Furnaces for air handling systems are known. Some furnaces are power vented using tubular heat exchangers. Other types of heat exchangers, such as drum/tube and clamshell heat exchangers are also used in some furnaces, but they are in some cases impractical for use in some air handling system configurations for a variety of reasons. In operation, the air to be heated is passed over the outside of the heat exchanger tubes, wherein each tube of the heat exchanger has a burner associated with it. The burners are arranged in a row (either horizontally or vertically) so that a flame on one burner will travel to the remaining burners. An example burner is an ‘inshot’ type burner manufactured by Beckett Gas (see U.S. Pat. No. 5,186,620), and is designed with flame passageways to assist in the flame travel between burners. The burner on one end of the burner row is ignited using an ignition source, for example a sparking or hot surface ignition source, and the flame travels to the remaining burners. A flame sensor at the other end of the burner row verifies that the flame is established along the entire row. A combustion fan draws the air for combustion through the heat exchanger and discharges it outside of the unit.
A flammable gas (typically natural gas or LP gas) is supplied to each burner by a manifold with an orifice feeding gas to each burner. The gas is supplied to the manifold by gas control valve(s) which are electronically controlled. One common configuration is a modulating control with a 4:1 turndown. The turndown is defined as the ratio of the maximum firing rate to the minimum firing rate of the burner and/or furnace. Higher turndown is desirable to achieve better temperature control on mild days. The modulation is achieved using a modulating valve which controls the gas flow to the burners in a variable manner. A shutoff valve (labeled combo valve in the drawings above) is used to shut off gas flow to the furnace when heat is not required. The 4:1 furnace uses a two speed combustion fan to maintain a proper fuel to air ratio at lower firing rates. Other common options for gas control are one stage (on/off) and two stage (high/low/off) control.
Many manufacturers are also using this type of furnace and furnace control in the residential HVAC industry. The level of modulation (turndown) varies from one manufacturer to the next. 2:1 modulation has been around for a long time while 4:1 modulation has been common in the industry for about 15 years. In recent years, manufacturers have been starting to achieve 5:1 modulation more readily and a few have managed 6:1 modulation with the inshot burner/tubular heat exchanger design. However, further improvements in attaining even higher levels of modulation are desired.
A heating system is disclosed that achieves the relatively high turndown capabilities of a drum and tube heater in an application that utilizes the construction of a tubular type heat exchanger. In one example, the heating system is a furnace having a 16:1 turndown with seamless turndown operation. The furnace can include a first burner section with a first plurality of burner tubes and a second burner section with a second plurality of burner tubes. In one example, the second plurality of burner includes three times the number of tubes in the first plurality of burner tubes. As configured, a first plurality of burners is connected to each of the first plurality of burner tubes and a second plurality of burners is connected to each of the second plurality of burner tubes. The system can also include a gas manifold including a first inlet in fluid communication with a first plurality of outlets and can include a second inlet in fluid communication with a second plurality of outlets. In one aspect, the first plurality of burners is operably connected to the first plurality of outlets and the second plurality of burners is operably connected to the second plurality of outlets, wherein a first modulating valve is operably connected to the gas manifold first inlet and a second modulating valve is operably connected to the gas manifold second inlet.
Non-limiting and non-exhaustive embodiments are described with reference to the following figures, which are not necessarily drawn to scale, wherein like reference numerals refer to like parts throughout the various views unless otherwise specified.
Various embodiments will be described in detail with reference to the drawings, wherein like reference numerals represent like parts and assemblies throughout the several views. Reference to various embodiments does not limit the scope of the claims attached hereto. Additionally, any examples set forth in this specification are not intended to be limiting and merely set forth some of the many possible embodiments for the appended claims.
Referring to
Referring to
A burner 104 is disposed at the first end 102a of each burner tube 102 and injects a flame into each tube 102. This operation causes the tubes 102 to be heated which in turn causes the airflow stream passing across the tubes 102 within the air handling unit 10 to be heated. A suitable burner 104 for use in the disclosed heating system 100 is referred to as an “inshot” type burner and is disclosed in U.S. Pat. No. 5,186,620 issued on Feb. 16, 1993 and entitled GAS BURNER NOZZLE, the entirety of which is incorporated in its entirety by reference herein. With burners of this design, primary air is mixed with the gas as the gas passes through a Venturi portion of the burner. Secondary air is then introduced in a space where the flame is exposed between the end of the burner 104 and the inlet of the heat exchanger tube 102
The second ends 102b of the burner tubes are connected to a common collector box 106 such that the combustion gases from the burners 104 can be captured and appropriately exhausted to the atmosphere. A combustion fan 108 is placed in fluid communication with the collector box 106 to actively draw the gases through the tubes 102. A gas flue or stack (not shown) can be attached to the combustion fan 108 to ensure the combustion gases are appropriately exhausted. The combustion fan 108 can be a two-speed fan or a fan with fully modulating speed, for example via a variable frequency drive.
As shown, each of the burners 104 is connected to a gas manifold 110 which is in turn connected to a gas source 111, such as a natural gas pipe routed within a facility served by the air handling unit 10. As configured, the gas manifold 110 includes a main tube 112 which is separated into a first section 112a and a second section 112b by a partition member 114. The ends of the main tube 112 are also enclosed by end pieces 116, 118. Although a single tube 112 is shown as being used with the partition member 11, the first and second sections 112a, 112b could also formed by two non-connected tubes.
As most easily seen at
Referring to
Electronic control system 50 is also shown as having a number of inputs and outputs that may be used for implementing the operation of the heating system 100. Example outputs are ignition/spark outputs (SPARK) to each of the burner sections, on/off/speed control (low/high) to the motor 109 (CM) for the combustion fan 108, open/closed operation of the shutoff valves 122 (MV), 132 (MV2), and modulation/position control of the valves 124, 134. Example inputs are downstream airflow (i.e. heated air) temperature, upstream air temperature, collector box pressure/flow, and flame sensors. The electronic control system 50 may also include a number of maps or algorithms to correlate the inputs and outputs of the control system 50.
In one configuration, the control system 50 activates the combustion fan motor upon a call for heat. A fan pressure switch PS2 provides a verification input of actual airflow to the control system 50. Once this verification is made, the valves 122, 132 are then allowed to open and operate. If the verification is not made, a first controller 50a responsible for the operation of the valves 122, 124 ensures that the valve 122 is automatically closed (e.g. power is cut for a normally closed valve). The controller 50a is also connected to a second controller 50b responsible for the operation of the valves 132, 134. This connection is made in such a way (e.g. with a relay) that if the pressure switch verification is not made, the first controller 50a cuts off power to the second controller 50b, thus ensuring that valve 132 cannot open.
In one aspect, each of the burners 104 associated with the modulating valves 124, 134 has a turndown of 4:1 or ¼, meaning the valve can modulate between a maximum rated firing rate down to one quarter of the maximum rate. Accordingly, shutting off the large section (e.g. valve 132) and running only the small section (e.g. valve 122), a turndown of as high as 16:1 can be achieved. This high turndown operation can be illustrated by an example installation using a 400,000 BTU/h furnace. The small section of the manifold is capable of 100,000 BTU/h while the large section is capable of 300,000 BTU/h. When the small section is turned down to minimum and the large section is off, a minimum firing rate of 25,000 BTU/h can be achieved which is 1/16th of 400,000 BTU/h. When only the small section is operating, the combustion fan speed will be controlled as necessary to ensure proper combustion. When the heat requirement reaches the level where the small section is operating at 100%, the furnace will be operating at 100,000 BTU/h which is 25% of the total heating output of the system. If additional heat is needed, the large section will be turned on and both sections will be modulated down to 25%. Since the whole 400,000 BTU/h furnace is now operating at 25%, the furnace is still able to maintain 100,000 BTU/h. Thus, the transition between operating the small section alone to operating both sections is “seamless” as no jump in output occurs. The manifold sections can then modulate up from there to whatever firing rate is needed to meet the heat demand. The combustion fan speed will again be controlled as necessary to maintain proper air for combustion. As noted previously, seamless modulation is achieved when the system heating output can be fully modulated between the minimum system heating output and the maximum system heating output. In this example, the minimum system heating output is equal to the heating output generated by the burners 104 associated with the first section 112a are at their minimum firing rate, and the maximum system heating output is equal to the sum of the heating output generated by all of the burners 104 of both sections 112a, 112b when at their maximum firing rate. This operation is illustrated in the method 1000 flow chart presented at
Referring to
Once the startup sequence is completed, the burners 104 associated with the first section 112a (i.e. the small section) are ignited at step 1010. At 1012a, 1012b, it is respectively determined whether more or less heat is required, for example, by comparing a sensed temperature value to a temperature setpoint. Where more or less heat is required, the controller modulates the valve 124 up or down at 1014a, 1014b to satisfy the load. With reference to
If the burners 104 of the first section 112a reach a minimum heat output at 1016b (i.e. valve 124 is in a minimum position) and less heat is required, the burner shuts down at 1018 and the system returns to 1002. If the burners 104 of the first section 112a reach a maximum heat output at 1016a (i.e. valve 124 is in a maximum position) and further heat is still required, the large manifold is activated at 1020. Activation of the large manifold 1020 can include opening the valve 132, modulating valve 134 to a minimum position, and igniting the burners 104 associated with the second section 112b.
If the burners 104 of the first and second sections 112a, 112b reach a minimum heat output at 1026b (i.e. valves 124, 134 are both in the minimum position) and less heat is required, valve 132 closes to shut down the burners 104 associated with the second section 112b, and the system returns to 1010. If the burners 104 of the first and second sections 112a, 112b reach a maximum heat output at 1026a (i.e. valves 124, 134 are in a maximum position) and further heat is still required, the system determines whether additional staged burners (i.e. stages typically provided with non-modulating, two-position burner control valves) are present at 1030a, 1030b. Where no additional staged burners are present, the valves 124, 134 remain in their maximum positions such that the burners 104 of the first and second sections 112a, 112b remain at their maximum heating output at 1032. Where additional staged burners are present, the staged burners are turned on (e.g. valve opened, burners ignited, etc.) at 1034 and the system returns to steps 1022a, 1022b where the valves 124, 134 can return to modulating to satisfy the heating load. As the heating load decreases, the staged burner(s) can be deactivated sequentially.
Where the valves 124, 134 are modulated together at 1020, the system will beneficially provide even heating across all of the tubes 102 at certain operating output ranges (e.g. total heat output required is greater than 25% of maximum) to prevent stratification. During such times, the furnace or heating system will be temporarily operating at an effective turndown equaling the turndown of the individual valves, which in this example is a 4:1 turndown.
As noted above, additional staged or modulating burners/furnaces can be provided and can be shut off independently of the modulating furnace valves 124, 134. In this configuration, the overall turndown of the unit will be increased (e.g. one additional furnace of the same capacity=32:1 turndown, two additional furnaces of similar capacity=48:1 turndown, etc.). The additional furnace(s) can be placed in either a parallel or series configuration.
Achieving a 16:1 modulation with a single tubular-type furnace will provide industry leading turndown. This improvement over the prior art will allow air handling and makeup air units to achieve more precise control of supply air temperature than what has been previously possible. This becomes especially important on mild days where only a small amount of heat is needed. On furnaces with less advanced turndown, mild days present a challenge because the minimum firing rate of the furnace will still provide more heat than is needed to condition the air. This results in the furnace staging on and off in an attempt to add some heat to the air without overheating it. This staging creates undesirable temperature swings that negatively affect occupant comfort. The 16:1 turndown will allow our furnace to modulate down to the precise amount of heat needed to properly condition the air.
Another option that could be used to achieve 16:1 modulation is to use a single modulation valve near the inlet to the furnace. The modulated gas can then be routed to various sections of the manifold with a simple on/off shutoff valve used to control the flow of gas to each manifold section. However, a disadvantage with this setup is the inability to maintain proper firing rate settings as manifold sections are turned on and off Minimum and maximum firing rates on inshot burner/tubular heat exchanger furnaces are typically set by adjusting the gas control valves. To achieve proper turndown and combustion, it is important that each manifold section operate at the proper minimum and maximum firing rates they are designed for. If a single modulating valve is used and the gas control valves are set when the entire furnace is operating, the high and low fire set points will change when section(s) of the manifold are turned off. This means that the furnace will not achieve the turndown it is designed for and portions of the furnace will be overfired while others are underfired. This will result in poor combustion performance and reduced furnace life. Accordingly, the disclosed heating system or furnace 100 will eliminate all these issues by allowing the firing rates of each manifold section to be adjusted independently without affecting the adjustment of the other manifold sections.
The various embodiments described above are provided by way of illustration only and should not be construed to limit the claims attached hereto. Those skilled in the art will readily recognize various modifications and changes that may be made without following the example embodiments and applications illustrated and described herein, and without departing from the true spirit and scope of the disclosure.
This application claims priority to U.S. Provisional Patent Application No. 62/371,419 (entitled INDIRECT GAS FURNACE), filed on Aug. 5, 2016, the entirety of which is incorporated herein.
Number | Date | Country | |
---|---|---|---|
62371419 | Aug 2016 | US |