The present invention relates to a method of testing braces designed to restrain objects relative to a fixed structure during an earthquake, for example, to restrain sprinkler pipes in a building.
Design codes and standards (e.g., Uniform Building Code, International Building Code, NFPA-13 (National Fire Protection Association)) estimate the amplitude of the seismic load in sprinkler-pipe braces, but they do not specify the number of cycles for which this load must be resisted by various components of pipe braces.
The sprinkler pipes in a building are typically supported from the roof or the floor above by hanger rods that are designed to transfer the gravity load from the pipes to the supporting structure. In seismic regions, the pipes need to be restrained laterally and longitudinally at discrete locations along their length by seismic braces. In an earthquake, inadequately restrained sprinkler piping can suffer damage by large differential movement within the piping or by impacts with adjacent structural and nonstructural components. In the past, seismic damage to sprinkler pipes has been in the form of broken sprinkler heads, failed couplings and fittings, unseated hanger-rods and broken braces. To perform their function, the seismic braces must resist the dynamic load imposed by the vibrating sprinkler-pipe without breaking or deforming excessively.
Design codes and standards estimate the amplitude of the seismic load, but they do not estimate the number of cycles for which the load is applied.
Because the components can fail in low-cycle fatigue, the number of load cycles must be considered in establishing the strength of the brace components. By the present invention, the number of cycles for which a component must resist its rated capacity is determined. Strong-motion records from 18 severely shaken buildings were incorporated into a low-cycle fatigue model to develop a test criterion for measuring the seismic strength of brace components. In addition, a series of tests was conducted to gain insight into the cyclic behavior of brace components. Furthermore, a test protocol was established to measure the seismic strength of brace components. The protocol can be applied to many other non-structural components.
By the present invention, both the amplitude of the load on seismic braces and the number of load cycles are taken into consideration in establishing the seismic strength of the braces. The number of cycles for which a brace component must resist the seismic load is determined, a series of tests to gain insight into the cyclic behavior of brace components is conducted, and a protocol for determining the seismic-strength of brace components is established.
Strong-motion records from severely shaken buildings are incorporated into a low-cycle fatigue model to develop a simple, yet rational protocol for determining the seismic strength of sprinkler pipe sway-brace components. The protocol essentially determines the load a component can resist for 15 cycles without breaking or deforming more than a certain value derived from clearance requirements.
Tests have shown that the brace components can exhibit significant degradation in strength, stiffness, and energy dissipation under cyclic conditions.
The failure modes in cyclic tests can be significantly different from those in monotonic tests. In other words, cyclic tests reveal weaknesses that are not apparent in the monotonic tests.
From the analysis of test results, it has been found that friction-based components should be tested at 3 Hz to obtain a conservative load rating, whereas nonfriction-based components should be tested at 0.1 Hz to obtain a conservative load rating.
a) shows the acceleration history of the roof of a six-story hospital building shaken by the 1994 Northridge, California earthquake;
b) shows the horizontal deformation in a brace supporting a 40-foot length of a 2.5-inch water-filled steel pipe subjected to the motion shown in
a)–9(d) show the brace deformation corresponding to a 2-inch horizontal displacement of sprinkler pipe for various angular orientations of the brace;
a) shows force-deformation plots for the last three of 15 cycles for a pipe-attached subassembly tested at 0.1 Hz and 5 Hz at a 60° orientation;
b) shows force-deformation plots for the last three of 15 cycles for a pipe-attached subassembly tested at 0.1 Hz and 5 Hz at a 90° orientation;
a) is an applied deformation history for the building-attached component in the 60° orientation in
b) is the measured force history for the building-attached component in a 60° orientation in
a)–18(d) are force-deformation plots for the 1st, 2nd, 3rd, and 15th cycles, respectively, for the building-attached component in the 60° orientation in
a) is an applied deformation history for a pipe-attached component at a 30° orientation;
b) is a measured force history for a pipe-attached component in a 30° orientation;
a) is a cyclic force-deformation for a sample that breaks before reaching a predetermined limiting deformation; and
b) is a cyclic force-deformation plot for a sample that does not break at the predetermined limiting deformation.
The following description is written in terms of sprinkler pipes in a building, but the present invention also encompasses objects other than sprinkler pipes and fixed structures other than buildings.
The components of a “rigid” seismic brace 10 are shown in
a shows the acceleration history at the roof of a 6-story hospital building shaken by the 1994 Northridge, California earthquake (California Strong Motion Instrumentation Program 1994, Station # 24514).
For illustration purpose, an effective horizontal stiffness of 1,000 lb/inch for all values of load is assumed. This gives the deformation history shown in
Because the brace pipe 12 and the fasteners 18 are generally very stiff compared to the pipe-attached and the building-attached components, most of the deformations plotted in
Coffin and Manson independently proposed in 1954 the following expression for the number of uniform-amplitude cycles to failure:
where, u is the plastic deformation, and C and c are constants that are determined from experiments (Coffin, L. F., Jr. A Study of the Effects of Cyclic Thermal Stresses in Ductile Metals, Transactions of ASME, Vol. 76, pp. 931–950, 1954, and Manson, S. S. Behavior of Materials under Conditions of Thermal Stress, NACA TN 2933, 1954). Assuming that each cycle contributes equally to the damage, the damage done by a cycle of amplitude u is:
The damage caused by a non-uniform deformation history of the type shown in
in which D=1 implies complete damage (fatigue-failure), and n is the total number of cycles (Miner, M. A. Cumulative Damage in Fatigue, Journal of Applied Mechanics, Vol. 12, Trans. ASME, Vol. 67, pp. A159–A164, 1945).
Because the deformation histories are unlikely to contain symmetric cycles (with equal positive and negative amplitudes), it was decided in the present invention to accumulate damage from each half-cycle instead of each full-cycle. The damage expression (Equation 3) may then be rewritten as:
where, ui=the deformation amplitude of the ith half-cycle and n is now the number of half-cycles.
In the above model, the load-sequence effects (i.e., relative occurrence of small-amplitude cycles with respect to the large-amplitude cycles) are ignored. No conclusive evidence has been found to suggest that the load-sequence is important in low-cycle fatigue. The above model does not specify the frequency at which the load is applied. The loading frequency that gives the most conservative estimate of cyclic strength is determined in the test program described later herein.
There are several uniform-amplitude deformation histories that will cause the same damage as the non-uniform deformation history shown in
Tests performed on steel samples have shown that the damage exponent c is approximately equal to 2 (Krawinkler, H., Zohrei, M., Lashkari-Irvani, B., Cofie N. G., and Hadidi-Tamjed, H. Recommendation for Experimental Studies on the Seismic Behavior of Steel Components and Materials, Report No. NSF/CEE-83320, Stanford University, Stanford, Calif., September 1983; and Boyer, H. E. Atlas of Fatigue Curves, American Society of Metals, OH, 1999). Applying Equation 5 to the deformation history shown in
In other words, the uniform-amplitude deformation history shown in
In determining the deformation history shown in
As per the Coffin-Manson model (Equation 1), the damage is caused by plastic deformations only. However, the deformations shown in
To illustrate the above arguments, a bilinear elastic-plastic force-deformation relationship for the brace is assumed, as shown in
Applying Equation 5 to the deformation history shown in
Equation 5 shows that the number of uniform-amplitude cycles depends on the shape rather than the amplitude of the deformation history. For the same ground motion, the shape of the deformation history in a building depends on (1) the type of building, (2) the location (height) of the piping within the building, and (3) the natural period of the piping. The ground motion depends on (1) the earthquake magnitude, (2) the distance from the source, and (3) the local soil conditions. The uncertainties in all of the above factors, affecting the number of cycles, were addressed by using a statistical approach.
The uncertainties in building type and location (distance from earthquake source) are addressed by choosing 32 strong-motion records from 18 buildings (3 to 54 stories high) of various structural types, located 7 to 32 km from the epicenter of the 1994 magnitude 6.7MW Northridge earthquake. The average spectra of roof motions from these buildings are shown in
The uncertainty in the period of the piping system is addressed by estimating the periods of sprinkler pipes of various diameters and spans. These periods are found to range between 0.02s and 0.5s.
The natural period of lateral vibration of pipe can be computed from the following equation:
where,
The uncertainty in location within the height of the building is addressed by selecting only roof records which have the longest duration and hence give the maximum number of cycles. The adjustment made for an earthquake magnitude larger than 6.7MW is discussed hereinafter.
Twenty-five values of period were selected in the range 0.02 seconds to 0.5 seconds. These were considered to adequately represent the period of all sprinkler systems. For each period, the number of cycles was computed for the 32 strong-motion records, i.e., 25×32=800 values of number of cycles.
The Northridge earthquake had a magnitude of 6.7MW. In regions of high seismicity, the design earthquake (e.g., 475-year return period) may be larger than magnitude 6.7MW. A larger magnitude earthquake will result in longer duration of ground shaking, hence a larger number of cycles. There are many definitions of strong-motion duration, but the most common is the bracketed-duration, which is defined as the elapsed-time between the first and the last exceedances of threshold acceleration of 5% g, as is described in Bolt, B. A. Duration of Strong Motion, Proc. 4th World Conf on Earthquake Engrg., Santiago, Chile, pp. 1304–1315, 1969. The bracketed-duration for a magnitude 7.2MW earthquake is roughly 40 percent more than that for a magnitude 6.7MW (Northridge) earthquake as is described in Chang, F. K., and Krinitzsky, E. L. Duration, Spectral Content, and Predominant Period of Strong Motion Earthquake Records from Western United States, Miscellaneous Paper 5-73-1, U.S. Army Corps of Engineers Waterways Experiment Station, Vicksburg, Miss., 1977. Further, assuming that the number of cycles is proportional to duration, the 90th percentile value of the number of cycles at the roofs of buildings for a 7.2MW earthquake is 11×1.4=15. For most sites, the design (475-year return period) earthquake will not be greater than 7.2MW. Therefore, the number of cycles that has a 10% chance of being exceeded in 50 years is 15. Due to the conservative assumptions made in every step of the analysis, 15 cycles are expected to be sufficient for earthquake magnitudes even higher than 7.2MW.
Thus, it has been established by the present invention that, for a component to be rated for a certain load, it must resist that load for 15 cycles without failing structurally or functionally. In other words, a component should not break (structural failure) nor should it undergo excessive deformation (functional failure) at the rated load applied for 15 cycles.
Horizontal deformation greater than 2 inches at brace locations is considered excessive based on the clearance requirements for sprinkler piping. For example: (1) a minimum of 2 inches clearance is required between the pipe and the structural members, and (2) at wall penetrations with large-diameter piping, the hole diameter is required to be 4 inches larger than the pipe diameter, according to National Fire Protection Association (NFPA). Installation of Sprinkler Systems, NFPA-13, Quincy, Mass., 1996.
The deformation of the brace 10 is a result of deformations in the pipe-attached component 14, the building-attached component 16, the brace-pipe 12, and the fastener 18 (see
A component (pipe-attached or building-attached) can be rated for a load F if it can resist the load F for 15 cycles without breaking or exceeding these deformation limits:
where, θ is the brace angle measured from the vertical (
There are two options to conduct cyclic tests: (1) in force-control, or (2) in deformation-control. In force-control, a uniform-amplitude force history is applied and the resulting deformation history measured, while in deformation-control, a uniform-amplitude deformation history is applied and the resulting force history measured. For a test specimen that can undergo sudden changes in stiffness, it is difficult to achieve a good quality of ‘control’ in force-control. Therefore, the initial series of tests is conducted in deformation-control.
Because the brace components generally have different stiffness in tension and compression, a symmetric deformation history (with identical positive and negative amplitudes) does not result in a symmetric force history, and likewise a symmetric force history does not result in a symmetric deformation history. Therefore, it needs to be determined whether the force history or the deformation history should be kept symmetric.
As can be appreciated from
Testing is undertaken to gain insight into the cyclic behavior of brace components. Primary objectives of the test program are to evaluate (1) scatter in test results, (2) effect of load-rate (frequency), (3) effect of load-angle (orientation), and (4) degradation in strength, stiffness, and energy dissipation. In one test program, a total of 144 (66 monotonic+78 cyclic) tests were conducted.
As can be seen from
The failure mode was different for monotonic and cyclic loading. Under monotonic loading, the failure occurred in the set-screw. However, under cyclic loading, the failure occurred in the pin.
In general, components showed significant degradation in strength (under cyclic conditions) whenever the applied deformation was more than one-third the ultimate deformation measured under monotonic conditions. For applied deformation less than one-third of the ultimate deformation, the degradation in strength from 1st to 15th cycle was less than 15%.
The scatter in test results can range from very low for some tests to very high for other tests. For the tests conducted, the coefficient of variation ranged from 2 to 47 percent.
Components that rely, at least in part, on friction to secure the brace 10 to a building or an object appear to exhibit lower strength at higher frequencies. At least most pipe-attached components, including the pipe-attached component 14 of
Components that do not derive their strength from friction exhibit greater strength at higher frequencies. Such components can be tested at a slow rate (e.g., 0.1 Hz) to obtain a conservative estimate of cyclic strength.
Based on the tests conducted, an orientation-independent cyclic strength of the components could not be guaranteed. Therefore, it was decided to test the components at four different orientations: 30°, 45°, 60°, and 90°.
Components used with larger diameter pipes showed more flexible response than similar components used with smaller diameter pipes. Components used with lower schedule (thinner wall) pipes showed more flexible response than those used with higher schedule (thicker wall) pipes.
Components showed significant degradation in strength (under cyclic conditions) whenever the applied deformation was more than one-third the ultimate deformation measured under monotonic conditions. For applied deformation less than one-third the ultimate deformation, the degradation in strength from 1st to 15th cycle was less than 15%.
Analysis of a particular brace component in a single orientation showed 18% hysteretic damping in the first cycle and 5% hysteretic damping in the 15th cycle. The net damping in the piping system will be different depending on what fraction of the total deformation takes place in the brace and what fraction takes place in the pipe. However, a 5% damping for the piping system under strong shaking is not considered too high.
The failure modes under monotonic and cyclic loadings can be significantly different.
Test Protocol
A test protocol was established to determine the load a brace component can resist for 15 cycles without breaking or deforming more than the limiting value given by Equation 7. The protocol consists of a series of monotonic tension, monotonic compression, and cyclic tests. The monotonic tension and compression tests are performed to gather data for the cyclic tests. The load rating is determined primarily from the results of the cyclic tests.
Monotonic Testing
Samples of each size and style of seismic sway-brace component to be tested are subjected to monotonic tests until either the sample fails, or the deformation exceeds 3.5 inch (89 mm). The monotonic tests are performed for four orientations: θ=30°, 45°, 60°, and 90°, unless it is obvious that the stress distribution in the component is independent of orientation.
The test fixture is set to the required installation angle θ=30°, 45°, 60°, or 90°). The seismic sway-brace component is assembled according to manufacturer's specifications, and the test assembly is installed in the test fixture of a testing apparatus. The test assembly is subjected to monotonic tension loading until either the component fails, or the deformation exceeds 3.5 inches (89 mm). The maximum load is designated as Ft (see
Cyclic Testing
The objective of the cyclic tests is to determine the maximum load a component can resist for 15 cycles without breaking or exceeding the deformation limits given by Equation 7. Based on the results of cyclic tests, the seismic sway-brace components are assigned horizontal load ratings at installation angles of θ=30°, 45°, 60°, and 90°.
The following tests are performed using an appropriately sized load frame, or test apparatus 41, of, for example, the type shown in
For the selected orientation (θ=30°, 45°, 60°, or 90°) and from the results plotted from the monotonic tension and compression tests, the flexible loading direction is identified by the more gradual slope of the data curve, as shown in
From the flexible loading direction, the test deformation δ1 the sample can resist for 15 cycles is estimated. Although not shown in
Using the labeled force-deformation plot of
A fresh sample is subjected to 15 cycles of unsymmetric deformation history (δ1 on the flexible side and δ2 on the stiff side, as determined above from
The test apparatus also generates a graph, similar to
If δ1 is less than {overscore (δ)}, more points on the cyclic force-deformation chart (
The highest load on the force-deformation chart (
The horizontal load rating at θ orientation is Hθ=Fθ·sin θ.
Steps 1 to 8 are repeated for all four orientations. Four horizontal load ratings are assigned to the specimen (H30, H45, H60 and H90).
It will be apparent to those skilled in the art and it is contemplated that variations and/or changes in the embodiments illustrated and described herein may be made without departure from the present invention. Accordingly, it is intended that the foregoing description is illustrative only, not limiting, and that the true spirit and scope of the present invention will be determined by the appended claims.
Number | Name | Date | Kind |
---|---|---|---|
2754679 | Petroff | Jul 1956 | A |
3561322 | Gerstine et al. | Feb 1971 | A |
3589175 | Bock et al. | Jun 1971 | A |
3714854 | Kubacki | Feb 1973 | A |
3793880 | Sugi et al. | Feb 1974 | A |
3813990 | Coppola et al. | Jun 1974 | A |
3912181 | Mullendore | Oct 1975 | A |
3963099 | Skinner et al. | Jun 1976 | A |
3964521 | Kao et al. | Jun 1976 | A |
3964522 | Kao et al. | Jun 1976 | A |
3986808 | Keith | Oct 1976 | A |
4065218 | Biggane | Dec 1977 | A |
4078752 | Kindorf | Mar 1978 | A |
4602555 | Bushey | Jul 1986 | A |
4869111 | Ohya et al. | Sep 1989 | A |
4947341 | Shine | Aug 1990 | A |
4950458 | Cunningham | Aug 1990 | A |
4956822 | Barber et al. | Sep 1990 | A |
5024102 | Klock et al. | Jun 1991 | A |
5261493 | Brammer | Nov 1993 | A |
5305645 | Reifsnyder et al. | Apr 1994 | A |
5349870 | Webber et al. | Sep 1994 | A |
5396804 | Moet et al. | Mar 1995 | A |
5567867 | Nazar | Oct 1996 | A |
5641912 | Manahan | Jun 1997 | A |
5765313 | Lee et al. | Jun 1998 | A |
5899064 | Cheung | May 1999 | A |
6006487 | Leek | Dec 1999 | A |
6073493 | Sakamoto et al. | Jun 2000 | A |
6247274 | Thompson et al. | Jun 2001 | B1 |
6256943 | Mander et al. | Jul 2001 | B1 |
6269733 | Reust | Aug 2001 | B1 |
6327831 | Leek | Dec 2001 | B1 |
6332364 | Buschmann et al. | Dec 2001 | B1 |
6341258 | Inoue et al. | Jan 2002 | B1 |
6530182 | Fanucci et al. | Mar 2003 | B1 |
6543077 | Ouchi et al. | Apr 2003 | B1 |
6553320 | Roch et al. | Apr 2003 | B1 |
6643986 | Commins et al. | Nov 2003 | B1 |
6805377 | Krupp et al. | Oct 2004 | B1 |
20050104349 | Stevens | May 2005 | A1 |
20050116454 | Stevens et al. | Jun 2005 | A1 |
20050151358 | Burns | Jul 2005 | A1 |
20050200103 | Burns et al. | Sep 2005 | A1 |
20050218637 | Burns | Oct 2005 | A1 |
20050218638 | Burns et al. | Oct 2005 | A1 |
Number | Date | Country | |
---|---|---|---|
20050016087 A1 | Jan 2005 | US |