The present request for Invention patent deals with an inedited “ELECTRICAL CIRCUIT QUICK CONNECTION AND DISCONNECTION SYSTEM WITH AUTOMATIC SHORT CIRCUIT OF CURRENT TRANSFORMER SECONDARIES AND SIMILAR DEVICES”; more specifically of a multipole plug and receptacle system with automatic short circuit capacity between poles upon initiating the disconnection between the plug and receptacle, without incurring in the temporary opening of the circuit, for application in current transformer secondary circuits and other applications requiring the same characteristics.
Current transformers, also called CTs, are devices used in electrical installations to convert the magnitude of an alternate electric current, typically stepping down the current present in its primary circuit, which may of the order of tens, hundreds or thousands of amperes (A), to values in the order of 5 A in its secondary circuit. For such, the current transformer is connected in series with a load, so that the current consumed by said load crosses its primary circuit, while in the secondary circuit devices are connected for the functions of load current measurement, load protection against overcurrents, etc.
Constructively speaking, current transformers can be independent equipment or they can be associated with other power equipment, installed on transformer bushings, circuit breakers, etc. In this case, the wiring coming from the current transformer secondaries is directed to a crossover panel located on the equipment body, together with cables coming from other auxiliary devices. All the auxiliary devices' wiring is connected on this panel by means of crossover terminals; these devices include:
Current transformers are equipped with a set of coils between their primary and secondary circuits; this set of coils, while stepping down the value of the electric current, increases the voltage present in the secondary if it is not connected to a low impedance circuit. In fact, when the current transformer secondary is kept open and a current is applied to its primary circuit, the voltage produced between its two secondary terminals can reach values large enough to break the isolation of the circuits connected to the secondary, with a safety risk to operators and possible damage to the equipment. To reduce this risk, the crossover terminals used to connect the current transformer secondaries allow these secondaries to be short-circuited when necessary to disconnect the load associated to them, avoiding the development of elevated voltages.
As already commented, if the current transformer secondaries are maintained open, the high voltages therein developed may produce serious accidents, with the risk of death and damage to the equipment. To attenuate this risk, crossover terminals are used, allowing to short-circuit the current transformer secondaries before disconnecting the load cables connected to said secondaries; this is performed, for example, by screwing a conductive bar on the upper part of the terminals. As can be observed, this maneuver requires extreme care on the part of the operators, since, if the sequence of operations is inverted (disconnection of the cables before installation of the short-circuit) the consequences may be extremely serious. This system possesses, therefore, the following inconveniences:
For increased ease of installation, operation and maintenance, there is a trend to substitute the crossover terminals that exist on the equipment panel for a system based on multipole plugs and receptacles as requested in patent request PI-0503641-0. Despite the advantages presented by this system, in the case of CT secondaries, its use is made impossible due to the increased risk of opening of the secondaries in the case of an accidental disconnection of the receptacles while the equipment is energized. Therefore, it was chosen to use a system based on multipole plugs and receptacles for all the auxiliary circuits, with the exception of the CT secondaries, which continues to use the crossover terminal system, with its inherent disadvantages.
The new invention consists of a multipole plug and receptacle system with automatic short-circuit capacity between poles upon initiating the disconnection between plug and receptacle, without incurring in the temporary opening of the circuit, for application in current transformer secondary circuits and other applications requiring the same characteristics.
The system is equipped with a number N of paired poles, with each pair of poles connected to a CT secondary, therefore allowing the connection of N CT secondaries. Each pair of poles is equipped with a system that, under normal usage conditions of connected plug and receptacle, allows the normal passage of current from the CT secondary to the load connected to the same, without short-circuiting the CT secondary.
Upon initiating the mechanical disconnection between the plug and the receptacle, with the electric connection between plug and receptacle still present, the CT secondary is automatically short-circuited before the circuit is interrupted. After this, continuing with the mechanical disconnection, the electric connection between plug and receptacle is interrupted, however without the risk of the development of dangerous voltages in the CT secondary, since it has already been short-circuited.
The following is a technical explanation of the invention, using as a base the following drawings:
FIG: 5: Schematic showing drawing of the mechanically and electrically disconnected plug and receptacle showing the locking system locking out the automatic short-circuit capacity.
The “ELECTRICAL CIRCUIT QUICK CONNECTION AND DISCONNECTION SYSTEM WITH AUTOMATIC SHORT CIRCUIT OF CURRENT TRANSFORMER SECONDARIES AND SIMILAR DEVICES”, object of this Invention patent request, consists of a multipole plug (6) and receptacle (11) system with capacity of automatic short-circuit between poles (7, 12) upon initiating the disconnection between plug (6) and receptacle (11), without incurring in the temporary opening of the circuit, for application on current transformer (3) secondary circuits (3B) and other applications requiring the same characteristics.
The system is equipped with a number N of paired poles (7, 12), with each pair of poles (7, 12) connected to a CT (3) secondary (3B), capable therefore of handling N CT (3B) secondaries. Each pair of poles (7, 12) is equipped with a system that, under normal conditions of use, that is, with the plug (6) and receptacle (11) connected, allows the normal passage of current from the CT (3) secondary (3B) to the load (14) connected to it, without short-circuiting the CT (3) secondary (3B).
Upon initiating the mechanical disconnection between the plug (6) and the receptacle (11), with, however, the electrical connection between the plug (6) and the receptacle (11) still present, the CT (3) secondary (3B) is automatically short-circuited before the circuit is actually interrupted. Following this, continuing with the mechanical disconnection, the electrical connection between the plug (6) and the receptacle (11) is interrupted, however without the risk of developing dangerous voltages in the CT (3) secondary (3B), since it has already been previously short-circuited.
More specifically, the system proposed in
Upon completion of the mechanical connection between the plug (6) and the receptacle (11), as demonstrated in
Performing the inverse process, in other words, disconnecting the plug (6) from the receptacle (11), we return to the condition shown in
Following this, upon completion of the disconnection between the plug (6) and the receptacle (11), as shown in
In addition to the configurations shown in the previous figures in which the fixed (10) and moveable (9) short circuit contacts are assembled next to the male poles (7), the constructive arrangement in which the fixed (10) and moveable (9) contacts are assembled next to the female poles (12) is also possible, as shown in
The plug (6) and receptacle (11) system herein described can also be applied in situations in which the automatic short-circuit between poles is not necessary or desirable, and, for this reason, the system is equipped with a locking system (15) capable of maintaining the moveable short-circuit contact (9) separated from the fixed short-circuit contact (10), even if the plug (6) and receptacle (11) are not connected. As shown in
Number | Date | Country | Kind |
---|---|---|---|
0601439 | Apr 2006 | BR | national |
Filing Document | Filing Date | Country | Kind | 371c Date |
---|---|---|---|---|
PCT/BR2007/000062 | 3/15/2007 | WO | 00 | 4/7/2009 |
Publishing Document | Publishing Date | Country | Kind |
---|---|---|---|
WO2007/121453 | 11/1/2007 | WO | A |
Number | Name | Date | Kind |
---|---|---|---|
3322964 | Walter et al. | May 1967 | A |
3512043 | Werner et al. | May 1970 | A |
4871323 | Ohsumi | Oct 1989 | A |
5601442 | Harting et al. | Feb 1997 | A |
5834919 | Liu | Nov 1998 | A |
5946180 | Simpson | Aug 1999 | A |
7354287 | Hickam | Apr 2008 | B1 |
20080102672 | Hickam | May 2008 | A1 |
Number | Date | Country |
---|---|---|
4444551 | Jun 1996 | DE |
0 555 653 | Aug 1993 | EP |
09-035822 | Feb 1997 | JP |
Number | Date | Country | |
---|---|---|---|
20090186504 A1 | Jul 2009 | US |