The present invention relates to distributed power generation systems, and more specifically, to detection and correction of unintentional island formation in distributed power generation systems.
Distributed power generation, in which relatively small electrical generation sources (sometimes known as distributed energy resources or DERs) that may be primarily intended to serve a specific load are interconnected with a larger-scale electrical power grid to enable sharing of excess power that they generate, is coming into increasing use as a way of facilitating the use of renewable energy resources and improving the overall reliability and efficiency of the power grid. A persistent problem in distributed power generation systems, however, is the hazard to personnel and equipment that occurs when a segment of the grid containing a DER becomes unintentionally disconnected from the remainder of the grid containing the primary central generation source. When a segment is disconnected, the DER may continue to power the disconnected segment, forming an “island.” This can endanger personnel who may be working to restore connection of the segment with the grid and may wrongly assume the islanded segment is not energized. Further, voltage or frequency deviations in the islanded segment may damage electrical equipment connected to the segment. For these reasons, industry standards such as IEEE 1547 have been developed that require distributed generators to detect unintentional island formation so that appropriate corrective action can be taken in a timely fashion.
Prior attempts have been made at developing methods for detecting island formation, and have included active, passive, and communications-based methods. None of these prior methods, however, have proven entirely satisfactory. For example, communications-based methods many be ineffective if communications are interrupted before an islanding event occurs. Some of the prior methods rely on complex signal processing techniques, which to be effective, often require the use of expensive, high-powered computational equipment. Other active prior islanding detection methods require the distributed generation system to inject a perturbation with a specific detectable signature. Such methods, however, require specialized equipment to generate, inject, and detect the signature.
What is still needed in the industry is an effective, yet relatively simple and inexpensive method for detection of islanding in distributed power generation systems.
Embodiments of the present invention address the need in the industry for an effective, yet relatively simple and inexpensive, method for detection of islanding in distributed power generation systems. According to embodiments of the invention, statistical analysis of the local line frequency, as measured at the distributed generator, is performed to detect when an island has been formed. The statistical characteristics of the local frequency are controlled by the grid when the distributed generator is not islanding. When an island is formed, however, frequency control switches to circuitry associated with the distributed generator. Because the statistical characteristics of the frequency control performed by the distributed generator are markedly different from those of the grid, the islanding condition can be detected.
The new passive method of islanding detection according to embodiments of the invention is tentatively named RoCoF-H, which stands for “Rate of Change of Frequency-Histogram.” This method involves measuring and recording the histogram of rate of change of frequency (RoCoF, also denoted df/dt), over a selected time period—in other words, the recent history of the rate of change of frequency—and then analyzing the histogram to extract an index value that allows a determination of whether the system is islanded. This value is then used in an anti-islanding decision algorithm to either command disconnection of the DER if an islanding condition is indicated, or to allow the DER to “ride-through” without disconnection if an islanding condition is not indicated.
The above summary is not intended to describe each illustrated embodiment or every implementation of the subject matter hereof. The figures and the detailed description that follow more particularly exemplify various embodiments.
Subject matter hereof may be more completely understood in consideration of the following detailed description of various embodiments in connection with the accompanying figures, in which:
While various embodiments are amenable to various modifications and alternative forms, specifics thereof have been shown by way of example in the drawings and will be described in detail. It should be understood, however, that the intention is not to limit the claimed inventions to the particular embodiments described. On the contrary, the intention is to cover all modifications, equivalents, and alternatives falling within the spirit and scope of the subject matter as defined by the claims.
In
In
In
According to embodiments of the invention, the differing distributions of |df/dt| depending on whether feeder 10 is grid-tied or is islanded can be used to detect an islanding condition. As depicted conceptually in
It will be appreciated that over any time period T, there will be determinable numbers of events that fall into each of Bin 1, Bin 2, and Bin 3. Using observed values for the respective numbers of these events over the time period T, a bimodality index BI can be computed as follows:
where Bin1, Bin2, and Bin3 are the histogram bins with boundaries chosen to correspond to the low, middle and high groupings depicted in
It will be appreciated that the threshold values ToB1 and ToB2 should be selected to maximize the probability that the desired “middle distribution” depicted in
It will also be appreciated that it is important in an island detection method to balance detection effectiveness with some degree of false-trip immunity—accordingly, it is desirable to carefully select the decision criterion for determining whether a given result indicates the DERs should “ride-through,” or an unintentional island case, in which the DERs should disconnect or enter a “micro-grid” mode. For example, a complicating factor can be the effect of large local switching events, such as a heavily-loaded large motor switched to the feeder.
One preferred approach to address this is a technique developed by the inventor and called the “zero-time” method: over a given time window, the number of samples is determined for which BI=0, and the duration represented by those samples is summed and compared to the total window duration. For example, if a five-second window is chosen, and the total duration for which BI=0 is less than 1 second, an island would be indicated. These times (the five and 1 second times) can be adjusted to improve response speed, if the system's properties will permit this without a loss of selectivity. The inventor has found that an accurate indication of island formation for most systems is obtained when the value of BI is in the range of 0<BI<10 over more than 75% of a given window duration. Selectivity in some cases can be enhanced by using extremely high values of BI to suggest a system-wide event instead of an island and command a ride-through of the DERs. Another method is to use the average of BI over a shorter window, but this method is inferior in selectivity. Standard deviation of BI over a window (or standard deviation of df/dt directly) may also be used, but this may be significantly inferior in selectivity.
Table 1 below is a table presenting the results of exemplary simulations using the RoCoF-H method according to the invention and the “zero-time” criterion. Representative simulation results are reported on two feeders. The two feeders were: (1) the IEEE 34-bus distribution feeder, which is unusually long, mostly overhead, and high-impedance; and (2) a real-world feeder of medium stiffness (medium impedance) and serving a suburban region. Modeling was performed using EMTP-RV and MATLAB/Simulink, and in the case of the real-world feeders, using detailed observed feeder data supplied by the electric utility serving the feeders.
On each of the two feeders, four cases were simulated. The first two cases were chosen to represent difficult cases for island detection. Case A is a multiple-inverter case, in which many three-phase inverters were added to the feeder until a generation-load match could be achieved. As one example, the number of three-phase inverters added to the IEEE 34 bus system was 18. These inverters were spread along the feeder because the inductance between the inverters is believed to exacerbate the loss of anti-islanding effectiveness in the multi-inverter case. Phase-phase balancing was achieved by adding single-phase inverters to the more heavily loaded phases.
Case B was a case involving a mixture of types of DER. From an anti-islanding perspective, the most difficult combination of DERs arises when inverter-based DERs are combined with synchronous generators, so that is the case that was selected here. Some of the inverters in the multiple-inverter case were removed to make room for a single 1 MVA synchronous generator.
The latter two cases C and D do not involve islands, but instead are indicative of false-trip immunity (i.e., cases in which ride through is desired). Case C was a desired ride-through case simulating a loss of mainline generation resulting in a system-wide frequency event. In this case, it is highly desirable that the island detection method be able to distinguish this case from an unintentional islanded case and stay online to support the system. For this simulation, the frequency trajectory used was one measured during a major Italian blackout of 2003, scaled to 60 Hz. To implement this frequency trajectory, a programmable variable-frequency source was created in EMTP-RV and programmed to follow this trajectory based on a lookup table.
Case D is another ride-through case, this one involving a major local switching event such as mentioned above with respect to
In each of the simulations, ToB1 was set to 3 mHz/sec, and ToB2 to 8 mHz/sec. The frequencies were measured by a phase-locked loop.
As can be seen, the RoCoF-H method and “zero-time” criterion achieved the desired result in each of the simulated cases for both feeders.
In use, the RoCoF-H method is applied to a DER coupled to a grid-tied feeder by first determining the appropriate ToB1 and ToB2 values to be used with the system. Although the baseline values of 3 mHz/s and 8 mHz/s as discussed above are expected to be appropriate for use with most systems, it may be necessary to adjust these values to fit the individual characteristics of the feeder and the frequency control and monitoring equipment used with the DER. It may be necessary to conduct a system study in simulation and observe the histograms. The inventor has discovered that while it is usually possible to determine the grid-tied histogram simply through measurements, it is often not possible to obtain the islanded histogram experimentally.
As depicted in block diagram form in
Various embodiments of systems, devices, and methods have been described herein. These embodiments are given only by way of example and are not intended to limit the scope of the claimed inventions. It should be appreciated, moreover, that the various features of the embodiments that have been described may be combined in various ways to produce numerous additional embodiments. Moreover, while various materials, dimensions, shapes, configurations and locations, etc. have been described for use with disclosed embodiments, others besides those disclosed may be utilized without exceeding the scope of the claimed inventions.
Persons of ordinary skill in the relevant arts will recognize that the subject matter hereof may comprise fewer features than illustrated in any individual embodiment described above. The embodiments described herein are not meant to be an exhaustive presentation of the ways in which the various features of the subject matter hereof may be combined. Accordingly, the embodiments are not mutually exclusive combinations of features; rather, the various embodiments can comprise a combination of different individual features selected from different individual embodiments, as understood by persons of ordinary skill in the art. Moreover, elements described with respect to one embodiment can be implemented in other embodiments even when not described in such embodiments unless otherwise noted.
Although a dependent claim may refer in the claims to a specific combination with one or more other claims, other embodiments can also include a combination of the dependent claim with the subject matter of each other dependent claim or a combination of one or more features with other dependent or independent claims. Such combinations are proposed herein unless it is stated that a specific combination is not intended.
Any incorporation by reference of documents above is limited such that no subject matter is incorporated that is contrary to the explicit disclosure herein. Any incorporation by reference of documents above is further limited such that no claims included in the documents are incorporated by reference herein. Any incorporation by reference of documents above is yet further limited such that any definitions provided in the documents are not incorporated by reference herein unless expressly included herein.
For purposes of interpreting the claims, it is expressly intended that the provisions of 35 U.S.C. §112(f) are not to be invoked unless the specific terms “means for” or “step for” are recited in a claim.
This application is a continuation of application Ser. No. 13/689,153, filed Nov. 29, 2012, entitled METHOD AND SYSTEM FOR ISLAND DETECTION AND ANTI-ISLANDING PROTECTION IN DISTRIBUTED POWER GENERATION SYSTEMS, which claims the benefit of U.S. Provisional Patent Application No. 61/565,292, entitled METHOD AND SYSTEM FOR ISLAND DETECTION AND ANTI-ISLANDING PROTECTION IN DISTRIBUTED POWER GENERATION SYSTEMS, and filed Nov. 30, 2011, each of which is hereby fully incorporated herein by reference.
Number | Date | Country | |
---|---|---|---|
61565292 | Nov 2011 | US |
Number | Date | Country | |
---|---|---|---|
Parent | 13689153 | Nov 2012 | US |
Child | 15066703 | US |