneration modes for components, which needs many valves and air dampers, which are prone to failing.
As the IEC performance degrades when the incoming air has a high humidity, several groups have proposed to combine the IEC with MVC. For example, [1] evaluated the energy-saving potential of the hybrid IEC-MVC system under the climatic condition of Beijing, China. Compared with a standalone MVC, the hybrid system demonstrated a seasonal energy saving of 38.2%. [2] studied the performance of the hybrid IEC-MVC system in four cities of Iran. According to this study, the IEC could reduce the cooling load and electricity consumption by 75% and 55%, respectively. [3] experimentally evaluated the energy-saving potential of the hybrid IEC-MVC system for an office building in North Italy. The total electricity consumption according to this study was 38% lower. [4, 5] presented an experimental and analytical study of a hybrid IEC-MVC system under the climatic conditions of Singapore. According to these studies, the IEC can reduce the cooling load of MVC by 32%. The authors in [6, 7] conducted a numerical study on IEC that works as a pre-cooler for an MVC system. Their results revealed that the channel gap and the cooler height had the most influence on the cooling performance.
However, all these studies indicate that the hybrid process is still at an undeveloped stage with several technical gaps. Firstly, most of the existing studies are based on the climatic data of a specific area, and there is no systematic evaluation of the system's performance that covers different weather conditions. Secondly, as the IEC operates with room exhaust air in the wet channels, there is simultaneous cooling and dehumidification in the dry channels, making the system behavior different from that in a regular IEC. Further, most of the existing studies on such a process are based on numerical simulation, and there is a lack of actual experimental investigation and actual devices being built.
Thus, there is a need for an improved system that is configured for decoupled sensible and latent heat removal that is efficient and capable of cooling the incoming air stream under extreme temperature conditions.
According to an embodiment, there is a hybrid air conditioning system for cooling a chamber and the system includes a mechanical vapor compression, MVC, unit configured to cool, through evaporation and condensation of a medium, a first air stream (MA1, MA, MA2), and an indirect evaporative cooling, IEC, unit configured to cool a second air stream (CA, MA2, OA), which is related to the first air stream (MA1, MA, MA2), through direct heat exchange between wet channels that are placed adjacent to dry channels. The MVC unit is fluidly connected to the IEC unit so that a generated supply air stream SA is cooled by decoupling sensible and latent heat removal.
According to another embodiment, there is a hybrid air conditioning system for cooling a chamber, and the hybrid system includes an indirect evaporative cooling, IEC, unit configured to cool a first air stream (CA, MA2, OA), through direct heat exchange between wet channels that are placed adjacent to dry channels, and a mechanical vapor compression, MVC, unit configured to cool, through evaporation and condensation of a medium, a second air stream (MA1, MA, MA2), which is related to the first air stream (CA, MA2, OA). The IEC unit is fluidly connected to the MVC unit so that a generated supply air stream SA is cooled by decoupling sensible and latent heat removal.
According to yet another embodiment, there is a method for cooling air with a hybrid air conditioning system, and the method includes cooling a first air stream (MA1, MA, MA2), with a mechanical vapor compression, MVC, unit, through evaporation and condensation of a medium, to generate a second air stream (CA, MA2, OA), and cooling the second air stream (CA, MA2, OA) with an indirect evaporative cooling, IEC, unit through direct heat exchange between wet channels that are placed adjacent to dry channels. The MVC unit is fluidly connected to the IEC unit so that a generated supply air stream SA is cooled by decoupling sensible and latent heat removal.
For a more complete understanding of the present invention, reference is now made to the following descriptions taken in conjunction with the accompanying drawings, in which:
The following description of the embodiments refers to the accompanying drawings. The same reference numbers in different drawings identify the same or similar elements. The following detailed description does not limit the invention. Instead, the scope of the invention is defined by the appended claims. The following embodiments are discussed, for simplicity, with regard to a hybrid air conditioning system that includes a mechanical chiller and an IEC system. However, the embodiments to be discussed next are not limited to cooling the air, but may also be applied to heating the air.
Reference throughout the specification to “one embodiment” or “an embodiment” means that a particular feature, structure or characteristic described in connection with an embodiment is included in at least one embodiment of the subject matter disclosed. Thus, the appearance of the phrases “in one embodiment” or “in an embodiment” in various places throughout the specification is not necessarily referring to the same embodiment. Further, the particular features, structures or characteristics may be combined in any suitable manner in one or more embodiments.
According to an embodiment, a novel hybrid air conditioning system includes a mechanical chiller and an indirective evaporative cooler system. The mechanical chiller may include an evaporator, an expansion valve, a compressor and one or two condensers. One of the condensers may be placed in series with the evaporator, and it is cooled by the off-coil air of the evaporator to lower the saturation pressure of condenser. A portion of the off-coil air leaving the evaporator is extracted as a purged air stream of the IEC system and the outlet of purged air is directed to the de-superheat condenser for heat rejection. In this de-coupled manner, the sensible load of the dry channels is removed from the IEC (at more than twice COP of the MVC), and the MVC removes the latent load at a much-improved COP. The mixed air (condenser outlet and returned air) is supplied to the IEC system for the sensible heat removal to achieve the desired supply air temperature but at a lower absolute humidity, to achieve human comfort in the room space. The details of this embodiment and other embodiments are now discussed with regard to the figures.
The MVC system 110 includes an evaporator 112 that is fluidly connected to a compressor 114, which is fluidly connected to a first condenser 116. The piping that achieves these fluid connections is configured to handle the refrigerant or medium of the MVC system, not the various air streams discussed later. The first condenser 116 is further fluidly connected to a second condenser 118, which in turn is fluidly connected to a valve 120. The valve 120 is fluidly connected to the evaporator 112, which completes the fluid path of the MVC system 110. Note that the path described above is a closed fluid path through which an appropriate medium 122 (e.g., the refrigerant) flows. No air stream enters into this path. The compressor 114 forces the medium 122 to continuously move through the evaporator and the two condensers.
When the medium 122 enters the evaporator 112, the medium 122 experiences a latent heat exchange as it transforms from liquid to vapor, due to the heat provided by the outside air stream OA that enters the evaporator. As a consequence, condensed water 112C is formed inside the chamber 112A from the entering air stream OA, which has a high humidity. The condensed water forms on the outside of the coil 113 and accumulates at the bottom of the chamber 112A. In one application, no fabric material is used inside or outside the coils to prevent or limit biofouling. Thus, the condensed water 112C in the chamber 112A may be used either as water supply to the IEC system 160 (to be discussed later) or for other purposes. Due to this process, the incoming air stream OA loses moisture, i.e., experiences dehumification. This process absorbs energy (the latent heat) from a mixture air stream MA1, which is obtained by mixing the incoming air stream OA (hot outdoor air) with a first partial return air RA1 from the chamber 170. Note that the partial return air RA1 is just a fraction of the total return air RA from the chamber 170. This means that an initial temperature T1 of the incoming air stream OA is decreasing to a temperature T1 of the mixture MA1 due to the mixing with the cool air RA1, which has a final temperature Tf, i.e., Tf<T1<Ti. After the air mixture stream MA1 passes through the chamber 112A of the evaporator 112, and contacts the outside wall of a coil 113 present inside the chamber 112A, which holds the medium 122, heat is transferred from the mixture MA1 to the medium 122, which results in an air stream (EA) leaving the evaporator that has a temperature T3 lower than the temperature T1, i.e., T3<T1. In one application, the temperature T3 is at or below the dew point temperature to remove the moisture from the air. Thus, the evaporator 112 cools the outside air OA, before being supplied to the IEC system 160 and before being supplied to the chamber 170, while evaporating the medium 122 of the MVC system 110.
Next, the air stream EA leaving the evaporator is split into two streams at a pipe junction 126, a purge air stream PA0 and a first mixture air stream MA2. The air stream PA0 is directly supplied to the wet channels 162 of the IEC system 160 as purge air, while the remaining part of the air stream EA is mixed with the remaining fraction RA2 of the return air RA, to generate the second air stream mixture MA2, which is supplied to the second condenser 118. Note that a temperature T4 of the second air stream mixture MA2 is lower than the temperature T3 of the EA stream as the temperature Tf of the RA stream is low (the coldest temperature of the system is achieved inside the chamber 170 if the system runs long enough and this temperature is the same with the supply air stream SA's temperature, which is supplied by the IEC system 160).
In one application, the percentages of the air volume that are mixed for obtaining the air streams OA, MA2, PA0, RA1, and RA2 are illustrated in
The air stream MA2 thermally interacts with the medium 122 that flows through the coil 119, inside a housing 118A of the second condenser 118. The second condenser 118 condenses the vapor medium into liquid medium 122, which results in heat release into the air stream MA2. This means that the air stream CA exiting the second condenser 118 has a temperature T5 higher than the temperature T4 of the incoming air stream MA2. This air stream CA enters next the dry channel 164 of the IEC system 160 and loses heat to the wet channel 162, which makes the final air stream SA to arrive at the desired temperature Tf. This air stream SA is then supplied at an input 172 of the chamber 170 as the cooling air.
The return air streams RA1 and RA2, previously discussed, are extracted from the room 170, at an output 174. Thus, the room 170, whose air temperature is desired to be controlled, not only receives the air stream SA, at the input 172, which cools the room, but also supplies from output 174 part of the ambient air to be mixed with the hot outdoor air stream OA to be cooled again.
The purge air stream PA0 receives the heat from the air stream CA, inside the IEC system 162 and then is supplied as heated air stream PA1 to the first condenser 116. The air stream PA1 thermally interacts with the vapor medium 122, which flows through a coil 117 located inside the chamber 116A of the second condenser 116. The air stream PA1 takes the heat from the vapor that condenses inside the first condenser 116 and is discharged outside as heated air stream PA2.
Within the MVC system 110, the medium 122 flows through the closed piping circuit 124 as a vapor (1) from the evaporator 112 to the compressor 114, then still as a vapor (2) from the compressor 114 to the first condenser 116, then to the second condenser 118 as a mixture (3) of liquid and vapor, then to the valve 120 as liquid (4), and then to the evaporator 112 as liquid (5), where it is transformed from liquid to vapor (1). The valve 120 may be a throttling valve that controls the amount of liquid passing from the second condenser to the evaporator. A controller 140, for example, a processor or a smart device, may be used to control the compressor 114 and the valve 120. Various temperature and/or humidity sensors S may be distributed at one or more of the elements discussed above to monitor their temperature and/or humidity. Based on these measurements, the controller 140 may slow down or increase the speed of the compressor 114 and/or may close or open the valve 120 and/or may increase or decrease the air flowrates through the various ducts (for example, using one or more fans 180) and/or may increase or reduce an amount of water that is applied to the wet channels (for example, with a pump 182). In one application, as illustrated in the Table 1 in
The novel hybrid system 100 is able to provide a lower supply air temperature (20° C.) due to the use of cold and dry air in the wet channels of the IEC system 160. In contrast, traditional IEC systems usually supply air at a temperature higher than 22° C. Further, the hybrid system 100 has a much higher energy efficiency than the existing systems. This is because the MVC system 110 is mainly used to remove the latent load, while the sensible load is mainly handled by the IEC system 160. In the MVC system 110, the cooling medium is the cold air stream EA leaving the evaporator 112 and the air stream PA1 leaving the wet channels 162, which lowers the condensation pressure and reduces the compressor power. Meanwhile, the sensible load is handled by the IEC system, which has a high COP. The hybrid system 100 may also have a high compactness form factor. The evaporator 112 and the condensers 116 and 118 may be integrated in line with the air ducting system 130, while the compressor 114 and the expansion valve 120 can be installed in the spare space of the IEC system 160. The operation of the hybrid system 100 does not require any switch of air or refrigerant flow.
The ducting system 130 includes plural ducts which are fluidly connected to each other for handling the various air streams as now discussed. A first duct 130-1 communicates with the ambient and provides the outside air stream OA. The first duct is fluidly connected to a second duct 130-2, which is fluidly connected to the chamber 170, and provides the air from this chamber. The first duct 130-1, after being merged with the second duct 130-2, is fluidly connected at an input 1121 of the evaporator 112. A third duct 130-3 is fluidly connected to an output 1120 of the evaporator 112 and extends up to an input 1181 of the second condenser 118. The third duct 130-3 is fluidly connected to a fourth duct 130-4 and to a fifth duct 130-5, in this order. The fourth duct 130-4 is connected with the other end to the wet input 1621 of the IEC system 160. The fifth duct 130-5 is connected with the other end to the second duct 130-2. The output 1180 of the second condenser 118 is fluidly connected to one end of a sixth duct 130-6, while the other end of the sixth duct is connected to the dry input 1641 of the IEC system 160. The dry output 1640 of the IEC system is fluidly connected to a seventh duct 130-7, which is also connected to the input 172 of the chamber 170. An eight duct 130-8 fluidly connects the wet output 1620 of the IEC system 160 to an input 1161 of the first condenser 116. A final ninth duct 130-9 fluidly connects the output 1160 of the first condenser 116 to the ambient. It is noted that the inputs and outputs of the evaporator and condensers are fluidly connected to a corresponding chamber, and they do not fluidly communicate with the medium 122 that flows through the corresponding coils 113, 117, and 119.
Table 2 in
The configuration shown in
In yet another variation of the embodiment of
The return air stream RA1 is provided to the wet channels 162 of the IEC system 160, where water collected from the evaporator 112 and also from an external water source (provided through pipe 140) is sprayed on the channels to obtain the evaporative cooling effect. The wet air stream WA leaving the IEC system 160 is mixed with an additional outdoor air stream OA2 to obtain the mixed air stream MA2, which is then circulated through the condenser 116 for heat rejection, i.e., to condense the liquid medium 122 circulating through the condenser 116. The resulting air flow PA is then discharged into the ambient, outside the chamber 170. The flow of the medium 122 through the MVC system 110 is similar to that discussed above with regard to
The ducting system for the system of
The hybrid system 700 shown in
A variation of the embodiment illustrated in
According to this embodiment, the room exhaust air (A4), which is cold and dry, flows through the wet channels 162 to cool down the outdoor air stream (A1) in the dry channels 164. The wet channels 162 are supplied with water, which evaporates and absorbs heat from the air to further cool down the outdoor air (A4). When the temperature in the dry channels 164 is lower than the dew-point temperature of the outdoor air (A1), condensation occurs, and the humidity ratio of the outdoor air drops. The pre-cooled and dehumidified outdoor air (A2) is then passed through the evaporator coils 113 of the mechanical chiller 110 to further bring down its temperature and humidity to the desired values and it is supplied as supply air (A3) to the room 170. Meanwhile, the exhaust air (A5) leaving the wet channels 162 is mixed with outdoor air (A1′) and channeled as mixed air (A6) to the condenser 116 for heat rejection, after each, the resulting air (A7) is purged to the ambient.
In one implementation, the inventors designed and manufactured a 1-Rton IEC unit to experimentally test the efficiency of the new system 1100. The unit has a cross-flow configuration with a dimension of 1 m×1 m×0.7 m. 200 mm× 300 mm chamfers are cut at the four corners to form the entrances and exits of dry and wet channels. The air flow channels are connected to acrylic ducts. At the inlet of the wet channels 162, two rows of spray nozzles are installed to supply fine water droplets to form the water films 168. The heat and mass exchanger in the IEC system 110 includes in this implementation 50 dry channels and 50 wet channels arranged in an alternating manner. The channel walls are made of aluminum plates with a thickness of 300 μm. These plates are separated with spacers (5 mm thickness) to form the flow channels.
Employing this experimental setup, the energy recovery performance of the IEC was evaluated. Hot and humid air, provided by an environmental chamber (a chamber that can control the temperature and humidity of a supplied air), is supplied to the dry channels to simulate the outdoor air. Its temperature is ranged between 30 and 42° C., and the humidity ratio is 10-20 g/kg. The wet channel is supplied with room air, which has a temperature of 23±1° C. and a humidity ratio of 11±1 g/kg. The air flowrate in the dry channels is varied between 280 and 420 CMH by controlling the fan speed, while that in the wet channels is fixed at 230 CMH.
As there are simultaneous heat and mass transfer in the dry channels, the enthalpy exchange effectiveness and COP allow better measurement of the IEC system's performance, as they account for both temperature and humidity change. In this regard,
A higher air flowrate also promotes heat and mass transfer coefficients and leads to higher IEC effectiveness, as shown in
Based on the experimental results on the IEC system discussed above, the inventors compared the COP of the hybrid IEC-MVC process with that of a standalone MVC. The effectiveness of energy recovery from the IEC system is firstly calculated. Then, the energy consumption to further cool down the outdoor air to the supply condition is calculated. For comparison purposes, the energy consumption of a standalone air-cooled MVC chiller, which directly cools down the outdoor air to the supply condition is also calculated. For both systems, the isentropic efficiency (ncomp) is assumed to be fixed at 0.65 under all the operating conditions.
With different percentages of cooling load undertaken by the IEC system, the overall system COP is also different. When the outdoor air is dry, the overall energy efficiency is dominated by the COP of the IEC system. Therefore, the higher the outdoor temperature, the higher the overall COP, as illustrated in
When the outdoor humidity ratio is higher then 15 g/kg, more cooling load has to be handled by the MVC system. In this case, the overall COP changes marginally with the temperature, which is a result of the completing effects between the IEC and MVC systems. The improvement over standalone MVC system reduces to 24-79%, which is still significant. The overall COP starts to drop with outdoor temperature when the outdoor humidity ratio is higher at 20 g/kg, while the values are still 19-59% higher than that of standalone MVC system.
A method for operating one of the hybrid systems discussed above is illustrated in
In one application, the hybrid air conditioning system includes a MVC unit configured to cool the first air stream (MA1, MA, MA2) and the IEC unit is configured to cool the second air stream (CA, MA2, OA), which is related to the first air stream (MA1, MA, MA2). As illustrated in
In another application, as illustrated in
The method may also be implemented with the hybrid air conditioning system 700 or 1100 for cooling the chamber. For this configuration, the method uses first the IEC unit to cool a first air stream (CA, MA2, OA), through direct heat exchange between the wet channels 162 that are placed adjacent to dry channels 164, and then uses the MVC unit 110 to cool, through evaporation and condensation of the medium 122, a second air stream (MA1, MA, MA2), which is related to the first air stream (CA, MA2, OA).
The first air stream enters the dry channels of the IEC unit to be pre-cooled and a first return air stream RA1, from the chamber, is supplied to the wet channels of the IEC unit. In one application, as shown in
In another application, as illustrated in
In yet another application, as illustrated in
The disclosed embodiments provide a hybrid air conditioning system that uses an indirect evaporative cooler system and a mechanical vapor compression system, in this or a reversed order, for cooling and/or heating the air in a chamber. It should be understood that this description is not intended to limit the invention. On the contrary, the embodiments are intended to cover alternatives, modifications, and equivalents, which are included in the spirit and scope of the invention as defined by the appended claims. Further, in the detailed description of the embodiments, numerous specific details are set forth in order to provide a comprehensive understanding of the claimed invention. However, one skilled in the art would understand that various embodiments may be practiced without such specific details.
Although the features and elements of the present embodiments are described in the embodiments in particular combinations, each feature or element can be used alone without the other features and elements of the embodiments or in various combinations with or without other features and elements disclosed herein.
This written description uses examples of the subject matter disclosed to enable any person skilled in the art to practice the same, including making and using any devices or systems and performing any incorporated methods. The patentable scope of the subject matter is defined by the claims, and may include other examples that occur to those skilled in the art. Such other examples are intended to be within the scope of the claims.
The entire content of all the publications listed herein is incorporated by reference in this patent application.
This application claims priority to U.S. Provisional Patent Application No. 63/192,667, filed on May 25, 2021, entitled “HYBRID AIR-CONDITIONING SYSTEM COMBINING COOLING COILS AND INDIRECT EVAPORATIVE COOLER FOR DECOUPLED SENSIBLE AND LATENT HEAT REMOVAL,” the disclosure of which is incorporated herein by reference in its entirety.
Filing Document | Filing Date | Country | Kind |
---|---|---|---|
PCT/IB2022/054621 | 5/18/2022 | WO |
Number | Date | Country | |
---|---|---|---|
63192667 | May 2021 | US |