The present invention relates to a method for controlling a capacitor or reactor in a wind power plant, with at least one wind turbine generator, the invention also relates to wind power plant wherein there is a controller for a capacitor or reactor.
With increasing penetration of wind power generation, the requirements for the connection of Wind Power Plants (WPP) to the electrical grid are defined by new and emerging grid connection codes. The grid connection requirements vary in different parts of the world, but they share common aims, like to permit the development, maintenance and operation of a coordinated, reliable and economical transmission or distribution system. Wind power plants differ from other traditional generation sources; thus, they are particular in certain aspects of their control and layout. Therefore, replacing traditional power plants, including their control characteristics, during periods of strong wind could be a concern. Grid operators are solving this challenge by means of redacting specific sections in the grid codes for WPP performance.
The new requirements generally demand that wind power plants provide ancillary services to support the network in which they are connected. In the present case, voltage regulation is of interest, and has been introduced recently by some grid operators. Voltage regulation with wind power plants entails the integration of all the available control devices installed at substations and plant.
Normally, the requirements of the utilities can be solved by the turbines and the park controller. When the wind turbines are not enough to fulfill the grid code requirements, then reactive power compensation equipment should be installed. This equipment could be static compensators if the plant needs more voltage dynamic capability, mechanical switching capacitors/reactors if the requirement is related to steady state performance, or just simply it could be a combination of both. The adoption of each one of the possible solutions, and choosing the method and combination of components for voltage regulation is one of the design decisions. The prevalent position is minimizing the cost of investments while offering the fulfillment of the requirements.
WPPs are composed by a large number of generation units, thus introducing communication delays in the plant control when processing the data and these could be in the range of hundreds of milliseconds.
The reactive power and voltage control of the wind turbines is relatively fast, with characteristic time constants in tens of milliseconds, the reactive power and voltage control of the central plant control is somewhat slower, with characteristic time constants in a range of hundreds of milliseconds, and this is used for voltage control in the agreed node in the transmission system in accordance with the requirements of the grid codes. As voltage control is actuated by reactive power from the turbines, it is possible to affirm that the voltage control design will cover an inner reactive power/voltage control loop, located at turbine level, and an outer voltage control loop, located at the Point of Common Coupling (PCC) where it is intended to control the voltage.
It may be seen as an object of embodiments of the present invention to provide a method and a control arrangement for controlling a reactive power source.
This Summary is provided to introduce a selection of concepts in a simplified form that are further described below in the Detailed Description.
This Summary is not intended to identify key features or essential features of the claimed subject matter, nor is it intended to be used as an aid in determining the scope of the claimed subject matter.
The above-mentioned object is complied with by providing, in a first aspect, a method for controlling at least one capacitor or reactor in a wind power plant, with at least one wind turbine generator, the method comprises the steps of:
An advantage of this embodiment is that the connection/disconnection of the passive devices is upon the location of the calculated reactive power in the inductive or capacitive area.
An advantage of the subtracting the reactive power of the connected device from the total calculated reactive power, thus minimizing the transient in the control system.
Many of the attendant features will be more readily appreciated as the same become better understood by reference to the following detailed description considered in connection with the accompanying drawings. The preferred features may be combined as appropriate, as would be apparent to a skilled person, and may be combined with any of the aspects of the invention.
a shows a DFIG diagram.
b shows a simplified control diagram of the DFIG controller.
The present invention will now be explained in further details. While the invention is susceptible to various modifications and alternative forms, specific embodiments have been disclosed by way of examples. It should be understood, however, that the invention is not intended to be limited to the particular forms disclosed. Rather, the invention is to cover all modifications, equivalents, and alternatives falling within the spirit and scope of the invention as defined by the appended claims.
Still referring to
A brief description of the DFIG will be given in the following. Referring to
A simplified control diagram of the DFIG controller is depicted in
Most of the grid codes for operating modern wind power plant connected to an electrical asks for having a voltage capability regulation within a minimum power factor between 0.9 or 0.95, for the whole active power range. As can be seen in
Voltage regulation including static converters, e.g. Wind turbines with DFIG or full scale converters (wind turbine generators where all the power is converted through a power converter) or STATCOMs, are viewed primarily as a fast reactive power source (VAr) to counteract rapid and unexpected voltage disturbances. In order to fulfill this requirement, it is necessary to ensure that the compensator will have sufficient VAr capacity to handle unpredictable disturbances; for this reason normally the WPPs include switchable capacitor (MSCs) and reactor banks (MSRs) for keeping converters dynamic capability to the maximum. It should be noted that the operations of these switchable components are considered as a way to offset the operation level not as a voltage regulation itself, whereas the static converters operate more as a voltage regulation mean.
The MSCs strategy proposed in this idea is basis on the idea that the steady state operation of the Q injected by the converters is inside the range ±0.1 pu (as an example) in this way the sizing of the capacitor banks and its control is designed accordingly. One should realized that the bigger the range, the lower the amount of switching operation for the MSCs, but the bigger the switching energy losses annually from the static converters supplying the reactive power. The inductive operation area of the MSRs are may not be included, since the power converter of the wind turbine generators by themselves reach more than the needed maximum operation point at the PCC, when the wind turbines are equipped with DFIG generators, and just with an operation of 0.1 pu inductive can almost reach the maximum required. This might not be the case with other types of generators in the wind turbines, here other factors also play a role, such as cabling, transformers etc.
The amount of capacitor steps can be adapted to as many as wanted; having two steps (CAP1 and CAP2) is just for the sake of simplification. The controller could be programmed to have several ranges of operations instead of one.
These ranges could be triggered by different voltage levels, wind level, or by different active power level injections. Having for example smaller ranges for high power, 0.05 pu and bigger for low power 0.1 pu. Since more power fluctuations is expected in this area.
It should be noted that this concept can be applied to other kind of WTG topologies, including WTGs with full scale power converters.
Vref is calculated according to
The mentioned control strategy calculates the total reference (Vref_total) to be outputted by the WPP components, where the components often comprises wind turbine generators, STATCOMs, MSCs and perhaps MSRs. Before this reference is sent to them, it is altered by the capacitor control, which may subtract/add a fraction to the reference (ΔVCap) if one of the capacitor steps is going to be connected/disconnected. After this the reference is processed in the dispatcher block, which splits the calculated reference among the WTGs and STATCOM, according to the injected active power.
The Capacitor control strategy suggested by the present invention is depicted in
The control strategy of the present invention uses the previous calculated Vref to calculate the needed Q by using equation 1.
(1−Vref)KWTG=IqWTG≈QWTG=Qref
In the case that the wind power plant controller is calculating voltage references, to calculate what will be the reactive power injected by each wind turbine generator (WTG), the K_WTG gain is used (K_WTG is the voltage slope gain of the WTG control), one have to take into account that when the reference calculated by the wind power plant is calculated, in terms of reactive power reference, no translation is needed. The same would also apply to a STATCOM.
If the control is working in “per unit” (as it is in the schemes), the Iqwtg, in Equation 1, is the total of all of them, if the control is working in real units, Iqwtg will be the reactive current of only one wind turbine, it is therefore needed to multiply by the total amount of WTG on line to get the total reactive power of the wind power plant.
The Qref_cap reference is compared with some threshold value (Converter operation steady-state, which defines the maximum level of the converters is going to be used for reactive power generation), if the reference is greater than this level, then the output is set to Qref_cap, otherwise remain 0. The next block (Switching Logic), processes this signal and decided which step to connect/disconnect basis on some timer functions and the current status of the capacitors. The outputs of the block are the switching commands to turn on or off of capacitor bank 1 (C1) or capacitor bank 2 (C2) and the ΔVCap offset.
Attention should be drawn to the input reference connected to the Capacitor Control (Vref instead of Vref_total), this ensure that the processed Vref is the one related to the operation of the WTGs and a STATCOM .
The effect of the present embodiment gives a ΔVCap offset compensation which is to center the disturbance of the capacitor connection, thus decreasing the peak value of the transient. The action of the ΔVCap offset can be disabled in some situations, such as when disconnecting the capacitors, and when the measured voltage is greater than a certain percentage of nominal voltage, for example 1.08 pu, and when connecting capacitors and the voltage is below a certain percentage of nominal voltage, for example 0.92 pu. In these situations it is better not to center the transient, in order to avoid increasing/decreasing the voltage even more.
In summary the invention relates to, a control system and an associated method for controlling a capacitor/reactor bank for delivering an amount of reactive power delivered from a wind power plant to an associated power supply grid, keeping the reactive power output of the wind turbines/STATCOM within a maximum operation band, the control system comprising a wind power plant controller and a number of wind turbine controllers each being in communication with said wind power plant controller, wherein the wind power plant controller is adapted to provide a grid voltage reference in response to a required total amount of reactive power to at least one wind turbine controller and operating a Switched Capacitor bank.
Any range or device value given herein may be extended or altered without losing the effect sought, as will be apparent to the skilled person.
It will be understood that the benefits and advantages described above may relate to one embodiment or may relate to several embodiments. It will further be understood that reference to ‘an’ item refer to one or more of those items.
It will be understood that the above description of a preferred embodiment is given by way of example only and that various modifications may be made by those skilled in the art. The above specification, examples and data provide a complete description of the structure and use of exemplary embodiments of the invention. Although various embodiments of the invention have been described above with a certain degree of particularity, or with reference to one or more individual embodiments, those skilled in the art could make numerous alterations to the disclosed embodiments without departing from the spirit or scope of this invention.
Number | Date | Country | Kind |
---|---|---|---|
2010 70240 | Jun 2010 | DK | national |
Filing Document | Filing Date | Country | Kind | 371c Date |
---|---|---|---|---|
PCT/DK2011/050184 | 5/31/2011 | WO | 00 | 12/3/2012 |
Publishing Document | Publishing Date | Country | Kind |
---|---|---|---|
WO2011/150932 | 12/8/2011 | WO | A |
Number | Name | Date | Kind |
---|---|---|---|
4359678 | Raivola et al. | Nov 1982 | A |
4565929 | Baskin et al. | Jan 1986 | A |
4567424 | Dobsa et al. | Jan 1986 | A |
4999565 | Nilsson | Mar 1991 | A |
5343139 | Gyugyi et al. | Aug 1994 | A |
5351181 | Brennen et al. | Sep 1994 | A |
5402057 | D'Aquila et al. | Mar 1995 | A |
5541498 | Beckwith | Jul 1996 | A |
5646512 | Beckwith | Jul 1997 | A |
5698969 | Gyugyi | Dec 1997 | A |
5751138 | Venkata et al. | May 1998 | A |
5798634 | Terada et al. | Aug 1998 | A |
5841267 | Larsen | Nov 1998 | A |
6121758 | Bellina et al. | Sep 2000 | A |
6411067 | Bjorklund | Jun 2002 | B1 |
6924565 | Wilkins et al. | Aug 2005 | B2 |
6963187 | Bebic et al. | Nov 2005 | B2 |
7081689 | Tilscher et al. | Jul 2006 | B2 |
7095597 | Cousineau | Aug 2006 | B1 |
7312537 | Walling et al. | Dec 2007 | B1 |
7321834 | Chu et al. | Jan 2008 | B2 |
7397143 | Walling | Jul 2008 | B2 |
7432609 | Obayashi et al. | Oct 2008 | B2 |
7505833 | Delmerico et al. | Mar 2009 | B2 |
7606638 | Fortmann et al. | Oct 2009 | B2 |
7804280 | Deaver et al. | Sep 2010 | B2 |
7813884 | Chu et al. | Oct 2010 | B2 |
7839024 | Cardinal et al. | Nov 2010 | B2 |
7923862 | Cardinal et al. | Apr 2011 | B2 |
8138637 | Herold et al. | Mar 2012 | B2 |
8174138 | Castelli Dezza et al. | May 2012 | B2 |
8203856 | Radbrandt | Jun 2012 | B2 |
8249852 | Thulke | Aug 2012 | B2 |
8290634 | Larsen et al. | Oct 2012 | B2 |
8527104 | Arinaga et al. | Sep 2013 | B2 |
8536722 | Wakasa et al. | Sep 2013 | B1 |
20050015182 | Bebic et al. | Jan 2005 | A1 |
20050040655 | Wilkins et al. | Feb 2005 | A1 |
20050194787 | Tilscher et al. | Sep 2005 | A1 |
20100109447 | Achilles et al. | May 2010 | A1 |
20100114388 | Ooi et al. | May 2010 | A1 |
20100327599 | Nielsen et al. | Dec 2010 | A1 |
20120101640 | Stapelfeldt | Apr 2012 | A1 |
20130181532 | KJ R | Jul 2013 | A1 |
Entry |
---|
Paserba J J, IEEE “Secondary voltage-Var controls applied to static compensators (STATCOMs) for fast voltage control and long term Var management”, 2002 IEEE Power Engineering Society. Summer Meeting. Chicago, IL Jul. 21-25, 2002. |
Martinez et al., “Design and coordination of a capacitor and on-load tap changer system for voltage control in a wind power plant of doubly fed induction generator wind turbines”, Wind Energy, May 26, 2011 pp. 1-17. |
European Patent Office, Search Report and Written Opinion issued in related International application No. PCT/DK2001/050184 dated Mar. 5, 2012. |
Martinez, et al., “Centralized Slope Voltage Control for a DFIG Wind Power Plant with STATCOM and Capacitor Banks”, May 28, 2010. |
Number | Date | Country | |
---|---|---|---|
20130076037 A1 | Mar 2013 | US |
Number | Date | Country | |
---|---|---|---|
61353668 | Jun 2010 | US |