This invention relates to cascade control systems having nested control loops for controlling a plant, such as, for example, a thermal reactor for processing of semiconductor substrates.
In semiconductor processing, the wafer size continues to increase and the integrated circuit feature size continues to decrease. Further increases wafer size and further decreases in feature size require improvements in thermal process control. The temperature at which wafers are processed has a first-order influence on the diffusion, deposition, and other thermal processes. Batch furnaces continue to play a significant role for thermal processing because of their large batch size and correspondingly low cost per processed wafer. A target in batch thermal processing is to achieve improved temperature control while maintaining high equipment utilization and large wafer batch sizes. The requirements of high-quality temperature control include a high ramp rate with good temperature uniformity during the ramp, fast temperature stabilization with little or no temperature overshoot, smaller steady-state temperature error band, shorter downtime for controller parameter tuning, etc. The traditional single-loop Proportional-Integral-Derivative (PID) controllers cannot achieve the required temperature control performance. PID controllers with cascade or nested control loops have been used in attempts to provide improved temperature control. However, these and other previous approaches have practical drawbacks related to complexity and computational requirements.
The present invention solves these and other problems by providing a computationally-efficient hybrid cascade MBPC control system that can be implemented on a typical control microprocessor. In one embodiment, the hybrid cascade MBPC control system is a cascade-type system with nested control loops having an MBPC controller in an outer control loop and a conventional controller in an inner control loop. In one embodiment, the conventional controller is a PID controller. In one embodiment, the conventional controller is an H∞ controller. In one embodiment, the hybrid control system uses a simplified MBPC control loop and a modified PID loop with a robust auto-tuner. The MBPC controller acts as a main or outer control loop, and the PID loop is used as a slave or inner control loop.
In one embodiment, the hybrid cascade MBPC can be used to control a thermal process reactor where the MBPC controller generates the desired spike TC control setpoint according to both planned paddle control setpoint trajectory and the dynamic model related to paddle and spike TC. In the thermal process reactor, the PID loop is used to control the power actuator of the heater to reach the required spike control setpoint by acting as a local system to quickly follow changes in the spike control setpoints.
The PID tuning parameters are relatively weakly coupled with the MBPC loop. The sampling time ts1 in the PID control loop is preferably shorter than the sampling time ts2 in the MBPC control loop. In one embodiment, ts1 is on the order of approximately 1 second and ts2 is on the order of approximately 4 seconds. In one embodiment, based on both dynamic and static models, tuning of the PID parameters is realized automatically. Compared with a single loop MBPC, the model order and the predictive time horizon in this control scheme can dramatically be reduced while the model still adequately describes and predicts the behavior of the actual system. In one embodiment, model derivations are done prior to wafer processing.
In one embodiment, the expected temperature control range [Tmin, Tmax] is divided into R temperature sub-ranges ([Tmin1, Tmax1], [Tmin2, Tmax2] . . . [Tmin R, Tmax R], where Tmin=Tmin1, Tmax=Tmax R and Tmax r−1=Tmin r). This allows the use of linear dynamic models for an adequate description of the dynamic behavior within each temperature zone. Corresponding to each sub-temperature range and heating zone, two kinds of dynamic linear models are built as:
Pdnr(t)=fnr(Spnr(t)) (1)
Spnr(t)=gnr(Pwnr(t),Pdnr(t)) (2)
where n is the heating zone number, r is the temperature sub-range, Pd is the temperature measured by the paddle TC, Sp is the temperature measured by the spike TC, Pw is the system power output, and fn,r and gn,r are linear functions.
In one embodiment, the dynamic model of Equation (1) is used for both MBPC control and soft-sensor computing, and the dynamic model of Equation (2) is used for soft-sensor computing and PID parameter auto-tuning of the inner control loop.
Corresponding to the expected temperature control range, the static polynomial models are built as:
Spn=hn(Pdn) (3)
where, hn are the static polynomial models. In one embodiment, the static models are used in limiters of the MBPC controller and for inner PID parameter auto-tuning.
In one embodiment, the MBPC control algorithm embeds intuitive tuning parameters (e.g., ku, ks) into the control law, the trajectory planner and the limiters. The intuitive tuning parameters can be used to improve both the dynamic control performance and the static control performances. The simplified MBPC control structure and fixed-time predictive horizon avoids the need of online matrix inversion during wafer processing. As a consequence, the online computing overhead is greatly reduced. In this way, the hybrid cascade MBPC control system algorithm can be implemented on microprocessors typically used in practice in the semiconductor processing industry.
In one embodiment, a generic trajectory planer is added to the MBPC control loop to generate the temperature control setpoint reference trajectory. Based on the desired ramp rate and temperature range, the trajectory planner divides the temperature range into two sub-ranges: fast ramp; and reduced ramp. In the fast ramp sub-range, the planner generates the temperature control setpoints reference trajectories to enable the MBPC to achieve the desired ramp rate. In the reduced ramp sub-range, the planner provides at least one intuitive tuning parameter to control the temperature ramp speed to reach the desired control setpoint. Temperature stabilization time and overshoot are also controlled. This provides a flexible way to meet the varying temperature control requirements from the different processes.
When a temperature ramp range covers more than one temperature sub-range, the MBPC switches its internal dynamic models so that the dynamic model, operative at a certain moment, corresponds with the actual temperature sub-range at that moment. In one embodiment, fuzzy logic switches and inference are added to the MBPC control loop to realize a smooth transition of the dynamic models when going from one temperature sub-range to an adjacent temperature range. In this case, fuzzy inference is effective to bring about a gradual change of one dynamic model to the other without inducing extra disturbance into the control system.
In one embodiment, static limiters based on static models are embedded in the MBPC loop. The limiters help the MBPC to generate the correct control setpoint for the inner-control loop under various control cases (normal, faster/slower ramp, boat in/out, different load or gas flow and so on).
In one embodiment, the PID controller in the inner control loop is provided with a parameter auto-tuner and/or anti-wind-up capability to enhance the robustness of the PID controller, and simplifies its usage. The inner PID follows the spike control setpoint changes that are generated by the MBPC control loop.
In one embodiment, a software detector and control logic are included to detect TC measurement hardware failure. When a TC sampling failure appears, the detector and control logic switch on a related soft temperature sensor that is based on dynamic model computing. Then the soft-sensor is used to replace the real TC in its place as a control system input. This prevents the reactor operation from shutting down, and reduces the loss of the whole batch process due to the detection of one or more temperature measurement hardware failures.
A typical vertical thermal reactor 100 is shown in
Historically, the temperature in thermal reactors was controlled by a spike TC control loop, using a PID control algorithm. By profiling the furnace in a static mode, using a paddle TC, the relation between paddle TC and spike TC under static conditions was established and stored in a profile table. Such a profiling procedure was performed at regular intervals or after maintenance. Because the paddle TC gives a more relevant reading for the actual wafer temperature, there has been a desire to use a paddle TC control loop that would make the time-consuming profiling procedure unnecessary. A control configuration 200 employing such a paddle TC control loop is shown in
A so-called cascade controller 300, as shown in
A typical thermal process starts at a standby temperature at which the wafers are loaded into the thermal reactor. After loading, the thermal reactor heats up to the desired process temperature for oxidation, annealing, drive, or CVD. After performing the process, the thermal reactor cools to the stand-by temperature again and unloads the wafers. If the standby temperature, ramp up/down rate, and process temperatures are set in reasonable ranges, acceptable temperature control performance can be achieved during the process by using the cascade PID controller 300. However, optimizing the performance of the cascade PID controller 300 often requires significant off-line time for tuning of the controller parameters such as the PID parameters. Tuning of a cascade controller is often more of an art than a science and usually very time consuming. The best choice of tuning parameters depends on a variety of factors including the dynamic behavior of the controlled process, the controller's objectives, and the operator's understanding of the tuning procedures. For a cascade PID controller, the inner and outer loop tuning is strongly coupled, which adds to the tuning complexity. Besides the tuning of PID parameters, for dealing with long time delay, the outer or “profile” PID control loop of a cascade PID controller still needs a “profiling table” to provide constraints. Generating the profiling table involves a procedure that requires many hours of off-line equipment time. Off-line time cannot be used for useful wafer processing and is thus very expensive.
With the advances in modern control technology and system identification, more advanced control systems, such as, for example Model-Based Predictive Controllers (MBPC), have been developed, but these more advanced control methods are often computationally complex, typically requiring matrix inversion during online processing.
In one embodiment, the sensor output 505 corresponds to sensors that tend to respond relatively more quickly but relatively less accurately to certain desired parameters than the sensors corresponding to the sensor output 506. In one embodiment, the sensor output 506 corresponds to sensors that tend to respond relatively less quickly but relatively more accurately to certain desired parameters than the sensors corresponding to the sensor output 505. Thus, in one embodiment, the inner loop controller 502, using the sensor output 505 is able to respond relatively quickly to certain changes in the plant 509 but relatively less accurately. The outer loop controller 501, using the sensor output 506 is able to respond relatively less quickly to certain changes in the plant 509 but relatively more accurately to certain desired parameters. In one embodiment, the outer loop controller 501 is configured to produce a setpoint for the inner loop controller 502 to improve the controlled properties of the plant. In one embodiment the inner loop controller 502 includes a conventional controller, such as a PID controller. In one embodiment, the outer loop controller includes a predictive-type controller. In one embodiment, the outer loop controller includes a MBPC controller.
As the name implies, the MBPC 520 is based on a model of the controlled plant. In a thermal process reactor, the MBPC 520 typically relies on several models corresponding to the different thermal zones of the vertical thermal reactor. The simplest model is a static model, describing the relation between spike TC temperature and paddle TC temperatures under steady-state conditions according to Equation (3). In one embodiment, the static model is based on 4th order polynomial models representing the relation between spike TC and paddle TC temperatures over a specified temperature range. Dynamic models describe the dynamic response of the system. A dynamic paddle model gives the paddle TC temperature as a function of spike TC temperature according to Equation (1) and a dynamic spike model gives the spike TC temperature as a function of power output and paddle TC temperature, according to Equation (2). By dividing the temperature range in a plurality of temperature sub-ranges, a set of linear dynamic models can be obtained. This simplifies the required calculations. The various models are acquired experimentally from a measurement procedure as described below.
The identification test design plays an important role in a successful model identification and MBPC design. Current practices of identification methods are to use single variable step or finite impulse tests for MBPC model identification. The tests are carried out manually. The advantages of these methods are that the system dynamic responses are described in an intuitive manner. One drawback with the step or finite impulse tests is that the data from these tests may not contain enough information about the multivariable characteristics of the process because the step or pulse signals may not induce enough dynamic behavior of the process. A second drawback of these step or impulse tests is that they can be very time consuming. To avoid the above-mentioned drawbacks of common identification methods, during the identification procedure for the MBPC 720, the inner-loop PID control loop 740 is actively used. The PID constants used during the model identification are based on previous control experiences of the vertical thermal reactor. Then, using this inner-loop PID controller 740, the system identification can be carried out automatically by using a model identification and data acquisition recipe. The signals inducing dynamic behavior of the system are real control signals, and the conditions are similar to real process conditions. In this case, the PID controller 740 helps to keep the spike TC temperatures within their limits. The models based on these inner closed-loop data enhance the performance and stability margins of the system 700.
In one embodiment, the modeling data acquisition is achieved by using the control scheme shown in
An example identification control process sequence (i.e., a “recipe”) for a vertical thermal reactor starts at room temperature and ramps up at a ramp rate (that is, a time rate of change) of 10° C./min, stabilizing the spike temperature for approximately 45 minutes at 200, 400, 600, 800 and finally 1000° C., using a PID controller in the configuration of
The data collected from the recipe is divided into five data subsets, corresponding to the five stabilization temperatures of the model identification and data acquisition recipe. Each subset starts at the beginning of a ramp up period and ends just before the beginning of the next ramp up period.
In contrast to prior art model identification methods where data is acquired in open loop control, in the present invention the data is acquired in closed loop control as shown in
2. Model Structure
2.1 Static Models
For each zone, a static model is derived. For each stabilization temperature in the identification recipe, at least one value is extracted both for the spike TC temperature and the paddle TC temperature. These pairs of values, 5 in the example shown in
where n is the zone number, snq are the static models parameters to be determined, and q is the order of the static model. The model according to equation (4) gives an adequate description of the relationship between the spike temperature Sp and the paddle temperature Pd over the desired temperature range.
2.2 Dynamic Models
For each zone, a dynamic model is derived from each data subset for the spike TC and the paddle TC. This means that in the case of five zones and five temperature sub-ranges, according to the present example, 25 dynamic paddle linear models and 25 dynamic spike linear models are used. It will be clear to one of ordinary skill in the art that any number of thermal zones and temperature sub-ranges can be selected, depending on the circumstances. In one embodiment, a linear least-squares algorithm is used. The model equations for the dynamic linear models are:
where n is the zone number, r is the temperature range number, t is the discrete time index, anrl and bnrm are paddle model parameters, l and m are model orders of the paddle models, and cnrx, dnry and pnrz are spike model parameters, Further, x, y, and z are model orders of the spike models, and enrp and enrs are model errors or disturbances. Typically, a first or second order approximation (m=1 or 2) is adequate for the model of equation (5) whereas the order for the model of equation (6) is typically 20 or more (e.g., l=28) for an adequate description.
Model validation can be provided by visual comparison of the measured and calculated model output, simulation, residual analysis, cross-correlation analysis, etc.
3. Mathematics of Model Extraction
The methods used for parameter estimation for both the static models and the dynamic models involve solving a linear least-squares problem (LLS). This can be done via the so-called normal equations, or via a QR-decomposition. The method via QR-decomposition typically requires more calculations, but tend to be numerically more stable. For most cases, solving the normal equations gives good results, but for higher orders it is safer to use the QR-decomposition.
The method of solving the LLS problem is described below. Given a system of equations defined as A·x=b, where A is a matrix and x and b are vectors, the linear least-squares problem is to find a vector x that minimizes
φ(x)=∥A·x−b∥ (7)
If the matrix A is non-singular (i.e., if the inverse of A exists), this problem has a unique solution.
3.1 Solving LLS via the Normal Equations
The direct method of solving a LLS problem is via the normal equations. If a function has a minimum, its derivative at that minimum is zero. Thus φ(x) has a minimum where d φ(x)/dx=0 or:
ATA·x−AT·b=0 (8)
where AT is the inverse matrix of A. This results in the so-called Gaussian normal equations:
ATA·x=AT·b (9)
From these equations, x can be calculated as
x=(ATA)−1ATb (10)
3.2 Solving LLS via OR-decomposition
Another method of solving a LLS problem is via QR-decomposition. With this algorithm the matrix A is expressed as the product of an orthogonal matrix Q and an upper triangular matrix R.
A=QR (11)
The QR-decomposition of the matrix A can be computed by calculating the Householder reflection H for each column of A. The Householder reflection Hk of the kth column can be calculated as:
s
k
=√{square root over (a
k,k
2
+a
k+1,k
2
+ . . . +a
n,k
2
)} (12)
where ai,j is the element of matrix A at the ith row and jth column, and n is the number of columns and I is the unity matrix.
The matrices Q and R can be calculated as
Q=H1H2 . . . Hn−1 (15)
R=Hn−1Hn−2 . . . H1A (16)
For a matrix A of m rows and n columns, where m is greater than n, the last m-n rows of the upper-triangular matrix R are completely zero.
Once the matrix A is expressed as A=QR, the LLS problem can be written as:
Q is orthogonal, so
y=QTb (18)
With y and R known, x can be calculated. Since R is upper-triangular, this is simply done via backward substitution. By way of example, the solution is shown for a 3 by 3 matrix in the equation below.
This system can be solved via backward substitution starting at the bottom row.
r31·x1=y3x1=y3/r31
r21·x1+r22·x2=y2x2=y2/r22−r21·x1=y2/r22−r21·y3/r31
r11·x1+r12·x2+r13·x3=y1x3=y1/r13−r11·x1−r12·x2=y1/r13−r11·y3/r31−r12·(y2/r22−r21·y3/r31) (20)
When using the QR-decomposition for solving a LLS problem, the orthogonal matrix Q is usually not explicitly calculated. Instead, R and y are calculated in a recursive algorithm, with initial conditions
R=A
y=b (21)
Next for each column of R, the vector w is calculated. With this vector, R and y are updated according to the following formulas.
Rk=Rk−2(wkTRk)wk
y=y−2(wkTy)wk (22)
where Rk is the kth column of R. This is repeated for all columns of R. The solution of the LLS problem can then be calculated via backward substitution as described before.
4. Extraction of the Dynamic Models
The dynamic models (shown in Equations (5) and (6)) for the MBPC can be represented by the following equations:
{circumflex over (P)}dnr(t)=φnrpT(t)·θnrp (23)
Ŝpnr(t)=φnrsT(t)·θnrs (24)
where {circumflex over (P)}dnr and Ŝpnr are model predictive outputs, and
With the model structure defined above, given the model orders and a set of input and output data, the parameters of the model are found by minimizing a so-called loss function. An often-used loss function is the summed squared error:
where N is the number of input and output samples and ε is the prediction error vector, defined as the difference between measured and predicted output:
εpd(t|θ)=Pdnr(t)−{circumflex over (P)}dnr(t|θ)=Pdnr(t)−φnrpT(t)θnrp (26)
εsp(t|θ)=Spnr(t)−Ŝpnr(t|θ)=Spnr(t)−φnrsT(t)θnrs (27)
For simplification, the matrix Φ and vector Y are used, defined as:
The loss function now becomes:
JN(θ)=|Y−Φθ|2 (29)
where θ is equal to θnrp or θnrs.
Minimizing this loss function can be accomplished by solving a linear least-squares problem.
5. Extraction of the Static Models
The parameters of the static models shown in Equation (4) are obtained by polynomial fitting using groups of input and output data. Thus, Equation (4) can be rewritten as:
Spn(k)=sn0+sn1Pdn(k)+sn2Pdn(k)2+ . . . +snPdn(k)q (30)
where k is the kth value of the input and output sequence.
The identification problem can now be formulated as follows. Given input and output signals Spn=[Spn(1), Spn(2), . . . , Spn(k)]T, Pdn=[Pdn(1), Pdn(2), . . . , Pdn(k)]T, and model order q, find appropriate values for parameters Sn=[snq, . . . , sn1, sn0]T. First a Vandermonde matrix V is constructed:
Next, the parameters are estimated by solving the following least-squares problem.
which can be written as
Spn=V·Sn (33)
Here the identification problem has become a linear least-squares problem, thus the parameters of a polynomial fit can be calculated as
Sn=(VTV)−1VTSpn (34)
Alternatively, the QR decomposition algorithm can also be used to find the parameters for the polynomial fit.
Model validation can be provided by visual comparison of the measured and calculated model output, simulation, residual analysis, cross-correlation analysis, etc.
6. MBPC Structure
The internal structure of one embodiment of an MBPC corresponding to the MBPC 520 from
Inputs to the MBPC controller 1200 are the paddle control setpoint temperature Pdset and the actual paddle temperatures Pd. The paddle control setpoint temperature is provided to the trajectory planning module 1220 and the actual paddle temperatures Pd are provided to a memory 1210 for storing past inputs and outputs. The memory 1210 provides input to the MBPC algorithm module 1230. Additional input for the models include actual spike temperatures. The Trajectory planning module 1220 generates N paddle control setpoints Pdset(1 . . . N) distributed over a predictive horizon, where Pdset(1) is the control setpoint for the present moment and Pdset(N) is the most future predicted control setpoint. These control setpoints Pdset(1 . . . N) are provided to a first input of an adder 1222 via a line 1221. Further, the modeled paddle values {tilde over (P)}dfr(1 . . . N), which are provided as output by the MBPC control algorithm module 1230, are provided to a second input of the adder 1222 via a line 1233. The adder 1222 calculates error signals Es(1 . . . N) which are provided to the Optimizer module 1232 of the MBPC algorithm module 1230 via a line 1223. The optimizer module 1232 optimizes the model output by minimizing a cost function 1235 as represented by equation (35), using constraints 1236. The least-squares error between the modeled predicted paddle control setpoint temperatures {tilde over (P)}dfr(1 . . . N) and the actual paddle control setpoint temperatures Pdset(1 . . . N) from the trajectory planner 1220 is minimized over the predictive horizon. The predicted paddle control setpoint temperatures are optimized by using the disturbance model (the last term in equation (35)) so that the predictive values approach the actual values.
The spike correction value ΔSp is calculated, according to equation (45). The modeled values {tilde over (P)}dfr(1 . . . N) are provided to the memory 1210 via a line 1234. The spike correction value ΔSp is provided from the MBPC algorithm into a spike output calculation module 1212 to calculate the modeled spike control setpoint Spset(1) according to equation (46). The modeled spike control setpoint Spset(1) is provided to the MBPC outputs fuzzy inference module 1240 via a line 1211. The modeled spike control setpoint value is provided to the Output limiter 1250 where the output is limited according to equation (54). The algorithms will be discussed in further detail below.
Based on the dynamic linear models described in Equation (5), the predictive control algorithm calculates the control strategy ΔSpset(t) by minimizing the cost function J, defined as:
where N and Nu are the prediction horizon, ku and ks are weight parameters, and Pdset(t+k) is the kth paddle control setpoint generated by the trajectory planner. Further, {tilde over (P)}d(t+k|t) is the kth model predictive output at time t, which can be considered as the combination result of two separate contributions:
{tilde over (P)}d(t+k|t)={tilde over (P)}dfr(t+k|t)+{tilde over (P)}dfo(t+k|t) (36)
where {tilde over (P)}dfr(t+k|t) is the free response, and {tilde over (P)}dfo(t+k|t) is the forced response. Among them, {tilde over (P)}dfr(t+k|t) can be computed directly from Equation (6) as:
where
is the disturbance model output, and
e(t)=[Pd(t)−{tilde over (P)}dfr(t)]−[Spset(t−1)−Sp(t)].
Then, {tilde over (P)}dfo(t+k|t) can be calculated as:
where gi is the coefficient of the module step response of the model from Equation (5), which can be obtained as:
where aj and bj are the coefficients from Equation (5).
By using matrix notation, Equations (38), (36) and (35) can be rewritten as:
{tilde over (P)}d
fo
=GΔSp (40)
Minimizing J with respect to ΔSp, i.e.,
then ΔSp gives the optimal solution:
ΔSp=(kuGTG+ksI)−1GTku(Pdset−{tilde over (P)}dfr) (43)
where I is a identity matrix, and the matrix (kuGTG+ksI) to be inverted has Nu×Nu dimension. The value of Nu need not be 1, but it is instructive to note that when Nu=1, then Eq. (43) is simplified as the scalar control law:
Substitute Eq. (39) into (44), then:
In one embodiment, the MBPC employs a “receding horizon” control principle, where only the first element ΔSp(t|t) is required to compute the MBPC output:
Spset(t)=Spset(t−1)+ΔSp(t|t) (46)
At the next sampling instant (t+1), the whole procedure is repeated.
6.2 Trajectory Planning
To control the desired speed to approach the paddle TC control setpoint, a trajectory planer is used. In one embodiment, the trajectory planner reduces the ramp rate when the actual paddle temperature Pd approaches the desired paddle control setpoint Pdw to within a range δ:
where rp is the desired ramp rate, δ is the stabilization range and α is the trajectory reference time constant. An example trajectory reference is shown in
δ=krrpε[δmin, δmax] and kr<1 (48)
where kr is a proportional constant, and ks is a constant for the stabilization time control that is also used in the control law in Equation (44).
The parameters δ and α can be selected and adjusted to provide optimum control under a variety of circumstances by setting the values of the constants kr and ks. It can be seen from
6.3 MBPC Outputs Inference by Using Fuzzy Logic
During controlling temperature ramp up/down to a desired temperature level, the temperatures may cross several different temperature sub-ranges, particularly, when the temperature is close to the defined edges of a temperature sub-range. The MBPC needs to switch from the dynamic models that are valid for one temperature sub-range to the dynamic models that are valid for another, adjacent, temperature sub-range. In one embodiment, a fuzzy logic software algorithm is used to ensure that the MBPC controller has a smooth transition of its outputs, without introducing disturbances into the control system when it needs to switch between the models.
The fuzzy sets are defined as shown in
By using fuzzy inference and a center of area (COA) defuzzification operator, the outputs of the MBPC are calculated as:
where n is the zone number, m is the fuzzy rule number, Spsetn(t) is the spike control setpoint for zone n, μi(i=1, 2, . . . , m) are the fuzzy membership functions that are defined in
where [Tmin, Tmax] is the desired temperature control range, ΔT is a parameter that characterize the membership functions.
where j=2, . . . , m−1 are the sub-temperature control ranges, and T1=Tmin.
6.4 MBPC Output Limiters
The hybrid cascade MBPC and PID control scheme has an important advantage over single loop systems in that it reduces the disturbance effects of inner-loop process variability. However, such a scheme also presents some conceptual difficulties, and can result in poorer dynamic performance if the inner loop PID is not fast enough to follow the control setpoint generated by the MBPC. Moreover, model mismatches can appear in cases where the reactor system is changed or disturbed (e.g., boat in/out, when the door of the reactor is open, different ramp rates and load sizes, etc.). In these cases, the conceptual difficulties arise from the fact that the MBPC needs to know its control effort limits in order to function properly. To deal with these difficulties, limiters based on static models are added to the MBPC control loop. The limiters are defined as:
where Spn is computed by Equation (30), ΔT is an adjustable temperature constant for compensation of the model outputs mismatches, and ku is a tuning parameter that is also used in the control law Equation (45). Tuning ku, can improve the temperature uniformity (shown in
It can be seen from
By using Equation (54), some uncertain factors caused by the system non-linearity and disturbances are limited in the MBPC control loop, which ensures that the MBPC can always generate the reasonable control setpoints for the inner PID control loop, enhances the stability, control margins and robustness of the hybrid cascade MBPC control system.
7. PID Design
The PID loop is an inner control loop that works in concert with the outer MBPC control loop. Tuning parameters (e.g., control gains) of the PID controller are based on the accumulated control experiences and the open-loop identification analysis of the vertical thermal reactor. The PID controller is used for both modeling (
The structure of a PID controller 1300 is shown in
In the integrating action module 1340, an integration constant ki is calculated in block 1348 and applied in block 1342. A summation is carried out in block 1344. Then the calculated integrating action passes through the output limiter 1346, mathematically represented by Equation (58). In one embodiment, the output of the differentiating action module, Dout, is also used as an input for calculating the integrating action, as shown by feedback line 1331. The purpose of this feedback is to achieve improved control during ramp-up and ramp-down. The outputs of both the differentiating action module 1320 and the integrating action module 1340 are provided to the proportional action module 1360 via lines 1330 and 1350, respectively. In the proportional action module 1360, the proportionality action is calculated in block 1362, using a proportionality constant kp calculated in block 1366. Then the output signal Pw passes through output limiter 1364, represented by Equation (60).
The PID parameters kd, ki and kp are calculated in blocks 1328, 1348 and 1366 according to the formulas:
where Spset(T) is calculated by using the static model according to Equation (3), and kp0, kp1, kp2, ki0, ki1, and ki2 are predetermined constants relating to system gain and time constants. Tds is a delay time. Tmin and Tmax are the lower and upper temperature boundaries of the temperature control range. After dynamic and static models are identified, the kp
For anti-wind-up and integral saturation, the following linear limiters are included in the PID controller 1300, and defined as:
By using Equations (57)–(60), the dynamic response of the inner-loop PID is stable and provides the desired speed of response. The control results are shown in
It can be seen from
The MBPC safety control configuration for paddle TC failure is shown in
Similarly, the MBPC safety control configuration for spike TC failure is shown in
9. MBPC Parameter Tuning
The presence of the inner-loop PID control with outer-loop MPBC control makes the control system robust such that in many cases parameters tuning only needs to be performed during the design phase. For small changes in the furnace system, additional parameter tuning can be omitted in many cases. Since both the dynamic and static models are derived from the closed-loop data controlled by the inner-loop PID controller, slowing down or speeding up the inner-loop does not seriously degrade the performance of the outer MBPC loop. In this case, the inner and outer loop tuning are not strongly coupled. In the design of the inner loop, parameter tuning can be realized automatically (shown in Equation (56)). For control flexibility, in the outer MBPC loop design, two parameters (ku and ks) are provided for the adjustment of the dynamic ramp-up temperature uniformity (shown in
Although the present invention has been described with reference to a specific embodiment, other embodiments occur to those skilled in the art. For example, the hybrid cascade MBPC can be used to control many linear and/or non-linear plants, not just the vertical thermal process reactor. It is to be understood therefore, that the invention herein encompasses all such embodiments that do not depart from the spirit and scope of the invention as defined in the appended claims.
The present application claims priority benefit of U.S. Provisional Application No. 60/427,143, filed Nov. 14, 2002, titled “HYBRID CASCADE MODEL-BASE PREDICTIVE AND PROPORTIONAL-INTEGRAL-DERIVATIVE TEMPERATURE CONTROL SYSTEM FOR VERTICAL THERMAL REACTORS,” the entire contents of which is hereby incorporated by reference.
Number | Name | Date | Kind |
---|---|---|---|
3567895 | Paz | Mar 1971 | A |
4272466 | Harris | Jun 1981 | A |
4346433 | Rutledge | Aug 1982 | A |
4385362 | Arcara | May 1983 | A |
4630189 | Ohmori et al. | Dec 1986 | A |
4639853 | Rake et al. | Jan 1987 | A |
5102331 | Brekke et al. | Apr 1992 | A |
5568378 | Wojsznis | Oct 1996 | A |
5635409 | Moslehi | Jun 1997 | A |
5697436 | Johnson et al. | Dec 1997 | A |
5895596 | Stoddard et al. | Apr 1999 | A |
6056781 | Wassick et al. | May 2000 | A |
6128586 | Pfeiffer | Oct 2000 | A |
6162488 | Gevelber et al. | Dec 2000 | A |
6207936 | De Waard et al. | Mar 2001 | B1 |
6222164 | Stoddard et al. | Apr 2001 | B1 |
6369716 | Abbas et al. | Apr 2002 | B1 |
6373033 | De Waard et al. | Apr 2002 | B1 |
6411944 | Ulyanov | Jun 2002 | B1 |
6424873 | Przybylski | Jul 2002 | B1 |
6496749 | Yamaguchi et al. | Dec 2002 | B1 |
6501998 | Pfeiffer | Dec 2002 | B1 |
6574972 | Giacobbe et al. | Jun 2003 | B1 |
6819347 | Saquib et al. | Nov 2004 | B1 |
20030202910 | Sinha et al. | Oct 2003 | A1 |
Number | Date | Country |
---|---|---|
1011037 | Jun 2000 | EP |
2004119804 | Apr 2004 | JP |
Number | Date | Country | |
---|---|---|---|
20040098145 A1 | May 2004 | US |
Number | Date | Country | |
---|---|---|---|
60427143 | Nov 2002 | US |