The piping network 12 connects the sprinkler heads 16 to a source of pressurized water 18, which could be, for example, a municipal water main, or a reservoir. Water flow from the source to the sprinkler heads 16 is controlled by a supply valve 20 positioned in the network 12 between the water source 18 and the various branches 14, 14a-14f of the piping network on which the heads 16 are mounted. As noted, the system shown is a dry type system wherein the piping network downstream of supply valve 20 is not charged with water in its ready state. However, there may still be residual stagnant water in the piping network, for example, water remaining due to incomplete draining after a test of the system or a previous actuation.
Supply valve 20 is actuated by a control system 22, for example, a programmable logic controller or a microprocessor with resident software. The control system may also include a pressure sensitive actuator (with or without an accelerator mechanism) that is in communication with the piping network, one or more heat sensitive actuators, radiation sensitive actuators, smoke sensitive actuators or other actuators that are capable of detecting a fire condition and providing a signal to the control system causing it to open the main valve and allow water to flow to the sprinkler heads.
An air pump 24 is in fluid communication with the piping network 12 between the supply valve 20 and the sprinkler heads 16. In the embodiment shown in
Various branches 14 of the piping network may have an air vent 28, preferably positioned downstream of the last sprinkler head 16 in the branch. The air vents allow ambient air 30 to be drawn into the piping network through the branches by the vacuum pump 24. Preferably the air vents provide continuous fluid communication between the piping network and the ambient when the system is in the ready state. The air flow may be substantially continuous through the branches with the pump 24 operating intermittently to maintain a negative pressure between a predetermined minimum and maximum within the piping network. Negative pressure may be maintained within the system 10 through the use of a simple feed back loop which comprises a pressure sensor 32 which senses the gas pressure within the piping network 12 and returns a signal to the control system 22, which cycles the vacuum pump 24 on and off as needed to maintain the desired pressure. Air 30, drawn through the network, is exhausted to the atmosphere by the vacuum pump.
Air flow through each branch 14 is controlled by a flow restrictor 34 depicted schematically in branch 14. Various types of restrictors may be employed, such as an orifice 36 shown in branch 14a, a throttle valve 38 in branch 14b, as well as a venturi 40, shown in branch 14c. Other types of flow restrictors are also feasible. The restrictors may be all of the same type, or mixed types may be used in a single system. The flow characteristics of the flow restrictors may be varied to balance the air flow through the various branches. Thus, the sizes of the orifices 36 may be different in different branches depending upon their length and distance from the vacuum pump 24, with longer branches and more distant branches having larger orifices than shorter, closer branches to compensate for the greater resistance to flow through the longer or more distant branch. Similarly, throttle valves may be adjusted individually as required to different opening sizes to balance the flow for a particular negative pressure.
In branches 14a-14c, the flow restrictors 36, 38 and 40 also comprise the air vents 28. Alternately, as depicted in branches 14d-14f, the flow restrictors 36, 38 and 40 are positioned within the piping network 12 in spaced relation away from the air vents 28. Filters 42 may be used in conjunction with the air vents 28 to filter particulates from the air 30 to prevent clogging of the various flow restrictors.
An air dryer 44 may be positioned between each air vent 28 and the last sprinkler head 16 in each branch of the piping network 12. Desiccant dryers, which absorb water using granular material such as activated alumina or silica gel, are particularly advantageous because they are effective, inexpensive, compact and require little maintenance. Other drying devices, such as refrigeration dryers, membrane filters and compressed air dryers, are also feasible. Each dryer 44 is protected from water in the branch by a check valve 46 positioned in the branch between the dryer and the last sprinkler head. The check valves 46 are arranged to permit flow of air 30 from the air vent 28 to the vacuum pump 24, but prevent water flow from the water source 18 to the dryers 44.
In operation, the fire suppression sprinkler system 10 may be activated, for example, in a test or in an actual fire event. The control system 22 opens supply valve 20, supplying water to the network 12 and its various branches 14. In a fire event, one or more sprinkler heads 16 in the vicinity of the fire will trigger, allowing water to be discharged to suppress the fire. The check valves 46 prevent water from entering the dryers 44 and exiting the system through air vents 28. The control system also closes cut-off valve 26, protecting vacuum pump 24.
Upon completion of the fire or test event, the supply valve 20 is closed and a drain valve 48 is opened to drain the piping network 12 so that it is substantially devoid of water as appropriate for a dry type system in the absence of a fire. Any sprinkler heads 16 that opened during the fire are replaced, and the cut-off valve 26 is then opened. The system 10 is again reset in the ready state, capable of detecting a fire and operating to suppress it. It is expected, however, that despite draining the system, residual water will remain in the piping network 12, for example, in any or all of the branches 14. The water may remain stagnant within the pipes for long periods of time between system actuations, providing ample opportunity for microbiological influenced corrosion, oxidative corrosion and scaling to damage the pipes and cause leaks or blockages. To mitigate this damage, the vacuum pump 28 is run intermittently to maintain a negative pressure within the piping network. This causes air 30 to be drawn into the branches through air vents 28. The flow rate is determined largely by the flow restrictors 34, such as the orifices 36, the throttling valves 38 and the venturis 40 in each branch in conjunction with the negative system pressure. The flow rate is established to ensure an adequate, substantially continuous air flow throughout the system capable of removing the residual water while operating within reasonable parameters for the duty cycle of the vacuum pump. For large systems multiple vacuum pumps 24 may be employed.
Moisture is removed from the ambient air 30 drawn into the piping network through air vents 28 as it passes through the dryers 44. The incoming air is dried to a predetermined dew point and then continues on through the piping network 12, whereupon it is exhausted to the atmosphere by the vacuum pump 24. As it travels through the various branches of the network, the dry air absorbs the residual water that would otherwise stagnate within the pipes. The continuous flow of initially dry air gradually removes the water from the piping network, starving the microbiological entities of the water they need to survive, and effectively curtailing microbiologically influenced corrosion damage. Other forms of corrosion, such as oxidative corrosion as well as scaling effects, are also significantly inhibited by removal of the water. In dry climates where the ambient air has low relative humidity it may be possible to dispense with the dryers. Similarly, for large systems formed of pipes having relatively small diameters, discrete flow restrictors may not be necessary, as the lengths and diameter of the pipes themselves may provide the desired air flow rates for effective drying.
In another system embodiment 50, shown in
The sprinkler system according to the invention is advantageously used with dry systems, but will also find use with wet systems that are seasonally converted to dry systems as, for example, in an unheated warehouse where the sprinkler system is operated as a wet system in the summer and as a dry system in the winter.
This application is based on and claims priority to U.S. Provisional Application No. 60/843,816, filed Sep. 12, 2006.
Number | Date | Country | |
---|---|---|---|
60843816 | Sep 2006 | US |