The present invention is concerned with a method for fault location in uncompensated power lines with two-end unsynchronized measurement, finding an application in the power industry and for overhead and overhead-cable transmission or distribution lines.
Two-end unsynchronized fault location technique has been known from the article “Unsynchronized two-terminal fault location estimation”, Novosel D., Hart D. G., Udren E., Garitty J., IEEE Trans. on Power Delivery, Vol. 11, No. 1, pp. 130-138, January 1996 and from the patent U.S. Pat. No. 5,455,776. In these documents the solution has been proposed, that different types of symmetrical components of the measured voltages and currents can be used for determining the distance to fault. However, use of the zero sequence components was not recommended, what results that the fault location methods for both single and double-circuit lines is identical. The method from the mentioned article and paper consist of the following steps.
From the US patent application US 2004/0167729 there is a known solution that partial overcoming of the drawbacks depicted in the known methods. In the method according to this invention it has been proposed to avoid iterative calculations of the synchronization angle by considering that the absolute value of unknown synchronization operator |ejδ| of the unknown synchronization angle δ, has a value equal 1. As a result of such consideration the quadratic formula for the unknown distance to fault has been obtained, for which, in general, there are two solutions. In some rare cases both the solutions of the quadratic formula lay in the line range (0 to 1 in [p.u.]). In order to select which the solution is valid and corresponds to the real fault case, it has been recommended to repeat the calculation of the distance to fault, again with use of the quadratic formula, but with taking the other type of the symmetrical components. As a result of using such approach, i.e. canceling the unknown synchronization angle by mathematical manipulations, the drawback of the method known from U.S. Pat. No. 5,455,776 and Novosel D., Hart D. G., Udren E., Garitty J., article in relation of no controlling the achieved result for the synchronization angle has been assured.
Further improvement of the method of fault location using two-end unsynchronized measurements has been known from the article “Accurate location of faults on power transmission lines with use of two-end unsynchronized measurements” Iżykowski J., Molag R., Rosolowski E., Saha M. M., IEEE Transactions on Power Delivery, Vol. 21,
NO. 2, Apr. 2006, pp. 627-633. The method according to the paper assures controlling which solution for the unknown synchronization angle, out of two possible solutions, is achieved. After the initial calculations, based on considering the lumped parameter line model without counting for the line shunt capacitances, the iterative Newton-Raphson based calculations are performed. In these iterative calculations both the synchronization angle and the distance to fault are treated as the unknowns and the distributed parameter line model is strictly considered. The results from the initial calculations are taken as the starting values for the iterative calculations. The iterative calculations are performed on the respective matrices and are not simple.
From international patent application WO02/048726 there are known method and device for location fault utilizing unsynchronized measurement of there phase voltages and currents acquired at the line terminals without synchronization. Phasors for symmetrical components of the measurement quantities are determined and used in the fault location algorithm. According to one embodiment , positive sequence phasors of post-fault quantities are used for estimation of the distance to fault and is distinctive that such estimation of a distance to fault is performed without essentially involving iterative techniques. In this embodiment , the fault location algorithm step is performed regardless of a the fault type. I later steps, the type fault may be obtained. According to another embodiment of the invention, at the occurrence of a fault, the type of fault is determined. If it is determined that is not a three-phase balanced fault, negative sequence phasors are used for the estimation of the distance to fault. On the other hand, if it is a three-phase balanced fault, the incremental positive sequence phasors are used.
From international patent application WO03/044547 there is known a method to locate a fault in a section of a transmission line using measurement s of current, voltage and angles between the phases at first A and a second B end of said section. The presented invention is characterized by the steps of, after the occurrence of a fault along the section, calculating a distance from A end or B end to the fault dependent on a fault current measured at one of said first and second ends and phase voltages measured at both of said first and second ends A and B, where the distance to fault is calculated from the end A or B where the fault is measured. The invention is particularly suitable when a current transformer at either of the first A or second ends B is saturated. If so , then a distance to a fault is calculated dependent on a fault current measured at the non-affected end and phase voltages measured at both the affected end and non-affected end.
From Swedish patent application No SE528863, published also as WO02007/079990 there is known a method for locating a fault in two-terminal power transmission or distribution line comprises the steps of receiving measurements of the three phase currents from both terminals, receiving measurements of the three phase voltages from one line terminal , receiving parameters of the line and receiving the fault type. Base on this information the distance to fault from the one terminal where the phase voltages were measured is determined and output. Since only the phase voltages of the line terminal are needed, the functionality of a device , in particular a current differential relay can be expended to determine the distance to fault in an off-line mode.
The essence of the inventive method for locating faults in a section of at least one transmission line consist of the following:
The advantage of the method according to the invention is the overcoming of all the limitations and drawbacks of the known methods. The iterative calculations are completely avoided and the distributed parameter line model is considered from the very beginning. Simplicity of calculations is assured by simultaneous use of two kinds of symmetrical components of the measured voltage and current signals. Such simultaneous use of two kinds of symmetrical components of the measured voltage and current signals is not applied in any other known fault location technique. In particular, for all faults except three-phase balanced faults—the positive sequence and negative sequence quantities are used, and for three-phase balanced faults—the positive sequence and incremental positive sequence quantities are used. The present invention is characterized by use of very simple calculations (solution of the quadratic formula for complex numbers) and at the same time the distributed parameter line model is strictly, i.e. without simplifications, applied. The synchronization angle is determined accurately, with strict considering the distributed parameter line model, what allows accurate analytical synchronization of the measurements acquired asynchronously. Then, the distance to fault is calculated as in case of using synchronized measurements. Therefore, the accuracy of fault location according to the invented method is at the same level as in case of using the synchronized measurements. As a result of that, the GPS synchronization is not required for the invented method and there is no deterioration in the fault location accuracy at all.
The method according to the present invention is explained in an embodiment shown in the drawing, where
FIG. 2—an equivalent circuit diagram for a distributed parameter model of the transmission line A-B under the fault at point F, for the positive sequence,
FIG. 3—an equivalent circuit diagram for a distributed parameter model of the transmission line A-B under the fault at point F, for negative sequence,
FIG. 4—an equivalent circuit diagram for a distributed parameter model of the transmission line A-B under the fault at point F, for the incremental positive sequence,
FIG. 5—shows a flow-chart of the example of a fault locations algorithm according to the present invention.
The electric network for the implementation of the inventive method is presented in the
In the exploitation conditions the fault locator is placed in a protection relay which is not presented on the drawings.
The method according to the invention can be realized as it is depicted in the
Step 101.
The digital phasor data of three phase voltages VA and three phase currents IA from terminal A and digital phasor data of three phase voltages VB and three phase currents IB from terminal B, impedance Z1L′ and admittance Y1L′ of the line for the positive sequence, line length l, and fault type in terms whether it is unbalanced or three-phase balanced fault, are delivered as the input data of the fault locator FL.
Step 102.
In this step the positive sequence quantities of voltage and currents VA1,IA1,VB1,IB1 from both terminals are determined. The details of such calculation are well known to those skilled in the art.
Step 103.
In this step based on analysis of distributed parameter line model of the faulted transmission lines for the positive sequence quantities, depicted in
The positive sequence voltage at the fault point F, viewed from the side B (superscript: B) equals:
VF1B=VB1 cos h(γ1Ll(1−d))−Zc1LIB1 sin H(γ1Ll(1−d)) (2)
which, after taking into account that:
cos h(γ1Ll(1−d))=cos h(γ1Ll)cos h(γ1Lld)−sin h(γ1Ll)sin h(γ1Lld) (3a)
sin h(γ1Ll(1−d))=sin h(γ1Ll)cos h(γ1Lld)−cos h(γ1Ll)sin h(γ1Lld) (3b)
can be presented as:
VF1B=(cos h(γ1Ll)VB1−Zc1L sin h(γ1Ll)IB1)cos h(γ1Lld)+(−VB1 sin h(γ1Ll)+Zc1L cos h(γ1Ll)IB1)sin h(γ1Lld) (4)
The voltages (1) and (4) are to be compared:
VF1A=VF1B (5)
Performing this comparison one obtains
(G1ejδ+H1)cos h(γ1Lld)+(S1ejδ+T1)sin h(γ1Lld)=0 (6)
where:
Step 104
In this step it is determined whether the fault is a three phase balanced fault or unbalanced fault based on the input data, the subroutine I, for the positive and negative sequence quantities and a distributed parameter line model or the subroutine II for the positive and incremental positive sequence quantities and a distributed parameter line model is run.
Step 105a in Subroutine I
In this step the negative sequence quantities of voltage and currents signals VA2,IA2,VB2,IB2, from both line terminals A, B are determined. The details of such calculation are well known to those skilled in the art.
Step 106a in Subroutine I
In this step based on analysis of distributed parameter line model of the faulted transmission line for the negative sequence quantities, depicted in
The propagation constant of the line for the negative sequence γ2L is assumed in future consideration as equal to the propagation constant of the line for the positive sequence γ1L:
γ2L=γ1L. (8)
The negative sequence voltage at the fault point F−VF2A, viewed from the side A (superscript: A) equals:
VF2A=VA2ejδ cos h(γ1Lld)−Zc1LIA2ejδ sin h(γ1Lld), (9)
where:
The negative sequence voltage at the fault point F, viewed from the side B (superscript: B) equals:
VF2B=VB2 cos h(γ1Ll(1−d))−Zc1LIB2 sin h(γ1Ll(1−d)), (10)
which, after taking into account (3a) and (3b) can be presented as:
VF2B=(cos h(γ1Ll)VB2−Zc1L sin h(γ1Ll)IB2)cos h(γ1Lld)+(−VB2 sin h(γ1Ll)+Zc1L cos h(γ1Ll)IB2)sin h(γ1Lld). (11)
The voltages (9) and (11) are to be compared:
VF2A=VF2B. (12)
Performing this comparison one obtains:
(G2ejδ+H2)cos h(γ1Lld)+(S2ejδ+T2)sin h(γ1Lld)=0, (13)
where:
107
a in Subroutine I
In this step the B2,B1,B0 coefficients are calculated by comparing the voltage at the fault point F for positive and negative sequence quantities:
Solving the quadratic equation (14) the two solutions are received ejδ
Step 108a in Subroutine I
In this step the valid results is selected. This selection is done base on the following criterion:
Additionally, for confirming the selection, the values of the synchronization angle δ1,δ2 are simply determined as: δ1=angle(ejδ
Step 109
In this steps the distance to fault d is calculated from the following equation:
Step 105b in Subroutine II
In this step the incremental positive sequence quantities of voltage and currents signals VAΔ1,IAAΔ1,VBΔ1,IBΔ1, from both line terminals A, B are determined. The details of such calculation are well known to those skilled in the art.
Step 106b in Subroutine II
In this step based on analysis of distributed parameter line model of the faulted transmission lines for the incremental positive sequence, depicted in
VFΔ1A=VAΔ1ejδ cos h(γ1Lld)−Zc1LIAΔ1ejδ sin h(γ1Lld), (16)
where:
The incremental positive sequence voltage at the fault point F, viewed from the side B (superscript: B) equals:
VFΔ1B=VBΔ1 cos h(γ1Ll(1−d))−Zc1LIBΔ1 sin h(γ1Ll(1−d)), (17)
which, after taking into account (3a) and (3b) can be presented as:
VFΔ1B=(cos h(γ1Ll)VBΔ1−Zc1L sin h(γ1Ll)IBΔ1)cos h(γ1Lld)+(−VBΔ1 sin h(γ1Ll)+Zc1L cos h(γ1Ll)IBΔ1)sin h(γ1Lld) (18)
The voltages (16) and (18) are to be compared:
VFΔ1A=VFΔ1B. (19)
Performing this comparison and rearranging (3b) one obtains:
(GΔ1ejδ+HΔ1)cos h(γ1Lld)+(SΔ1ejδ+TΔ1)sin h(γ1Lld)=0, (20)
where:
The propagation constant of the line for the incremental positive sequence γΔ1L was assumed in the consideration as equal to the propagation constant of the line for the positive sequence γ1L.
107
b in Subroutine II
In this step the B5[ejδ]2+B4ejδ+B3=0 coefficients are calculated by comparing the voltage at the fault point F for positive and incremental positive sequence:
Combining (6) and (20) one obtains the result which after rearranging gives the following quadratic formula for the unknown synchronization operator ejδ, in which the unknown distance to fault d is not involved.
B5[ejδ]2+B4ejδ+B3=0, (21)
Solving the quadratic equation (21) the two solutions are received ejδ
Step 108b in Subroutine II
In this step the valid results is selected. This selection is done base on the following criterion:
Additionally, for confirming the selection, the values of the synchronization angle δ1,δ2 are simply determined as: δ1=angle(ejδ
Step 109
In this steps the distance to fault d is calculated from the following equation:
Step 105b in Subroutine II
In this step the incremental positive sequence quantities of voltage and currents signals VAΔ1,IAAΔ1, VBΔ1,IBΔ1, from both line terminals A, B are determined. The details of such calculation are well known to those skilled in the art.
Step 106b in Subroutine II
In this step based on analysis of distributed parameter line model of the faulted transmission lines for the incremental positive sequence, depicted in
VFΔ1A=VAΔ1ejδ cos h(γ1Lld)−Zc1LIAΔ1ejδ sin h(γ1Lld), (16)
where:
The incremental positive sequence voltage at the fault point F, viewed from the side B (superscript: B) equals:
VFΔ1B=VBΔ1 cos h(γ1Ll(1−d))−Zc1LIBΔ1 sin h(γ1Ll(1−d)), (17)
which, after taking into account (3a) and (3b) can be presented as:
VFΔ1B=(cos h(γ1Ll)VBΔ1−Zc1L sin h(γ1Ll)IBΔ1)cos h(γ1Lld)+(−VBΔ1 sin h(γ1Ll)+Zc1L cos h(γ1Ll)IBΔ1)sin h(γ1Lld) (18)
or
Additionally, for confirming the selection, the values of the synchronization angle δ3,δ4 are simply determined as: δ3=angle(ejδ
Step 109
In this steps the distance to fault d is calculated from the following equation (15):
Number | Date | Country | Kind |
---|---|---|---|
07460017 | Jul 2007 | EP | regional |
Filing Document | Filing Date | Country | Kind | 371c Date |
---|---|---|---|---|
PCT/EP2008/005223 | 6/23/2008 | WO | 00 | 5/12/2010 |
Publishing Document | Publishing Date | Country | Kind |
---|---|---|---|
WO2009/010169 | 1/22/2009 | WO | A |
Number | Name | Date | Kind |
---|---|---|---|
4559491 | Saha | Dec 1985 | A |
5455776 | Novosel | Oct 1995 | A |
6097280 | Takeda et al. | Aug 2000 | A |
7283915 | Saha et al. | Oct 2007 | B2 |
7286963 | Saha et al. | Oct 2007 | B2 |
Number | Date | Country |
---|---|---|
528863 | Feb 2007 | SE |
0248726 | Jun 2002 | WO |
03044547 | May 2003 | WO |
2007079990 | Jul 2007 | WO |
2009010169 | Jan 2009 | WO |
Number | Date | Country | |
---|---|---|---|
20110037480 A1 | Feb 2011 | US |