Air conditioning is used worldwide to provide comfortable and healthy indoor environments that are properly ventilated and cooled and that have adequate humidity control. While being useful for conditioning supply air, conventional air conditioning systems are costly to operate as they use large amounts of energy (e.g., electricity). With the growing demand for energy, the cost of air conditioning is expected to increase, and there is a growing demand for more efficient air conditioning methods and technologies. Additionally, there are increasing demands for cooling technologies that do not use chemicals and materials, such as many conventional refrigerants, that may damage the environment if released or leaked. Maintenance is also a concern with many air conditioning technologies, and, as a result, any new technology that is perceived as having increased maintenance requirements, especially for residential use, will be resisted by the marketplace.
Evaporative coolers are used in some cases to address air conditioning demands or needs, but, due to a number of limitations, conventional evaporative coolers have not been widely adopted for use in commercial or residential buildings. Evaporative coolers, which are often called swamp coolers, are devices that use simple evaporation of water in air to provide cooling in contrast to conventional air conditioners that use refrigeration or absorption devices using the vapor-compression or absorption refrigeration cycles. The use of evaporative cooling has typically been limited to climates where the air is hot and humidity is low such as in the western United States. In such dry climates, the installation and operating costs of a conventional evaporative cooler can be lower than refrigerative air conditioning. Residential and industrial evaporative coolers typically use direct evaporative cooling with warm dry air being mixed with water to change the water to vapor and using the latent heat of evaporation to create cool moist air (e.g., cool air with a relative humidity of 50 to 70 percent). For example, the evaporative cooler may be provided in an enclosed metal or plastic box with vented sides containing a fan or blower, an electric motor to operate the fan, and a water pump to wet evaporative cooling pads. To provide cooling, the fan draws ambient air through vents on the unit's sides and through the dampened pads. Heat in the air evaporates water from the pads, which are continually moistened to continue the cooling process. The cooled, moist air is then delivered to the building via a vent in the roof or a wall.
While having an operation cost of about one fourth of refrigerated air conditioning, evaporative coolers have not been widely used to address needs for higher efficiency and lower cost conditioning technologies. One problem with many sump coolers is that in certain conditions these evaporative coolers cannot operate to provide adequately cooled air. For example, air may only be cooled to about 75° F. when the input air is 90° F. and 50 percent relative humidity, and such cooling may not be adequate to cool a particular space. The problem may get worse as temperatures increase well over 100° F. as found in many locations in the southwest portion of the United States and elsewhere. As a result, the air conditioning system may need to include refrigerated air conditioning to cool the outlet air from the evaporative cooler, which results in a system that is more expensive to purchase, operate, and maintain.
Additionally, conventional evaporative coolers provide no dehumidification of the air and, in fact, often output air at 80 to 90 percent relative humidity, which may only be acceptable in very dry environments as very humid air reduces the rate of evaporation for occupants of the building (e.g., reduces comfort levels) and can cause condensation resulting in corrosion or other problems. Dehumidification is provided as a second or later stage in some evaporative coolers such as by wicking a liquid desiccant along a wall of the air flow channel or chamber, but such systems have not been widely adopted due to increased operating and maintenance costs and concerns of having the desiccant expelled with the conditioned air. In general, maintenance is a concern with evaporative coolers as the evaporation process can result in mineral deposits on the cooling pads and other surfaces of the cooler that need to be cleaned or replaced to maintain the efficiency of the system, and the water supply line needs to be protected against freezing during the off season such as by draining the system. Due to these and other concerns, evaporative cooling is unlikely to be widely used to provide an energy efficient, air conditioning alternative for commercial and residential applications until significant improvements are made that address maintenance concerns while improving achievable cooling (e.g., providing adequately cooled output air for direct use in a building).
The foregoing examples of the related art and limitations related therewith are intended to be illustrative and not exclusive. Other limitations of the related art will become apparent to those of skill in the art upon a reading of the specification and a study of the drawings.
The following embodiments and aspects thereof are described and illustrated in conjunction with systems, tools and methods that are meant to be exemplary and illustrative, not limiting in scope. In various embodiments, one or more of the above-described problems have been reduced or eliminated, while other embodiments are directed to other improvements.
This is achieved, in part in some applications, by providing a mass/heat transfer assembly for use in indirect evaporative coolers or heat exchangers. The assembly is formed of alternating stacks each including a first (or upper) layer or sheet of membrane material, a separation wall, and a second (or lower) layer or sheet of membrane material. The membrane or membrane material for each layer is permeable to water molecules in the vapor state while the separation wall is impermeable to water but allows heat transfer (e.g., is a thin layer and/or is made of materials that conduct heat). In a first one of adjacent pairs of stacks, coolant such as water flows between the first membrane layer and the separation wall and liquid desiccant flows between the separation wall and the second membrane layer while in the second or next one of the adjacent pairs of stacks the flow order is reversed. This ordering is repeated throughout the mass/heat transfer assembly to form alternating supply and exhaust air flow channels or chambers. Supply air (or air to be conditioned) is directed through a channel between a first pair of stacks while a portion of the pre-cooled exhaust air (e.g., a fraction of the supply air that is cooled by flowing through the stacks) is directed through a chamber between a second or next pair of stacks (e.g., typically in a counterflow arrangement relative to the flow of the incoming supply air). Liquid desiccant is provided proximate to the supply inlet airflow while coolant such as water is provided proximate to the exhaust airflow (i.e., a fraction of supply outlet airflow directed to be exhausted) with the air only being separated from these flowing liquids by the water permeable membrane. The supply air inlet airflow, supply outlet airflow, exhaust airflow, liquid desiccant flow, and coolant flow are plumbed such as via one or more manifold assemblies to the mass/heat transfer assembly, which can be provided in a housing as a single unit (e.g., an indirect evaporative cooler).
In a typical embodiment, dehumidification and evaporative cooling are accomplished by separation of the air to be processed and the liquid and/or gas substances (e.g., liquid desiccant, water, desiccated air, and the like) by a membrane. The membrane is formed of one or more substances or materials to be permeable to water molecules in the vapor state. The permeation of the water molecules through the membrane is a driving force behind (or enables) dehumidification (or dehumidification in some implementations) and evaporative cooling of one or more process air streams. As described above, multiple air streams can be arranged to flow through chambers in the mass/heat transfer assembly such that a secondary (purge) air stream, such as the exhaust airflow of pre-cooled supply air, is humidified and absorbs enthalpy from a primary (process) air stream, such as the supply inlet airflow that can then be directed to a building as supply outlet airflow (e.g., make up air for a residential or commercial buildings or the like). The process air stream is sensibly cooled and is, in some embodiments, simultaneously dehumidified by providing a liquid desiccant flow contained by membranes defining the sidewalls of the supply inlet airflow channel or chamber.
The membrane is also used in some embodiments to define sidewalls of the exhaust (e.g., counter) airflow channel or chamber such that the membrane controls or separates coolant liquid from the exhaust air stream. Wicking materials/surfaces or other devices may be used to contain or control water flow (e.g., direct-contact wicking surfaces could be used in combination with the use of the liquid desiccant containment by a membrane), but membrane liquid control facilitates fabrication of the stacks or manifold structure useful for heat and mass exchanger/assembly configurations described herein that provide cooling, dehumidification, and/or humidification. In such configurations, the air streams can be arranged in counter-flow, counter-flow with pre-cooled exhaust air, cross-flow, parallel flow, and impinging flow to perform desired simultaneous heat and mass transfer in the evaporative cooling units.
By way of example, but not limitation, an embodiment includes an indirect evaporative cooler for cooling a stream of inlet supply air from a first temperature to a second, lower temperature using a stream of liquid coolant and a stream of exhaust or purge air. The cooler includes a first flow channel through which the stream of inlet supply air flows and a second flow channel adjacent the first flow channel through which the stream of exhaust air, at a lower temperature than the inlet or first temperature of the supply air, flows. The second flow channel is formed or defined in part by a sheet of a membrane or membrane material that is permeable to water vapor but that otherwise contains the liquid coolant. In this manner, the coolant flows on a side of the membrane (and not in direct contact with) the air in the second flow channel but mass is transferred as a vapor through the membrane to the exhaust air when or in response to heat being transferred from the inlet supply air to the liquid coolant. In some cases or configurations, as will become clear, the supply air stream (or inlet supply air) is cooled and dehumidified in this first stage. A second stage may be provided to sensibly cool the air stream to a very cool temperature, which could be below the dewpoint of the original supply inlet air as it was dehumidified initially or in the first state to allow this.
A separation wall that is spaced apart from the sheet of membrane is used to define a flow channel for the liquid coolant, with the wall being formed from a material (such as plastic) that is impermeable to the liquid coolant but that conducts or allows the heat to be transferred from the inlet air supply to the coolant. A second sheet of membrane may be spaced apart from the opposite side of this separation wall to define a flow channel for a liquid desiccant, and during operation, water vapor is transferred from the stream of inlet supply air through the membrane to the liquid desiccant, which results in the inlet supply air being concurrently cooled and dehumidified. The membrane is effective for resisting or even fully blocking flow of the liquid coolant and the liquid desiccant while allowing flow of water vapor, and, in some embodiments, the coolant is water and the desiccant is a halide salt solution (e.g., a weak desiccant such as CaCl or the like). The exhaust air in some cases is a redirected portion of the stream of inlet supply air after it has been cooled to the second, lower temperature (e.g., as it is exiting the first flow channel), and the exhaust air may flow in a direction through the second flow channel that is cross, counter, or a combination of these relative to the supply air flowing in the first flow channel.
In another exemplary embodiment, a method is provided for conditioning a process or return air for a residential or commercial building. The method includes first directing the process air through a first flow channel and second directing a stream or volume of liquid desiccant adjacent one or more walls defining the first flow channel, the liquid desiccant is separated from the process air by a membrane (e.g., the membrane provides the walls) that contains the liquid desiccant and also allows water vapor from the process air to flow into and be absorbed by the liquid desiccant, which dehumidifies the process air. The method further includes concurrent with the first and second directing, third directing a stream of purge air through a second flow channel proximate to the first flow channel (e.g., parallel and adjacent). The purge air is at a temperature lower than all or at least a substantial portion of the process air in the first flow channel, and in some cases, the purge air is a fraction of the dehumidified process air exiting the first flow channel that is directed in a counter flow direction relative to the process air through the second flow channel. The method also includes fourth directing a stream of liquid coolant adjacent a wall of the second flow channel. The liquid coolant is also separated from the air by a membrane that is permeable to vapor from the coolant such that mass is transferred from the coolant to the purge air. The method provides for concurrent (or single stage) dehumidification and cooling of the process air.
According to another aspect, a mass and heat transfer assembly is provided for use in an indirect evaporative cooler or exchanger device. The assembly includes a first stack including an upper membrane, a lower membrane, and a separation wall between the upper and lower membranes. The upper and lower membranes are permeable to water in vapor form and the separation wall is substantially impermeable to liquid and vapor. Second and third stacks are provided that also each includes an upper membrane, a lower membrane, and a separation wall positioned therebetween. In the assembly, the first stack and second stacks are spaced apart (such as less than about 0.25 to 0.5 inches apart) to define a flow channel for receiving a first stream of air (e.g., air to be conditioned) and the second and third stacks are spaced apart to define a flow channel for a second stream of air (e.g., purge or exhaust air directed in cross or counter flow relative to the first stream of air). In some configurations and/or operating modes, the device does only evaporative cooling and no dehumidification. Such that the membranes are only used on the purge side and the other side of the wall is left bare for the supply air to exchange heat.
The first, second, and third stacks may be considered a set of stacks, and the assembly includes a plurality of such sets of stacks to define a plurality of air flow channels spaced apart by the stacks or layers of membranes and separation walls. A divider or separator may be provided in the flow channels to maintain spacing of the membranes while allowing flow of the air streams in the channels. The assembly may further include in the first stack a liquid coolant flowing between the upper membrane and the separation wall and a liquid desiccant flowing between the separation wall and the lower membrane. In the second stack, a liquid desiccant flows between the upper membrane and the separation wall while a liquid coolant flows between the separation wall and the lower membrane. In the third stack, liquid desiccant flows between the upper membrane and the separation wall while liquid coolant flows between the separation wall and the lower membrane. The liquid coolant may be water and during operation water vapor may be transferred from the coolant through the membrane to the second stream of air. The liquid desiccant may be a salt solution (such as weak desiccant such as CaCl, or the like) and during operation or use of the assembly water vapor may be transferred from the first stream of air through the membrane to the liquid desiccant, whereby the first stream of air is simultaneously dehumidified and cooled to a lower temperature.
In some cases, the mass and heat transfer assembly may be configured with no membrane on the coolant (e.g., water) side of the device. In such a mass transfer assembly, liquid desiccant is contained by a vapor permeable membrane in the combined stacks, as discussed above. However, the coolant, which in many cases is water, is allowed to flow without membrane containment. To this end, the coolant is maintained or attached on a surface or side of the separator or separation wall through the use of surface tension forces on a wicked or flocked surface (e.g., a wicking layer is attached to the separation wall surface). The flocked surface or layer of wicking material is attached to the separation wall, and, thus, there is direct thermal contact between the separation wall and the liquid coolant (e.g., water flowing through the wicking material). Water evaporation occurs freely between this coolant-soaked/containing surface on the separation wall and the purge or exhaust air stream.
Further, the mass and heat transfer assembly may include a humidification stage. The heat and mass transfer assembly may include an assembly or section where water adjacent to a supply air stream is membrane contained with a vapor permeable membrane or in a layer of wicking material. The supply air would be in contact with the membrane and allow for humidification of the supply air stream prior to discharge from the mass and heat transfer assembly (e.g., a humidifier stage provided downstream from the sensible or indirect evaporative cooler stage).
In addition to the exemplary aspects and embodiments described above, further aspects and embodiments will become apparent by reference to the drawings and by study of the following descriptions.
Exemplary embodiments are illustrated in referenced figures of the drawings. It is intended that the embodiments and figures disclosed herein are to be considered illustrative rather than limiting.
The following provides a description of exemplary indirect evaporative coolers with dehumidification and mass/heat transfer assemblies for such coolers that provide inlet air stream chambers with sidewalls defined by permeable membrane sheets containing liquid desiccant. The assemblies also include outlet or exhaust air stream chambers (such as in counterflow to the inlet air streams) with sidewalls defined by permeable membrane sheets containing coolant such as water. In embodiments described below, the membrane is “permeable” in the sense that moisture in the form of a vapor (e.g., water in the vapor state) generally can permeate readily through the membrane such as from an inlet supply air and from liquid coolant via evaporation. However, the membrane generally contains or blocks moisture in the form of a liquid from flowing through as it is instead directed to flow within the channel or chamber. In some cases, water in the liquid state is contained by the membrane at pressures less than about 20 psi and more typically less than about 5 psi. The coolant and the liquid desiccant in some embodiments are maintained at pressures below about 2 psi, and the permeable membrane contains moisture such as water in the liquid state while water vapor permeates the membrane.
As will become clear from the following description, use of the assemblies such as for evaporative coolers or mass/heat exchangers provides a number of benefits. The inlet or process air stream can be cooled and dehumidified simultaneously or in a single chamber/stage, and this combined action reduces system size and cost as well as the number of required components and equipment (e.g., do not require a multi-stage unit or device to cool and then to dehumidify and/or further cool with refrigerant or the like). The combination of liquid desiccant dehumidification with indirect evaporative cooling provides very high energy transfer rates due to evaporation and absorption. The design creates a liquid desiccant system that does not require separate equipment for liquid desiccant cooling (e.g., a separate cooling tower or chiller). The stacked arrangements or multi-layered mass/heat transfer assemblies (or manifolded flow chambers/channels) enable ultra-low flow liquid desiccant designs. This is due in part to the enhanced geometry of the assembly and its ability to decrease the liquid desiccant's temperature to a lower temperature than achievable with traditional cooling tower technologies. Hence, in the cooler, there are higher concentration gradients of liquid desiccant (e.g., more than 20 percentage points of lithium chloride (LiCl) and similar gradients for other desiccants), which provides the following advantages: (a) a higher thermal coefficient of performance (COP) to regenerate the desiccant (i.e., to remove water from the desiccant) for reuse in the cooler; (b) less desiccant storage requirements due to better utilization; and (c) the ability to use desiccants that are less expensive than LiCl such as calcium chloride (CaCl), which may not be used in conventional systems because their absorption properties are not as favorable as LiCl but lower temperature operation provided by the cooler embodiments described herein makes the properties of this and other “weaker” desiccants more acceptable or favorable.
The use of membranes as chamber sidewalls facilitates fabrication of counter-flow and counter-flow with pre-cooled exhaust air embodiments. Liquid desiccant containment with water molecule-permeable membranes eliminates liquid desiccant “carry over” in which small droplets of desiccant are passed into the air stream as is a concern with direct contact arrangements. The embodiments described herein also provide considerable reduction or even elimination of deposited solids during the process of water evaporation or adsorption (and liquid flow rates can be maintained at levels that are high enough to further control potential deposits) whereas fouling leads to increased maintenance and operating costs with prior evaporative coolers.
As shown, an inlet air stream 120 is directed in a chamber or channel defined in part by a sheet or layer of a membrane 112. Liquid desiccant 124 flows in an adjacent chamber or channel on the other side of the membrane 112. The liquid desiccant 124 is contained by the membrane 112, which is permeable to water molecules in a liquid or vapor state but generally not to the components of the liquid desiccant 124. The chamber for the desiccant flow 124 is also defined by a sheet or layer of material that is impermeable to fluid flow (i.e., a separation wall) 114 so as to contain the liquid desiccant 124 in the chamber or flow path. The chamber for stream 120 is also defined by an opposing membrane (not shown) that is used to contain another flow of liquid desiccant. In this manner, heat is passed or removed from the inlet air stream 120 and transferred to the liquid desiccant flow 124 (and the desiccant behind the opposite sidewall/membrane (not shown)). Concurrently, the inlet air stream 120 is dehumidified as water 130 is removed by passing through the permeable membrane 112 into liquid desiccant 124.
The liquid (or gas) desiccant 124 may take many forms to act to dehumidify and cool the air stream 120 as it passes over the membrane 112. Desiccant 124 is generally any hygroscopic liquid used to remove or absorb water and water vapor from an air stream such as stream 120. Preferably, the desiccant 124 chosen would be a regenerable desiccant (e.g., a desiccant that can have the absorbed water separated and/or removed) such as a glycol (diethylene, triethylene, tetraethylene, or the like), a salt concentrate or ionic salt solution such as LiCl, CaCl, or the like, or other desiccants. The membrane 112 may be formed of any material that functions to contain liquid desiccant 124 and, typically, coolant 126 (e.g., water or the like) while also being permeable to molecules of water in liquid or vapor state. For example, polymer membranes may be used that have pores that are about the size or just bigger than a water molecule and, in some cases, that are also adapted to provide water molecules with high mobility through the membrane 112. In one particular embodiment, the membrane 112 is formed from a membrane material as described in detail U.S. Pat. No. 6,413,298 to Wnek, which is incorporated in its entirety herein by reference. The membrane material may also be obtained from a number of distributors or manufacturers such as, but not limited to, Dias-Analytic Corporation, Odessa, Fla., U.S.A. The membranes 112, 118 and separation wall 114 preferably also are formed from materials that are resistive to the corrosive effects of the desiccant, and in this regard, may be fabricated from a polymer or plastic with the wall 114 in some cases being formed of a corrosion resistant metal or alloy, which provides a higher thermal conductivity compared with a plastic.
The embodiment 100 shown is configured for counter-flow of the pre-cooled exhaust air stream 128 (relative to the inlet air stream 120). Other embodiments may use cross (at about a 90 degree flow path) or quasi-counter flow (e.g., not directly counter or opposite in direction but transverse such as a greater than 90 degree angle flow path relative to air stream 120). The exhaust air stream 128 flows in a channel or chamber defined by a sheet or layer of membrane (e.g., second or lower membrane) 118 and an upper membrane of another stack (not shown). The separation wall 114 and membrane 118 define a flow chamber or channel for coolant flow 126, which is typically a flow of water or the like. Heat is transferred from the liquid desiccant 124 to the coolant 126 through the separation wall, and the coolant 126 is cooled as heat and mass (e.g., water or other moisture 132) is transferred to the exhaust stream 128 via membrane 118. Heat transfer is not shown but generally is flowing through the membrane 112 to the liquid desiccant 124, through the separation wall 114 from the liquid desiccant 124 to the coolant 126, and through the membrane 118 from the coolant 126 to the exhaust air stream 128. The membranes 112, 118 are relatively thin with a thickness, tmem, that typically is less than 0.25 inches and more typically less than about 0.1 inches such as 100 to 130 microns or the like. The membrane 112, 118 may have a tendency to expand outward if unrestrained, and, in some embodiments, such as that shown in
Specifically, the stack 212 includes an upper membrane layer 214, a separation wall 216, and a lower membrane layer 218. Dividers or spacers (not shown) would typically be provided to space these layers apart to define flow channels for coolant 215 and for liquid desiccant 217. For example, the separators may be configured to also provide a connection to a supply line for coolant and for regenerated desiccant, provide a manifold(s) to direct flow through the various stacks 212, 230, 240, and provide a connection to a return line for the coolant and diluted desiccant. The stacks 230 and 240 likewise include an upper membrane layer 232, 242, a separation wall 234, 244, and a lower membrane layer 238, 248. The stack 240 has coolant (such as water) 243 directed in the chamber between the upper membrane 242 and wall 244 and desiccant 246 flowing between the wall 244 and lower membrane layer 248 similar to stack 212. In contrast, the stack 230 has liquid desiccant 233 directed to flow in the chamber defined by the upper membrane layer 232 and wall 234 and has coolant 236 directed to flow in the chamber or channel defined by the wall 234 and lower membrane layer 238.
The cooler 210 includes ducting and the like (not shown) to direct supply inlet air 250 through the channel or flow path between the stack 212 and the stack 230. The arrangement of the stacks 212, 230, 240 and contained fluids results in the supply inlet air 250 being passed over the surfaces of the membranes 218, 232 that are containing liquid desiccant 217, 233. As a result, supply outlet air 254 is output that is dehumidified as moisture in the air 250 is absorbed by the desiccant 217, 233 via permeable membrane 218, 232, and the air 254 is also cooled by the interaction with desiccant 217, 233. The cooling effect in the cooler 210 is in part effected by a fraction of supply outlet air 254 being redirected in the cooler 210 by ducting/manifolds (not shown) to flow as pre-cooled exhaust air 255 through the channel or flow path between stacks 230, 240 to be output as warmer and moister air 258. Heat passes from desiccant 233 through wall 234 to coolant 236 (with similar heat transfer occurring in stacks 212, 240), and the coolant 236 is able to transfer heat and mass (e.g., water molecules) via membrane 238 to the incoming exhaust air 255. As discussed above, the stack pattern or set provided by 212, 230, 240 would typically be repeated within the cooler 210 to create a mass/heat transfer assembly with numerous, parallel flow channels for air, coolant, and desiccant.
The cooler 210 is shown as a counter flow exchanger, but other flow patterns may be used to practice the desiccant-based dehumidification and cooling described herein. For example, cross flow patterns may readily be established as well as quasi (or not fully opposite) counter flow patterns. These patterns may be achieved by altering the manifolding and/or ducting/plumbing of the cooler as well as the dividers provided between the stacks. Additionally, the counter flow passages may be provided integral to the stack assembly rather than externally as is the case in the cooler 210. For example, the cooler 310 has a similar stack arrangement as shown in the cooler 210 of
An indirect evaporative cooler such as the cooler 400 using stack sets as shown in
The following table shows results in tabulated form for modeling of
where LiCl Inlet Concentration=44%; flow ratio (flow exhaust/(flow exhaust+flow supply)=0.3; supply outlet face velocity=175 SCFM; and ambient pressure=101.3 kPa.
The cooler 210 of
It may be useful at this point to review the process with reference to
The heat exchanger configuration shown at 400 in
Referring again to
The configuration shown with cooler 1000 of
The stack and membrane technology described herein are readily applicable to a number of indirect evaporative cooler designs (with and without use of liquid desiccant for dehumidification) and applications. However, it may be useful to discuss the use of the technology within an air conditioning or HVAC system with the belief that those skilled in the art will readily understand that the technology is useful in many other such systems.
The desiccant enhanced indirect evaporative cooler (DE-IDEC) 1320 is the portion of the system 1300 that takes strong desiccant and water to provide cooling to building 1310. The system 1300 provides both sensible and latent cooling to building 1310 on demand and in proportion to the demand, e.g., the system 1300 can provide cooling in the form of 100 percent sensible, 100 percent latent, or any combination thereof. The DE-IDEC 1320 uses some portion of outdoor air 1325 with equal exhaust air 1328 to reject the heat load outside of the building 1310. The DE-IDEC 1320 itself can sit inside or outside of the building envelope because it has no wet surfaces and the liquid streams 1334, 1338 are closed loop. This makes system 1300 acceptable for indoor use and for placement of cooler 1320 inside the building 1310. The water source (or coolant source, not shown) for water or coolant 1334 is not required to be potable, and the system 1300 is compact enough to be acceptable by building managers. The electricity usage is much less than that of typical vapor compression systems or units (e.g., less than 0.2 kW/ton peak compared with 1.2 kW/ton typical for conventional compression units).
The regenerator 1340 is another of the significant components to the operation of the system 1300. This unit 1340 takes the weakened desiccant from the DE-IDEC 1320 and applies heat with boiler 1342 (see list of heat sources below) to drive off the moisture contained in the desiccant 1338. The result is a desiccant 1338 that has higher salt concentration and can be re-used by the DE-IDEC 1320 (e.g., in the membrane contained/defined flow channels adjacent to supply inlet air 1325, 1326). A list of heat sources suitable for desiccant regeneration may include: (a) gas or other fossil fuel; (b) solar heat; (c) waste heat from any waste heat stream such as combine heat and power plant; and (d) waste heat from a condenser unit originating from a vapor compression cycle.
The inventors performed a test of a prototype fabricated similar to the cooler shown in
It was recognized that use of the membrane to contain the liquid desiccant and separate it from air flow is desirable in most if not all mass transfer/heat exchanger assemblies. For example, with reference to the indirect evaporative cooler 100 of
However, it was further determined that the second membrane 118 is not needed to practice many aspects of the evaporative coolers described herein. Particularly, an indirect evaporative cooler may be provided in which each stack only includes a single water-permeable membrane (such as membrane 112) while coolant flow is provided on the opposite side of a separation wall (such as wall 114) through other techniques such as by providing a flocking sheet or layer (or wicking element) on the separation wall 114 opposite the side of the wall defining the liquid desiccant flow chamber/channel. The stack may be arranged vertically in such embodiments of the evaporative cooler to make use of gravity to encourage coolant flow from the top to the bottom of the stack in the wicking layer. In other cases, though, the wicking layer or flocking may be provided on a top or bottom side of a separation wall (a horizontal stack arrangement) with capillary action (or other mechanisms) used to obtain a desired coolant flow through the stack.
As with cooler 100 of
Significantly, the wicking layer or flocking 1520 is attached to a side of the separation wall 114 and acts to wick or guide flow of a volume of coolant 126 in the stack 1510. In other words, the second membrane 118 of cooler 100 is removed as it is not needed to define a coolant flow channel/chamber. Instead, the wicking layer 1520 may be thought of as defining a channel or flow path for the coolant 126, which is shown to be counter to the exhaust air stream 128. The air in stream 128 is in contact with the wicking layer 1520 and the coolant 126.
The coolant 126 may be a flow of water or the like, and heat is transferred from the liquid desiccant 124 to the coolant 126 through the separation wall 114. The coolant 126 flowing or being wicked by wicking layer 1520 is cooled as heat and mass (e.g., water or other moisture 132) is transferred to the exhaust air stream 128 directly rather than through a membrane as in cooler 100 of
Capillary action may support flow of coolant 126 in wicking layer 1520 when the stack 1510 is arranged in a horizontal configuration, but some embodiments will position the stack 1510 including the separation wall 114 and attached/contacting wicking layer 1520 to be vertical such that gravity facilitated coolant flow 126 from the top to the bottom of the evaporative cooler 1500. As with the stack 110, the stack 1510 may be provided in multi-stack assemblies/coolers such as the cooler 210 with the stack 1510 being used to provide, or in place of, stack 230 (and/or other stacks 212, 240). In such an arrangement, the flow channel for the exhaust air stream 128 typically would be defined by facing but spaced apart wicking layers 1520 on separation walls 114 (e.g., spaced apart, flocked surfaces of two separation walls).
A variety of flocking materials may be used to implement the wicking layer 1520 on separation wall 114. The wicking layer 1520 acts to spread out or disperse the flowing coolant 126, e.g., to avoid rivulets of flowing coolant, which enhances heat transfer from the wall 114 and also mass/heat transfer to exhaust air stream 128 in the adjacent flow chamber/channel of stack 1510. The flocking material of the wicking layer 1520 also acts to impede gravity to get a slower flow in vertical configurations. The thickness of the layer 1520 may vary but in some cases may be approximately 0.015 inches thick while other useful implementations may use flocking in the range of 0.005 to 0.05 inches in thickness. Exemplary flocking for the wicking layer 1520 include: (a) knitted nylon fabric; (b) polypropylene woven or non-woven fabric; and (c) adhesive-backed flocking fibers (typically polyester or polypropylene), e.g., the layer 1520 may include fibers standing up along (or arranged transverse to) planar surface of wall 114 and may have lengths of 0.01 to 0.05 inches or more. In some embodiments, the wicking layer 1520 may be provided by one or more fabrics coated with a hydrophilic coating. While in other cases, the layer of wicking material 1520 is created with a hydrophilic coating on a surface of the separation wall 114.
While a wide variety of materials may be used in layer 1520, there are a number of wicking or flocking characteristics that may be desirable for operation of the cooler 1500. The wicking surface of layer 1520 provides a method or mechanism to evenly spread either desiccant or water (as shown in
As shown in
Generally, the cooling process or method provided by operation of an evaporative cooler (such as cooler 1500) involves receiving an input or process air stream. This process air stream undergoes dehumidification in a first section or portion of the evaporative cooler (i.e., the desiccant-contained dehumidification section), and this is followed by sensible cooling in a second section (i.e., indirect evaporative cooling section). As shown herein, though, dehumidification and sensible cooling may occur in a single or integral section or portion of the cooler to occur concurrently. The process air is then delivered to a work space or indoor area for use in cooling a space while the purge/exhaust air is used to remove heat from the coolant and is output/discharged from the cooler.
In some cases, it may be desirable for an indirect evaporative cooler to be provided with a humidification section. This would allow the above cooling method/process to be modified to include a step after sensible cooling in which the process air is humidified adiabatically to further drop the temperature of the air prior to output from the indirect evaporative cooler into a work space or building space. In some embodiments, humidification is provided by having the sensibly cooled air flowing in channels/chambers with one or both sidewalls defined by vapor permeable membranes. Particularly, the indirect section (indirect evaporative cooler) may be followed by a section that provides direct evaporative cooling, which also humidifies. This acts to further reduce the temperature of the outlet stream to provide higher sensible cooling, but such higher cooling comes at the expense of providing less latent cooling (dehumidification). Such additional cooling is shown with line 2025 in the psychrometric chart 2200 of
In other cases, though, a flocked surface may be used in the humidification section. For example,
At this point, it may be useful to describe a two-stage indirect evaporative cooler 1800 with reference to
The cooler 1800 is configured in two distinct stages or assemblies 1810 and 1850 providing a first-stage dehumidifier and a second-stage indirect evaporative cooler. As shown, the dehumidifier 1810 is made up of a number of stacks 1814 (as discussed above and shown in
The first-stage dehumidifier 1810 is a cross-flow heat and mass exchanger between two air streams 1820/1822 and 1826/1828. Desiccant 1816 and water 1818 flow vertically and are gravity driven. The liquid desiccant 1816 is contained by a polypropylene microporous membrane or other vapor permeable membrane (e.g., a Z-series from Celgard LLC or another distributor/manufacturer). In some implementations of cooler 1800, nozzles may be used to spray a high water flow rate (water 1818) that creates a two-phase flow of water and outdoor air in air stream 1826/1828 (air states “3” to “4”). The dehumidifier 1810 may be designed to provide a low water flow rate that is spread by wicked surfaces in contact with the air stream 1826/1828. In some embodiments, a waterside membrane may be used for controlling biological growth because it creates a barrier that blocks organisms from implanting or growing onto wet surfaces.
The second-stage or indirect evaporative cooler 1850 is formed with an assembly or number of stacks 1854 (as shown in
Top views of exemplary implementations of the stacks 1814 and 1854 of the stages 1810, 1850 are shown in
The second or paired air flow channel of first stage stack 1814 is defined by the other/opposite side of the separation wall 1966 upon which a wicking layer 1970 is provided. The wicking layer 1970 wicks coolant/water that is directly in contact with flowing exhaust air to allow heat to be released from liquid desiccant 1816 and air stream 1820, 1821. The second air flow channel is further defined by another separation wall 1974 (which may be a top wall of a next stack), and another wicking layer 1972 of flocking or wicking material is provided on the surface/side of the separation wall 1974 facing the wicking layer 1970. Coolant such as water is wicked or gravity fed through the wicking layer 1972 as the exhaust air flows through the stack 1814.
With regard to the second stage stack 1854 of the indirect evaporative cooler 1850, a flow channel is provided for air stream 1822. This channel is provided by a side/surface of a separation wall 1980 and a spaced apart second separation wall 1982. A second flow channel is provided in stack 1854 into which a portion 1862 of the supply air 1860 is returned into the stack 1854 to remove heat and be exhausted at 1866. A second air flow channel/chamber is defined by the opposite side of separation wall 1982, which is covered with flocking/wicking material to provide a wicking layer 1984. Water or coolant is gravity fed through this layer 1984 during use of the stack 1854 in a cooler assembly. The second flow channel for air stream 1862 is further defined by a second wicking layer 1988 provided on a facing side or surface of an additional separation wall 1990. As discussed throughout, numerous first and second stage stacks 1814, 1854 would be assembled or stacked upon each other to form a two-stage cooler 1800.
The cooler 1800 may be modified by adding a direct evaporative section or stage as shown in
As shown, the supply air 1860 flows in channels defined by separation walls 1991, 1993, and 1995 with wicking material or flocked surfaces 1992, 1994 facing into each channel. In this way, water may be caused to flow next to the air 1860 to provide humidification to the output supply air 1997 (cooled and humidified to air state “2.5” as shown in
The cooler 1800 (
The unbacked vapor permeable membrane was welded to the flutes/extrusions. A liquid manifold distributed desiccant to the space between the membrane and the flutes/extrusions. Air gaps on airstream 1820 to 1822 (air state “1” to air state “1.5”) were maintained by strips of spacers with the extruded flutes oriented parallel to the airflow. The design also incorporated spacers that mixed the airstream to enhance heat and mass transfer. Flutes were used to form the channels for airstream 1822 to 1860 (air state “1.5” to air state “2”). A nylon wick was applied to the outer walls of the separation wall/plastic sheets. These subassemblies were then stacked with spacers between each to form the channels for air flow 1862 to 1866 (air state “2” to air state “5”). A low flow of water 1858 was distributed into the second-stage channels from the top. The nylon wick had sufficient water upkeep to allow this flow rate to be marginally above the water evaporation rate. Thus, a solenoid valve controlling domestic cold water may be used to distribute water. Purge water was collected at the bottom of the plenum of air stream 1866, at which point it was directed to a drain.
Wicked surfaces provide a number of advantages for the indirect evaporative coolers described herein. The wicking ensures that the walls are fully wetted and that there is no lost evaporation area. The water feed rate can be held to a factor of 1.25 to 2 times that of the evaporation rate. This technique allows for “once-through” water use. The water that drains off the heat and mass exchanger is concentrated with minerals and can then be drained away. A sump and pumping system are not required, which improves energy performance and eliminates sump-borne biological growth. A simple controller can periodically use fresh (low concentration) water to rinse the heat and mass exchanger (such as cooler 1800) and clear any built-up minerals. Air streams 1822 to 1860 and 1862 to 1866 are in counterflow in the second-stage 1850. A sensitivity analysis showed that the cooling effectiveness could be reduced by as much as 20 percent if proper counterflow was not achieved. Air stream 1822 to 1860 flowed straight, through extruded flutes, but airstream 1862 to 1866 used a 90-degree turn before exiting the second stage 1850. Computational fluid dynamics software may be used design an air restrictor to ensure proper counterflow of air stream 1862 to 1866.
Likewise, the stacks including the membranes and wicking material may be formed in a variety of ways to implement a mass and heat exchanger of the present description (such as cooler 1800). The construction of one prototype revolved around laminated layers of polyethylene terephthalate (PET) plastic that were adhered with layers of acrylic pressure-sensitive adhesive. Although this assembly method may not easily be scaled to high-volume manufacturing, the achievable geometries are nearly ideal and, therefore, appropriate for prototypes. This enabled the creation of a prototype with parallel plate geometry that included airside turbulators to enhance heat and mass transfer on airstreams. Another prototype was built using layers of extruded polypropylene (PP). It is likely that formed aluminum sheets may be used to create a parallel plate structure to implement a cooler described herein. For example, the aluminum sheets may be corrugated to form a wavy flow channel, which would increase heat transfer by the waviness of the channel (which promotes mixing of the air stream and impingement of the air into the separator plate wall) and also act to reinforce the structure by giving the sheets/plates increased rigidity. Such an arrangement may work better in the second stage where there is no desiccant (since the desiccant may corrode the aluminum).
For the first-stage 1810, the laminated layers enabled the use of wicked surfaces in the air stream 1826 to 1828 channels. For the spacer, an off-the-shelf expanded aluminum grating was used, and the spacer was used in channels for air stream 1820 to 1822 and air stream 1826 to 1828. The design of the stacks such as stack 1814 used expanded polypropylene hydrophobic membrane backed with a nonwoven polypropylene fabric to add strength. The backing reduces vapor diffusion through the membrane but increases tear resistance. The backing was oriented to the airside gap, where tears can originate from abrasion by foreign objects or the aluminum spacer. A desiccant manifold was developed that used laminated layers of plastic and adhesive to effectively and evenly distribute liquid desiccant behind the membrane. The second stage 1850 used laminated construction but, with minimal spacers to create laminar flow, used parallel plate air channels. The design used strips as airflow spacers and wicked surfaces on the wet side of the heat and mass exchanger 1800.
The above description concentrated or stressed designs of heat/mass transfer assemblies for use in providing unique indirect evaporative coolers. Those skilled in the art will recognize that the coolers described can readily be included in more complete HVAC systems for residential and commercial use. Such HVAC systems would include plumbing and components to circulate liquid desiccant to and from the cooler at desirable and controllable flow rates. These systems would also include a regenerator for the desiccant (e.g., one that heats the liquid desiccant to remove absorbed water such as heat provided by solar panels, electrical heaters, or the like). The regenerator also may include a sump and lines for recovering potable water from the desiccant, and storage would be provided for the desiccant prior to it being pumped or fed to the cooler. Portions of the system that come into contact with the desiccant typically would be fabricated of corrosion resistant materials such as certain metals or, more typically, plastics. The HVAC system would also include ducting and other components such as fans or blowers for moving the return air from the building through the cooler and back to the cooled spaces, for moving make up air through the cooler and into the cooled spaces, and for discharging any purge or exhaust air. A coolant supply system with piping and pumps/valving (as necessary) would also provide coolant such as potable water to the cooler stacks (e.g., channels between membranes and separation walls).
The embodiments shown typically discussed ongoing use of the liquid desiccant to dehumidify the supply or process air. However, in many operating conditions, the cooler may be operated without desiccant flow, and these operating conditions may be considered “free evaporative cooling” conditions (or zones on a psychrometric chart). “Free cooling” is exemplified by cooling efficiency so high that the cost of energy to run the system is of no consequence. For example, cooling without drying/dehumidifying may be performed by coolers described herein when the humidity ratio is below about 80 (and the dry bulb temperatures are above 60° F.) while cooling and drying may be required above this humidity ratio at which point the cooler can be operated with flowing liquid desiccant. Such “free” cooling is practical for relatively large numbers of days in less humid areas of the world (such as the southwest portion of the United States).
Embodiments of an indirect evaporative cooler according to the above description and attached figures can be provided as a single unit that provides an integral heat and a mass transfer device utilizing a number of separation walls. The transfer device or assembly uses membrane containment and air flows do not come in direct contact with desiccant or water (coolant). The coolers use evaporative cooling to drive heat and mass exchange, with heat being transferred through the separation walls between the liquid desiccant and the coolant. The heat exchange is between two counter and/or cross flowing air streams. The mass exchange, such as during dehumidification, is generally the transfer of water vapor from the inlet supply air or process air through a water molecule-permeable membrane to a liquid state (e.g., to absorption by the liquid desiccant). The evaporative section of the coolers drives heat through the separation wall and expels that heat by evaporation from the coolant/water to an air stream.
It should also be kept in mind that the first and second stages (dehumidifier and indirect evaporative cooler) may be provided in a single system or machine and be packaged to be within a single housing or two or more housings within a single system. In some cases, the first, second, and third (when included) stages are provided in a single system with one, two, or more housings or machines. In other cases, though, the first and second stages are not packaged into the same machine but are configured to cool the same building space. The third stage if present may be provided with the second stage or in a separate machine/housing. Particularly, the dehumidifier can be packaged into a machine and take a mixture of indoor and outdoor air, dehumidify that air, then deliver it to the space. A second machine may pull air from the space (and maybe some outdoor air) and send it through the indirect evaporative cooler as described, then deliver colder supply air to the space. The second machine could exhaust some air so the dehumidifier machine would supply some make-up air from the outside. Essentially, the same process takes place as shown for single systems and/or machines but in two separate machines, one for each heat and mass exchanger.
In some embodiments, a method has been described for conditioning a supply air stream. The method includes the step of dehumidifying the supply air stream to provide a dehumidified air stream. Such dehumidifying includes directing the supply air stream through a first channel defined by a surface of a vapor permeable membrane containing liquid desiccant. The method further includes transferring heat from the liquid desiccant to a layer of coolant flowing in a second channel adjacent to the liquid desiccant.
In some implementations of the method, the layer of coolant comprises coolant flowing in a layer of wicking material positioned for heat transfer from the liquid desiccant. Then, the method may further include evaporating a portion of the coolant flowing in the layer of wicking material into an air stream flowing adjacent to the layer of wicking material. It may be useful in the method for the coolant in the layer to be flowing at a flow rate of less than about 50 inches per minute. In some cases, a temperature of the supply air stream is increased during the dehumidifying less than about 5° F. In the same or other cases, the dewpoint temperature of the supply air stream is decreased during the dehumidifying to less than about 55° F.
In some embodiments of the indirect evaporative cooler or supply air conditioning apparatus, a dehumidifier is included in a first stage, and the dehumidifier performs cooling of an air stream input to an inlet of the dehumidifier by absorption of water vapor from the input air stream. Such cooling may be performed using a membrane-contained liquid desiccant that is liquid cooled. The phrase “liquid cooled” may take a number of meanings including, but not limited to, flowing a liquid coolant such as water adjacent the channel containing the liquid desiccant, and the liquid coolant flows such that the temperature of the liquid is raised as it passes through the dehumidifier to carry away heat from the liquid desiccant.
The apparatus may also include a second stage comprising an indirect evaporative cooler in fluid communication with an outlet of the first stage to receive a cooled portion of the input air stream. The indirect evaporative cooler may be operable to sensibly cool the received and cooled portion of the input air stream to a temperature (or to be within a temperature range) less than the wet bulb temperature and greater than the dew point temperature of the input air stream. During operation of the apparatus, a first portion of the sensibly cooled air stream is supplied to a cooled space and a second portion of the sensibly cooled air stream is directed to a wet side of the indirect evaporative cooler and receives heat from the received and cooled portion of the input air stream.
In some implementations of such an apparatus, the dehumidifier performs the cooling using a membrane-contained liquid desiccant cooled by an indirect evaporative channel that includes a wicking layer containing a flow of coolant. In other implementations, the dehumidifier performs the cooling using a membrane-contained liquid desiccant that is liquid cooled. The apparatus may be operated such that the second portion comprises 10 to 40 percent of the received and cooled portion of the input air. It may be useful for a flow channel for the second portion of the sensibly cooled air stream in the indirect evaporative cooler to be defined in part by a surface of a separation wall. Then, a layer of wicking material may be provided on the surface acting to wick a stream of liquid coolant adjacent the flow channel.
In some settings, the apparatus includes a direct evaporative stage between the second stage and the cooled space. Then, during operations, the direct evaporative stage receives the first portion of the sensibly cooled air stream and provides additional cooling via direct evaporative cooling prior to supplying the first portion of the sensibly cooled air stream to the cooled space. Further, the direct evaporative stage may be adapted to contain flow of water with a vapor permeable membrane or within a layer of wicking material (e.g., the layer of wicking material is provided as a surface with a hydrophilic coating).
While a number of exemplary aspects and embodiments have been discussed above, those of skill in the art will recognize certain modifications, permutations, additions, and sub-combinations thereof. It is therefore intended that the following appended claims and claims hereafter introduced are interpreted to include modifications, permutations, additions, and sub-combinations to the exemplary aspects and embodiments discussed above as are within their true spirit and scope.
This application claims the benefit of U.S. Provisional Application No. 61/662,146, filed Jun. 20, 2012, which is incorporated herein in its entirety.
The United States Government has rights in this invention under Contract No. DE-AC36-08G028308 between the United States Department of Energy and the Alliance for Sustainable Energy, LLC, the Manager and Operator of the National Renewable Energy Laboratory.
Number | Date | Country | |
---|---|---|---|
61662146 | Jun 2012 | US |