BRIEF DESCRIPTION OF THE SEVERAL VIEWS OF THE DRAWINGS
The objects of the invention are achieved as set forth in the illustrative embodiments shown in the drawings which form a part of the specification.
FIG. 1 is a simplified representation of an electrical distribution system illustrating the installation of circuit breakers, fuses, and other protective devices in the system which react to occurrence of a fault;
FIG. 2 is a chart illustrating the differences between peak values of a load current contrasted with peak values of a fault current, and the residue of the two;
FIGS. 3
a and 3b display a Phase (φ) A to ground load condition signature on the LV (low voltage) side of a service transformer for both a light load (FIG. 3a) and a heavy load (FIG. 3b) condition;
FIG. 4 is a display similar to FIG. 3 but illustrating the phase to ground load condition signature on the MV side of the transformer;
FIG. 5 is a display of short circuit current from a feeder line fault past a recloser for the line with a 15 cycle closing time;
FIG. 6 is a display similar to FIG. 5, but for a 20 cycle reclosing time; and,
FIGS. 7
a and 7b display sympathetic feeder currents for two different power factors on one of the feeders, P.F.=0.65 (FIG. 7a) and P.F.=0.99 (FIG. 7b).