Onsite energy generation systems are known in the art. Distributed solar power generation is one such onsite energy generation system. In a typical distributed solar energy system, solar panels or photovoltaic (PV) modules are installed on a flat or South-facing roof plane of a customer premises. The direct-current power generated by the solar panels is converted to AC power using one or more inverters and that AC power is in turn delivered to the customer's main electrical panel or to a parallel line tap somewhere between the customer's meter and panel. In this way, power generated by the PV panels may be supplied to the loads on the main electrical panel or, assuming back-feeding is permitted, back-fed to the grid causing the meter to run in reverse.
Electrical utilities require that onsite energy generation systems do not back-feed any power to the grid during power outages. The reason for this being that line workers who are repairing the grid expect it to be free of current when the grid is down. If, however, the customer's onsite energy generation system is feeding current to the grid, those workers could be injured by unexpected voltage potential and current flow. As a result, grid-tied onsite energy generation systems typically do not operate when the grid is down.
Recent developments have made it possible to add distributed energy storage systems to existing onsite energy generation systems such as solar systems. Such systems are referred to herein as onsite energy generation and storage systems (OEGSS). Onsite energy generation systems with integrated energy storage provide several benefits to the customer, the system owner and the grid operator. First, the energy storage system can provide back-up power to the premises in the event of a grid outage. Second, the energy storage system can allow customers to utilize power at night from the PV energy generated and stored in the energy storage system during the day without needing to back-feed power to the grid so that customers can recoup their investment in their onsite energy generation systems in areas where net metering is prohibited or of little relative value. Finally, utilities and/or solar providers may use distributed energy storage to supplement grid power in times of peak demand. To insure safety for utility line workers, all of these possible use cases require mechanisms to prevent power from being back-fed to the utility when the utility grid is down, while still allowing customers to enjoy the benefits of onsite energy generation.
In a typical OEGSS, a PV back-feed breaker is used to selectively allow or prevent the flow of power from the OEGSS to be back-fed to the grid and/or to the main electrical panel. Referring to
This disclosure describes various embodiments that relate to systems and apparatus for cost effectively and efficiently providing power to home loads and channeling any excess power to the AC grid or to an energy storage system for backup and/or delayed consumption. The systems and apparatus of the disclosure may include an onsite energy generation and storage system (OEGSS) having a renewable energy source (e.g., solar panels) and an energy storage system both coupled to an inverter. The inverter may include a bidirectional battery pack connection configured to supply energy to or receive energy from the energy storage system, a bidirectional (input/output) connection configured to supply power to or receive power from the AC grid, and an output connection configured to supply power from one or both of the energy storage system and the renewable energy source (e.g., solar panels). A manually controlled coupling mechanism is configured to enable power transfer between the AC grid and the inverter via the inverter's bidirectional connection when in a first position (e.g., on-grid position), and also enable the main breaker in the main electrical panel at the same time (if applicable) and to enable power transfer from the one or both of the energy storage system and the renewable energy source (e.g., solar panels) to the home loads when in a second position (e.g., off-grid position). The manually controlled coupling mechanism may be located in a separate subpanel in the vicinity of the main electrical panel or disposed within the main electrical panel. The manually controlled coupling mechanism allows customers to back-up their entire main panel or subpanel (as applicable) and allow the customer to choose which load(s) to be on or off based on the customer's needs. This also avoids the cost and effort of migrating loads from the main panel to a back-up subpanel.
In accordance with the present disclosure, any excess energy generated by a renewable energy source of an onsite energy generation and storage system can be stored in a local energy storage system and/or transferred to the AC grid when the AC grid operates in its normal condition (e.g., is in on-grid condition), or transfer stored energy and/or renewable energy to the loads when the grid is not operating in the normal condition (e.g., is in off-grid condition) through a manually controlled coupling mechanism. The manually controlled coupling mechanism may include a first contact portion having a first electrical contact for coupling to the electric grid and a second electrical contact for coupling to an on-grid AC terminal of an inverter, a second contact portion having a third electrical contact for coupling to an off-grid output terminal of the inverter, and a manually activated multi-position switch for selecting between the first and second contact portion. In a first position, only the first contact portion of the manually controlled coupling mechanism is activated to transfer power between the electric grid, the on-grid AC terminal of the inverter and a main electrical panel, and in the second position, only the second contact portion is activated to supply power from the off-grid output terminal of the inverter to the main electrical panel
Some embodiments of the present invention also provide a system for energy storage and conversion to supply power to the grid and the home loads via a manually controlled coupling mechanism.
Other aspects and advantages of the invention will become apparent from the following detailed description taken in conjunction with accompanying drawings, which illustrate, by way of example, the principles of the described embodiments.
In order to facilitate a better understanding of the present disclosure, reference is now made to the accompanying drawings, in which like elements are referenced with like numerals. These drawings should not be construed as limiting the present disclosure, but are intended to be exemplary only.
Various embodiments of the invention comprise a manual transfer switch, also known as a two-position mechanical interlock that allows for selective routing of AC power between the grid, the onsite energy generation and storage system and a customer's main electrical panel. As used herein, the phrases “main electrical panel,” “main panel,” or “electrical panel” may be used interchangeably to refer to a customer's main electric service panel.
According to some embodiments of the present disclosure, a manually controlled coupling mechanism for onsite energy generation and storage systems includes a first contact portion having a first electrical contact for coupling to an electric grid and a second electrical contact for coupling to an on-grid AC terminal of an inverter, a second contact portion having a third electrical contact for coupling to an off-grid output terminal of the inverter, and a manually activated multi-position switch. In some embodiments, the manually controlled coupling mechanism is a manually operated two-position switch. In the first position, only the first contact portion is activated to allow power transfer between the electric grid, the on-grid AC terminal of the inverter and the main breaker in a main electrical panel at the same time. In the second position, only the second contact portion is activated, allowing back-up power transfer from the off-grid output terminal of the inverter to the main electrical panel.
The manually controlled coupling mechanism of the present disclosure may be enclosed within a protective housing located in a subpanel in the vicinity of the main panel or within the main panel. The manually controlled coupling mechanism eliminates the use of critical load subpanel 50 of the prior art technique shown in
Main panel 40 may include manual transfer switch (MTS) or mechanical interlock kit (MIK) 200 disposed between power meter 70 and output terminals of inverter 30. The term “manual transfer switch” or “MTS” will be used alternatively in this disclosure to refer to a mechanical switch that has only two positions and is manually activated. The designation “hybrid” in “hybrid inverter” refers to the fact that the inverter not only converts DC power from the PV array to AC power, but also serves as an inverter and charger for the connected storage system (i.e., multi-mode operation).
MTS 200 includes first contact portion 210 having first electrical contact 211 for coupling to the AC grid (also referred to herein as “grid”) and second electrical contact 212 for coupling to on-grid terminal 33 of hybrid inverter 30 through back-feed connection 35. MTS 200 also includes second contact portion 220 having third electrical contact 223 for coupling to backup output terminal 34 of hybrid inverter 30 through back-up/off-grid connection 36. MTS 200 additionally includes terminal 230 that electrically connects first and second contacts 211, 212 to bus bar 46 of main panel 40 when the system operates in a normal or on-grid condition (i.e., the AC grid is in normal condition). Terminal 230 also electrically connects third electrical contact 223 to bus bar 46 in an off-grid or back-up condition (e.g., when the AC grid has power outage). Switch 204 may selectively establish electrical connection between first and second contacts 211, 212 of MTS 200 to bus bar 46 when it is manually activated to be in a first position (on-grid position), or may establish electrical connection between third contact 223 of MTS 200 to bus bar 46 when switch 204 is manually activated to be in a second position (off-grid position). Switch 204 may be a toggle switch mounted on a box that houses MTS 200, and is selectively positioned between the first and second positions. In some embodiment, switch 204 may be a lever, a rod, a button, a bar, or the like that can activate a mechanical solenoid or some mechanical mechanisms to activate MTS 200 into the first position or the second position. It is noted that MTS 200 can only be in the first position or in the second position, but not in both positions. In some embodiments, a box housing MTS 200 may include visual indicia in correspondence to a position of switch 204 indicating the respective position. For example, the visual indicia may be “on”, “on-grid”, “back-feed” and the like when two-position switch 204 is in the first position, and may be “off”, “off-grid”, “back-up”, and the like when two-position switch 204 is in the second position.
Hybrid inverter 30 may include DC side 31 and AC side 32 that are connected to one another via a central capacitor bank (not shown). DC side 31 may include circuitry (not shown) for performing maximum power point tracking (MPPT) on the DC output of PV array 10 and a DC/DC boost stage for boosting the DC voltage provided by PV array 10 to a level appropriate for inversion. Storage device 20 may include one or more low voltage battery modules or one or more high voltage battery modules. It should be appreciated that other types of storage devices may be substituted for high voltage battery modules. In the case that storage system 20 consists of low voltage battery modules, the storage system may include a DC/DC buck-booster to boost the low voltage to a higher voltage level for the AC side for discharging or buck the high voltage to a lower level when charging. The AC side converts the energy from the central capacitor bank to AC current to supply to home loads and/or the AC grid. This typically involves synchronizing the voltage and phase of the hybrid inverter current/power to the AC grid. The AC grid is not limited to single-phase but is also applicable to three-phase systems, e.g., 120 Vac, 208 Vac, 230 Vac, 240 Vac, 277 Vac, 400 Vac, 480 Vac, 690 Vac, and the like. AC side 32 of inverter 30 may have an input/output terminal 33 (also referred to as on-grid or back-feed terminal) configured to transfer power from either of PV array 10, storage device 20, or both simultaneously to the AC grid through first and second electrical contacts 211, 212 of MTS 200. AC side 32 may also include output terminal 34 configured to transfer power from either of PV array or PV modules 10, storage device 20, or both simultaneously to the home loads through third electrical contact 223 of MTS 200 when the AC grid is not available.
Main panel 40 may include main breaker 43 disposed between power meter 70 and first electrical contact 211 of MTS 200 for protecting the home loads from an over-current situation. Main panel 40 may also include circuit breaker 42 disposed between first output terminal 33 of hybrid inverter 30 and second electrical contact 212 of MTS 200. Main panel 40 may additionally include circuit breaker 45 disposed between second output terminal 34 of hybrid inverter 30 and third electrical contact 223 of MTS 200. In some embodiments, circuit breakers 42 and 45 may be incorporated in a box that houses MTS 200, as indicated by the dotted-line box within MTS 200 in
System 2 may also include connection (or transfer) switches 38 (e.g., solid-state relays, electronic switches, electro-mechanical relays) disposed internal or external to hybrid inverter 30. The switches 38 are configured to selectively connect the AC grid, inverter 30, and the home loads with each other under the control of a controller (not shown). For example, connection switches 38 are connected to input/output AC terminal 33 and may be configured, under the control of the controller, to transfer power from PV array 10 to the AC grid or to storage device 20, or to transfer power to/from the AC grid from/to storage device 20. Switches 38 are also connected to output terminal 34 and may be configured, under the control of the controller, to transfer power from PV array 10 and/or storage device 20 to one or more home loads when the AC grid is unavailable.
System 5 also include a manually controlled coupling mechanism 500 having a multitude of mechanical transfer switches MTS-1, MTS-n. Each of hybrid inverter power control systems HIPCS5-1 to HIPCS5-n is connected to a corresponding MTS-1 to MTS-n. In some embodiments, each of mechanical transfer switches MTS-1 to MTS-n may be similar to or the same as MTS 300 in
In some embodiments, system 5 may include subpanel housing 550 in which manually controlled coupling mechanism 500 is disposed, and which can be installed near the main panel. In some embodiments, circuit breakers corresponding to each MTS are also disposed in subpanel housing 500. As with other embodiments, subpanel housing 550 in system 5 may include visual indicia of the set position of switch 504. In some embodiments, manually controlled coupling mechanism 500 may be disposed in the main panel.
During the discharge of storage device 20, power leaving the storage block may again flow through the DC/DC buck-boost stage where it is stepped up to a level equal to or above the grid voltage levels (e.g., 170 volts) before inversion to AC (by AC side 24) for supply to the home loads. Storage inverter 22 is a bidirectional inverter that can receive power from PV array 10 or the grid and store that power in battery modules to storage block 20.
Manual transfer switch 300 in system 6 of
System 6 may also include connection switches 28 (e.g., solid-state relays, electronic switches, electro-mechanical relays) disposed internal or external to storage inverter 22. Connection switches 28 are configured to selectively connect the grid, storage inverter 22, PV inverter 12, and the home loads with each other under the control of a controller (not shown). For example, connection switches 28 are connected to input/output terminal 25 (also referred to as on-grid or back-feed terminal) and are configured to transfer power from PV array 10 (through PV inverter 12) to the grid or storage device 20, or to provide power to/from the grid from/to storage device 20. Connection switches 28 are also connected to output terminal 26 (also referred to as the off-grid or back-up terminal) and are configured to transfer power from PV array 10 or storage device 20 to one or more home loads when the grid is unavailable. Input/output terminal 25 is coupled to second electrical contact 312 of MTS 300 through back-feed connection 35. Output terminal 26 is coupled to third electrical contact 323 of MTS 300 through back-up connection 36.
In some embodiments, system 6 may include a multitude of storage blocks 20 connected in parallel to increase energy capacity, similar to storage blocks 20a-20n in system 4 of
Manually controlled coupling mechanism 7 further includes a manually controlled user switch 704 that can be a toggle switch, a shift switch, a mechanical handle switch, a button switch and the like that has two positions (e.g., first position and second position that are mutually exclusive). Switch 704 may be connected to the internal switch assembly through a mechanical linkage such as a mechanical rod (or mechanical arm) 760 or other mechanism to move the switch assembly from the first position (e.g., on-grid) to the second position (e.g., off-grid), and vice versa. Switch 704 may be mounted in a mechanical handle 705 connected to the switch assembly so that user need only flip handle 705 of switch 704 to switch operation of the MTS between on-grid and off-grid modes of operation. The switch assembly is shown in
Manually controlled coupling mechanism 7 may further include visual indicia (not shown) indicating the position of the first contact portion and the second contact portion. For example, the visual indicia may have labels such as “On-grid”, “Off-grid”, “back-feed”, “back-up”, and the like at a location in the vicinity of switch 704 to indicate to a user the current mode of operation.
In summary, in accordance with the present disclosure, a manually controlled coupling mechanism includes a manual transfer switch that can be only be in one of two mutually exclusive positions at any given moment in time. When in the first position, grid power is joined in parallel with a two-way connection to the on-site energy generation and storage system's inverter for the PV back-feed and/or charging the storage device. The connection to the on-site energy generation and storage system's inverter is typically lower than the maximum current rating of the main panel. In embodiments described above, MTS circuit breakers (e.g., breakers 42, 45 in
The manually controlled coupling mechanism of the present disclosure integrated in an OEGSS as discussed above in relation to various embodiments advantageously eliminates critical load subpanel 50 of the prior art technique shown in
The embodiments described herein are not to be limited in scope by the specific embodiments described above. Indeed, various modifications of the embodiments, in addition to those described herein, will be apparent to those of ordinary skill in the art from the foregoing description and accompanying drawings. Further, although some of the embodiments have been described herein in the context of a particular implementation in a particular environment for a particular purpose, those of ordinary skill in the art will recognize that their usefulness is not limited thereto and that they can be beneficially implemented in any number of environments for any number of purposes. Accordingly, the disclosure should be construed in view of the full breath and spirit of the embodiments as disclosed herein.
This claims priority to U.S. Provisional Patent Application No. 62/419,424, filed on Nov. 8, 2016, the disclosure of which is hereby incorporated by reference in its entirety for all purposes.
Number | Date | Country | |
---|---|---|---|
62419424 | Nov 2016 | US |