Not applicable
Not applicable
The present subject matter relates to electrical circuit protection devices, and more particularly to circuit breaker status indication devices.
The status of a circuit breaker, (e.g. on or off), cannot always be easily determined from the position of an actuator, handle or button. This is particularly true under low ambient light levels, or when the observer is some distance away from the breaker, or when the observer is inexperienced at using circuit breakers. It is important to know the status of a given circuit breaker to help determine whether an electrical overload has occurred in a given circuit or whether the circuit breaker is in the open (off) or closed (on) position.
Lighted circuit breaker status indication devices may be built into the physical circuit breaker during manufacture. However, these devices require the circuit breaker to be purchased either with or without the lighted option.
In other examples, lighted circuit breaker status indication devices may attach to the circuit breaker as an add-on feature, such that the device is not part of the physical circuit breaker. However, these add-on devices typically require connection to the same circuit breaker terminals as those used to connect the circuit in the application to be protected. Positioning such devices in the areas of the circuit breaker terminals can interfere with normal terminal connection. Attaching multiple wire terminal lugs on circuit breaker terminals creates inherent installation, conductivity, reliability and positioning issues, making it more difficult to properly connect the normal “line” and “load” or “auxiliary” and “battery” wires of the application circuit.
Lighted circuit breaker status indication devices which may attach to the circuit breaker as an add-on feature, but do not require physical connection to the main circuit breaker terminal areas, require either additional connections to a second circuit (to power the light) or stored energy devices, like batteries or capacitors, to power the lighted indicator. The additional connections and secondary circuits can be expensive, cumbersome, or even unavailable in many applications. Stored energy devices are often also expensive. Additionally, stored energy devices are generally useful only as long as they maintain enough energy to power the light.
Accordingly, there remains a need for a lighted indicator system which will better show to a remote observer the on/off state of a circuit breaker, and which can be added onto a circuit breaker which may have already been installed in a field application, and which will not connect to the existing circuit breaker terminations nor require stored energy devices.
According to one aspect, a lighted circuit breaker status indication device includes a light guide made of one of transparent and translucent material, at least one light source configured to illuminate the light guide, and at least one electrical contact electrically coupling the light source to a circuit breaker. The lighted circuit breaker status indication device further includes a status circuit path coupled to the circuit breaker. The status circuit path is configured to provide power to the light source when the circuit breaker is both energized and open, but not to provide power to the light source when the circuit breaker is one of not energized and closed.
According to another aspect, a system for providing visual indication of an on/off status of a circuit breaker includes a light guide and a status circuit path configured to be coupled to a protected circuit path of the circuit breaker. The status circuit path is further configured to provide power to a light source when the protected circuit path is both energized and open, but not to provide power to the light source when the protected circuit path is one of not energized and closed. Additionally, when power is provided to the light source, the light source illuminates the light guide.
A lighted circuit breaker status indication device 20 is provided. The lighted circuit breaker status indication device 20 is configured to be attached in retrofit fashion to an existing circuit breaker 22. The lighted circuit breaker status indication device 20 may be powered by an existing circuit to be protected while not interfering with the circuit breaker terminations 68a, 68b (shown in
Referring now to
Referring now to
As seen in
As installed on circuit breaker 22, the status circuit path 54 of the lighted circuit breaker status indication device 20 is from one electrical contact mating point 46a through spring 38a, the traces 36, the light source(s) 34, the resistor 40, and back through a spring 38b to the other electrical contact mating point 46b. The resistor 40 may vary in ohmic value depending on the application of the circuit breaker. In one example embodiment, the ohmic value of the resistor 40 is 330 ohms. This status circuit path 54 of the lighted circuit breaker indication device 20 constitutes a parallel electrical circuit path to the (internal) protected circuit path 56 of the circuit breaker 22 and the voltage drop between points 46a and 46b within the protected circuit path 56 provides the power to illuminate the light source(s) 34 when appropriate voltage is applied to the circuit path 56 and the circuit breaker 22 is in the open (off) position.
In another example embodiment shown in
In this example embodiment, with the circuit breaker 22 in the closed (on) position and installed in an application with appropriate voltage applied to the circuit path 56 being protected, the voltage drop across the circuit breaker 22 will be insufficient to allow enough current to flow through the status circuit path 54 to illuminate the light source(s) 34 of the status indication device 20. If the circuit breaker 22 switches to the open (off) position, either due to an electrical overload, being manually switched, or through some other means, with appropriate voltage still applied to the circuit path 56 of the circuit breaker 22, the voltage drop across the circuit breaker 22 will allow sufficient current through the status circuit path 54 of the lighted circuit breaker status indication device 20 to illuminate the light source(s) 34. The illumination from the light source(s) 34 is transmitted through and illuminates the light guide 24 (including upright legs 26 of light guide 24) thereby assisting an observer in determining whether an electrical overload has occurred in a given circuit to be protected and that the circuit breaker 22 is in the open (off) position. When the light source(s) 34 illuminate the light guide 24, the illumination of the light guide 24 signifies to an observer that the circuit breaker is both energized and open (off). However, the absence of illumination may signify to an observer that the circuit breaker 22 is not energized, the circuit breaker is closed (on) and energized, or that the circuit breaker is open (off) but not energized.
In an example embodiment, when the light source(s) 34 are powered by the status circuit path 54 the entire body of the light guide 24 may be visibly illuminated, including the legs 26 and the top 58 and bottom 60 surfaces of the light guide 24. The bottom surface 60 of the light guide is disposed between the legs 26. Alternatively, the light guide 24 may be configured to provide a number of illumination patterns. In another embodiment, only the top surface 58 of the light guide 24 may be visibly illuminated. In still another example embodiment, selected surfaces of the light guide 24 and legs 26 may be visibly illuminated.
The upright legs 26 of light guide 24 are positioned so as to be close to or touching the sides 52a, 52b of the circuit breaker 22 when installed, as seen in
In an alternative embodiment shown in
The status indication device 20 as shown in
The lighted circuit breaker status indication device 20 provides for the ability to easily determine the on or off status of a circuit breaker 22, regardless of ambient light levels, viewing angle, or visibility of an actuator, handle or button. In addition, the status indication device 20 is able to be installed as a retrofit device onto an existing circuit breaker 22 already in use in an application. This may provide for flexibility in both purchase and use of a circuit breaker 22, as the determination of whether lighted status indication is necessary can be made at a time after the initial purchase or installation of a circuit breaker 22. Use of existing circuit voltage to power the lighted circuit breaker status indication device 20 negates many reliability issues inherent in stored energy devices.
The status indication device 20 provided herein allows for automatic connection to a circuit breaker 22 by use of springs 38a, 38b during installation at locations other than the main circuit breaker 22 terminals. Installation of the status indication device 20 away from the circuit breaker 22 terminals may reduce hazard, reliability, or interference issues with the main circuit connections. Since there is only one mounting configuration that allows mating of the springs 38a, 38b of the status indication device 20 to the circuit breaker 22, this assures the status indication device 20 will contact the correct electrical contact mating points 46a and 46b of the circuit breaker 22.
As seen, a lighted circuit breaker status indication device 20 is provided. The status indication device 20 is configured to be attached to an existing circuit breaker 22 and powered by an existing circuit path 56 of the circuit breaker 22. The status indication device 20 has a light guide 24 transmitting light along the sides 52a, 52b of the circuit breaker 22 from light source(s) 34 in the status circuit path 54 parallel with the circuit breaker 22. The status indication device 20 is configured to make use of the empty space between the circuit breaker 22 and a mounting panel surface 70. The status indication device 20, in this example embodiment, makes electrical contact at the bottom 42 of the circuit breaker 22 to avoid interference with existing circuit breaker 22 terminals. The light source(s) 34, providing illumination of light guide 24, may be positioned underneath circuit breaker 22 as an indicator of the on/off status of the circuit breaker. Illuminated light is made visible from the front of the circuit breaker 22 by the front surface 58 of light guide 24. The light guide 24 further has upright legs 26 that extend around the circuit breaker 22 and abut sides 52a, 52b of the circuit breaker 22.
The light source(s) 34 are coupled with electrical contact mating points 46a, 46b on the underside of the circuit breaker terminals 68a, 68b via springs 38a, 38b and traces 36 to electrical contact points 62a, 62b of the status circuit path 54 that provides power to said light source(s) 34. The lighted circuit breaker status indication device 20 is configured to be positioned under a circuit breaker 22 during installation, such that it may be utilized as an aftermarket type of add-on device. In this example embodiment, light source(s) 34 may be illuminated when the circuit breaker 22 is open (i.e. tripped position, not conducting current). The light source(s) 34 are not illuminated when the circuit breaker is closed (i.e. latched position, and conducting current). As such, the status indication device 20 allows an observer to easily assess the on/off status of the circuit breaker 22 without the device 20 interfering with existing circuit breaker terminals.
The embodiment(s) detailed above may be combined in full or in part, with any alternative embodiment(s) described.
It is important to know the status of a given circuit breaker to help determine whether an electrical overload has occurred in a given circuit or whether the circuit breaker is in the open (off) or closed (on) position. Accordingly, the status indication device contemplated above may provide a lighted indicator system that will better show to a remote observer the on/off state of a circuit breaker. Further, the status indication device contemplated above may address the need for a device that can be added onto a circuit breaker after the circuit breaker has already been installed in a field application. Further still, the status indication device contemplated above may neither require connection to the existing circuit breaker terminations nor require stored energy devices to provide power to the add-on feature.
The status indication device may provide further advantages such as ease of installation. The non-symmetrical positioning of the springs, which allows the status indication device to make electrical contact with the circuit breaker, contemplated in some embodiments allows for the alignment of the light guide, light guide legs, and electrical connections during installation of the device. The status indication device may be shaped in such a way to provide a customized fit to an existing circuit breaker. Alternatively, the status indication device may be provided with a generic shape that easily fits one or more styles and shapes of circuit breakers.
The use of the terms “a” and “an” and “the” and similar references in the context of describing the disclosure (especially in the context of the following claims) are to be construed to cover both the singular and the plural, unless otherwise indicated herein or clearly contradicted by context. Recitation of ranges of values herein are merely intended to serve as a shorthand method of referring individually to each separate value falling within the range, unless otherwise indicated herein, and each separate value is incorporated into the specification as if it were individually recited herein. All methods described herein can be performed in any suitable order unless otherwise indicated herein or otherwise clearly contradicted by context. The use of any and all examples, or exemplary language (e.g., “such as”) provided herein, is intended merely to better illuminate the disclosure and does not pose a limitation on the scope of the disclosure unless otherwise claimed. No language in the specification should be construed as indicating any non-claimed element as essential to the practice of the disclosure.
Numerous modifications to the present disclosure will be apparent to those skilled in the art in view of the foregoing description. Preferred embodiments of this disclosure are described herein, including the best mode known to the inventors for carrying out the disclosure. It should be understood that the illustrated embodiments are exemplary only, and should not be taken as limiting the scope of the disclosure.
The present application claims the benefit of Lamerdin et al., U.S. provisional patent application Ser. No. 62/056,160, filed on Sep. 26, 2014, and entitled “Lighted Circuit Breaker Status Indication Device”. The entire contents of this application are incorporated herein by reference.
Number | Date | Country | |
---|---|---|---|
62056160 | Sep 2014 | US |