Embodiments described herein generally relate to methods, systems and apparatus for using the vapor compression cycle in the active cooling of downhole tools and equipment. Embodiments of the present invention may be utilized in oil, gas, geothermal, water, and CO2 wells, as well as any subsurface application known to one skilled in the art.
The oil and gas exploration and production industry is likely to drill and produce deeper and hotter wells, with wells with a reservoir temperature above 150° C. forecast to increase. In general, these types of wells are considered a high pressure high temperature, or HPHT, environments. In addition, an increasing number of Ultra HPHT (high pressure high temperature with the temperature above 205° C.) wells are likely to be drilled in the future. Using conventional technologies, downhole tools experience high failure rates at temperatures above 160° C. At this time, there is a limited catalog of electronic components which can reliably operate above 150° C. Therefore, providing active/passive cooling for electronics is one of the options for extending the operation and reliability of downhole tools such that they may be more effectively used in HPHT and Ultra-HPHT regimes.
Passive methods of cooling downhole tools provide cooling for a short duration as they provide a fixed capacity for heat absorption from the tool. If the tool is likely to be exposed to HPHT or ultra HPHT conditions for long duration, then active cooling methods need to be used. Active cooling methods use electric power to reject heat absorbed from the tool at lower temperatures to the wellbore fluid (or the formation) at a higher temperature.
Embodiments relate to a method of and apparatus for cooling equipment including exposing a fluid at a temperature T and pressure P to a surface in communication with electronic components mounted on a tool chassis, compressing the fluid to a temperature T1 and pressure P1, exposing the fluid to a surface in communication with liquid or gas or both external to the tool wherein the fluid after exposure to the surface is at a temperature T2 and pressure P2, and allowing the fluid to expand to a temperature T3 and pressure P3 wherein the equipment is a tool in a subterranean formation and T is less than T2 and P is less than P2. Embodiments relate to an apparatus and methods for cooling oil field services tools including a tool that is in communication with a fluid that conducts heat from the tool to the fluid, a compressor that accepts fluid from the tool, a heat exchanger that accepts fluid from the compressor and that rejects heat from the fluid to the surrounding fluid or formation, and a valve or orifice to accept fluid from the compressor and to return fluid to the chassis within the tool wherein the compressor is controlled by a controller and the controller accepts temperature information from the tool and the surrounding fluid or formation. Embodiments relate to a method and apparatus for cooling an oil field services tool including exposing a fluid to a tool comprising electronic components, compressing the fluid in a compressor, exposing the fluid to a surface in communication with liquid or gas or both external to the tool, allowing the fluid to expand, and controlling the compressor using a temperature of the liquid or gas or both external to the tool. In some embodiments, the compressor includes a variable frequency drive and/or a temperature measurement of the surrounding formation and/or wellbore. In some embodiments, the fluid is water, brine, drilling mud, and/or formation fluid. In some embodiments, the fluid is paste, liquid, and/or pressurized gas.
The techniques used for cooling downhole tools in high temperature environments may be broadly classified in two—passive cooling and active cooling.
Passive Cooling
As the name suggests, this class of thermal management does not use energy or electric power to provide cooling. Commonly vacuum jacketed pipes, high insulation materials, and phase change materials are used for reducing heat ingress from the high temperature environment of the wellbore while providing a mechanism for cooling the components inside the tool body. However, this strategy can only provide limited cooling capacity for tools in a high temperature environment. It is a useful strategy for some downhole tools that are only deployed for a short duration. However, for certain tools that have longer mission profiles at high temperatures, the options for avoiding failure of electronic boards are either providing active cooling of standard electronic components or specially designed high temperature electronic components.
Active Cooling
It is useful to define the problem in standard terms. Consider Tc as the temperature at which we need to maintain the tool, while the wellbore temperature is Th. Let Q is sum of the rate of heat leaked through the housing to the tool and the rate of heat generated on the chassis (where the electronic components are mounted), and W is the rate of work done on the system. It is possible to construct a thermodynamic cycle (commonly referred to as a heat pump) to absorb heat Qc at a cold temperature Tc and reject it at higher Th using W as the work done. Note that the Clausius statement of the second law of thermodynamics states that heat generated cannot spontaneously flow from a material at a lower temperature to a material at a higher temperature. Therefore, any embodiment of a strategy to absorb heat continuously at Tc and rejecting it at Th will require input work or electric power.
It is important to choose the most appropriate thermodynamic cycle and working fluid for absorption of heat from the tool and dissipation of heat to the drilling mud. It would be appropriate to choose a thermodynamic cycle with the highest possible efficiency so that the power consumption downhole is minimized.
There are several techniques that may be used to provide this cooling. These include thermoelectric devices, sterling or pulse tube refrigerators, thermoacoustic coolers and our cycle of choice, the vapor compression cycle. Thermoelectric devices are generally used for local area cooling/heating and generally have low coefficient of performance (COP, defined as Qc/W). Thermoacoustic coolers, sterling cryocoolers and pulse tube refrigerators can all be described using the reverse-Brayton cycle (shown in
This cycle, as described is completely reversible as both compression and expansion are reversible. Therefore, it is the perfect embodiment of an ideal heat pump. Consider Tc=150° C. and Th=250° C. For a heat pump, the ideal or Carnot COP is defined as Tc/(Th−Tc)=4.12 for our process.
We simulated the above process using a process simulator Aspen HYSYS. The simulation results are shown in
Allowing for a tool heat pickup of 173.6 W at 150° C., we chose a temperature at T1 of 149.1° C. (since we needed a temperature below 150° C. for sensible heat transfer to the fluid). We assumed an ideal heat exchanger with the outlet fluid stream after absorbing heat from the tool at 150° C. We also assumed an ideal exchanger for cooling the compressed gas stream (T3 to T4 being 262.1° C. to 250° C., and 252.9° C. to 250° C.), which is compressed in two stages. The first stage of compression uses the work recovered in expansion of the gas stream from stage 4 to stage 1 and the second stage of compression uses an electric motor driven compressor (with input power Ws). The expansion across expander K-101 is considered to be ideal with an adiabatic efficiency of 100%.
This cycle is thus simulated to be as ideal as possible in a conventional simulator. The calculated COP for this process is 3.432, which is close to the Carnot COP of 4.12. In principle, a COP of 4.12 should be achievable if we increase the temperature at stage T1 from 149.1 to as close to 150° C. as possible. Practically, it would entail a much higher flow rate and an extremely large ideal heat exchanger E-101. The current example suffices to prove our point that, theoretically, the reverse-Brayton cycle and its many manifestations as sterling, pulse tube or thermoacoustic coolers are the most efficient heat pump cycle.
However, in a practical manifestation of this cycle, shown in
In this cycle, we chose Argon as the working fluid. T1 was chosen as 30.57° C. to get a reasonable flow rate for Argon. After heat pickup of 126.6 W from the tool, the temperature increased to 140° C., an approach of 10° C. to Tc of 150° C., so that we may be able to design a reasonable heat exchanger. The compressor and the expander adiabatic efficiencies were fixed at 75%, which is realistic. Fluid temperatures after rejecting heat to the wellbore at 250° C. were set at an approach of 10° C., to 260° C.
The COP for this practical cycle was calculated to be only 0.3236, almost a factor of ten below the ideal cycle and less than 10% of the Carnot COP.
As discussed previously, we selected the vapor compression cycle, or VCC. The vapor compression cycle is shown in red lines in the T-S space in
A schematic for this cycle is also shown in
Starting at stage 1, or saturated vapor, the fluid is compressed using a suitable compressor to point 2, labeled “Superheated Vapor”. This process requires work input, shown as Ws in
An ideal version of this cycle was simulated using Aspen HYSYS and the results are shown in
In this instance, the compressor adiabatic efficiency was assumed to be 100% and the heat exchangers were assumed to be 100% efficient, as for the ideal reverse-Brayton cycle. The ideal cycle COP is calculated to be 3.178, lower than the ideal reverse-Brayton cycle COP as expansion across the valve VLV-100 is not adiabatic (or iso-entropic of reversible). It is iso-enthalpic, or, in other words, there is loss of entropy associated with this process. About 110.7 W of heat are absorbed from the tool for this simulation.
A practical version of this cycle was simulated using Aspen HYSYS and the results are shown in
The compressor K-100 adiabatic efficiency was set at 75% and a 10° C. approach was used for all heat exchangers. The temperature of stream 4 (past the heat exchanger E-100) is cooled to 260° C. as Th is at 250° C. The two-phase fluid, stream 5 is introduced to the tool heat exchanger (e-101) at 140.7° C. It picks up 106.6 W of heat from the tool. The COP for this cycle is calculated to be 1.862, or 45.2% of the Carnot COP.
Therefore, it is obvious from the preceding discussion that although the reverse-Brayton cycle represents the highest achievable COP for an ideal cycle, for a practical thermodynamic cycle using components with reasonable efficiencies, the VCC represents the best option for cooling downhole tools.
Several versions of downhole cooling cycles are discussed for cooling downhole tools in U.S. Pat. No. 5,701,751, U.S. Pat. No. 6,769,487, U.S. Pat. No. 6,978,828 which are incorporated by reference herein.
This discussion is directed toward methods, systems and apparatus for active cooling of downhole tools using the vapor compression cycle. Additional methods, systems, apparatus for active cooling of downhole tools using the vapor compression cycle are further detailed in a section below entitled “Example Implementations.” These recited additional features, systems, methods and/or apparatus represent a non-exhaustive potential implementation and are recited for illustrative purposes.
Refrigerant Choice
The choice of a suitable refrigerant for this cycle requires a fundamental thermodynamic analysis. Most Freon based refrigerants commonly used for room temperature cooling are not suitable as they have low critical temperatures. For this particular application, it is useful to examine this cycle in the Temperature-entropy (or the T-S) space, shown in
In this cycle, there are several constraints on the choice of a fluid. Some of these are listed below.
We then conducted a search on fluids with a critical temperature between 300-1000° C. and a Triple point temperature below 100° C. The fluids with such properties include water, duodecane, propylcyclohexane, decane, methyl linoleate, methyl linolenate, methyl oleate, methyl palmitate, methyl stearate, nonane, toluene and heavy water. Of these fluids, water is the environmentally friendly, available freely and has a high latent heat of vaporization. Therefore, for our purpose, we choose this fluid for the vapor compression cycle.
Experimental Implementation
This thermodynamic cycle was demonstrated in a wireline tool.
Heating elements and thermocouples were installed on these faces to simulate heat generated from electronic components during operation. The chassis 902 is wired up with a thermocouple on each face and a 64 Watt heater around each Zone. These heaters are wired together in parallel and are controlled by a variable transformer to give a total distributed heat load across the delta chassis ranging from 30-190 W.
To simulate the high-temperature downhole environment, the chassis is put inside a vacuum insulated pipe, and the pipe is heated to simulate heating from the formation in which the tool may be operating. The pipe is heated by two 4.5 ft jacket heaters.
As shown in
During operation, the system operates with the internal fluid temperature maintained at 140° C. The system is charged with water to 38.3 psig, corresponding to saturated vapor/liquid conditions at 140° C. for water, and the external heating jackets are turned on.
In order to demonstrate the feasibility of the vapor compression cycle, testing has been done for the two temperatures, 200° C., and 250° C. When the refrigerant is able to absorb the heat that is being generated on the chassis, the zone temperatures remain close to 140° C., the saturated temperature of steam at 38 psig, the pressure in the chassis tubes. Once the chassis generated heat load exceeds the ability of the refrigerant to absorb the heat, Zone 4 begins to increase in temperature and the other Zones 3, 2 and 1 subsequently follow suit. The experimental results are shown in
The conditions are identical (to those in
This application claims benefit of U.S. Provisional Patent Application Ser. No. 61/415,540, filed on Nov. 19, 2010, and entitled, “Method for Active Cooling of Downhole Tools Using the Vapor Compression Cycle,” which is incorporated by reference herein in its entirety.
Number | Name | Date | Kind |
---|---|---|---|
3435629 | Hallenburg | Apr 1969 | A |
4467621 | O'Brien | Aug 1984 | A |
5020320 | Talbert et al. | Jun 1991 | A |
5099651 | Fischer | Mar 1992 | A |
5701751 | Flores | Dec 1997 | A |
6769487 | Hache | Aug 2004 | B2 |
6978828 | Gunawardana | Dec 2005 | B1 |
7231775 | Dilk et al. | Jun 2007 | B2 |
7428925 | Brown et al. | Sep 2008 | B2 |
20040112601 | Hache | Jun 2004 | A1 |
20050097911 | Revellat et al. | May 2005 | A1 |
20050257533 | Gunawardana et al. | Nov 2005 | A1 |
20060213660 | DiFoggio et al. | Sep 2006 | A1 |
20060213669 | Shipley et al. | Sep 2006 | A1 |
20080223579 | Goodwin | Sep 2008 | A1 |
20090272129 | Petty | Nov 2009 | A1 |
20100242534 | Stockton, Jr. | Sep 2010 | A1 |
20110146967 | Winslow | Jun 2011 | A1 |
20130104572 | DiFoggio | May 2013 | A1 |
Entry |
---|
“Design of Vapor-Compression Refrigeration Cycles” Published Sep. 7, 2002. http://www.qrg.northwestern.edu/thermo/design-library/refrig/refrig.html. |
International Search Report and Written Opinion of PCT Application No. PCT/US2011/061243 dated Nov. 5, 2012. |
Number | Date | Country | |
---|---|---|---|
20120125614 A1 | May 2012 | US |
Number | Date | Country | |
---|---|---|---|
61415540 | Nov 2010 | US |