According to the prior art, manual or semi-manual test procedures (using stake-less or one or more stakes) are employed for testing earthing grids where considerable time and manual labor is involved for setting up test equipment and running test procedures. Testing done as per the prior art is less accurate due to variation in performing the same manual activities, and variation in setting up the test equipment. Besides, such procedures do not provide timely measurements.
Earthing grids are a mandatory safety mechanism in all commercial, industrial and residential facilities and buildings. Improper earthing can result in numerous issues such as electrical energy measurement errors, equipment damage, hazardous events (fire, shock) causing damage to life and property. Earthing grids are designed, constructed and maintained to meet local safety standards. Earthing grids consist of multiple Earth Pits located across the facility (or site) connected with strips of conductive metal or cables to form a conductive (for electric charges) grid. Each Earthing Pit consists of a pit containing conductive materials (special chemicals or salts) and an electrode. The electrode connects to the Earthing grid using conductive metal strip or cable. All equipment, buildings, power systems are connected to the Earthing Grid to allow any accidental current leakages or lightning surges to flow effectively into the ground. A well designed and operational Earthing Grid conducts all unintentional leakage currently effectively into ground and prevents any hazards. A properly functioning Earthing Grid is of vital importance to meet local regulations and avert costly disasters. Earthing Grid's functioning degrades over time owing to multiple factors such as corrosion, rust, damage etc. To ensure Earthing grid functions properly, it is important to carry out regular maintenance of Earthing grid which involves testing the grid health and taking corrective actions in case of adverse findings.
The health of Earthing Grid is represented by effective resistance of all the Earthing Pits connected to the Grid. The connection of each Earth Pit to the Earth Grid (on one side) and to ground (on other side) creates a path for leakage currents to flow. Each electrode introduces electrical resistance (termed as “Electrode Resistance” or “Earth-Pit Resistance” measured in Ohms) to the electric leakage currents flowing through it to ground. The effective resistance of all the parallelly connected Earthing Electrodes form the “Grid Resistance” measured in Ohms. The health of Earthing Grid can be determined by measuring the Electrode Resistance and Grid Resistance. The goal of a well-designed healthy Earthing Grid is to have close to zero resistance (in Ohms) for each of Earth-Pit's Electrode Resistance and Grid Resistance. In reality this is rarely achieved as there is always some resistance to the leakage current flowing through Grid and Earth Pit.
Whenever there is earthing leakage (of signal at principle electrical frequency or other noise), a proper functioning earthing grid will conduct it safely to earth. However, the existing monitoring mechanisms as per prior art cannot identify automatically if there is active leakage and where in the grid is a leakage occurring. Eliminating leakage faults is the safest approach, and hence it is very important to identify if there is leakage and locate the source of leakage for corrective actions.
When designing earthing grids, it is important to measure soil resistance and space the earthing-pits to achieve an approximate equivalent resistance for leakages flowing to earth. Measuring soil resistance is also a best practice for ongoing earthing grid monitoring as it reflects the inherent resistance to the ground leakages.
The monitoring of earthing grid is carried out by testing regularly for Electrode Resistance and effective Grid Resistance. This is done according to prior art using manual or semi-automatic test procedures which do not produce consistently accurate and timely results. This approach is both costly, time-consuming and introduces risks associated with inaccurate results. This invention introduces a new approach to automatically monitor the earthing grid in real-time.
The present invention addresses the aforementioned concerns, and others, of prior art.
The present invention provides a fully-contained monitoring unit that once installed can be used to automatically monitor the health of an earthing grid in real-time by measuring individual earthing electrode resistance, effective grid resistance, electrical mains frequency leakage currents, and electrical noise. This monitoring can be accomplished without any manual activity or grid disconnections. The monitoring unit has communication capability allowing it to receive commands from remote systems, and respond with the earthing grid measurement data. The earthing grid data can then be trended, monitored and used for alerting and analytics in real-time.
In a preferred embodiment of the present invention, the monitoring unit comprises of a main processing sub-unit handling power management, data processing and communications; and an auxiliary sensor sub-unit handling the sensing. In this embodiment, the monitoring unit will be powered by battery, and use wireless communications (Zigbee or Bluetooth) to receive commands and send responses and data. In this embodiment, the monitoring unit will be designed and manufactured to comply to IP67 rating for deployment in outdoor under-ground locations.
In an alternative embodiment, the monitoring unit will be designed and manufactured to meet hazardous area installation requirements in compliance with IEC 60079-11.
In an alternative embodiment, the monitoring unit will be powered by wired 12-24 VDC supply, and it will use wireless communications to receive commands and send responses and data.
In an alternative embodiment, the monitoring unit will be powered by wired 12-24 VDC supply, and it will use wired RS-485 communications to receive commands and send responses and data.
In an alternative embodiment, the monitoring unit will be powered by battery, and it will use wireless communications to receive commands and send responses and data.
In an alternative embodiment, the monitoring unit will be powered by solar panel+charger+battery, and it will use wireless communications to receive commands and send responses and data.
In an alternative embodiment, the monitoring unit will be powered by solar panel+charger+battery, and it will use wired RS-485 communications to receive commands and send responses and data.
The current invention will hereinafter be described in conjunction with the appended drawings, provided to illustrate and not to limit the disclosed aspects.
As per current invention, the apparatus comprising of one or more monitoring units needs to be installed permanently on earthing grid to be monitored. Each monitoring unit comprises of main processing sub-unit (MPSU), auxiliary sensor coil sub-unit (ASCSU) and auxiliary sensor stake sub-unit (ASSSU) as shown in
The monitoring unit's logical component schematic is shown in
After the one-time installation of monitoring unit, the health of earthing grid can be monitored automatically and in real-time by giving periodic measurement requests from external remote systems or scheduling measurements at pre-defined intervals. Irrespective of the mode of measurement requests, the measurements are done following an automatic sequence of steps shown in
Pre-check: MPSU1 sets Test Signal Frequency Fi to value between (4.44 KHz to 8.88 KHz) distinct from Electrical Mains Frequency. MPSU1 captures signal from ASCSU1 secondary coil without providing any excitation to ASCSU1 primary coil. MPSU1 performs FFT on signal and calculates Electrical Mains Frequency Leakage (50 or 60 Hz) and Electrical Noise (all other frequencies). If Electrical Noise signal contains Test Signal Injection Frequency components, then the Test Signal Injection Frequency Fi is changed and the Pre-check step is repeated till a test signal frequency is identified that is not present in the Electrical noise signal. The final Electrical Mains Frequency Leakage and Electrical Noise measurements are saved in MPSU1 data buffer.
Earthing Electrode Resistance Measurement Sub-step1: MPSU1 keeps Sw1 open and Sw2 Open at input of Differential Amplifier. MPSU1 excites ASCSU1 Primary coil with Test Signal of fixed voltage V1 and fixed frequency Fi (identified in previous step). This results in induction of Voltage V1′ across loop of Electrode resistance, Grid Resistance, and Soil Resistance (equivalent to series connected resistances). This develops current I1 in the earthing loop whose value depends on Electrode Resistance Re1 and Grid Resistance Rg1. Same current I1 flowing through ASCSU1 secondary coil will induce voltage V2. This signal at ASCSU1 secondary coil terminals is acquired by MPSU1, FFT transformation is performed and the FFT amplitude at Test Signal Injection Frequency Fi is extracted. This amplitude is saved in data buffers as Mag1. Mag1 is proportional to I1.
Earthing Electrode Resistance Measurement Sub-step2: MPSU1 closes Sw1, keeping Sw2 open at input of Differential Amplifier. MPSU1 excites ASCSU1 Primary coil with Test Signal of fixed voltage V1 and fixed frequency Fi (identified in previous step). Sw1 closing applies the voltage Ve1 developed at Junction Je1 to MPSU1 Differential Amplifier input. The other input to MPSU1 Differential Amplifier is Vs1 developed at ASSSU1 Junction Js1. This differential input induces additional bias current I2 flowing through the output of MPSU1 Differential Amplifier, through the ASCSU1 secondary coil to the ground. The output signal of MPSU1 Differential Amplifier and output signal of ASCSU1 secondary coil is analyzed and FFT component at Test Signal Injection Frequency Fi is extracted. The FFT amplitude at Test Frequency at the Differential Amplifier output is voltage V3 and at ASCSU1 secondary coil is voltage V2′. V2′ is saved in data buffers as Mag2. Mag2 is proportional to (I1+I2). The earthing electrode resistance Re1 is calculated using formula: ((Mag2−Mag1)/Mag1)*Rs1 and saved in data buffers. The formula is arrived at by following the steps below. Refer to
Earthing Grid Resistance Measurement Sub-step1: This step is same as Earthing Electrode Resistance Measurement Sub-step1. MPSU1 keeps Sw1 open and Sw2 Open at input of Differential Amplifier. MPSU1 excites ASCSU1 Primary coil with Test Signal of fixed voltage V1 and fixed frequency Fi (identified in previous step). This results in induction of Voltage V1′ across loop of Electrode resistance, Grid Resistance, and Soil Resistance (equivalent to series connected resistances). This develops current I1 in the loop whose value depends on Electrode Resistance Re1 and Grid Resistance Rg1. Same current I1 flowing through ASCSU1 secondary coil will induce voltage V2. This signal at ASCSU1 secondary coil terminals is acquired by MPSU1, FFT transformation is performed and the FFT amplitude at Test Signal Injection Frequency Fi is extracted. This amplitude is saved in data buffers as Mag1. Mag1 is proportional to I1.
Earthing Grid Resistance Measurement Sub-step2: MPSU1 closes Sw2, keeping Sw1 open at input of Differential Amplifier. MPSU1 excites ASCSU1 Primary coil with Test Signal of fixed voltage V1 and fixed frequency Fi (identified in previous step). Sw2 closing applies the voltage Vg1 developed at Junction Jg1 to MPSU1 Differential Amplifier input. The other input to MPSU1 Differential Amplifier is Vs1 developed at ASSSU1 Junction Js1. This differential input induces additional bias current I2 flowing through the output of MPSU1 Differential Amplifier, through the ASCSU1 secondary coil to the ground. The output signal of MPSU1 Differential Amplifier and output signal of ASCSU1 secondary coil is analyzed and FFT component at Test Signal Injection Frequency Fi is extracted. The FFT amplitude at Test Frequency at the Differential Amplifier output is voltage V3 and at ASCSU1 secondary coil is voltage V2′. V2′ is saved in data buffers as Mag2. Mag2 is proportional to (I1+I2). The earthing grid resistance Rg1 is calculated using formula: ((Mag2−Mag1)/Mag1)*Rs1 and saved in data buffers. The formula is arrived at by following the steps below. Refer to
Communication of measurement data to external remote systems: MPSU1 conveys the electrode resistance, earthing grid resistance, electrical mains frequency leakage currents, electrical noise measurements saved in data buffers to external remote systems using the communication link configured during setup.