The present application generally relates to air circulation systems and in particular to removal of various substances from and/or cleaning of air circulation systems.
Heating, Ventilation and Air-Conditioning (“HVAC”) are standard in virtually every modem building. Indeed, HVAC is often one of the largest parts of the entire energy budget of most buildings. This is particularly the case in extreme climates, both hot and cold. One of the goals of HVAC systems is to provide comfortable and healthy environment for building occupants, in terms of temperature, humidity, composition and cleanliness of air.
Central HVAC systems in buildings typically include one or more central air handling unit(s) and an air distribution system, where supply air is directed to various parts of a building through a network of ducts, and return air flows from these spaces, through other ducts or a plenum, back to the air handling unit(s). In the air handling unit, the air is cooled and/or heated, as well as filtered and often dehumidified and/or humidified, as needed. Thus, HVAC systems constantly circulate air through the building while continually adjusting its temperature and humidity to maintain comfortable environment.
However, in order to maintain good air quality, not all the air is recirculated. Some of the air leaks out through doors, windows, etc. and some fraction of the circulating air is intentionally exhausted outside the building. This is referred to as exhaust air. The exhaust air is replaced by an intake of outside air, also known as makeup air, to make up for the exhaust air being taken out. This is also referred to as “fresh air” or ventilation. This replacement of air is done because occupants of the building and the equipment consume oxygen and emit carbon dioxide (CO2) as well as a variety of other contaminants that gradually compromise quality and safety of the air. Such replacement of the air maintains fresh air quality.
Oxygen represents approximately 21% of atmospheric air and that is normally the desired level of indoor air as well. On the other hand CO2 is present only in very low levels in the outside air, typically at a level of approximately 400 parts per million (“ppm”). Once elevated levels of CO2 or reduced levels of oxygen are created, a fairly significant amount of outside air is needed to bring their respective concentrations close to the desired level. Indeed, to fully restore oxygen and CO2 concentration virtually all the air may need to be replaced.
The outside air represents an additional, and depending on the outside climate conditions often a significant, thermal load on the air handling unit. In the case of a hot and humid climate, for example, the outside air injected into the HVAC system can require additional energy for cooling and dehumidifying the outside air and can represent a significant fraction of the entire thermal load and energy usage of the HVAC system.
The amount of exhaust air and outside air can be adjusted to meet the air quality standards. Certain minimum amounts of levels of oxygen, CO2 and other contaminants, a variety of organic gases collectively referred to as volatile organic compounds or VOCs, are often set to maintain air quality. In the USA, the American Society of Heating, Refrigeration and Air-conditioning Engineers (“ASHRAE”) issues guidelines, including the ASHRAE Standard 62, for the amount of outside air ventilation recommended for a given space and number of occupants. However, the greater the rate of air replacement, the more energy is consumed by the HVAC system.
In some embodiments, the amount of supply air used by an HVAC system, and hence the amount of energy used for heating and cooling, while maintaining desirable air quality and composition, can be reduced by removing unwanted substances such as gases, including carbon dioxide (CO2), contaminants, particles, etc. using scrubbers or other devices that can separate these gases from the circulating air. Optionally, the quality of air can be further improved with injection of concentrated oxygen. In some embodiments, a fraction of the circulating air can be diverted though the scrubbers to achieve the desired result. While in a normal HVAC system frequent extensive replacement of the building air is performed, scrubbing of CO2 and other unwanted gases and vapors, can achieve the same goal, but with much lower thermal load on the HVAC system, thereby providing significant energy saving for the building and reducing demands on the entire electrical grid.
In some embodiments, the HVAC system can include an oxygen injection system that can inject oxygen-enriched air into the circulated air.
In some embodiments, a control system for use with an HVAC system can include a gas scrubbing system for removal of an unwanted substance gas from circulated air. The control system can include a sensor for determining an amount of the unwanted substance(s), particle(s), gas(es), etc. in the circulated air. A minimum level of outside air replacement can be maintained, and a controller can modify a rate of exhaust of circulating air and intake of outside air so as to adjust overall air replacement according to the measured amount of unwanted substance(s), particle(s), gas(es), etc. in the circulated air. The control system also can include an oxygen sensor for determining an amount of oxygen in circulated air. The controller can further modify the rate of oxygen injection.
In some embodiments, the system can be a modular system that can be connected to an HVAC system that can circulate air in an enclosed environment. The modular system can include a module for scrubbing configured to reduce a level of an unwanted substance in the circulating air.
In some embodiments, the current subject matter relates to a system for circulating air in an enclosed environment. The system can include an inlet configured to receive an outside air from outside of the enclosed environment and an air handling unit coupled to the inlet to receive the outside air through the inlet and configured to receive a circulated air from the enclosed environment. The air handling unit can be configured to affect a temperature of at least one of the received outside air and the received circulated air. Based on the received outside air and the received circulated air, the air handling unit can be further configured to generate air for supplying to the enclosed environment. The current subject matter system can also include an air circulation system configured to circulate the generated air from the air handling unit to the enclosed environment and back to the air handling unit and a scrubbing system coupled to at least one of the air handling unit and the air circulation system and configured to reduce presence of at least one substance in the air supplied to the enclosed environment.
In some embodiments, the current subject matter relates to a process for circulating air in an enclosed environment. An outside air from outside of the enclosed environment and a circulated air from the enclosed environment are received. At least one of the received outside air and the received circulated air are conditioned so as to supply at least one of the received outside air and the received circulated air at a desired temperature to the enclosed environment. The conditioned air is circulated into and from the enclosed environment. At least some of the received circulated air from the enclosed environment is scrubbed to reduce presence of at least one substance in the circulated air. The scrubbed air is recirculated. At least a portion of the circulated air is exhausted from the enclosed environment.
In some embodiments, the current subject matter relates to a control system for use with an HVAC system having a gas scrubbing system for removal of an unwanted gas from circulated air. The control system can include a sensor for determining an amount of the unwanted gas in the circulated air and a controller configured to modify a rate of exhaust of circulated air or intake of outside air so as to adjust an overall air replacement according to the measured amount of unwanted gas in the circulated air.
The details of one or more variations of the subject matter described herein are set forth in the accompanying drawings and the description below. Other features and advantages of the subject matter described herein will be apparent from the description and drawings, and from the claims.
The current subject matter is described with reference to the accompanying drawings. In the drawings, like reference numbers indicate identical or functionally similar elements. Additionally, where applicable, the left-most digit(s) of a reference number identifies the drawing in which the reference number first appears. In the figures:
In operation, the fans or blowers that can be disposed in the AHU 106 force the flow of the conditioned supply air (“SA”) through ducts that distribute the conditioned air throughout the various parts of the occupied space 102 (which can be an enclosed environment). For ease of illustration, the following description refers to a building as an example of an enclosed environment 102. The building 102 can have different zones for which rates of air flow can be different. Return air can flow back to the air handling unit 106 via lines 114 and can be filtered to remove particles, bacteria, substances, various fumes, and/or a combination thereof. Some of the return air can be exhausted outside the building 102 as exhaust air. The air can be exhausted through valves that control the amount of exhaust air being released. At the same time, fresh outside air can be pulled in to replace the exhaust air and maintain a correct overall volume and pressure of air in the building 102. Typically 10-15% of airflow can be released as exhaust and replaced, but this number can vary widely. In some environments, such as bathrooms and kitchens, the HVAC system can be configured to exhaust and replace 100% of the air flow. The constant replacement of exhaust air with outside air can be intended to maintain good air quality, and in particular, replenish oxygen consumed by the building occupants and remove substances, particles, gases (e.g., carbon dioxide), fumes other compounds, and/or a combination thereof generated by occupants, equipment and/or materials located inside the enclosed environment 102.
In some embodiments, the enclosed environment 102 can be an office building, a commercial building, a bank, a residential building, a house, a school, a factory, a hospital, a store, a mall, an indoor entertainment venue, a storage facility, a laboratory, a vehicle, an aircraft, a ship, a bus, a theatre, a partially and/or fully enclosed arena, an education facility, a library and/or other partially and/or fully enclosed structure and/or facility which can be at times occupied by equipment, materials, live occupants (e.g., humans, animals, synthetic organisms, etc.), etc., and/or any combination thereof.
In some embodiments, only a fraction of the circulating air stream can be diverted to the scrubber, which can intercept the flow of the diverted air. The scrubber can subsequently allow scrubbed air to continue to flow back into the general circulation with substances, compounds, particles, fumes, gases (e.g., CO2), etc. partially and/or fully captured, filtered, and/or removed from the scrubbed air. As shown in
In some embodiments, to absorb substances, compounds, particles, fumes, gases, etc. the scrubber 204, 208, 212 can use adsorbent materials, molecular sieves, porous materials, sponge-like materials, electrically and/or electro-magnetically charged liners or objects, any other chemical, biological attractants, and/or any combination thereof. Such materials can be placed in a container, stacked in columns, disposed as a sheet or a lining the inside of one or more lines of the system shown in the
More recent developments in the field of solid adsorption or CO2 include metal organic frameworks (U.S. Pat. No. 6,930,193 to Yaghi et al.; U.S. Pat. No. 7,662,746 to Yaghi et al.) and amine-impregnated clays (U.S. Pat. No. 6,908,497 to Siriwardane). These adsorbents can be suitable for use in the current subject matter systems described herein. The current subject matter system can be implemented with any past, currently-available, and future adsorbents designed to scrub or “clean” air. In some embodiments, the combination of several different adsorbents in the same unit or as separate units may offer the better performance.
As such substances, particles, fumes, gases, hazardous vapors (e.g., radioactive vapors) etc. (hereinafter, “substances”) captured from the circulating air accumulate in the scrubber 310, the substances can be removed from the scrubber 310 at a predetermined rate. Removal of substances can be referred to as a “regeneration” or a “regeneration cycle”. Such substances can be released into the atmosphere or otherwise collected, disposed of, sequestered, and/or any combination thereof. Regeneration can be achieved by a combination of heating, purging, pressure change, electrical energy, and/or any combination thereof. In some embodiments, the release of substances can be achieved by a combination of heating and purging with air or other purge gas. Thus, an adsorption-desorption cycle can sometimes be referred to as a temperature-swing adsorption.
As stated above, during the regeneration cycle, the scrubber 310 can be isolated from the HVAC system circulation by Valves 1 and 2, shown in
In some embodiments, the scrubber adsorbent bed design can include an appropriate choice of adsorbent material, its amount, its spatial distribution, an air flow pattern and its overall capacity can be compatible with various airflow design requirements. In designing the scrubber, system size and cost versus throughput, frequency of regeneration and energy requirements for regeneration can be also considered. The amount of substances, CO2, VOCs, etc. that can be collected and released in each temperature swing adsorption cycle can depend on the amount of active and accessible adsorbent material, and for certain adsorbents can depend on the temperature gap between the adsorption and purge cycle. Thus, to achieve a certain rate of gas capture one can use less material and operate with more frequent purge cycles. The cycles as well as their frequency can also depend on natural kinetic rates of adsorption and desorption for a particular material, flow rate and temperature that constrain the cycle time for a given amount of material. To minimize energy required, i.e., the energy that can be required to heat the purge gas, a lower purge gas temperature can be used, which can reduce the amount of material desorbed per cycle. In an application that is primarily driven by energy savings, one can start with the temperature and volume of purge gas that can be generated using an excess heat of the HVAC system and use that available purge temperature to design the thermal range of the temperature swing cycle, which in turn will determine the kinetics of the adsorbent design the dimensions of the bed.
In some embodiments, an HVAC system having temperature swing adsorption with solid adsorbents can provide simplicity, durability, scalability to different sizes, and a relatively low operating cost. There are many other ways to remove substances, CO2, VOCs, as well as other unwanted gases, fumes, and/or vapors. In some embodiments, substance, CO2, VOC, etc. scrubbing can be achieved by reactions with alkaline hydroxide bases. In some embodiments, substance, CO2, VOC, tec. scrubbing can be achieved using aqueous amine gas solutions, such as monoethanolamine or other amines that are well known. In some embodiments, scrubbing can be achieved by a chemical cycle in which sodium carbonate combines with carbon dioxide and water to form sodium bicarbonate (e.g., U.S. Pat. No. 3,511595 to Fuchs). Other techniques for removal of substances, CO2, VOCs, etc. can include selective membranes, for example, PRISM membranes from Air Products, Inc, or CYNARA membranes from Cameron International Corp. Since the scrubber can be a separate module in this systems, other scrubbing technologies (past, currently available, or future) can be used in such system without having to change its other components.
In some embodiments, to regenerate the scrubber, at least some of the above techniques can use heat for regeneration. Some of that heat can be obtained by harvesting waste heat produced by other systems nearby, including the compressor and the air handling unit of the HVAC system, as well as solar energy. This can further improve the overall economics of the system. In some embodiments, the purging of the adsorbent bed utilizes warm air from the cooling unit to purge the bed during regeneration. In some embodiments, solar energy can be collected on a rooftop unit and/or a separately located unit and used to heat the purge gas. Solar heating and harvesting compressor heat and other wasted heat can be used in combination with one another to minimize the energy usage of the system as a whole. Independent or additional heating can be performed to achieve a particular purge gas temperature in which case a heating coil, a furnace or a gas burner can be incorporated to the system before the entry point of the purge gas.
Referring back to
In some embodiments, the scrubber can collect CO2 and potentially other substances that can be disposed of in various ways. The collected substances can be released to the atmosphere, collected in containers for handling and disposing at another location, flowed through pipelines to another location or facility to be stored, processed and/or utilized, or otherwise disposed of in any other fashion. For example, CO2 is beneficial for greenhouses and could be directed to such greenhouses by pipes or by containers. Alternatively, these byproduct gases can be sequestered indefinitely simply to avoid releasing them into the atmosphere. There can be a higher cost to such disposition of these gases and, in some situations, it might not necessarily be economically justifiable to do so.
The oxygen concentrator 406 can be implemented in a number of ways. In some embodiments, the technique for oxygen concentration can include a known Pressure Swing Adsorption (“PSA”) technique, Vacuum Swing Adsorption (“VSA”) technique, and/or any other technique and/or any combination thereof. Systems employing these techniques can come in different sizes and output capacities, as stand-alone systems for providing concentrated oxygen directly from air, as well as in any other forms. Example VSA oxygen generating systems include at least one of the following: the PRISM VSA oxygen generation systems by Air Products Inc.; the OXYSWING product line by Innovative Gas Systems, Inc.; the ADSOSS line of oxygen generators by Linde; the VPSA oxygen generating system from Praxair Inc. These PSA/VSA systems can utilize highly porous adsorptive solids, usually a synthetic zeolite bed, in one or more container, typically shaped as a cylindrical column, and can use pumps and compressors to change the pressure of gases in these containers. The technique can rely on differential adsorption of oxygen and nitrogen onto the adsorbent. Thus, it can take an inflow of normal air (or other gas mixtures) and generate two separate outputs: an oxygen-concentrated air and oxygen-depleted air. One of the advantages of PSA/VSA systems is that these systems can continually generate oxygen for extended periods without much maintenance.
Other ways to separate or concentrate oxygen are also available. Cryogenic separation can be an effective way for large volumes and high purity, where the different condensation/boiling temperatures of different gases are used to separate oxygen from air. Selective membranes and selective diffusion media can also separate oxygen from air. Concentrated oxygen can also be generated from electrolysis of water, where electrical current through water generates oxygen gas on one electrode and hydrogen gas at the other. While these are energy intensive processes, pure hydrogen or nitrogen created as by products and can be collected and utilized for other applications.
In some embodiments, the presence of both the scrubber 402 and the oxygen concentrator 406 does not eliminate exhaust air and outside air. In some embodiments, exhaust air and outside air can be kept at a controlled level, which can be lower than in a conventional HVAC system but at a level that can be warranted or desired in order to assure that there is no gradual deterioration in air quality despite the benefits of the oxygen concentrator and the scrubbers.
In embodiments where the oxygen concentrator 406 is not used, the scrubber 404 can be configured to provide a majority of benefits related to circulation of quality air. This can be useful in scrubbing of carbon dioxide. While oxygen consumption and CO2 emission go hand in hand and occur in almost identical molecular quantities, which can imply that a drop in oxygen concentration can be commensurate with a rise in CO2 levels, as long as makeup air in the HVAC system is not eliminated altogether, even without a scrubber and an oxygen source, the oxygen and CO2 levels can stabilize at certain asymptotical concentrations that together sum up approximately to 21%, the same as that of outside air. The asymptotic level of oxygen, X, is given by
where X0 is the concentration of oxygen in outside-air, Bo is the net amount of oxygen consumed (in CFM, liters/second or any other units) by the occupants and M is the amount of outside air injected (in same units, CFM, liter/second, etc respectively). Similarly, CO2 level, Y, can be calculated by
where Y0 is the concentration of CO2 in outside-air and Bc is the net amount of CO2 produced by the occupants of the occupied space. Thus, as long as Bc ≈ Bo, at least approximately, then X+Y ≈ X0+Y0. However, adding a scrubber that extracts CO2 at a rate, Sc, (in same units, CFM, liter/second, etc. respectively) can result in
Analogously, the impact of an oxygen generator injecting at a net rate of Go (in same units, CFM, liter/second, etc., respectively) can change the asymptotic value of X to
For illustration purposes only, to understand why oxygen replenishment is less critical, the following example is provided: if outside air is at the normal 21% oxygen, and occupants of the occupied space consume oxygen at a rate of 2 CFM (cubic feet per minute) and exhale CO2 at a similar rate, and if makeup air is at a relatively low 100 CFM, with no scrubbing or oxygen injection, then oxygen can gradually approach 19%, while CO2 can approach 2%. There can also be elevated levels of other VOCs alongside the CO2. Whereas a 19% concentration of oxygen can be acceptable, a 2% concentration of CO2 is not. Further, the VOC levels most likely will be unacceptably high as well. Thus, adding a scrubber with Sc = 2CFM capacity alone could bring CO2 levels down to normal. Oxygen can still be depleted approximately to 19%, unless supplemental oxygen is injected, but even so air quality might be acceptable at this level even without an oxygen source, and can require less hardware and less operating costs.
The sensors 531, 533, 535 can be installed in various locations in the occupied space 102 and can be configured to provide a feedback to the system 502 system. Sensors (Y) can be distributed through the occupied space and detect levels of one or more substances, gases (such as CO2 and/or oxygen, and other gases), fumes, vapors, VOCs, etc., and/or any combination thereof. Sensors for CO2 are commercially available, examples of which include C7232 sensor from Honeywell Corp., TELAIRE sensors from General Electric, etc. Upon detection of and/or a particular concentration such substances, gases, etc., the sensor(s) (Y) can be configured to generate a data signal that can be transmitted to the central control system 502 for processing. After processing the data signal(s), system 502 can generate appropriate commands to components within the system 500 (e.g., turn on a regeneration cycle of the scrubber 506; perform adsorption cycle at a predetermined time or when concentration of a substance reaches a certain level).
As stated above central control system (CC) 502 can be human operated, automated and/or computerized and can detect a signal from the sensors (Y). Based on these and the various parameters and settings of the system 500, the CC 502 can control and/or modify at least one of the following, in order to achieve targeted conditions: OC power (on/off), OC settings, OC valves (OC is not shown in
The control system 502 can permit the amount of scrubbing or injection of oxygen to be adjustable, whether directly or indirectly, whether electronically or manually. Adjustments can be achieved by changing the power or settings applied to the various compressors, pumps, motors, heaters, actuators or valves associated with the scrubbers and the oxygen concentrators. The adjustments to the amount of scrubbing or oxygen injection can be automatically done in response to a measurement of air quality or air composition in one or more locations. The adjustments to the amount of scrubbing or oxygen injection can also be automatically done based on building occupancy, time of day, day of the week, date, season or outside climate.
In some embodiments, the scrubber 506 can be set to run at a constant operating mode. The capacity and efficiency of the scrubber 506 in that mode can be selected based on the occupied space and the amount of activity in the occupied space, so as to maintain desirable levels of CO2 (and/or other substances). In some embodiments, the control system 502 can control a rate of exhaust air and outside air. The baseline can be a preset minimum. If the capacity and efficiency of the scrubber is insufficient to handle the CO2 load, then the rate of exhaust air and outside air can be adjusted automatically to a higher level. The oxygen flow can be separately controlled to maintain a target level of oxygen in the occupied space. Both the control of the exhaust air valves and the oxygen inflow can be subject to a feedback loop, with a proportional-integral-differential (“PID”) algorithm with upper and lower set points. The coupling of the oxygen concentrator to the air flow manifold can be done using any tube of duct fitting, with or without a control valve and/or a flow meter.
In some embodiments, the system can be designed in a modular way so that it can be retrofitted on a pre-existing or pre-designed HVAC system. This can be beneficial in buildings that already have HVAC systems, as the integration of the system can have relatively lower costs. The oxygen concentrator and scrubber, with a control system, can be installed and connected to a conventional HVAC system without having to replace the ductwork or the central air handling unit.
In some embodiments, the current subject matter relates to a system for circulating air in an enclosed environment. The system can include an inlet configured to receive an outside air from outside of the enclosed environment and an air handling unit coupled to the inlet to receive the outside air through the inlet and configured to receive a circulated air from the enclosed environment. The air handling unit can be configured to affect a temperature of at least one of the received outside air and the received circulated air. Based on the received outside air and the received circulated air, the air handling unit can be further configured to generate air for supplying to the enclosed environment. The current subject matter system can also include an air circulation system configured to circulate the generated air from the air handling unit to the enclosed environment and back to the air handling unit and a scrubbing system coupled to at least one of the air handling unit and the air circulation system and configured to reduce presence of at least one substance in the air supplied to the enclosed environment.
In some embodiments, the current subject matter can also include one or more of the following optional features. The scrubbing system can be configured to intercept at least a portion of the received circulated air prior to the circulated air reaching the air handling unit. The scrubbing system can intercept at least a portion of the circulated air after the circulated air is processed by the air handling unit. In some embodiments, between approximately 1% to approximately 50% of the circulated air can be diverted to the scrubbing system and a remainder of the circulated air can bypass the scrubbing system. In some embodiments, between approximately 3% to approximately 25% of the circulated air can be diverted to the scrubbing system and a remainder of the circulated air can bypass the scrubbing system. In some embodiments, between approximately 5% to approximately 15% of the circulated air can be diverted to the scrubbing system and a remainder of the circulated air can bypass the scrubbing system. In some embodiments, at least one substance in the air is carbon dioxide. In some embodiments, at least one substance in the air can include at least one of the following: volatile organic compounds, carbon monoxide, nitrous oxides and sulfur oxides.
The current subject matter system can include a control system coupled to at least one sensor, where at least one sensor is disposed in at least one of the following: the enclosed environment and the air circulation system. At least one sensor can determine a composition of the circulated air and provide the determination of the composition of the circulated air to the control system. Based on the determination of the composition of the circulated air, the control system can control at least one of the following: the scrubbing system and the air inlet system, and can be further configured to maintain a desired composition of the circulated air. An airflow through the inlet is such that the desired air quality can be maintained with a lower amount of outside air than would be possible without the scrubbing system.
The scrubbing system can include at least one adsorbent, wherein a concentration of the at least one substance is reduced by adsorption of the at least one substance onto the adsorbent. At least one adsorbent can include at least one of the following: a molecular sieve, a synthetic zeolite, an activated charcoal, porous alumina, silica gel, a clay-based material, and a metal organic framework. The scrubbing system can include at least one additional adsorbent. At least one additional adsorbent can be mixed with the at least one adsorbent in the scrubbing system. The scrubbing system can include a plurality of beds, wherein each bed in the plurality of beds is configured to intercept a flow of circulated air, and at least two of beds in the plurality of beds have different adsorbents. The scrubbing system can also include a system for controlling a reversible chemical reaction that includes carbon dioxide. The reversible chemical reaction can be a sodium carbonate and sodium bicarbonate cycle. Also, the reversible chemical reaction can be between an amine compound and carbon dioxide. The scrubbing system can utilize one or more bases. The base can be an alkaline hydroxide. The scrubbing system can be a temperature swing adsorption system. The scrubbing system can further include a purge cycle during which a purge substance is applied to the scrubbing system to release the at least one substance from the scrubbing system. The purge substance can be gas. The purge substance can be heated by applying heat generated a component of a heating, ventilation and air-conditioning system incorporating the air circulation system.
The current subject matter system can include a heating system configured to heat the purge substance. The heating system can use solar energy. The scrubbing system can include an adsorbent and a cooling system configured to cool the adsorbent, wherein the cooling system uses a chilled fluid provided by the air handling unit. The scrubbing system can be coupled to the air circulation system such that at least one part of the circulated air is configured to flow through the scrubbing system and at least another part of the circulated air is configured to bypass the scrubbing system.
The current subject matter system can also include an oxygen injection system that injects oxygen or an oxygen-concentrated air into the circulated air. The current subject matter system can further include a control system coupled to at least one sensor disposed in the enclosed environment. At least one sensor can determine an oxygen level in the circulated air and provide the determination of the oxygen level in the circulated air to the control system. Based on the determination of the oxygen level in the circulated air, the control system can control the oxygen injection system so as to maintain a desired level of oxygen in the circulated air. The oxygen injection system can include at least one of the following: a pressure swing adsorption and a vacuum swing adsorption system.
In some embodiments, the current subject matter relates to a control system for use with an HVAC system having a gas scrubbing system for removal of an unwanted gas from circulated air. The control system can include a sensor for determining an amount of the unwanted gas in the circulated air and a controller configured to modify a rate of exhaust of circulated air or intake of outside air so as to adjust an overall air replacement according to the measured amount of unwanted gas in the circulated air.
Further features and advantages of the invention, as well as structure and operation of various embodiments of the current subject matter, are disclosed in detail below with references to the accompanying drawings.
Example embodiments of the methods and components of the current subject matter have been described herein. As noted elsewhere, these example embodiments have been described for illustrative purposes only, and are not limiting. Other embodiments are possible and are covered by the current subject matter. Such embodiments will be apparent to persons skilled in the relevant art(s) based on the teachings contained herein. Thus, the breadth and scope of the current subject matter should not be limited by any of the above-described exemplary embodiments, but should be defined only in accordance with the following claims and their equivalents.
This application is a continuation of U.S. Pat. Application No. 16/983,636, filed Aug. 3, 2020, which is a continuation of U.S. Pat. Application No. 16/144,733, filed on Sep. 27, 2018, (now U.S. Pat. 10,730,003), which is a continuation of U.S. Pat. Application No. 14/845,041, filed on Sep. 3, 2015, (now U.S. Pat. No. 10,086,324), which is a continuation of U.S. Pat. Application No. 13/937,320, filed on Jul. 9, 2013, which is a continuation of U.S. Pat. Application No. 13/440,356, filed on Apr. 5, 2012, (now U.S. Pat. No. 8,491,710), which is a continuation of U.S. Pat. Application No. 13/109,833, filed on May 17, 2011, (now U.S. Pat. No. 8,157,892), which is a continuation-in-part of U.S. Pat. Application No. 12/848,788, filed Aug. 2, 2010, and entitled “Method and System for Improved-Efficiency Air-Conditioning,” which claims priority to U.S. Provisional Pat. Application No. 61/345,194, filed May 17, 2010, and U.S. Provisional Pat. Application No. 61/351,968, filed Jun. 7, 2010. The disclosures of all of the above applications are incorporated herein by reference in their entireties.
Number | Date | Country | |
---|---|---|---|
61345194 | May 2010 | US | |
61351968 | Jun 2010 | US |
Number | Date | Country | |
---|---|---|---|
Parent | 16983636 | Aug 2020 | US |
Child | 18107438 | US | |
Parent | 16144733 | Sep 2018 | US |
Child | 16983636 | US | |
Parent | 14845041 | Sep 2015 | US |
Child | 16144733 | US | |
Parent | 13937320 | Jul 2013 | US |
Child | 14845041 | US | |
Parent | 13440356 | Apr 2012 | US |
Child | 13937320 | US | |
Parent | 13109833 | May 2011 | US |
Child | 13440356 | US |
Number | Date | Country | |
---|---|---|---|
Parent | 12848788 | Aug 2010 | US |
Child | 13109833 | US |